Loading...
HomeMy WebLinkAboutINSPECTION SUMMARY - 11-00066 - Wingers - ElectricalPermit Inspection Summary Permit Status of (Open) as of Report Date: 05/08/2020 11:25 am Permit Details Permit Number: 11-00066 Wingers - Electrical 475 N 2nd E Commercial Electrical Misc. Permit Issued Date: 09/03/2014 Permit Inspection Statistics 2Total Inspections Completed: 1Total Inspections Passed: Inspection Pass Rate: 50.00% Permit Inspection History *Refer to Individual Inspection Report for more Details Electrical 02/28/2011FailBret StoddardCOM & MFR Electrical Service Inspection I did not write a ticket because I met with Brad with RMP to cut the seal on the meter and there had not been a permit pulled at the time-electrical contractor had not pulled a permit yet, need to install a fitting in the bottom of the meter base where the grounding electrode conductor goes through, need to identify the neutral conductor in the meter-green presently, call for a re-inspect when ready-need the utility there also for this inspection to remove the seal. Inspector Comments: 03/15/2011PassBret StoddardCOM & MFR Electrical Service Inspection Approved to stay energized for permanent power.Inspector Comments: