HomeMy WebLinkAboutLOAD SHORT FORMS - 20-00254 - 848 & 854 S 2400 W - Summerfield TwinhomesCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 1 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Load Short Form 4/20/2020Date:Entire House Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) AH B 1563 28903 18014 644 767 AH A 1563 28903 17562 644 767 Entire House 3125 57806 35576 1288 1534 Other equip loads 3322 632 Equip. @ 0.95 RSM 34253 Latent cooling 273 TOTALS 3125 61129 34525 1288 1534 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 2 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Load Short Form 4/20/2020Date:AH A Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N95ESN0401410AA2 Cond N4A324AKN20 AHRI ref 4705245 Coil END4X24L14A1++TDR AHRI ref 9386153 Efficiency 96 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh21698 Heating output Btuh33345 Latent cooling Btuh0 Temperature rise °F56 Total cooling Btuh21698 Actual air flow cfm644 Actual air flow cfm767 Air flow factor cfm/Btuh0.022 Air flow factor cfm/Btuh0.044 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Mech A 30 0 0 0 0 M WIC A 45 962 134 21 6 Mud A 37 1555 304 35 13 M Bath A 74 353 86 8 4 Master A 191 4607 1489 103 65 Bath A 52 801 117 18 5 Bedroom 2 179 4598 2261 102 99 Bedroom 3 A 156 2857 2068 64 90 Kit/Din/Family A 799 13171 11104 293 485 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 3 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W AH A 1563 28903 17562 644 767 Other equip loads 3322 632 Equip. @ 0.95 RSM 17212 Latent cooling 0 TOTALS 1563 32225 17212 644 767 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 4 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Load Short Form 4/20/2020Date:AH B Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5030Inside humidity (%) -2935Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Day & Night Make Day & Night Trade DAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N95ESN0401410AA1 Cond N4A324AKN20 AHRI ref 4705245 Coil END4X24L14A1++TDR AHRI ref 9386153 Efficiency 96 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh21698 Heating output Btuh33345 Latent cooling Btuh0 Temperature rise °F56 Total cooling Btuh21698 Actual air flow cfm644 Actual air flow cfm767 Air flow factor cfm/Btuh0.022 Air flow factor cfm/Btuh0.043 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 0.99 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Mech B 30 0 0 0 0 M WIC B 45 962 132 21 6 Mud B 37 1555 300 35 13 M Bath B 74 353 85 8 4 Master B 191 4607 2133 103 91 Bath B 52 801 115 18 5 Bedroom 2 B 179 4598 2234 102 95 Bedroom 3 B 156 2857 2043 64 87 Kit/Din/Family B 799 13171 10971 293 467 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 5 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W AH B 1563 28903 18014 644 767 Other equip loads 0 0 Equip. @ 0.95 RSM 17041 Latent cooling 136 TOTALS 1563 28903 17177 644 767 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 1 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Building Analysis 4/20/2020Date:Entire House Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 15.091565.0Walls 20.41247336.0Glazing 6.2376929.9Doors 7.847941.5Ceilings 11.871912.32.3Floors 15.293024.0Infiltration 18.211122Ducts 00Piping 00Humidification 5.43322Ventilation0Adjustments 100.061129Total Cooling Walls Glazing DoorsCeilings OtherInfiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 2.48830.5Walls 40.51466742.4Glazing 2.59147.3Doors 7.326310.8Ceilings 0.51970.1Floors 2.69490.4Infiltration 21.37695Ducts 1.7632Ventilation 21.17640Internal gains 00Blower 0Adjustments 100.036208Total Latent Cooling Load = 273 Btuh Overall U-va lue = 0.0 57 Btuh/ft²-°F Data entries checked. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 2 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Building Analysis 4/20/2020Date:AH A Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 14.245785.0Walls 19.4623636.0Glazing 5.8188529.9Doors 7.423971.5Ceilings 11.235952.32.3Floors 14.446514.0Infiltration 17.35561Ducts 00Piping 00Humidification 10.33322Ventilation0Adjustments 100.032225Total Cooling Walls Glazing DoorsCeilings OtherInfiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 2.44420.5Walls 39.1710841.1Glazing 2.54577.3Doors 7.213160.8Ceilings 0.5980.1Floors 2.64740.4Infiltration 21.13847Ducts 3.5632Ventilation 21.03820Internal gains 00Blower 0Adjustments 100.018194Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 57 Btuh/ft²-°F Data entries checked. