LOAD SHORT FORM - 20-00190 - Shaw - 907 Pine Brook Ln - New SFR
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1 ...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Load Short Form 2/28/2020Date:Entire House Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor: 170 N Eastern Ave, Idaho Falls,, Idaho Phone: 208-523-5542 Email: derik@alpineheatingair.com Design Information InfiltrationClgHtg SimplifiedMethod90-7Outside db (°F) Semi-tightConstruction quality7570Inside db (°F) 0Fireplaces1577Design TD (°F) H-Daily range 5050Inside humidity (%) -2962Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Carrier Make Carrier Trade Carrier Comfort 95 Single-Stag...Trade CARRIER Model 59SC5B060E17--14 Cond 24ABB336A00610 AHRI ref 0 Coil CNPVP3617ALA++TDR AHRI ref 9165046 Efficiency 96.5 AFUE Efficiency 10.5 EER, 13 SEER Heating input Btuh60000 Sensible cooling Btuh32301 Heating output Btuh46980 Latent cooling Btuh0 Temperature rise °F55 Total cooling Btuh32301 Actual air flow cfm925 Actual air flow cfm1127 Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.069 Static pressure in H2O0.90 Static pressure in H2O0.90 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Mech 78 0 0 0 0 Storage 203 0 0 0 0 Br 5 WIC 58 1189 57 33 4 Bedroom 5 162 1573 1026 44 71 Room5 66 330 5 9 0 Bedroom 4 240 1944 1032 54 71 Family Rm 664 4530 1459 127 101 Bedroom 6 214 2151 782 60 54 Br 6 WIC 43 540 11 15 1 Cold Rm 44 0 0 0 0 TR 31 906 290 25 20 Utility 85 1806 801 51 55 Master 234 1811 1380 51 95 M WIC 57 1101 139 31 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2 ...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N M Bath 88 836 418 23 29 Bath 50 486 266 14 18 Bedroom 2 166 2460 737 69 51 Bedroom 3 129 1331 609 37 42 Kit/din/living rm 760 7007 5809 196 401 Sitting Rm 213 3055 1503 85 104 Entire House 3585 33056 16322 925 1127 Other equip loads 7412 1411 Equip. @ 0.95 RSM 16776 Latent cooling 0 TOTALS 3585 40467 16776 925 1127 2020-Mar-27 14:54:30 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Building Analysis 2/28/2020Date:Entire House Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 36.3147044.4Walls 14.1571324.5Glazing 4.7188529.9Doors 7.028501.5Ceilings 7.731351.71.7Floors 11.847702.0Infiltration 00Ducts00Piping00Humidification18.37412Ventilation0Adjustments100.040467Total Cooling Walls Glazing DoorsCeilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 4.98620.3Walls 38.1675129.0Glazing 2.64577.3Doors 8.815640.8Ceilings 000Floors2.74780.2Infiltration 00Ducts8.01411Ventilation35.06210Internal gains 00Blower0Adjustments100.017733Total Latent Cooling Load = 0 BtuhOverall U-value = 0.048 Btuh/ft²-°F Data entries checked. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Entire House Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 2110.4821844.9921.00.065438n 80.48794.9921.00.06516ne 1600.4816554.9921.00.065332e 2300.4823794.9921.00.065477s 1650.4817054.9921.00.065342w 90.48894.9921.00.06518nw 7810.4880924.9921.00.0651623all 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 300.0522273.8519.00.043578n 110.0410793.6919.00.043292e 240.0420583.7719.00.043546s 170.0512483.8519.00.043324w 810.0566123.8019.00.0431741all Partitions(none) Windows2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 67911.3147324.500.32060n 34435.923524.500.32010ne 47447.424524.500.32010e 151847.478524.500.32032e 243330.4196424.500.32080s 97330.478524.500.32032s 32935.922524.500.3209nw 675129.0571324.500.320233all Doors11D0: Door, wd sc type 3057.25125629.900.39042n 1527.2562829.900.39021s 4577.25188529.900.39063all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 15640.8428501.5350.00.0201858 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.0221772 0029901.69 001451.6900.02286 0031351.6900.0221858all 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Mech Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings (none) Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02278 001321.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Storage Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 70.054853.8519.00.043126n 60.054333.8519.00.043113w 120.059193.8519.00.043239all Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.022203 003421.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 5...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Br 5 WIC Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 30.052433.8519.00.04363n Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02258 00981.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 6...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Bedroom 5 Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 60.054423.8519.00.043115n 20.033233.6019.00.04390e 80.047653.7419.00.043205all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 75947.439324.500.32016e Doors(none) Ceilings(none) Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.022162 002731.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 7...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Room5 Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 30.051913.8519.00.04350e Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02266 001111.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 8...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Bedroom 4 Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 40.034273.6519.00.043117e 80.055633.8519.00.043146s 110.049903.7619.00.043263all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 75947.439324.500.32016e Doors(none) Ceilings(none) Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.022240 004041.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 9...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Family Rm Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 40.052773.8519.00.04372n 130.0410683.7719.00.043283s 160.0513453.7919.00.043355all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 48730.439324.500.32016s Doors(none) Ceilings(none) Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.022664 0011211.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 10...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Bedroom 6 Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 30.052513.8519.00.04365n 40.034273.6519.00.043117s 70.055293.8519.00.043137w 140.0512073.7819.00.043319all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 48730.439324.500.32016s Doors(none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 20.8431.5350.00.0202 Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.022214 003611.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 11...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Br 6 WIC Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 30.052603.8519.00.04368n 20.051473.8519.00.04338w 50.054073.8519.00.043106all Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02243 00731.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 12...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Cold Rm Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, light dry soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 40.052693.8519.00.04370n 20.051393.8519.00.04336e 20.051393.8519.00.04336w 70.055463.8519.00.043142all Partitions(none) Windows (none) Doors (none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 360.84661.5350.00.02043 Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02244 00741.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 13...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:TR Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 310.483184.9921.00.06564s 170.481794.9921.00.06536w 480.484974.9921.00.065100all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 18330.414724.500.3206s Doors(none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 260.84481.5350.00.02031 Floors (none) 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 14...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Utility Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 210.482214.9921.00.06544n 480.484944.9921.00.06599w 690.487144.9921.00.065143all Partitions(none) Windows (none) Doors 11D0: Door, wd sc type 1527.2562829.900.39021n Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 720.841311.5350.00.02085 Floors(none) 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 15...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Master Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 500.485174.9921.00.065104s 100.481014.9921.00.06520w 600.486184.9921.00.065124all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 60830.449124.500.32020s Doors(none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 1970.843591.5350.00.020234 Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02231 00521.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 16...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:M WIC Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 260.482694.9921.00.06554e 410.484264.9921.00.06586s 670.486954.9921.00.065140all Partitions(none) Windows (none) Doors (none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 480.84871.5350.00.02057 Floors21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02221 00361.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 17...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:M Bath Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 370.483854.9921.00.06577e Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 28547.414724.500.3206e Doors(none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 740.841351.5350.00.02088 Floors (none) 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 18...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Bath Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 210.482164.9921.00.06543e Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 19047.49824.500.3204e Doors(none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 420.84771.5350.00.02050 Floors (none) 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 19...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Bedroom 2 Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 380.483944.9921.00.06579n 670.486954.9921.00.065140e 80.48794.9921.00.06516w 1130.4811684.9921.00.065234all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 22611.349124.500.32020n Doors(none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 1400.842541.5350.00.020166 Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02219 00321.69 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 20...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Bedroom 3 Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 330.483384.9921.00.06568n 90.48904.9921.00.06518w 410.484284.9921.00.06586all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 22611.349124.500.32020n Doors(none) Ceilings16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 1090.841981.5350.00.020129 Floors (none) 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 21...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Kit/din/living rm Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 830.488604.9921.00.065173n 1080.4811184.9921.00.065224s 190.482024.9921.00.06541w 2100.4821804.9921.00.065437all Partitions(none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 164330.4132524.500.32054s Doors11D0: Door, wd sc type 1527.2562829.900.39021n 1527.2562829.900.39021s 3057.25125629.900.39042all Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 6400.8411661.5350.00.020760 Floors (none) 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 22...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Component Constructions 2/28/2020Date:Sitting Rm Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542 Email: derik@alpineheatingair.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 1577Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-29.461.7Moisture difference (gr/lb)CoolingHeating Infiltration:90-7Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) Semi-tightConstruction quality61-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-0sw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 360.483714.9921.00.06575n 80.48794.9921.00.06516ne 90.48904.9921.00.06518e 540.485614.9921.00.065113w 90.48894.9921.00.06518nw 1150.4811914.9921.00.065239all Partitions (none) Windows 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk: 2 glazing, clr low-e outr, argon gas, vnl frm mat, clr innr, 1/2" gap, 1/8" thk; foreground = new concrete (0.32); 6.67 ft head ht 22611.349124.500.32020n 34435.923524.500.32010ne 32935.922524.500.3209nw 90023.295124.500.32039all Doors(none) Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 1800.843271.5350.00.020213 Floors 21A-28v: Bg floor, light dry soil, 6.5' depth, vinyl flr fnsh 00.02214 00241.69 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Project Summary 2/28/2020Date:Entire House Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor:170 N Eastern Ave, Idaho Falls,, IdahoPhone: 208-523-5542Email: derik@alpineheatingair.comINFORMATION CONTAINED WITHIN THE REPORT IS PER THE RESCHECK COMPLIANCE CERTIFICATE. IF ANY OF THESE VALUES SHOULD CHANGE, THIS REPORT WILL BE NULL AND VOID. Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-7 Outside db °F90Inside db °F70 Inside db °F75Design TD °F77 Design TD °F15Daily range HRelative humidity %50Moisture difference gr/lb-29 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh33056 Structure Btuh16322DuctsBtuh0DuctsBtuh0Central vent (105 cfm)7412 Btuh Central vent (105 cfm)Btuh1411Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh40467 Use manufacturer's data nRate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh16776 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Semi-tight0Fireplaces Structure Btuh806DuctsBtuh0Central vent (105 cfm)Btuh-1754CoolingHeatingOutside air35853585Area (ft²)Equipment latent load Btuh02125421254Volume (ft³)Air changes/hour 0.100.19 Equipment Total Load (Sen+Lat)Btuh16776Equiv. AVF (cfm)3567 Req. total capacity at 1.00 SHR ton1.4 Heating Equipment Summary Cooling Equipment Summary Make Carrier Make CarrierTradeCarrier Comfort 95 Single-Stag...Trade CARRIERModel59SC5B060E17--14 Cond 24ABB336A00610AHRI ref 0 Coil CNPVP3617ALA++TDRAHRI ref 9165046Efficiency96.5 AFUE Efficiency 10.5 EER, 13 SEERHeating input Btuh60000 Sensible cooling Btuh32301Heating output Btuh46980 Latent cooling Btuh0Temperature rise °F55 Total cooling Btuh32301Actual air flow cfm925 Actual air flow cfm1127Air flow factor cfm/Btuh0.028 Air flow factor cfm/Btuh0.069Static pressure in H2O0.90 Static pressure in H2O0.90Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Entire House Mech 2 Exposed wall 406.6 ft 0 ft3Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft78.4x1.0 5 Room area 3584.6 ft²78.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 540 438 2184 211 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 60 0 1473 679 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 42 42 1256 305 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 578 578 2227 30 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 25 16 79 8 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 10 0 235 344 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 342 332 1655 160 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 10 0 245 474 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 324 292 1079 11 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 32 0 785 1518 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 578 477 2379 230 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 80 0 1964 2433 0 0 0 0DD11D011D00.3900.390 ss 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 578 546 2058 24 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 32 0 785 973 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 342 342 1705 165 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 324 324 1248 17 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 27 18 89 9 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 9 0 225 329 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 1858 1858 2850 1564 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 1772 1772 2990 0 78 78 132 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 86 86 145 0 0 0 0 0 6 c) AED excursion 0 0 Envelope loss/gain 28285 9634 132 0 12 a)Infiltration 4770 478 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 7 1610 0 0 Appliances/other 4600 0 Subtotal (lines 6 to 13)33056 16322 132 0 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00-132 014Subtotal330561632200 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 33056 16322 0 0 Air required (cfm)Air required (cfm)925 1127 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Storage Br 5 WIC 2 Exposed wall 26.5 ft 7.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.8x14.8 ft7.8x7.5 5 Room area 202.8 ft²58.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 126 126 485 7 63 63 243 3 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 113 113 433 6 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 203 203 342 0 58 58 98 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -1 0 Envelope loss/gain 1261 12 341 3 12 a)Infiltration 134 13 35 4 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1395 25 376 7 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-1395 -25 813 5014Subtotal00118957 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 1189 57 Air required (cfm)Air required (cfm)0 0 33 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 5 Room5 2 Exposed wall 24.5 ft 5.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft161.8x1.0 ft5.5x12.0 5 Room area 161.8 ft²66.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 115 115 442 6 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 106 90 323 2 50 50 191 3GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 16 0 393 759 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 162 162 273 0 66 66 111 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 16 0 Envelope loss/gain 1430 783 302 2 12 a)Infiltration 124 12 28 3 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1554 1026 330 5 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution1800014Subtotal157310263305 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1573 1026 330 5 Air required (cfm)Air required (cfm)44 71 9 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 4 Family Rm 2 Exposed wall 31.0 ft 41.