HomeMy WebLinkAboutLIGHTING COMCHECK - 20-00363 - BYUI Manwaring - RemodelCOMcheck Software Version 4.1.1.0
Interior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type:Alteration
Construction Site:
Rexburg, ID
Owner/Agent:
BYU-Idaho
Rexburg, ID
Designer/Contractor:
Payne Engineering
1823 E Center St.
Pocatello, ID 83201
Project Information
Energy Code:
BYU - Manwaring Remodel
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-School/University 10250 0.81 8302
8303Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
School/University (10250 sq.ft.)
LED 1: F1: 2X2 LAY-IN GRID TROFFER: Other:1 83 30 2490
LED 2: F2: 2X2 LAY IN FLAT PANEL: Other:1 29 30 870
LED 4: F4: ARCHITECHTURAL LIGHTING PANEL: Other:1 38 85 3230
LED 5: F5: 6" CYLINDER: Other:1 26 15 390
LED 6: F6: 4FT LED STRIP: Other:1 18 30 540
LED 7: F7: 6" ROUND RECESSED LED CAN: Other:1 6 15 90
LED 8: F8: 6" ROUND RECESSED LED CAN: Other:1 17 30 510
8120Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any
applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
BYU - Manwaring Remodel
\\paynefileserver\Main File Storage\2020\BYU-I Career Center -
2012\05_Calculations\Comcheck\Lighting Comcheck Career Center.cck
05/14/20Report date:
61 ofPage