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 3 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Building Analysis 4/20/2020Date:AH B Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 15.845785.0Walls 21.6623636.0Glazing 6.5188529.9Doors 8.323971.5Ceilings 12.435952.32.3Floors 16.146514.0Infiltration 19.25561Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.028903Total Cooling Walls Glazing Doors CeilingsOtherInfiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 2.54420.5Walls 42.0755943.7Glazing 2.54577.3Doors 7.313160.8Ceilings 0.5980.1Floors 2.64740.4Infiltration 21.43847Ducts 00Ventilation 21.23820Internal gains 00Blower 0Adjustments 100.018014Total Latent Cooling Load = 136 Btuh Overall U-va lue = 0.0 57 Btuh/ft²-°F Data entries checked. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 1 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Component Constructions 4/20/2020Date:Entire House Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1870.4819364.9921.00.065388n 2130.4822044.9921.00.065442e 1870.4819364.9921.00.065388s 2970.4830814.9921.00.065618w 8830.4891564.9921.00.0651837all Partitions (none) Windows 4A5-2ov: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 31912.790136.000.47025n 1082545.9850836.000.470236e 77030.890136.000.47025s 275245.9216336.000.47060w 1466742.41247336.000.470346all Doors 11D0: Door, wd sc type 1527.2562829.900.39021n 3057.25125629.900.39042e 1527.2562829.900.39021s 3057.25125629.900.39042w 9147.25376929.900.390126all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 26310.8447941.5350.00.0203125 Floors 20P-38v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-38 cav ins, amb ovr 1970.0671912.3038.00.0303125 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 2 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Component Constructions 4/20/2020Date:AH A Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1870.4819364.9921.00.065388n 1060.4811024.9921.00.065221e 1490.4815414.9921.00.065309w 4420.4845784.9921.00.065918all Partitions (none) Windows 4A5-2ov: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 31912.790136.000.47025n 541345.9425436.000.470118e 137645.9108136.000.47030w 710841.1623636.000.470173all Doors 11D0: Door, wd sc type 1527.2562829.900.39021n 1527.2562829.900.39021e 1527.2562829.900.39021w 4577.25188529.900.39063all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 13160.8423971.5350.00.0201563 Floors 20P-38v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-38 cav ins, amb ovr 980.0635952.3038.00.0301563 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 3 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Component Constructions 4/20/2020Date:AH B Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-29.435.3Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 1060.4811024.9921.00.065221e 1870.4819364.9921.00.065388s 1490.4815414.9921.00.065309w 4420.4845784.9921.00.065918all Partitions (none) Windows 4A5-2ov: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 541345.9425436.000.470118e 77030.890136.000.47025s 137645.9108136.000.47030w 755943.7623636.000.470173all Doors 11D0: Door, wd sc type 1527.2562829.900.39021e 1527.2562829.900.39021s 1527.2562829.900.39021w 4577.25188529.900.39063all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 13160.8423971.5350.00.0201563 Floors 20P-38v: Flr floor, frm flr, 12" thkns, vinyl flr fnsh, r-38 cav ins, amb ovr 980.0635952.3038.00.0301563 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 1 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Project Summary 4/20/2020Date:Entire House Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F77 Design TD °F15Daily range H Relative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh46685 Structure Btuh27881 Ducts Btuh11122 Ducts Btuh7695Central vent (47 cfm)3322 Btuh Central vent (47 cfm)Btuh632 Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh61129 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh34253 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh421 Ducts Btuh-148Central vent (47 cfm)Btuh-786 CoolingHeating31253125Area (ft²)Equipment latent load Btuh273 2812528125Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh34525 Equiv. AVF (cfm)70131 Req. total capacity at 0.70 SHR ton4.1 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiencyn/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 2 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Project