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft14.8x16.3 ft664.2x1.0 5 Room area 239.7 ft²664.2 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 0 0 0 0 72 72 277 4 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 133 117 427 4 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 16 0 393 759 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 146 146 563 8 299 283 1068 13GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 16 0 393 487 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 0 0 0 0 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 240 240 404 0 664 664 1121 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 16 10 Envelope loss/gain 1787 786 2859 513 12 a)Infiltration 157 16 209 21 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 900 Subtotal (lines 6 to 13)1944 1032 3068 1434 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution0014622514Subtotal1944103245301459 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1944 1032 4530 1459 Air required (cfm)Air required (cfm)54 71 127 101 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 5...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 6 Br 6 WIC 2 Exposed wall 37.3 ft 11.8 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft213.7x1.0 ft5.8x7.5 5 Room area 213.7 ft²43.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 65 65 251 3 68 68 260 3 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 133 117 427 4 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 16 0 393 487 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 137 137 529 7 38 38 147 2 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 2 2 3 2 0 0 0 0FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 214 214 361 0 43 43 73 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 31 0 Envelope loss/gain 1963 533 480 5 12 a)Infiltration 189 19 59 6 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2151 782 540 11 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal215178254011 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2151 782 540 11 Air required (cfm)Air required (cfm)60 54 15 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 6...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Cold Rm TR 2 Exposed wall 15.8 ft 11.8 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft44.0x1.0 ft4.0x7.8 5 Room area 44.0 ft²31.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 70 70 269 4 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 36 36 139 2 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 70 64 318 31GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 6 0 147 183DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 36 36 179 17 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 36 36 139 2 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 43 43 66 36 31 31 48 26FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 44 44 74 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -2 12 Envelope loss/gain 686 42 692 268 12 a)Infiltration 80 8 214 21 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)766 50 906 290 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-766 -50 0 014Subtotal00906290 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 906 290 Air required (cfm)Air required (cfm)0 0 25 20 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 7...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Utility Master 2 Exposed wall 18.3 ft 16.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft11.0x7.8 ft17.0x13.8 5 Room area 85.3 ft²233.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 65 44 221 21 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 21 21 628 152 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 124 104 517 50GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 20 0 491 608DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 99 99 494 48 20 20 101 10 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 85 85 131 72 234 234 359 197FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 31 31 52 0 6 c) AED excursion -25 26 Envelope loss/gain 1473 268 1520 891 12 a)Infiltration 333 33 292 29 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 2 460 Appliances/other 500 0 Subtotal (lines 6 to 13)1806 801 1811 1380 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal180680118111380 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1806 801 1811 1380 Air required (cfm)Air required (cfm)51 55 51 95 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 8...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name M WIC M Bath 2 Exposed wall 15.5 ft 9.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.0x9.5 ft9.3x9.5 5 Room area 57.0 ft²87.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 0 0 0 0.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 54 54 269 26 83 77 385 37GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 6 0 147 285 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 86 86 426 41 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 57 57 87 48 88 88 135 74FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 21 21 36 0 0 0 0 0 6 c) AED excursion -4 5 Envelope loss/gain 819 111 667 401 12 a)Infiltration 282 28 169 17 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1101 139 836 418 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal1101139836418 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1101 139 836 418 Air required (cfm)Air required (cfm)31 10 23 29 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 9...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bath Bedroom 2 2 Exposed wall 5.3 ft 28.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.3x9.5 ft165.7x1.0 5 Room area 49.9 ft²165.7 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 0 0 0 0 99 79 394 38.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 0 0 0 0 20 0 491 226.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 47 43 216 21 140 140 695 67GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 4 0 98 190 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 0 0 0 0 16 16 79 8 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 50 50 77 42 166 166 254 140FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 19 19 32 0 6 c) AED excursion 4 -23 Envelope loss/gain 390 256 1945 455 12 a)Infiltration 96 10 515 52 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13)486 266 2460 737 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal4862662460737 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 486 266 2460 737 Air required (cfm)Air required (cfm)14 18 69 51 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 10...