Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
PROJECT INFORMATION - 20-00142-00144 - 1030 S 5th W - Eden Townhomes
2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Manual S Compliance Report Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Cooling Equipment Design Conditions °F76.2Entering coil DB:Btuh12725Sensible gain:°F97.1Outdoor design DB: °F61.9Entering coil WB:Btuh0Latent gain:°F64.4Outdoor design WB: Btuh12725Total gain:°F75.0Indoor design DB: cfm600Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 4TTR3018H1+4GXCB004AC6HUAModel:TraneManufacturer: cfm600Actual airflow: % of load113Btuh14400Sensible capacity: % of load0Btuh3600Latent capacity: %80SHR:% of load141Btuh18000Total capacity: Heating Equipment Design Conditions °F65.5Entering coil DB:Btuh16584Heat loss:°F-13Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Gas furnaceEquipment type: S9X1B040U2PS***Model:TraneManufacturer: cfm600Actual airflow: °F50Temp. rise:% of load235Btuh39000Output capacity: Meets all requirements of ACCA Manual S. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Manual S Compliance Report Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Cooling Equipment Design Conditions °F76.5Entering coil DB:Btuh12010Sensible gain:°F97.1Outdoor design DB: °F61.9Entering coil WB:Btuh0Latent gain:°F64.4Outdoor design WB: Btuh12010Total gain:°F75.0Indoor design DB: cfm600Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 4TTR3018H1+TMM4A0B18S21SAModel:TraneManufacturer: cfm600Actual airflow: % of load120Btuh14400Sensible capacity: % of load0Btuh3600Latent capacity: %80SHR:% of load150Btuh18000Total capacity: Heating Equipment Design Conditions °F64.6Entering coil DB:Btuh13532Heat loss:°F-13Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Gas furnaceEquipment type: S9X1B040U2PS***Model:TraneManufacturer: cfm600Actual airflow: °F50Temp. rise:% of load288Btuh39000Output capacity: Meets all requirements of ACCA Manual S. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Manual S Compliance Report Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Cooling Equipment Design Conditions °F76.5Entering coil DB:Btuh11954Sensible gain:°F97.1Outdoor design DB: °F61.9Entering coil WB:Btuh0Latent gain:°F64.4Outdoor design WB: Btuh11954Total gain:°F75.0Indoor design DB: cfm593Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 4TTR3018H1+GMU2APB30Model:TraneManufacturer: cfm593Actual airflow: % of load119Btuh14240Sensible capacity: % of load0Btuh3560Latent capacity: %80SHR:% of load149Btuh17800Total capacity: Heating Equipment Design Conditions °F64.5Entering coil DB:Btuh13452Heat loss:°F-13Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Gas furnaceEquipment type: S9X1B040U2PS***Model:TraneManufacturer: cfm593Actual airflow: °F50Temp. rise:% of load290Btuh39000Output capacity: Meets all requirements of ACCA Manual S. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Manual S Compliance Report Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Cooling Equipment Design Conditions °F76.5Entering coil DB:Btuh12010Sensible gain:°F97.1Outdoor design DB: °F61.9Entering coil WB:Btuh0Latent gain:°F64.4Outdoor design WB: Btuh12010Total gain:°F75.0Indoor design DB: cfm593Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 4TTR3018H1+GMU2APB30Model:TraneManufacturer: cfm593Actual airflow: % of load119Btuh14240Sensible capacity: % of load0Btuh3560Latent capacity: %80SHR:% of load148Btuh17800Total capacity: Heating Equipment Design Conditions °F64.5Entering coil DB:Btuh13532Heat loss:°F-13Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Gas furnaceEquipment type: S9X1B040U2PS***Model:TraneManufacturer: cfm593Actual airflow: °F50Temp. rise:% of load288Btuh39000Output capacity: Meets all requirements of ACCA Manual S. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Manual S Compliance Report Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Cooling Equipment Design Conditions °F76.2Entering coil DB:Btuh12589Sensible gain:°F97.1Outdoor design DB: °F61.9Entering coil WB:Btuh0Latent gain:°F64.4Outdoor design WB: Btuh12589Total gain:°F75.0Indoor design DB: cfm593Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 4TTR3018H1+GMU2APB30Model:TraneManufacturer: cfm593Actual airflow: % of load113Btuh14240Sensible capacity: % of load0Btuh3560Latent capacity: %80SHR:% of load141Btuh17800Total capacity: Heating Equipment Design Conditions °F65.5Entering coil DB:Btuh16265Heat loss:°F-13Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Gas furnaceEquipment type: S9X1B040U2PS***Model:TraneManufacturer: cfm593Actual airflow: °F50Temp. rise:% of load240Btuh39000Output capacity: Meets all requirements of ACCA Manual S. Right-Suite® Universal 2019 19.0.13 RSU12258 Form RPER 1 15 Mar 09 Residential Plans Examiner Review Form for HVAC System Design (Loads, Equipment, Ducts) Header