HomeMy WebLinkAboutFIRE ALARM SPECS -20-00128 - Madison Memorial Radiology RemodelFeatures:
• Approvals include: UL Standard 1971, UL Standard
464, California State Fire Marshal (CSFM), New York City
(MEA), Factory Mutual (FM) and Chicago (BFP) See
approvals by model in Specifications and Ordering
Information
• Designed to meet or exceed ADA/NFPA/UFC/ANSI
Standards and Accessibility Guidelines
• Complies with OSHA 29, Part 1910.165
• Series MT appliances have IN and OUT wiring
terminations that accept two #12 to #18 American
Wire Gauge (AWG) wires at each terminal. Inputs are
polarized for compatibility with standard reverse polarity
type supervision
• One alarm appliance with (8) eight selective signals to
provide superior sound penetration for various ambient
and wall conditions with two field selectable sound output
levels
• Code-3 Horn and Tone meet ANSI/NFPA temporal pattern
for standard emergency evacuation signaling
• Audible and strobe can operate from a single NAC circuit
or from separate NAC circuits with any of the (8) eight
audible sounds
• MT Strobe models are available with Wheelock patented
MCW Multi-Candela strobes with field selectable c
andela settings at 15/30/75/110cd or with single candela
1575cd strobes. The strobes can be synchronized using
Wheelock sync modules or power supplies with built in
Sync Protocol
• Selectable input voltage on non-strobe versions. Strobe
versions are factory set for either 12 or 24VDC, with wide-
Listed voltage range, filtered (DC) and FWR
• No additional trimplate required for flush mounting
Description:
The Wheelock Series MT and MT Strobe Multitone electronic
appliances offer a choice of eight (8) nationally and internationally
recognized alerting sounds: Horn, Bell, March Time Horn, Code-
3 Tone, Code-3 Horn, Slow Whoop, Siren or Hi/Lo Tone. The
Code-3 Horn and tone patterns are engineered to comply with
NFPA/ANSI Temporal Pattern specifications without requiring
additional equipment. With MT and MT Strobe appliances, one
alarm appliance meets most of your signaling needs. The MT
strobes can be synchronized using the Wheelock SM, DSM Sync
Modules or the PS-24-8MC Power Supply with the Wheelock
patented Sync Protocol.
The MT Strobes are designed for ADA applications while meeting
or exceeding the latest requirements of NFPA 72, ANSI 117.1,
UFC and UL Standard 1971 as well as meeting ADA requirements
concerning photosensitive epilepsy.
Each MT and MT Strobe appliance has two installer selective
sound output levels: STANDARD dBA and HIGH dBA. Non-strobe
versions provide selectable voltage capability in one unit, 12VDC
or 24VDC. Strobe versions are specific for either 12VDC or 24VDC
and all models may be used with filtered or unfiltered (full-wave-
rectified) input voltages. Separate input terminals are available,
shunt wires are provided to enable both tone and strobe to operate
simultaneously from a single input.
The Series MT Multitone Strobe appliances are UL Listed for
indoor wall mount applications under Standard 1971 for Signaling
Devices for the Hearing Impaired and under Standard 464 for
Audible Signaling Appliances.
MT4-115-WH SERIES MT-12/24SERIES MT STROBE
For Weatherproof MTWP See Data Sheet S9004
Series MT and MT Strobe Multitone Electronic Appliances
THE CITY OF
NEW YORK
DEPARTMENT OF BUILDINGS
UL®
151-92-EE5946 7135-0785:118 (MT4)
7125-0785:155 (MT)
7125-0758:156 (MTWP)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters .
WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,
SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND
WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
General Notes:
• Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range” (16-33v for 24VDC units and
8-17.5v for 12VDC units). Regulated Voltage Range is the newest terminology used by UL to identify the listed voltage range.
• All candela ratings represent minimum effective Multitone Strobe intensity based on UL Standard 1971.
• MT Strobe models are UL Standard 1971 Listed for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and
maximum humidity of 93% ±2%. The MT-12/24, MTWP and MT4 models and listed for outdoor use at -31°F to 150°F (-35°C to
66°C) and maximum humidity of 95% (See Data Sheet S9004 or Installation Instruction Sheet P84150 for more detail on MTWP).
MTWP and MT4 strobes are listed under UL 1638.
• MT Audible is UL Standard 464 Listed.
