HomeMy WebLinkAboutINSPECTION SUMMARY - 11-00202 - 582 Woodbridge St - New SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 04/16/2020 9:41 am
Permit Details Permit Number: 11-00202
582 Woodbridge St - New SFR
582 Woodbridge St
New Single Family Residence
Permit Issued Date: 09/22/2014
Permit Inspection Statistics
28Total Inspections Completed:
17Total Inspections Passed:
Inspection Pass Rate: 60.71%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
06/09/2011PassQuinton OwensResidential Footing Inspection
OK to pourInspector Comments:
06/15/2011PassTed DyeFoundation Inspection
ok to pour
some rebar
Inspector Comments:
11/21/2011FailTed DyeResidential Framing/Structure Inspection
Master Bedroom: Exterior sheeting had ataples that missed stud. (marked with
red crayon)
Hurricane clip missing nails in SW bedroom.
Bearing wall in basement meeds anchor bolts every 6' on center.
Call when completed.
Inspector Comments:
11/21/2011PassTed DyeResidential Framing/Structure Inspection
11/30/2011PassPLL ADMINResidential Insulation Inspection
12/02/2011FailTed DyeResidential Sheetrock/Drywall Inspection
Need to see clearance at ceiling and insulation shield.Inspector Comments:
12/05/2011PassTed DyeResidential Sheetrock/Drywall Inspection
OKInspector Comments:
07/12/2012FailQuinton OwensResidential Building Final
House numbers missing. Back door exit requires a landing (existing steps ok for
temp. use only). Condition air in crawl space. Finish vapor barrier in crawl space.
CO det. outside sleeping rooms.
Garage handrail to be 34-38" above front of tread. Patch holes/penetrations in
garage separation wall. Firestop ring around ABS pipe penetrating into garage.
Inspector Comments:
08/14/2012PassQuinton OwensResidential Building Final
Building final OKInspector Comments:
12/13/2012PassQuinton OwensSidewalk Inspection
No inspection request.Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 11-00202
582 Woodbridge St - New SFR
582 Woodbridge St
New Single Family Residence
Permit Status of (Open) as of Report Date: 04/16/2020 9:41 am
Permit
Inspection
Summary
Electrical
08/26/2011FailBret StoddardResidential Electrical Service Inspection
Do not inspect the conduit from RMP powers j-box to the meter-RMP inspects
this.
Inspector Comments:
11/09/2011FailBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Rebar clamp (ufer) not rated for rebar-ground rod clamp used, bare copper wire
for service must be a #4 minimum, cable clamp required for all boxes mounted
on outside walls for receptacles and lights, range box needs proper NM clamp, no
wire pulled to recessed 6" can in bedroom, need ground wire stubbed out for TV
and phone (intersystem bonding termination), call for a re-inspect when ready.
Inspector Comments:
11/14/2011PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power-no separate ticket was
written-inspected the service on the rough-in.
Inspector Comments:
11/14/2011PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover.Inspector Comments:
06/04/2012FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Need to install an intersystem bonding termination, soffit receptacle needs damp
location cover, spark rings needed throughout the house for devices with boxes
back in the wall-wood on the walls, call for a re-inspect when ready.
Inspector Comments:
06/06/2012PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Approved for a final and C.O.-items were corrected from prior inspection.Inspector Comments:
Mechanical
09/29/2011PassPLL ADMINHVAC Rough-in
As per Jon Berry
Furnace, vent and ducting ok
Dryer vent ok
Fireplace and bath vents not installed
Inspector Comments:
07/12/2012FailQuinton OwensHVAC Final Inspection
Condition air in crawl space. Furnace condensate must go to approved drain.Inspector Comments:
08/14/2012PassQuinton OwensHVAC Final Inspection
Mech final OKInspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 11-00202
582 Woodbridge St - New SFR
582 Woodbridge St
New Single Family Residence
Permit Status of (Open) as of Report Date: 04/16/2020 9:41 am
Permit
Inspection
Summary
Plumbing
06/05/2011FailDon AllenPlumbing Final Inspection
6/5/12 - bathroom sink needs change out. Flex concrete on P-trap. Kitchen sink
needs to use a disposal kit and only one p-trap on sink. Need to put putty cups
on toilet bolts. Need shut off valve on water heater cold sink.
Inspector Comments:
06/30/2011PassSAUREY AMANDAPlumbing Sewer
Approved and okay to cover, per Larry Watts.Inspector Comments:
06/30/2011PassDon AllenPlumbing Water
Approved and okay to cover, per Larry Watts.Inspector Comments:
11/09/2011FailDon AllenPlumbing Rough-in
11/10/2011 needs to put in 3 inch end of the line clean outs, change sand tees
in the venting they are in the wrong way, redo the vent and drainage for the
tubs, change the drainage for the water heater and softer room needs to vent it
also, add softener loop, need soft water for kitchen sink,
Inspector Comments:
11/17/2011FailDon AllenPlumbing Rough-in
11/17/2011 needs to run hard water line to kitchen sink, vent tub in main bath
room, needs to take out sand-tee in the vent line and replace it with the proper
fitting ,
Inspector Comments:
06/06/2012FailDon AllenPlumbing Final Inspection
Only one joint from P-trap to trap arm.Inspector Comments:
06/07/2012PassDon AllenPlumbing Final Inspection
Approved for C/OInspector Comments:
06/18/2012PassDon AllenPlumbing Underground Inspection
06/18/2012PassDon AllenPlumbing Rough-in
11/22/2011 approved just needs to put air test on.(5lb for 15 min)Inspector Comments:
Page 3 of 3