Summary 4/20/2020Date:AH A Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F77 Design TD °F15Daily range H Relative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh23342 Structure Btuh13715 Ducts Btuh5561 Ducts Btuh3847Central vent (47 cfm)3322 Btuh Central vent (47 cfm)Btuh632 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh32225 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh17212 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh210 Ducts Btuh-74Central vent (47 cfm)Btuh-786 CoolingHeating Outside air15631563Area (ft²)Equipment latent load Btuh0 1406314063Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh17212 Equiv. AVF (cfm)3566 Req. total capacity at 1.00 SHR ton1.4 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & NightTradeDAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N95ESN0401410AA2 Cond N4A324AKN20AHRI ref 4705245 Coil END4X24L14A1++TDR AHRI ref 9386153Efficiency96 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh21698Heating output Btuh33345 Latent cooling Btuh0 Temperature rise °F56 Total cooling Btuh21698Actual air flow cfm644 Actual air flow cfm767 Air flow factor cfm/Btuh0.022 Air flow factor cfm/Btuh0.044Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 3 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Project Summary 4/20/2020Date:AH B Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor:3846 East 100 North, Rigby, ID 83442 INFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F77 Design TD °F15Daily range H Relative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh23342 Structure Btuh14166 Ducts Btuh5561 Ducts Btuh3847Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none)Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh28903 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh17041 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh210 Ducts Btuh-74Central vent (0 cfm)Btuh0 CoolingHeating (none)15631563Area (ft²)Equipment latent load Btuh136 1406314063Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh17177 Equiv. AVF (cfm)3566 Req. total capacity at 1.00 SHR ton1.4 Heating Equipment Summary Cooling Equipment Summary Make Day & Night Make Day & NightTradeDAY & NIGHT Trade 13 SEER N SERIES R410A AC Model N95ESN0401410AA1 Cond N4A324AKN20AHRI ref 4705245 Coil END4X24L14A1++TDR AHRI ref 9386153Efficiency96 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh21698Heating output Btuh33345 Latent cooling Btuh0 Temperature rise °F56 Total cooling Btuh21698Actual air flow cfm644 Actual air flow cfm767 Air flow factor cfm/Btuh0.022 Air flow factor cfm/Btuh0.043Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 0.99 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 1...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:Entire House Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Entire House AH B 2 Exposed wall 256.5 ft 128.3 ft 3 Room height 9.0 ft 9.0 ft 4 Room dimensions 5 Room area 3125.0 f t²1562.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 434 388 1936 187 0 0 0 0 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 36.0536.05 12.7512.75 25 0 901 319 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 720 442 2204 213 360 221 1102 106 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 236 0 8508 10825 118 0 4254 5413 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 42 42 1256 305 21 21 628 152 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 434 388 1936 187 434 388 1936 187 GG 4A5-2ov4A5-2ov 0.4700.470 ss 36.0536.05 30.8130.81 25 0 901 770 25 0 901 770 DD 11D011D0 0.3900.390 ss 29.9129.91 7.257.25 21 21 628 152 21 21 628 152 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 720 618 3081 297 360 309 1541 149 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 60 0 2163 2752 30 0 1081 1376 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 42 42 1256 305 21 21 628 152 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 3125 3125 4794 2631 1563 1563 2397 1316 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 3125 3125 7191 197 1563 1563 3595 98 6 c) AED excursion 0 0 Envelope loss/gain 37382 19292 18691 9872 12 a)Infiltration 9302 949 4651 474 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 8 1840 4 920 Appliances/other 5800 2900 Subtotal (lines 6 to 13)46685 27881 23342 14166 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 46685 27881 23342 14166 15 Duct loads 24%28%11122 7695 24%27%5561 3847 Total room load 57806 35576 28903 18014 Air required (cfm)Air required (cfm)1288 1534 644 767 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 2...