HomeMy WebLinkAboutINSPECTION SUMMARY - 11-00052 - 918 S 2400 W - New SFR TwinhomePermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 05/08/2020 11:50 am
Permit Details Permit Number: 11-00052
918 S 2400 W - New SFR Twinhome
918 S 2400 W
New Single Family Residence
Permit Issued Date: 08/28/2014
Permit Inspection Statistics
23Total Inspections Completed:
17Total Inspections Passed:
Inspection Pass Rate: 73.91%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
03/16/2011PassTed DyeResidential Footing Inspection
03/18/2011PassTed DyeFoundation Inspection
04/20/2011FailQuinton OwensResidential Framing/Structure Inspection
Some anchorbolts missing washers and nuts.
2hr fire separation above ceiling? Separation at front required. Firecaulk gaps and
penetrations.
Truss Details missing.
Inspector Comments:
04/22/2011PassQuinton OwensResidential Insulation Inspection
4/22/11 - Firewall and framing items done. Insulation OK
4/25/11 - Tedd - OK to hang drywall.
Inspector Comments:
04/28/2011FailTed DyeResidential Framing/Structure Inspection
Latteral bracing needed in trusses
Missing bracing circled one truss spec
Broken webb on one truss
Inspector Comments:
04/28/2011PassTed DyeResidential Framing/Structure Inspection
4/12/11 - Tedd - Sheeting Only
4/22/11 - Quintono - Firewall done, Firecaulk gaps over patio at bottom of truss.
Need Truss details; to be checked before drywall.(both units).
4/28/11 - Tedd - Ok all laterals in place
Broken truss repaired as per engineers instructions
Engineering is in file
Inspector Comments:
05/02/2011PassTed DyeResidential Sheetrock/Drywall Inspection
OKInspector Comments:
06/03/2011FailTed DyeResidential Building Final
Need number on outside of unit
Back Step missing
Range and dishwasher missing
Inspector Comments:
06/23/2011PassTed DyeSidewalk Inspection
06/23/2011PassTed DyeResidential Building Final
Page 1 of 3
(Continued)
Permit Details Permit Number: 11-00052
918 S 2400 W - New SFR Twinhome
918 S 2400 W
New Single Family Residence
Permit Status of (Open) as of Report Date: 05/08/2020 11:50 am
Permit
Inspection
Summary
Electrical
03/28/2011PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power-no receptacles are mounted.Inspector Comments:
04/20/2011PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover.Inspector Comments:
06/03/2011FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
A/C unit 25A max breaker-30A installed, furnace needs flex installed on the NM
cable, closet light clearance not sufficient, call for a re-inspect when ready.
Inspector Comments:
06/23/2011FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Door was locked-left message for Tyson-5:15pm.Inspector Comments:
06/27/2011PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Approved for a final and a C.O.Inspector Comments:
Mechanical
04/18/2011FailPLL ADMINHVAC Rough-in
As per Jon Berry
Support gasline and seal ducting in furnace room
Inspector Comments:
04/20/2011PassPLL ADMINHVAC Rough-in
As per Jon Berry
HVAC reinspect OK
Inspector Comments:
06/15/2011PassPLL ADMINHVAC Final Inspection
As per Jon Berry
HVAC final Completed. OK.
Inspector Comments:
Plumbing
03/22/2011PassPLL ADMINPlumbing Sewer
Approved by Brad JohnsonInspector Comments:
03/22/2011PassDon AllenPlumbing Water
Approved by Brad JohnsonInspector Comments:
03/29/2011PassSAUREY AMANDAPlumbing Underground Inspection
Underground looks good, per Jeff Hackworth.Inspector Comments:
04/18/2011PassPLL ADMINPlumbing Rough-in
As per Brad JohnsonInspector Comments:
06/02/2011PassSAUREY AMANDAPlumbing Final Inspection
Final plumbing approved, per Jeff Hackworth.Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 11-00052
918 S 2400 W - New SFR Twinhome
918 S 2400 W
New Single Family Residence
Permit Status of (Open) as of Report Date: 05/08/2020 11:50 am
Permit
Inspection
Summary
Page 3 of 3