HomeMy WebLinkAboutFAULT CALCS - 20-00248 - Vista Medical Office - Lot 3, Blk 1 Trejo Professional Park
Created Using Eaton's Bussmann Series - Available Fault Current Calculator 1.5 Page 1
Your System Details
Project Name: Vista Medical
System Type: Single-Phase
Creator Email: proelectric1@mdn.com
Creation Date: May 4, 2020 @ 9:28pm
INFINITE PRIMARY SOURCE
TRANSFORMER - T1
KVA 100
Voltage secondary 240
%Z 2.00
%Z TOL -10% (Max Fault)
FAULT - X1
Itotal s.c. (L-L)23,150 AMPS
Itotal s.c. (L-N)34,725 AMPS
Voltage (L-L)240 V
CONDUCTOR RUN - C1
LENGTH 75 FT
SIZE 250
QTY
(per phase)1
TYPE Three Single Conductors
CONDUIT Nonmagnetic
WIRE Al, 600 V
FAULT - X2
Itotal s.c. (L-L)10,894 AMPS
Itotal s.c. (L-N)7,938 AMPS
Voltage (L-L)240 V