Information Contractor:ATTACHEDREQUIRED ATTACHMENTSJM Mechanical NoYesManual J1 Form (and supporting worksheets):Brock AlmondMechanical license:NoYesor MJ1AE Form* (and supporting worksheets): NoYesOEM performance data (heating, cooling, blower): Building plan #:NoYesManual D Friction Rate Worksheet: NoYesDuct distribution sketch: Home address (Street or Lot#, Block, Subdivision):555 Mikn, Unit1 HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Front Door faces SouthBuildingWinter Design Conditions North, East, West, South, Northeast, Northwest, Southeast, SouthwestOrientation:°F-13Outdoor temperature: °F70Indoor temperature: 1Number of bedrooms:Btuh16584Total heat loss: ft²637Conditioned floor area: 2Number of occupants:Summer Design Conditions °F97Outdoor temperature: Windows°F75Indoor temperature: ft0Eave overhang depth:% RH50gr/lb @-22Grains difference: Blinds, drapes, etc.noneInternal shade:Btuh12463Sensible heat gain: Btuh0Latent heat gain: 0Number of skylights:Btuh12463Total heat gain: HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Blower DataCooling Equipment Data 600Heating cfm:Air Conditioner, Heat pump, etc.Split ACEquipment type:Furnace, Heat pump, Boiler, etc.Gas furnaceEquipment type: 600Cooling cfm: Fan's rated external static pressure for design airflow in H2O0.80Static pressure:TraneModel:TraneModel: S9X1B040U2PS***4TTR3018H1+4GXCB004AC6HUA Btuh0Total cooling capacity:Heat pumps - capacity at winter design outdoor conditionsBtuh39000Heating output capacity: Btuh0Sensible cooling capacity: Btuh0Latent cooling capacity:Btuh0Aux. heating output capacity: HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Duct Materials Usedft229Longest supply duct:cfm600Design airflow: Sheet metalTrunk duct:ft140Longest return duct:in H2O0.80Equipment design ESP: ft369Total effective length (TEL):in H2O-0.4Total device pressure losses: Sheet metal, Stud/joist spaceBranch duct:Friction Rate = ASP ÷ (TEL x 100)in/100ft0.111Friction rate:in H2O0.41Available static pressure (ASP): I declare the load calculation, equipment, equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature:Date: Reserved for County, Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist Right-Suite® Universal 2019 19.0.13 RSU12258 Form RPER 1 15 Mar 09 Residential Plans Examiner Review Form for HVAC System Design (Loads, Equipment, Ducts) Header Information Contractor:ATTACHEDREQUIRED ATTACHMENTSJM Mechanical NoYesManual J1 Form (and supporting worksheets):Brock AlmondMechanical license:NoYesor MJ1AE Form* (and supporting worksheets): NoYesOEM performance data (heating, cooling, blower): Building plan #:NoYesManual D Friction Rate Worksheet: NoYesDuct distribution sketch: Home address (Street or Lot#, Block, Subdivision):555 Mikn, Unit2 HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Front Door faces SouthBuildingWinter Design Conditions North, East, West, South, Northeast, Northwest, Southeast, SouthwestOrientation:°F-13Outdoor temperature: °F70Indoor temperature: 0Number of bedrooms:Btuh13532Total heat loss: ft²637Conditioned floor area: 2Number of occupants:Summer Design Conditions °F97Outdoor temperature: Windows°F75Indoor temperature: ft0Eave overhang depth:% RH50gr/lb @-22Grains difference: Blinds, drapes, etc.noneInternal shade:Btuh11763Sensible heat gain: Btuh0Latent heat gain: 0Number of skylights:Btuh11763Total heat gain: HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Blower DataCooling Equipment Data 600Heating cfm:Air Conditioner, Heat pump, etc.Split ACEquipment type:Furnace, Heat pump, Boiler, etc.Gas furnaceEquipment type: 600Cooling cfm: Fan's rated external static pressure for design airflow in H2O0.80Static pressure:TraneModel:TraneModel: S9X1B040U2PS***4TTR3018H1+TMM4A0B18S21SA Btuh0Total cooling capacity:Heat pumps - capacity at winter design outdoor conditionsBtuh39000Heating output capacity: Btuh0Sensible cooling capacity: Btuh0Latent cooling capacity:Btuh0Aux. heating output capacity: HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Duct Materials Usedft225Longest supply duct:cfm600Design airflow: Sheet metalTrunk duct:ft101Longest return duct:in H2O0.80Equipment design ESP: ft326Total effective length (TEL):in H2O-0.4Total device pressure losses: Sheet metal, Stud/joist spaceBranch duct:Friction Rate = ASP ÷ (TEL x 100)in/100ft0.126Friction rate:in H2O0.41Available static pressure (ASP): I declare the load calculation, equipment, equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature:Date: Reserved for County, Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist Right-Suite® Universal 2019 19.0.13 RSU12258 Form RPER 1 15 Mar 09 Residential Plans Examiner Review Form for HVAC System Design (Loads, Equipment, Ducts) Header Information Contractor:ATTACHEDREQUIRED ATTACHMENTSJM Mechanical NoYesManual J1 Form (and supporting