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Bedroom 3 Kit/din/living rm 2 Exposed wall 11.8 ft 59.3 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft129.2x1.0 ft759.8x1.0 5 Room area 129.2 ft²759.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-0sw12F-0sw 0.0650.065 nn 4.994.99 0.480.48 88 68 338 33 194 173 860 83.GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nn 24.5424.54 11.3211.32 20 0 491 226 0 0 0 0.DD 11D011D0 0.3900.390 nn 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 nn 3.853.85 0.050.05 0 0 0 0 0 0 0 0 11 WW 12F-0sw12F-0sw 0.0650.065 nene 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nene 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ee 4.994.99 0.480.48 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ee 3.693.69 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ee 24.5424.54 47.4247.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ss 4.994.99 0.480.48 0 0 0 0 299 224 1118 108GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 54 0 1325 1643DD11D011D00.3900.390 ss 29.9129.91 7.257.25 0 0 0 0 21 21 628 152 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ss 3.773.77 0.040.04 0 0 0 0 0 0 0 0GG2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 ss 24.5424.54 30.4230.42 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 ww 4.994.99 0.480.48 18 18 90 9 41 41 202 19 WW 15B19-0wc-615B19-0wc-6 0.0690.069 ww 3.853.85 0.050.05 0 0 0 0 0 0 0 0 WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.994.99 0.480.48 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3202 glazing, clr low-e 0.320 nwnw 24.5424.54 35.9235.92 0 0 0 0 0 0 0 0CC16B-50ad16B-50ad 0.0200.020 --1.531.53 0.840.84 129 129 198 109 760 760 1166 640FF21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 FF 21A-28v21A-28v 0.0220.022 --1.691.69 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -19 4 Envelope loss/gain 1117 357 5927 2801 12 a)Infiltration 214 21 1080 108 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 0 2900 Subtotal (lines 6 to 13)1331 609 7007 5809 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal133160970075809 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1331 609 7007 5809 Air required (cfm)Air required (cfm)37 42 196 401 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:30Right-Suite® Universal 2019 19.0.12 RSU28163 Page 11...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J® Worksheet 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Room name Sitting Rm 2 Exposed wall 30.8 ft3Room height 9.0 heat/coolft 4 Room dimensions ft213.4x1.0 5 Room area 213.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 n 4.99 0.48 95 75 371 36.G 2 glazing, clr low-e 0.320 n 24.54 11.32 20 0 491 226.D 11D0 0.390 n 29.91 7.25 0 0 0 0 .W 15B19-0wc-6 0.069 n 3.85 0.05 0 0 0 0 11 W 12F-0sw 0.065 ne 4.99 0.48 25 16 79 8 G 2 glazing, clr low-e 0.320 ne 24.54 35.92 10 0 235 344 W 12F-0sw 0.065 e 4.99 0.48 18 18 90 9G2 glazing, clr low-e 0.320 e 24.54 47.42 0 0 0 0 W 15B19-0wc-6 0.069 e 3.69 0.04 0 0 0 0G2 glazing, clr low-e 0.320 e 24.54 47.42 0 0 0 0 W 12F-0sw 0.065 s 4.99 0.48 0 0 0 0G2 glazing, clr low-e 0.320 s 24.54 30.42 0 0 0 0D11D00.390 s 29.91 7.25 0 0 0 0 W 15B19-0wc-6 0.069 s 3.77 0.04 0 0 0 0G2 glazing, clr low-e 0.320 s 24.54 30.42 0 0 0 0 W 12F-0sw 0.065 w 4.99 0.48 113 113 561 54 W 15B19-0wc-6 0.069 w 3.85 0.05 0 0 0 0 W 12F-0sw 0.065 nw 4.99 0.48 27 18 89 9 G 2 glazing, clr low-e 0.320 nw 24.54 35.92 9 0 225 329C16B-50ad 0.020 -1.53 0.84 213 213 327 180F21A-28v 0.022 -1.69 0.00 0 0 0 0 F 21A-28v 0.022 -1.69 0.00 14 14 24 0 6 c) AED excursion -47 Envelope loss/gain 2493 1147 12 a)Infiltration 562 56 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 300 Subtotal (lines 6 to 13)3055 1503 Less external load 0 0 Less transfer 0 0Redistribution0014Subtotal30551503 15 Duct loads -0%0%0 0 Total room load 3055 1503 Air required (cfm)85 104 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Entire House Mech 2 Running Feet of Exposed Wall 406.6 ft 0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²8899.1ft 9.0 ft²369.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²3584.6 1.0 x 78.4 ft ft²78.4 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²3584.6°0 ft²78.4° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 540 2184 211 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 60 1473 679 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 42 1256 305 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 578 2227 30 0 0 0 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 25 79 8 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 10 235 344 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 342 1655 160 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 10 245 474 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 324 1079 11 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 32 785 1518 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 578 2379 230 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 80 1964 2433 0 0 0DoorDoor11D011D0ss29.9129.91 7.257.25 21 628 152 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 578 2058 24 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 32 785 973 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 342 1705 165 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 324 1248 17 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 27 89 9 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 9 225 329 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 1858 2850 1564 0 0 0FlorFlor21A-28v21A-28v --1.691.69 0.000.00 1772 2990 0 78 132 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 86 145 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 4770 0EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 478 0 00.100.10 Latent Load (Btuh)-594 Internal a Occupants at 230 and 200 Btuh 7 1610 1400 0 0 0 b Scenario number 3400 0 13 c Default Adjustments d Custom Appliances 1200 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 33056 16322 806 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 7412 1411 -1754 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 0 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 40467 17733 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Storage Br 5 WIC 2 Running Feet of Exposed Wall 26.5 ft 7.