Alarm Tones
TONE ALARM TONES PATTERN DESCRIPTION
HORN BROADBAND HORN (Continuous)
BELL 1560 Hz MODULATED (0.07 sec. ON/Repeat)
MARCH TIME
HORN HORN (0.25 sec. ON/0.25 sec. OFF/Repeat
CODE-3 HORN HORN (ANSI S3.41 Temporal Pattern)
CODE-3 TONE 500 Hz (ANSI S3.41 Temporal Pattern)
SLOW WHOOP 500-1200 Hz SWEEP (4.0 sec. ON/0.5 sec. OFF/Repeat)
SIREN 600-1200 Hz SWEEP (1.0 sec. ON/Repeat)
HI/LO 1000/800 Hz (0.25 sec. ON/Alternate)
Table 2: Strobe Current Ratings
RMS Current (amps)
Model MT-121575 MT-241575 MTWP-2475 MT-24MCW
Candela 1575cd 1575cd 180cd 15cd 30cd 75cd 110cd
@ 24VDC 0.152 0.060 0.094 0.041 0.063 0.109 0.140
UL max*0.255 0.090 0.138 0.060 0.092 0.165 0.220
Note: If the strobe and audible operate on the
same circuit, add the strobe current from Table 2
to the audible current from Table 1.
Table 1: dBA and Current Ratings for Multitone Audible Portion
RMS Current (amps)dBA @ 10ft (UL Reverberant)dBA @ 10ft (anechoic)
dBA @ 10ft (UL Reverberant)
24 VDC 12 VDC 120 VAC 24 VDC 12 VDC 12 and 24 VDC 120 VAC
HI Output STD Output HI Output STD Output HI
Output
STD
Output HI
Output
STD
Output
HI
Output
STD
Output
HI
Output
STD
Output
HI
Output
STD
Output@ 24
VDC
UL
max*
@ 24
VDC
UL
max*
@ 24
VDC
UL
max*
@ 24
VDC
UL
max*
UL
max*
UL
max*
Horn 0.074 0.108 0.033 0.044 0.145 0.176 0.023 0.034 0.050 0.042 92 87 90 77 99 93 88 82
Bell 0.040 0.053 0.018 0.024 0.077 0.095 0.014 0.020 0.041 0.039 86 80 85 69 92 87 82 75
March Time
Horn 0.067 0.104 0.033 0.038 0.109 0.142 0.023 0.034 0.050 0.040 89 84 89 74 99 93 85 79
Code-3 Horn 0.069 0.091 0.026 0.035 0.100 0.142 0.023 0.034 0.050 0.042 88 83 88 73 99 93 85 75
Code-3 Tone 0.061 0.075 0.026 0.035 0.088 0.105 0.015 0.021 0.042 0.040 85 80 84 70 95 90 79 75
Slow Whoop 0.069 0.098 0.028 0.037 0.100 0.142 0.025 0.035 0.050 0.042 90 89 89 75 99 94 88 82
Siren 0.080 0.104 0.027 0.036 0.122 0.152 0.021 0.030 0.045 0.041 89 84 89 75 98 93 85 82
HI/LO 0.044 0.057 0.020 0.026 0.089 0.114 0.018 0.026 0.042 0.039 86 81 86 71 93 88 82 79
* RMS current ratings are per UL average RMS
method. UL max current rating is the maximum RMS
current within the listed voltage range (16-33v for 24v
units). For strobes the UL max current is usually at
the minimum listed voltage (16v for 24v units). For
audibles the max current is usually at the maximum
listed voltage (33v for 24v units). For unfiltered FWR
ratings, see installation instructions.
WARNING: CONTACT WHEELOCK FOR THE CURRENT “INSTALLATION INSTRUCTIONS” P82467 MT-12/24, P84155 MT w/Strobe
P84150 MTWP WEATHERPROOF “GENERAL INFORMATION” SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS DO
UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE
MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE
PRODUCTS, INCLUDING:
• TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
• FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON
THOSE CIRCUITS.
• COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON’S FIELD OF VIEW.
• THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED INPUT VOLTAGE RANGE.
• INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES.
• USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON
CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY
NOT FLASH.
• FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT
IN IMPROPER INSTALLATION, APPLICATION, AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
• CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND
INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters’ Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
Wiring Diagrams (for all models)
Specifications and Ordering Information
**MTWP-2475W is Weatherproof and rated for 180 cd @ 77°F (25°C). See Data Sheet S9004 or Installation Instruction P84150.