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:Entire House Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name AH A 2 Exposed wall 128.3 ft 3 Room height 9.0 ft 4 Room dimensions 5 Room area 1562.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 4.99 0.48 434 388 1936 187 .G 4A5-2ov 0.470 n 36.05 12.75 25 0 901 319 .D 11D0 0.390 n 29.91 7.25 21 21 628 152 .W 12F-0sw 0.065 e 4.99 0.48 360 221 1102 106 1 1 G 4A5-2ov 0.470 e 36.05 45.87 118 0 4254 5413 D 11D0 0.390 e 29.91 7.25 21 21 628 152 W 12F-0sw 0.065 s 4.99 0.48 0 0 0 0 G 4A5-2ov 0.470 s 36.05 30.81 0 0 0 0 D 11D0 0.390 s 29.91 7.25 0 0 0 0 W 12F-0sw 0.065 w 4.99 0.48 360 309 1541 149 G 4A5-2ov 0.470 w 36.05 45.87 30 0 1081 1376 D 11D0 0.390 w 29.91 7.25 21 21 628 152 C 16B-50ad 0.020 -1.53 0.84 1563 1563 2397 1316 F 20P-38v 0.030 -2.30 0.06 1563 1563 3595 98 6 c) AED excursion 0 Envelope loss/gain 18691 9420 12 a)Infiltration 4651 474 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 4 920 Appliances/other 2900 Subtotal (lines 6 to 13)23342 13715 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 23342 13715 15 Duct loads 24%28%5561 3847 Total room load 28903 17562 Air required (cfm)644 767 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 3...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH A Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name AH A Mech A 2 Exposed wall 128.3 ft 1.8 ft 3 Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft29.8x1.0 5 Room area 1562.5 f t²29.8 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 434 388 1936 187 16 16 79 8 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 36.0536.05 12.7512.75 25 0 901 319 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 360 221 1102 106 0 0 0 0 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 118 0 4254 5413 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 360 309 1541 149 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 30 0 1081 1376 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 1563 1563 2397 1316 30 30 46 25 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 1563 1563 3595 98 30 30 68 2 6 c) AED excursion 0 0 Envelope loss/gain 18691 9420 193 34 12 a)Infiltration 4651 474 63 6 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 0 0 Appliances/other 2900 0 Subtotal (lines 6 to 13)23342 13715 256 41 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -256 -41 14 Subtotal 23342 13715 0 0 15 Duct loads 24%28%5561 3847 24%28%0 0 Total room load 28903 17562 0 0 Air required (cfm)Air required (cfm)644 767 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 4...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH A Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M WIC A Mud A 2 Exposed wall 6.5 ft 6.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft8.5x5.3 ft5.8x6.5 5 Room area 44.6 f t²37.4 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 59 38 187 18 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 36.0536.05 12.7512.75 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 59 59 292 28 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 45 45 68 38 37 37 57 31 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 45 45 103 3 37 37 86 2 6 c) AED excursion 0 -1 Envelope loss/gain 463 68 958 203 12 a)Infiltration 236 24 236 24 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)699 92 1194 227 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 78 12 62 10 14 Subtotal 777 105 1256 237 15 Duct loads 24%28%185 29 24%28%299 67 Total room load 962 134 1555 304 Air required (cfm)Air required (cfm)21 6 35 13 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 5...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH A Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M Bath A Master A 2 Exposed wall 0 ft 27.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft8.5x8.8 ft191.1x1.0 5 Room area 74.4 f t²191.1 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 115 90 447 43 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 36.0536.05 12.7512.75 0 0 0 0 25 0 901 319 .DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 131 131 651 63 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 74 74 114 63 191 191 293 161 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 74 74 171 5 191 191 440 12 6 c) AED excursion 0 4 Envelope loss/gain 285 67 2732 602 12 a)Infiltration 0 0 988 101 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13)285 67 3721 1163 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 285 67 3721 1163 15 Duct loads 24%28%68 19 24%28%886 326 Total room load 353 86 4607 1489 Air required (cfm)Air required (cfm)8 4 103 65 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 6...