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²497.3ft 9.0 ft²255.3ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)14.8 x 13.8 ft ft²202.8 7.5 x 7.8 ft ft²58.1 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²202.8°0 ft²58.1° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 0 0 0 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 126 485 7 63 243 3 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 113 433 6 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 0 0 0 0 0 0FlorFlor21A-28v21A-28v --1.691.69 0.000.00 203 342 0 58 98 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 134 35EffectWARWAR 12 Sensible Load (Btuh)ACH 0.03 13 0.01 40.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 1189 57 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -1 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 1189 57 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 3...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Bedroom 5 Room5 2 Running Feet of Exposed Wall 24.5 ft 5.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²458.3ft 9.0 ft²297.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 161.8 ft ft²161.8 12.0 x 5.5 ft ft²66.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²161.8°0 ft²66.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 0 0 0 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 115 442 6 0 0 0 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 106 323 2 50 191 3GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 16 393 759 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 0 0 0 0 0 0FlorFlor21A-28v21A-28v --1.691.69 0.000.00 162 273 0 66 111 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 124 28EffectWARWAR 12 Sensible Load (Btuh)ACH 0.03 12 0.01 30.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 1 230 200 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1573 1026 330 5 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 16 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1573 1026 330 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 4...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Bedroom 4 Family Rm 2 Running Feet of Exposed Wall 31.0 ft 41.3 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²540.5ft 9.0 ft²1009.3ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)16.3 x 14.8 ft ft²239.7 1.0 x 664.2 ft ft²664.2 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²239.7°0 ft²664.2° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 0 0 0 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 0 0 0 72 277 4 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 133 427 4 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 16 393 759 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 146 563 8 299 1068 13GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 16 393 487 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 0 0 0 0 0 0FlorFlor21A-28v21A-28v --1.691.69 0.000.00 240 404 0 664 1121 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 157 209EffectWARWAR 12 Sensible Load (Btuh)ACH 0.03 16 0.04 210.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 1 230 200 0 0 0 b Scenario number 0 900 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1944 1032 4530 1459 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 16 10 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1944 1032 4530 1459 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 5...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Bedroom 6 Br 6 WIC 2 Running Feet of Exposed Wall 37.3 ft 11.8 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²498.0ft 9.0 ft²217.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 213.7 ft ft²213.7 7.5 x 5.8 ft ft²43.1 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²213.7°0 ft²43.1° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 0 0 0 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 65 251 3 68 260 3 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 133 427 4 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 16 393 487 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 137 529 7 38 147 2 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 2 3 2 0 0 0FlorFlor21A-28v21A-28v --1.691.69 0.000.00 214 361 0 43 73 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 189 59EffectWARWAR 12 Sensible Load (Btuh)ACH 0.04 19 0.01 60.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 1 230 200 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2151 782 540 11 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 31 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2151 782 540 11 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 6...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Cold Rm TR 2 Running Feet of Exposed Wall 15.8 ft 11.8 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²247.5ft 9.0 ft²211.5ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 44.0 ft ft²44.0 7.8 x 4.0 ft ft²31.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²44.0°0 ft²31.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 0 0 0 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 70 269 4 0 0 0 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 36 139 2 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 70 318 31GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 6 147 183DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 0 0 0 36 179 17 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 36 139 2 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 43 66 36 31 48 26FlorFlor21A-28v21A-28v --1.691.69 0.000.00 44 74 0 0 0 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 80 214EffectWARWAR 12 Sensible Load (Btuh)ACH 0.02 8 0.04 210.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 906 290 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -2 12 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 906 290 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 7...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Utility Master 2 Running Feet of Exposed Wall 18.3 ft 16.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²318.3ft 9.0 ft²499.8ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)7.8 x 11.0 ft ft²85.3 13.8 x 17.0 ft ft²233.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²85.3°0 ft²233.