HomeMy WebLinkAboutINSPECTION SUMMARY - 11-00038 - 653 Autumn Dr - SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 05/11/2020 1:05 pm
Permit Details Permit Number: 11-00038
653 Autumn Dr - SFR
653 Autumn Dr
New Single Family Residence
Permit Issued Date: 08/27/2014
Permit Inspection Statistics
22Total Inspections Completed:
15Total Inspections Passed:
Inspection Pass Rate: 68.18%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
02/11/2011PassTed DyeResidential Footing Inspection
OK to pour.Inspector Comments:
02/15/2011PassTed DyeFoundation Inspection
rebar in place
ufer bar installed next to electrical conduits
Inspector Comments:
05/06/2011FailTed DyeResidential Framing/Structure Inspection
Fireblocking needed at furdowns in basement
Smoke detector needed at bottom of stairs (basement)
Inspector Comments:
05/13/2011FailTed DyeResidential Framing/Structure Inspection
Fireblocking needed at furdowns in basement
Smoke detector needed at bottom of stairs (basement)
Inspector Comments:
05/13/2011FailTed DyeResidential Insulation Inspection
check framing notes
insulate (seal) penetrations in top plate to attic
Inspector Comments:
05/17/2011PassTed DyeResidential Framing/Structure Inspection
05/25/2011FailTed DyeResidential Sheetrock/Drywall Inspection
Finished basement
Remove sheetrock and insulation from around B vent
Note Wall sheetrocked before i could check fire blocking.
Inspector Comments:
05/30/2011PassTed DyeResidential Insulation Inspection
05/30/2011PassTed DyeResidential Sheetrock/Drywall Inspection
06/23/2011PassTed DyeSidewalk Inspection
front side walk ok to pour 12"-14" baseInspector Comments:
08/05/2011FailQuinton OwensResidential Building Final
Landing missing at back door.
Attic access lid missing
Finish guardrail/handrail in garage.
Inspector Comments:
08/08/2011FailTed DyeResidential Building Final
3' landing needed on back door.Inspector Comments:
08/18/2011PassTed DyeResidential Building Final
Page 1 of 2
(Continued)
Permit Details Permit Number: 11-00038
653 Autumn Dr - SFR
653 Autumn Dr
New Single Family Residence
Permit Status of (Open) as of Report Date: 05/11/2020 1:05 pm
Permit
Inspection
Summary
Electrical
03/23/2011PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power.Inspector Comments:
05/05/2011PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover.Inspector Comments:
08/05/2011FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Intersystem bonding termination required at the main service, tamper resistant
receptacle needed in the master bathroom, kitchen receptacles not GFCI
protected, GFCI protection required in the furnace room-receptacles, bathroom
receptacles downstairs reverse polarity(x2), closet light to close to the shelving
downstairs SW bedroom, receptacle missing gas range, A/C unit max breaker size
40A, range breaker 40A max-#8 wire, finish labeling the panel-#27, light missing
under shelving in garage, call for a re-inspect when ready.
Inspector Comments:
08/09/2011PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Approved for a final and C.O.-range receptacle was changed to 120V instead of
240V(20A)-gas.
Inspector Comments:
Mechanical
05/06/2011PassPLL ADMINHVAC Rough-in
As per Jon Berry
HVAC rough looks good. OK
Inspector Comments:
08/05/2011PassPLL ADMINHVAC Final Inspection
As per Jon Berry
HVAC final completed OK
Inspector Comments:
Plumbing
03/02/2011PassSAUREY AMANDAPlumbing Underground Inspection
02/18/11: Sewer main/underground test looks good, per Jeff Hackworth.Inspector Comments:
05/02/2011PassSAUREY AMANDAPlumbing Rough-in
04/29/11: Rough plumbing looks good, approved per Jeff Hackworth.Inspector Comments:
08/08/2011PassDon AllenPlumbing Final Inspection
Its all good to move in on the plumbing side.Inspector Comments:
Page 2 of 2