***For additional information on mounting please refer to Data Sheet S7000.
# 1575 strobes are UL Listed for 15cd with 75cd on AXIS.
## Series WH Strobe is listed for UL Standard 1638 only. See Instruction Sheet P83160.
Model
Number
Order
Code
Input
Voltage
Rated
Candela
Mounting
Options***
Agency Approvals
UL MEA CSFM FM BFP
MT-12/24-R 5023 12/24 -D,E,F,L,M,O,P,R X X X X X
MT-12/24-W 5024 12/24 -D,E,F,L,M,O,P,R X X X X X
MT-241575W-FR#8422 24 15 (75 on AXIS)D,E,F,L,M,O,P,R X X X X *
MT-24MCW-FR 3301 24 15/30/75/110 D,E,F,L,M,O,P,R X *X **
MT-24MCW-FW 3303 24 15/30/75/110 D,E,F,L,M,O,P,R X *X **
MT-121575W-FR#8421 12 15 (75 on AXIS)D,E,F,L,M,O,P,R X X X X *
MT-121575W-NW 9747 12 15 (75 on AXIS)D,E,F,L,M,O,P,R X X X X *
MTWP-2475W-FR**8420 24 180 @ 77°F (25°C)M X X X X *
MTWP-2475W-NW**9744 24 180 @ 77°F (25°C)M X X X X *
MT4-115-R 6223 120 VAC -D,E,J,K,N,O,R X X X X X
MT4-115-S 6142 120 VAC -D,E,J,K,N,O,R X X X X X
MT4-115-WH-VFR##6224 120 VAC 15 D,E,J,K,N,O,R X X X X X
MT4-12/24-R 5308 12/24 -D,E,J,K,N,O,R X ****
MT4-12/24-S 7997 12/24 -D,E,J,K,N,O,R X ****
NOTE:
MT SIGNAL AUDIBLE SIGNAL AND STROBE OPERATE
IN UNISON. RED AND BLACK SHUNT-WIRES
ARE SUPPLIED.
AUDIBLE SIGNAL AND STROBE
OPERATE INDEPENDENTLY
*Pending
Architects and Engineers Specifications
S2000 MT 06/06
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Wheelock Inc. standard terms and conditions.
The notification appliance shall be a Wheelock Series MT audible/visual appliance or equivalent. Notification appliance shall be
electronic and use solid state components. Electromechanical alternatives are not approved. Each electronic appliance shall provide
eight (8) field selectable alarm tones. The tones shall consist of: HORN, BELL, MARCH TIME HORN, CODE-3 HORN, CODE-3
TONE, SLOW WHOOP, SIREN and HI/LO. Tone selection shall be by durable dip switch assembly and not clips or jumpers. The
Multitone Audible appliance shall be UL Listed under Standard 464 for Audible Signal Appliances. The audible and the strobe shall
be able to operate from a single NAC circuit while producing any of these tones. The appliance shall provide two output sound levels:
STANDARD and HIGH dBA. The HIGH dBA setting shall provide a minimum 5 dBA increase in sound output at nominal voltage. The
HIGH anechoic dBA measurement at 10 feet at the alarm HORN SETTING shall be 99 dBA minimum. Operating voltages shall be
either 12 VDC or 24 VDC using filtered power or unfiltered power supply (full-wave-rectified). All models shall have provisions for
standard reverse polarity type supervision and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring.
Combination audible/visual appliances shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens or equivalent with solid
state circuitry. Strobe shall produce a flash rate of one (1) flash per second minimum over the voltage range. The MT strobe intensity
shall be rated per UL and Listed under Standard 1971 for Signaling Devices for the Hearing Impaired for 1575cd multi-candela with field
selectable 15/30/75/110 candela settings. The 1575 candela strobe shall be specified when 15 candela or with 75 candela intensity
on-axis is required. Strobe Models shall incorporate circuitry for synchronized strobe flash and shall be designed for compatibility
with Wheelock SM and/or DSM Sync Modules or Wheelock’s Power Supplies with Sync Protocol. The strobes shall not drift out of
synchronization at any time during operation. If the module fails to operate (i.e., contacts remain closed), the strobes shall revert to a
non-synchronized default flash rate. Strobe activation shall be via independent input or from the same input circuit as the audible.
The combination audible/visual appliances shall be installed indoors and may be surface or flush mounted. They shall mount to
standard electrical hardware requiring no additional trimplate or adapter. The aesthetic appearance shall not have any mounting holes
or screw heads visible when the installation is completed. The appliance shall be finished in a textured red color.
The Series MT-12/24, MTWP and MT4 appliances may be installed indoor or outdoor with the proper back box.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Made in USA
273 Branchport Avenue
Long Branch, NJ 07740
Phone: (800) 631-2148
Fax: (732) 222-2588
www.cooperwheelock.com