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 65 221 21 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 21 628 152 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 0 0 0 0 0 0 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 124 517 50GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 20 491 608DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 99 494 48 20 101 10 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 85 131 72 234 359 197FlorFlor21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 31 52 0 Infiltration Heating Load (Btuh)0.190.19 333 292EffectWARWAR 12 Sensible Load (Btuh)ACH 0.07 33 0.06 290.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 2 460 400 b Scenario number 500 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1806 801 1811 1380 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -25 26 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1806 801 1811 1380 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 8...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room M WIC M Bath 2 Running Feet of Exposed Wall 15.5 ft 9.3 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²261.5ft 9.0 ft²320.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)9.5 x 6.0 ft ft²57.0 9.5 x 9.3 ft ft²87.9 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²57.0°0 ft²87.9° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 0 0 0 0 0 0.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 0 0 0 0 0 0 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 54 269 26 83 385 37GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 6 147 285 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 86 426 41 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 57 87 48 88 135 74FlorFlor21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 21 36 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 282 169EffectWARWAR 12 Sensible Load (Btuh)ACH 0.06 28 0.04 170.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1101 139 836 418 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -4 5 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1101 139 836 418 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 9...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Bath Bedroom 2 2 Running Feet of Exposed Wall 5.3 ft 28.3 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²246.8ft 9.0 ft²477.2ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)9.5 x 5.3 ft ft²49.9 1.0 x 165.7 ft ft²165.7 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²49.9°0 ft²165.7° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 0 0 0 99 394 38.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 0 0 0 20 491 226.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 0 0 0 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 0 0 0 0 0 0 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 47 216 21 140 695 67GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 4 98 190 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 0 0 0 16 79 8 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 50 77 42 166 254 140FlorFlor21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 19 32 0 Infiltration Heating Load (Btuh)0.190.19 96 515EffectWARWAR 12 Sensible Load (Btuh)ACH 0.02 10 0.11 520.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 1 230 200 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 486 266 2460 737 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 4 -23 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 486 266 2460 737 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 10...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Bedroom 3 Kit/din/living rm 2 Running Feet of Exposed Wall 11.8 ft 59.3 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²387.6ft 9.0 ft²1312.1ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 129.2 ft ft²129.2 1.0 x 759.8 ft ft²759.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²129.2°0 ft²759.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-0sw12F-0sw nn 4.994.99 0.480.48 88 338 33 194 860 83.GlazGlaz 2 glazing, clr low-e n2 glazing, clr low-e n 24.5424.54 11.3211.32 20 491 226 0 0 0.DoorDoor 11D011D0 nn 29.9129.91 7.257.25 0 0 0 21 628 152 .WallWall 15B19-0wc-615B19-0wc-6 nn 3.853.85 0.050.05 0 0 0 0 0 0 11 WallWall 12F-0sw12F-0sw nene 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e ne2 glazing, clr low-e ne 24.5424.54 35.9235.92 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ee 4.994.99 0.480.48 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 15B19-0wc-615B19-0wc-6 ee 3.693.69 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e e2 glazing, clr low-e e 24.5424.54 47.4247.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ss 4.994.99 0.480.48 0 0 0 299 1118 108GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 54 1325 1643DoorDoor11D011D0ss29.9129.91 7.257.25 0 0 0 21 628 152 WallWall 15B19-0wc-615B19-0wc-6 ss 3.773.77 0.040.04 0 0 0 0 0 0GlazGlaz2 glazing, clr low-e s2 glazing, clr low-e s 24.5424.54 30.4230.42 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw ww 4.994.99 0.480.48 18 90 9 41 202 19 WallWall 15B19-0wc-615B19-0wc-6 ww 3.853.85 0.050.05 0 0 0 0 0 0 WallWall 12F-0sw12F-0sw nwnw 4.994.99 0.480.48 0 0 0 0 0 0 GlazGlaz 2 glazing, clr low-e nw2 glazing, clr low-e nw 24.5424.54 35.9235.92 0 0 0 0 0 0CeilCeil16B-50ad16B-50ad --1.531.53 0.840.84 129 198 109 760 1166 640FlorFlor21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 FlorFlor 21A-28v21A-28v --1.691.69 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.190.19 214 1080EffectWARWAR 12 Sensible Load (Btuh)ACH 0.04 21 0.23 1080.100.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 1 230 200 0 0 0 b Scenario number 0 2000 13 c Default Adjustments d Custom Appliances 0 0 900 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1331 609 7007 5809 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 105105 E CfmE Cfm 105105 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -19 4 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1331 609 7007 5809 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-27 14:54:32Right-Suite® Universal 2019 19.0.12 RSU28163 Page 11...