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH A Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bath A Bedroom 2 2 Exposed wall 5.5 ft 27.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft9.5x5.5 ft178.6x1.0 5 Room area 52.3 f t²178.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 50 50 247 24 113 113 561 54 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 36.0536.05 12.7512.75 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 137 112 560 54 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 0 0 0 0 25 0 901 1147 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 52 52 80 44 179 179 274 150 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 52 52 120 3 179 179 411 11 6 c) AED excursion 0 16 Envelope loss/gain 447 71 2707 1433 12 a)Infiltration 199 20 1006 103 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)647 91 3713 1765 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 647 91 3713 1765 15 Duct loads 24%28%154 26 24%28%885 495 Total room load 801 117 4598 2261 Air required (cfm)Air required (cfm)18 5 102 99 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 7...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH A Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bedroom 3 A Kit/Din/Family A 2 Exposed wall 11.5 ft 41.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft155.8x1.0 ft798.6x1.0 5 Room area 155.8 f t²798.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 83 83 415 40 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 36.0536.05 12.7512.75 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 104 79 391 38 119 30 151 15 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 25 0 901 1147 68 0 2451 3119 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 WW 12F-0sw12F-0sw 0.0650.065 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 171 120 598 58 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 30 0 1081 1376 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 156 156 239 131 799 799 1225 672 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 156 156 358 10 799 799 1838 50 6 c) AED excursion 17 -35 Envelope loss/gain 1890 1342 9016 5600 12 a)Infiltration 417 43 1505 153 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 2900 Subtotal (lines 6 to 13)2307 1615 10521 8653 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 116 18 14 Subtotal 2307 1615 10637 8672 15 Duct loads 24%28%550 453 24%28%2534 2433 Total room load 2857 2068 13171 11104 Air required (cfm)Air required (cfm)64 90 293 485 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 8...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH B Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name AH B Mech B 2 Exposed wall 128.3 ft 1.8 ft 3 Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft29.8x1.0 5 Room area 1562.5 f t²29.8 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 360 221 1102 106 0 0 0 0 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 118 0 4254 5413 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 434 388 1936 187 16 16 79 8 GG 4A5-2ov4A5-2ov 0.4700.470 ss 36.0536.05 30.8130.81 25 0 901 770 0 0 0 0 DD 11D011D0 0.3900.390 ss 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 360 309 1541 149 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 30 0 1081 1376 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 1563 1563 2397 1316 30 30 46 25 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 1563 1563 3595 98 30 30 68 2 6 c) AED excursion 0 0 Envelope loss/gain 18691 9872 193 34 12 a)Infiltration 4651 474 63 6 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 4 920 0 0 Appliances/other 2900 0 Subtotal (lines 6 to 13)23342 14166 256 41 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -256 -41 14 Subtotal 23342 14166 0 0 15 Duct loads 24%27%5561 3847 24%27%0 0 Total room load 28903 18014 0 0 Air required (cfm)Air required (cfm)644 767 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 9...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH B Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M WIC B Mud B 2 Exposed wall 6.5 ft 6.