HomeMy WebLinkAboutFIRE ALARM REPORT - 17-00358 - 310 Ella Ln - Kenneth Square Bldg 10 - MFRFIRE ALARM INSPECTION AND TESTING REPORT Testing performed in accordance with applicable NFPA 72 standards/ By NICET Certified Technicians �1 Building Occupied by: Kenneth square(bldg 8,9,10 ) Owner/ Manager: Name & Number: Address of Building: 310 Ella lane Rex Name of Tester: Gary /leo inspection: 5/5/20 Type of Inspection: Initial/ 24 hour battery Date of ins p Control Panel Manufacturer &Model: Silent knight Notification of Testing: YPG # Of Zones: n SLC Loops: 1 NAC's-FRCP: 2 FCPS: 4 System should be tested on Standby (battery power) for 30 min nrinr to Total NAC's: 6 FACP I Key to Panel Available Operating Instruction at Panel Newest Record posted at panel Circuit breaker marked red Circuit break panel:Bldglt 3 Trouble signal with AC power off System operates satisfactory on standby, power at max load All signals operate on AC power All LED's Illuminate No N/A ✓ All circuits checked for electrical supervision All functions and buttons work properly Does alarm system meet audibility standards Control panel checks made per manufacturer's instruction All interfaced equipment operates (elevators, Fans, Dampers) Yes Satisfactory N ZYes ✓ ✓ Units ✓ : No /A ✓ ✓ ✓ ✓ ✓ Name of Monitoring Company: Cops Account #.. 809-9401 Communication Verified: Yes N/A: Equipment Tested ) ype or rqulpment # of Satisfactory Satisfactory N #of y: Yes y: No Units : Yes : No /A Units in A tested BLDG. FCPS Power booster 2 2 Annunciators ✓ ✓ Elev. Recall Prima Dialer, Communicator 1 ✓ Elev. Recall Sec. 1 Horns, Strobes, Bells, 39 Chimes, Speakers, Etc. ✓ 39 Smoke detectors 3 ✓ release (failsafe) 3 Heat Detectors Auto release ✓ Duct Detectors 61Pull Stations 3 ✓ 3 Flow Switches 3 V Halon system 3 Tamper Switches 6 ✓ 6 Low/High Air Switches Smoke Control ✓ ✓ PIV Valve Antifreeze Tamper ✓ Ansul S stem Beam Detector O tEEE ✓ Cl Temp sensor ✓ ✓ O No Interfaced # of Satisfactor Satisfa wr N --i-of Equipment units y: Yes y: No / Units tested A in BLDG. Ventilation Controls ✓ Elev. Recall Prima ✓ Elev. Recall Sec. ✓ Elev. Recall Shunt Access control door release (failsafe) ✓ Auto release ✓ Door holders Halon system ✓ Smoke Control ✓ PIV Valve ✓ Beam Detector ✓ CO detector ✓ Problems Found: None Date: 5/ I Corrections Made: None /20 Date: 5/5/20 This is to certify that this fire alarm has been properly tested and inspected for liability to cover the items listed in the report, according to manufacturer's recommendation. Signature of Signature of Owner or Signature of Fire Marshal: Certified Tester: Representative: Date: 5/5/20 Date: SYSTEM TECHIM'.. : Pt' Date: 5/5/20 To place a system on Test Please Call: 208-505-8500 For a service call System Tech: 800-TEC14-097 Office Phone: 208-881-0362 W W W.STI-USA.NET