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Right-J8® Form J1 2/28/2020Date:Entire House Gene MillerBy:GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com 1 Name of Room Sitting Rm 2 Running Feet of Exposed Wall 30.8 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²473.8ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 213.4 ft ft²213.4 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²213.4° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12F-0sw n 4.99 0.48 95 371 36.Glaz 2 glazing, clr low-e n 24.54 11.32 20 491 226.Door 11D0 n 29.91 7.25 0 0 0 .Wall 15B19-0wc-6 n 3.85 0.05 0 0 0 11 Wall 12F-0sw ne 4.99 0.48 25 79 8 Glaz 2 glazing, clr low-e ne 24.54 35.92 10 235 344 Wall 12F-0sw e 4.99 0.48 18 90 9Glaz2 glazing, clr low-e e 24.54 47.42 0 0 0 Wall 15B19-0wc-6 e 3.69 0.04 0 0 0Glaz2 glazing, clr low-e e 24.54 47.42 0 0 0 Wall 12F-0sw s 4.99 0.48 0 0 0Glaz2 glazing, clr low-e s 24.54 30.42 0 0 0Door11D0s29.91 7.25 0 0 0 Wall 15B19-0wc-6 s 3.77 0.04 0 0 0Glaz2 glazing, clr low-e s 24.54 30.42 0 0 0 Wall 12F-0sw w 4.99 0.48 113 561 54 Wall 15B19-0wc-6 w 3.85 0.05 0 0 0 Wall 12F-0sw nw 4.99 0.48 27 89 9 Glaz 2 glazing, clr low-e nw 24.54 35.92 9 225 329Ceil16B-50ad -1.53 0.84 213 327 180Flor21A-28v -1.69 0.00 0 0 0 Flor 21A-28v -1.69 0.00 14 24 0 Infiltration Heating Load (Btuh)0.19 562EffectWAR 12 Sensible Load (Btuh)ACH 0.12 560.10 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 b Scenario number 0 13 c Default Adjustments d Custom Appliances 300 0ePlants0 14 Subtotals Sum lines 6 through 12 3055 1503 Duct EHLF & ESGF 0 0 0 015Loads ELG 0 Vent Cfm16Ventilation Loads 105 E Cfm 105 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -47 21 Total Load Sum lines 13 through 19 3055 1503 Job #: 907 Pine Brook Ln Performed by Gene Miller for: Alpine Heating And Air 170 N Eastern Ave Idaho Falls,, Idaho Phone: 208-523-5542 derik@alpineheatingair.com Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 107 Page 1 Right-Suite® Universal 2019 19.0.12 RSU28163 2020-Mar-27 14:55:42 ...e - Shaw - 907 PINE BROOK LN.rup N Basement Mech Storage Br 5 WIC Bedroom 5 Room5 Bedroom 4 Family Rm Bedroom 6 Br 6 WIC Cold Rm 71 cfm 71 cfm 63 cfm 9 cfm 33 cfm 15 cfm 63 cfm 60 cfm 6 " 6 " 14x3.25 14x3.25 6 " 14x3.25 6 "6 " 6 " 6 "6 " 6 " 6 " 6 " 6 " 6 " 6 " 6 " 28 x 8 22 x 814x3.2514x3.25 6 " 2-14x3.25 10 x 8 16 x 8 6 " 14x3.25 283 cfm 2-14x3.25 14 x 8 6 "6 " 8 " 6 " 10 x 8 8 x 8 6 " 6 " 12 x 88 x 8 60 cfm 4 x 8 Job #: 907 Pine Brook Ln Performed by Gene Miller for: Alpine Heating And Air 170 N Eastern Ave Idaho Falls,, Idaho Phone: 208-523-5542 derik@alpineheatingair.com Mechanical Compliance Solutions 4181 Aschli lane Idaho Falls, ID 83406 Phone: 208-881-3243 gene.mechcompliancesolutions@gmail.com Scale: 1 : 107 Page 2 Right-Suite® Universal 2019 19.0.12 RSU28163 2020-Mar-27 14:55:42 ...e - Shaw - 907 PINE BROOK LN.rup N Main Floor TR Utility Master M WIC M Bath Bath Bedroom 2 Bedroom 3 Kit/din/living rm Sitting Rm Pantry 25 cfm 55 cfm 52 cfm 52 cfm 69 cfm 42 cfm 18 cfm 29 cfm 95 cfm 80 cfm 80 cfm 80 cfm80 cfm 80 cfm 31 cfm 321 cfm 134 cfm 42 cfm 69 cfm 278 cfm 2020-Mar-27 14:54:33 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 1 ...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N 907 Pine Brook LnJob:Duct System Summary 2/28/2020Date:Entire House Gene MillerBy: GallatinePlan:Mechanical Compliance Solutions 4181 Aschli lane, Idaho Falls, ID 83406 Phone: 208-881-3243 Email: gene.mechcompliancesolutions@gmail.com Project Information Alpine Heating And AirFor: 170 N Eastern Ave, Idaho Falls,, Idaho Phone: 208-523-5542 Email: derik@alpineheatingair.com CoolingHeating External static pressure in H2O0.90in H2O0.90 Pressure losses in H2O0.41in H2O0.41 Available static pressure in H2O0.49in H2O0.49 Supply / return available pressure 0.244 / 0.246 in H2O in H2O0.244 / 0.246 Lowest friction rate in/100ft0.082in/100ft0.082 Actual air flow cfm1127cfm925 Total effective length (TEL)ft600 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st3210.021.5ShMt0x06.00.1061814266cBath st3A240.043.3ShMt0x06.00.08651692460hBedroom 2 st3230.031.0ShMt0x06.00.0944237609cBedroom 3 st3A220.032.0ShMt0x06.00.09771541032cBedroom 4 st3A230.040.0ShMt0x06.00.09171441026cBedroom 5 st4B245.054.3ShMt4x85.00.08254602151hBedroom 6 st3240.030.5ShMt0x06.00.0904331189hBr 5 WIC st4B250.045.0ShMt0x06.00.083115540hBr 6 WIC st4225.023.8ShMt0x06.00.09850632265hFamily Rm st4A230.042.0ShMt0x06.00.09050632265hFamily Rm-A st4220.027.3ShMt0x06.00.09980391162cKit/din/living rm st4A235.035.3ShMt0x06.00.09080391162cKit/din/living rm-A st4A220.049.8ShMt0x06.00.09180391162cKit/din/living rm-B 95.07.0ShMt0x06.00.24080391162cKit/din/living rm-C st4210.031.8ShMt0x06.00.10180391162cKit/din/living rm-D st3220.024.0ShMt0x06.00.1002923418cM Bath st3A235.038.8ShMt0x06.00.08910311101hM WIC st3235.026.8ShMt0x06.00.09395511380cMaster st3225.023.3ShMt0x06.00.09809330hRoom5 st2155.016.8ShMt0x06.00.1425243752cSitting Rm st2145.027.0ShMt0x06.00.1425243752cSitting Rm-A st4B240.056.0ShMt0x06.00.0832025906hTR st4B230.048.5ShMt0x06.00.0885551801cUtility Bold/italic values have been manually overridden 2020-Mar-27 14:54:33 Right-Suite® Universal 2019 19.0.12 RSU28163 Page 2 ...e\Shaw\Gallatine - Shaw - 907 PINE BROOK LN.rup Calc = MJ8 Front Door faces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 365 391 0.086 587 10.0 12x8 ShtMetl st1 st4B Peak AVF 151 130 0.082 340 6.0 8x8 ShtMetl st4A st2 Peak AVF 85 104 0.142 297 8.0 0x0 ShtMetl st1 Peak AVF 800 943 0.082 772 14.0 22x8 ShtMetl st3A Peak AVF 198 203 0.086 456 7.8 8x8 ShtMetl st3 st4 Peak AVF 435 552 0.082 709 11.5 14x8 ShtMetl st1 st4A Peak AVF 293 341 0.082 614 9.6 10x8 ShtMetl st4 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb1 0x 2830 248 273.3 0.090 447 8.8 2-3.25x14 2-10x18 SJSp rt2 rb3 0x 1570 321 230.5 0.107 508 8.9 2-3.25x14 2-10x18 SJSp rt3 rb4 0x 1050 134 300.8 0.082 423 6.8 3.25x14 10x9 SJSp rt3 rb5 0x 370 42 219.8 0.112 133 4.1 3.25x14 10x9 SJSp rt3 rb6 0x 690 51 257.0 0.096 218 5.1 3.25x14 10x9 SJSp rt3 rb7 0x 2140 278 87.8 0.280 879 6.9 3.25x14 10x9 SJSp rt1 rb8 0x 600 54 0 0 191 0 3.25x14 10x9 SJSp Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt3 Peak AVF 368 547 0.082 616 11.4 16x8 ShtMetl rt1 rt2 Peak AVF 283 248 0.090 509 8.8 10x8 ShtMetl rt1 rt1 Peak AVF 865 1073 0.082 690 14.7 28x8 ShtMetl