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft8.5x5.3 ft5.8x6.5 5 Room area 44.6 f t²37.4 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 59 38 187 18 GG 4A5-2ov4A5-2ov 0.4700.470 ss 36.0536.05 30.8130.81 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 59 59 292 28 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 45 45 68 38 37 37 57 31 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 45 45 103 3 37 37 86 2 6 c) AED excursion -1 -2 Envelope loss/gain 463 68 958 202 12 a)Infiltration 236 24 236 24 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)699 92 1194 226 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 78 12 62 10 14 Subtotal 777 104 1256 236 15 Duct loads 24%27%185 28 24%27%299 64 Total room load 962 132 1555 300 Air required (cfm)Air required (cfm)21 6 35 13 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 10...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH B Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name M Bath B Master B 2 Exposed wall 0 ft 27.3 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft8.5x8.8 ft191.1x1.0 5 Room area 74.4 f t²191.1 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 115 90 447 43 GG 4A5-2ov4A5-2ov 0.4700.470 ss 36.0536.05 30.8130.81 0 0 0 0 25 0 901 770 DD 11D011D0 0.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 131 131 651 63 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 74 74 114 63 191 191 293 161 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 74 74 171 5 191 191 440 12 6 c) AED excursion -1 67 Envelope loss/gain 285 67 2732 1117 12 a)Infiltration 0 0 988 101 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13)285 67 3721 1677 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 285 67 3721 1677 15 Duct loads 24%27%68 18 24%27%886 456 Total room load 353 85 4607 2133 Air required (cfm)Air required (cfm)8 4 103 91 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 11...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH B Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bath B Bedroom 2 B 2 Exposed wall 5.5 ft 27.8 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft9.5x5.5 ft178.6x1.0 5 Room area 52.3 f t²178.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 137 112 560 54 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 0 0 0 0 25 0 901 1147 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 50 50 247 24 113 113 561 54 GG 4A5-2ov4A5-2ov 0.4700.470 ss 36.0536.05 30.8130.81 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 52 52 80 44 179 179 274 150 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 52 52 120 3 179 179 411 11 6 c) AED excursion -1 7 Envelope loss/gain 447 70 2707 1424 12 a)Infiltration 199 20 1006 103 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)647 91 3713 1757 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 647 91 3713 1757 15 Duct loads 24%27%154 25 24%27%885 477 Total room load 801 115 4598 2234 Air required (cfm)Air required (cfm)18 5 102 95 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Apr-20 19:57:59Right-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 12...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Right-J® W or ksheet 4/20/2020Date:AH B Gene MillerBy:Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net 1 Room name Bedroom 3 B Kit/Din/Family B 2 Exposed wall 11.5 ft 41.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft155.8x1.0 ft798.6x1.0 5 Room area 155.8 f t²798.6 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG 4A5-2ov4A5-2ov 0.4700.470 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 104 79 391 38 119 30 151 15 1 1 GG 4A5-2ov4A5-2ov 0.4700.470 ee 36.0536.05 45.8745.87 25 0 901 1147 68 0 2451 3119 DD 11D011D0 0.3900.390 ee 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 83 83 415 40 GG 4A5-2ov4A5-2ov 0.4700.470 ss 36.0536.05 30.8130.81 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 171 120 598 58 GG 4A5-2ov4A5-2ov 0.4700.470 ww 36.0536.05 45.8745.87 0 0 0 0 30 0 1081 1376 DD 11D011D0 0.3900.390 ww 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 CC 16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 156 156 239 131 799 799 1225 672 FF 20P-38v20P-38v 0.0300.030 --2.302.30 0.060.06 156 156 358 10 799 799 1838 50 6 c) AED excursion 9 -79 Envelope loss/gain 1890 1334 9016 5556 12 a)Infiltration 417 43 1505 153 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 2900 Subtotal (lines 6 to 13)2307 1607 10521 8610 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 116 18 14 