Permit Status of (Open) as of Report Date: 04/13/2020 3:16 pm
Permit Details Permit Number: 11-00273
210 S 2nd W - LDS Church 13th Ward
210 S 2nd W
New Commercial Building
Permit Issued Date: 10/06/2014
Permit Inspection Statistics
30Total Inspections Completed:
25Total Inspections Passed:
Inspection Pass Rate: 83.33%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building
10/11/2011PassPLL ADMINFoundation Inspection
As per Jon Berry
N, S, and W foundation walls and rebar look good.
Completed.
Inspector Comments:
11/07/2011PassPLL ADMINCommercial Footing Inspection
As per Jon Berry
9/30/11 - FC 3.0 footings need #5 @ 14" OC crosswise (FAILED)
10/20/11 - Int. Footings and Foundation look good.
11/1/11 - Interior footings OK to pour north side and front. Tie rebar above
ground.
11/2/11 - South int. footings OK
11/3/11 - NE footings OK
11/4/11 - Center west interior footings look good.
11/7/11 - SE interior footings OK to pour.
Inspector Comments:
12/28/2011PassPLL ADMINSheeting
As per Jon Berry
Ext. sheathing nailed OK to cover.
Inspector Comments:
02/09/2012PassTed DyeCommercial Insulation Inspection
2/1/12 - Rm 202 NE corner needs insulation on lower corner OK Room on SW
corner needs insulation at Beam OK upper level last room on NE corner; hole on
upside of rafers in wall OK **NOTE** All gable ends** and walls are not yet
insulated.**
4/27/12 - Exterior walls approved (EXCEPT Entryways & Chapel popout -
incomplete)2-7, QO Entryway walls and chapel pop-out done. (2-9, QO) Ceilings
not done yet. Per QuintonO
Inspector Comments:
08/07/2012PassPLL ADMINSidewalk Inspection
As per Jon BerryInspector Comments:
Page 1 of 5
(Continued)
Permit Details Permit Number: 11-00273
210 S 2nd W - LDS Church 13th Ward
210 S 2nd W
New Commercial Building
Permit Status of (Open) as of Report Date: 04/13/2020 3:16 pm
Permit
Inspection
Summary
08/08/2012PassPLL ADMINCommercial Building Final
As per Jon Berry
ADA toilet paper not per code installed by church.
Inspector Comments:
10/06/2012PassPLL ADMINCommercial Framing/Structure Inspection
As per Jon Berry
Framing looks good OK to insulate
Inspector Comments:
10/06/2014PassPLL ADMINCommercial Sheetrock/Drywall Inspection
As per Jon Berry
2/9/12 - Sheetrock at exterior walls in rooms approved per QuintonO
1/9/12 - Nailing looks good south and west sides.
2/6/12 - Exterior sides OK for insulation (entryways and chapel incomplete)
ceiling drywall OK to tape.
Inspector Comments:
Page 2 of 5
(Continued)
Permit Details Permit Number: 11-00273
210 S 2nd W - LDS Church 13th Ward
210 S 2nd W
New Commercial Building
Permit Status of (Open) as of Report Date: 04/13/2020 3:16 pm
Permit
Inspection
Summary
Electrical
10/26/2011FailBret StoddardElectrical Underground Inspection
Did not inspect the underground conduits-already backfilled before inspection.Inspector Comments:
11/15/2011PassBret StoddardElectrical Underground Inspection
Approved for cover-underground conduits-home runs.Inspector Comments:
06/01/2012PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power-as per electrical contractor,
engineer only requires what the City requires-they did not install an equipment
grounding conductor from the C.T. enclosure to the main panel.
Inspector Comments:
06/22/2012PassBret StoddardCommercial Electrical Rough-in
1/27/12 - Approved for cover in TJI ceilings and perimeter classroom walls.
2/15/12 - Approved for cover in interior walls, cultural hall, and chapel areas.
3/23/12 - Approved for cover in restroom floor
6/22/12 - Approved for cover. walls only. wires stubbed up into ceiling area not
terminated into boxes.
Inspector Comments:
08/02/2012FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Label panels throughout, all A/C units have wrong size breakers installed
throughout, fire alarm system not done, romex needs to be covered in the north
and south mezzanine (vestibule walls), blank covers needed in two location in the
mezzanine area, call for a re-inspect when ready.
Inspector Comments:
08/07/2012FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Need to cover the NM-B cable in the mezzanine area on the north and south
side-vestibule, ground clamps not installed in the baptismal font area, call for a
re-inspect when ready.
Inspector Comments:
08/09/2012PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.Inspector Comments:
Page 3 of 5
(Continued)
Permit Details Permit Number: 11-00273
210 S 2nd W - LDS Church 13th Ward
210 S 2nd W
New Commercial Building
Permit Status of (Open) as of Report Date: 04/13/2020 3:16 pm
Permit
Inspection
Summary
Fire
11/29/2011PassBret StoddardFire Underground Inspection
11/28/11 - Approved for cover-10:10AM 209#, 12:15PM 209#-2 hour test
completed underground to street tie in.
11/29/11 - Flush Approved-4" for 10 minutes, 6" main line.
Inspector Comments:
02/23/2012PassPLL ADMINFire Sprinkler Rough-in
As per Jon Berry
Sprinkler visual and head inspection looked good.
Sprinkler piping main lines OK to cover over gym and chapel
Inspector Comments:
04/27/2012PassPLL ADMINFire Alarm Rough-in
As per Jon Berry
Visual inspection of piping and heads looked good.
Hydro to be scheduled.
Inspector Comments:
07/31/2012PassPLL ADMINFire Sprinkler Final Inspection
As per Jon Berry
Sprinkler hydro tested good after leak repaired
Hydro tested good at 200#
Inspector Comments:
08/03/2012PassPLL ADMINFire Alarm Final Inspection
As per Jon Berry
Fire alarm system without sprinkler system checked good. Sprinklers to be tested
8/7
Inspector Comments:
08/08/2012PassPLL ADMINFire Department Final Inspection
As per Jon Berry
Finals completed. System on line
*approved
Inspector Comments:
Mechanical
04/27/2012PassPLL ADMINHVAC Rough-in
As per Jon BerryInspector Comments:
07/23/2012FailQuinton OwensHVAC Final Inspection
-Fan not running in mens room
-Cap opening on sides of furnace (horizontal)
-Condensate pump 9west end) not working (power to outlet?)
Inspector Comments:
08/07/2012PassQuinton OwensHVAC Final Inspection
Page 4 of 5
(Continued)
Permit Details Permit Number: 11-00273
210 S 2nd W - LDS Church 13th Ward
210 S 2nd W
New Commercial Building
Permit Status of (Open) as of Report Date: 04/13/2020 3:16 pm
Permit
Inspection
Summary
Plumbing
08/28/2011PassDon AllenPlumbing Underground Inspection
10/28/2011 ground work is all good to coverInspector Comments:
03/01/2012PassSAUREY AMANDAPlumbing Rough-in
03/02/12: Men and Women's gang bathrooms look good, per Nathan Wood.
3/20/12 - The two bathrooms are all good -per Don Allen
Inspector Comments:
07/26/2012FailDon AllenPlumbing Final Inspection
Need to caulk everything. Air gap on softenerInspector Comments:
08/24/2012PassDon AllenPlumbing Sewer
08/24/2012PassDon AllenPlumbing Water
08/24/2012PassDon AllenPlumbing Final Inspection