Subtotal 2307 1607 10637 8628 15 Duct loads 24%27%550 436 24%27%2534 2343 Total room load 2857 2043 13171 10971 Air required (cfm)Air required (cfm)64 87 293 467 Job #: Kartchner Twin Homes Performed by Gene Miller for: Sprinter Heating & Hydronics 3846 East 100 North Rigby, ID 83442 Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 1sgmiller@cableone.net Scale: 1 : 115 Page 1 Ri ght -Sui te ® Uni versa l 2019 19.0.12 RSU28163 2020-Apr-20 19:58:24 ...home 4\Kartchner town home 4.rup N Main Mech A M WIC A Mud A M Bath A Master A Bath A Bedroom 2 Bedroom 3 A Kit/Din/Family A Mech B M WIC B Mud B M Bath B Master B Bath B Bedroom 2 B Bedroom 3 B Kit/Din/Family B 103 cfm 18 cfm 102 cfm 90 cfm 21 cfm 8 cfm 35 cfm 121 cfm 121 cfm 121 cfm 132 cfm 102 cfm 90 cfm 35 cfm 8 cfm 117 cfm 117 cfm 485 cfm 21 cfm 117 cfm 87 cfm 102 cfm 103 cfm 18 cfm 102 cfm132 cfm 87 cfm 6 " 8 " 6 " 6 " 8 " 8 " 8 " 6 " 8 " 16 " 12 " 8 " 8 " 8 " 503 cfm 12 " 6 " 6 " 6 " 6 " 6 " 6 "6 " 6 " 12 " 6 " 6 " 6 " 6 " 16 " 12 "8 " 6 " Pantry Pantry 8 " 121 cfm 8 " 117 cfm 6 " 2020-Apr-20 19:58:00 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 1 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Duct System Summary 4/20/2020Date:AH A Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0.41in H2O0.41 Available static pressure in H2O0.49in H2O0.49 Supply / return available pressure 0.233 / 0.257 in H2O in H2O0.233 / 0.257 Lowest friction rate in/100ft0.133in/100ft0.133 Actual air flow cfm767cfm644 Total effective length (TEL)ft370 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st3140.025.5VlFx0x06.00.141518801hBath A st3130.040.0VlFx0x08.00.137991024598hBedroom 2 st3130.026.2VlFx0x06.00.14990642068cBedroom 3 A st4130.025.0VlFx0x08.00.150121732776cKit/Din/Family A st4130.020.8VlFx0x08.00.154121732776cKit/Din/Family A-A st3130.025.9VlFx0x08.00.149121732776cKit/Din/Family A-B st3130.033.9VlFx0x08.00.142121732776cKit/Din/Family A-C 00VlFx0x0004886hM Bath A st4150.09.0VlFx0x06.00.147621962hM WIC A st3150.025.8VlFx0x08.00.133651034607hMaster A st4140.013.0VlFx0x06.00.15213351555hMud A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 203 262 0.147 749 8.0 0x0 ShtMetl st3 Peak AVF 433 502 0.133 639 12.0 0x0 ShtMetl 2020-Apr-20 19:58:00 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 2 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb1 0x 3460 503 191.5 0.134 641 12.0 x0 0 VlFx rt2 rb2 0x 1320 75 175.5 0.146 378 8.0 x0 0 VlFx rt2 rb3 0x 1020 99 190.1 0.135 293 8.0 x0 0 VlFx rt2 rb4 0x 640 90 193.9 0.133 259 8.0 x0 0 VlFx rt2 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 644 767 0.133 549 16.0 0x0 ShtMetl 2020-Apr-20 19:58:00 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 3 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Kartchner Twin HomesJob:Duct System Summary 4/20/2020Date:AH B Gene MillerBy: Twin HomesPlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: 1sgmiller@cableone.net Project Information Sprinter Heating & HydronicsFor: 3846 East 100 North, Rigby, ID 83442 CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.90in H2O0.90 Supply / return available pressure 0.402 / 0.498 in H2O in H2O0.402 / 0.498 Lowest friction rate in/100ft0.218in/100ft0.218 Actual air flow cfm767cfm644 Total effective length (TEL)ft414 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1140.028.0VlFx0x06.00.239518801hBath B st1130.037.4VlFx0x06.00.240951024598hBedroom 2 B st1130.025.0VlFx0x06.00.25987642043cBedroom 3 B st2130.026.8VlFx0x06.00.256117732743cKit/Din/Family B st2130.020.2VlFx0x06.00.267117732743cKit/Din/Family B-A st1130.033.5VlFx0x06.00.246117732743cKit/Din/Family B-B st1130.026.4VlFx0x06.00.257117732743cKit/Din/Family B-C st1150.013.0VlFx0x06.00.24648353hM Bath B st2150.011.5VlFx0x06.00.249621962hM WIC B st1160.024.5VlFx0x06.00.218911034607hMaster B st2140.012.5VlFx0x06.00.26313351555hMud B Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 203 252 0.249 722 8.0 0x0 ShtMetl st1 Peak AVF 441 515 0.218 656 12.0 0x0 ShtMetl 2020-Apr-20 19:58:00 Rig ht-Su ite® U niv er sal 20 19 19 .0.12 RSU2 8163 Page 4 ...\Kartchner Townhome 4\Kartchner town home 4.rup Calc = MJ8 Front Door faces: W Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb9 0x 3460 485 219.4 0.227 617 12.0 x0 0 VlFx rt1 rb10 0x 640 87 222.6 0.224 443 6.0 x0 0 VlFx rt1 rb11 0x 1020 95 229.1 0.218 522 6.0 x0 0 VlFx rt1 rb12 0x 1320 100 174.8 0.285 672 6.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 644 767 0.218 549 16.0 0x0 ShtMetl