worksheets):Brock AlmondMechanical license:NoYesor MJ1AE Form* (and supporting worksheets): NoYesOEM performance data (heating, cooling, blower): Building plan #:NoYesManual D Friction Rate Worksheet: NoYesDuct distribution sketch: Home address (Street or Lot#, Block, Subdivision):555 Mikn, Unit3 HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Front Door faces SouthBuildingWinter Design Conditions North, East, West, South, Northeast, Northwest, Southeast, SouthwestOrientation:°F-13Outdoor temperature: °F70Indoor temperature: 0Number of bedrooms:Btuh13452Total heat loss: ft²637Conditioned floor area: 2Number of occupants:Summer Design Conditions °F97Outdoor temperature: Windows°F75Indoor temperature: ft0Eave overhang depth:% RH50gr/lb @-22Grains difference: Blinds, drapes, etc.noneInternal shade:Btuh11708Sensible heat gain: Btuh0Latent heat gain: 0Number of skylights:Btuh11708Total heat gain: HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Blower DataCooling Equipment Data 593Heating cfm:Air Conditioner, Heat pump, etc.Split ACEquipment type:Furnace, Heat pump, Boiler, etc.Gas furnaceEquipment type: 593Cooling cfm: Fan's rated external static pressure for design airflow in H2O0.80Static pressure:TraneModel:TraneModel: S9X1B040U2PS***4TTR3018H1+GMU2APB30 Btuh0Total cooling capacity:Heat pumps - capacity at winter design outdoor conditionsBtuh39000Heating output capacity: Btuh0Sensible cooling capacity: Btuh0Latent cooling capacity:Btuh0Aux. heating output capacity: HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Duct Materials Usedft225Longest supply duct:cfm593Design airflow: Sheet metalTrunk duct:ft111Longest return duct:in H2O0.80Equipment design ESP: ft336Total effective length (TEL):in H2O-0.4Total device pressure losses: Sheet metal, Stud/joist spaceBranch duct:Friction Rate = ASP ÷ (TEL x 100)in/100ft0.122Friction rate:in H2O0.41Available static pressure (ASP): I declare the load calculation, equipment, equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature:Date: Reserved for County, Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist Right-Suite® Universal 2019 19.0.13 RSU12258 Form RPER 1 15 Mar 09 Residential Plans Examiner Review Form for HVAC System Design (Loads, Equipment, Ducts) Header Information Contractor:ATTACHEDREQUIRED ATTACHMENTSJM Mechanical NoYesManual J1 Form (and supporting worksheets):Brock AlmondMechanical license:NoYesor MJ1AE Form* (and supporting worksheets): NoYesOEM performance data (heating, cooling, blower): Building plan #:NoYesManual D Friction Rate Worksheet: NoYesDuct distribution sketch: Home address (Street or Lot#, Block, Subdivision):555 Mikn, Unit4 HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Front Door faces SouthBuildingWinter Design Conditions North, East, West, South, Northeast, Northwest, Southeast, SouthwestOrientation:°F-13Outdoor temperature: °F70Indoor temperature: 0Number of bedrooms:Btuh13532Total heat loss: ft²637Conditioned floor area: 2Number of occupants:Summer Design Conditions °F97Outdoor temperature: Windows°F75Indoor temperature: ft0Eave overhang depth:% RH50gr/lb @-22Grains difference: Blinds, drapes, etc.noneInternal shade:Btuh11763Sensible heat gain: Btuh0Latent heat gain: 0Number of skylights:Btuh11763Total heat gain: HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Blower DataCooling Equipment Data 593Heating cfm:Air Conditioner, Heat pump, etc.Split ACEquipment type:Furnace, Heat pump, Boiler, etc.Gas furnaceEquipment type: 593Cooling cfm: Fan's rated external static pressure for design airflow in H2O0.80Static pressure:TraneModel:TraneModel: S9X1B040U2PS***4TTR3018H1+GMU2APB30 Btuh0Total cooling capacity:Heat pumps - capacity at winter design outdoor conditionsBtuh39000Heating output capacity: Btuh0Sensible cooling capacity: Btuh0Latent cooling capacity:Btuh0Aux. heating output capacity: HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Duct Materials Usedft442Longest supply duct:cfm593Design airflow: Sheet metalTrunk duct:ft140Longest return duct:in H2O0.80Equipment design ESP: ft582Total effective length (TEL):in H2O-0.4Total device pressure losses: Sheet metal, Stud/joist spaceBranch duct:Friction Rate = ASP ÷ (TEL x 100)in/100ft0.071Friction rate:in H2O0.41Available static pressure (ASP): I declare the load calculation, equipment, equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature:Date: Reserved for County, Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist Right-Suite® Universal 2019 19.0.13 RSU12258 Form RPER 1 15 Mar 09 Residential Plans Examiner Review Form for HVAC System Design (Loads, Equipment, Ducts) Header Information Contractor:ATTACHEDREQUIRED ATTACHMENTSJM Mechanical NoYesManual J1 Form (and supporting worksheets):Brock AlmondMechanical license:NoYesor MJ1AE Form* (and supporting worksheets): NoYesOEM performance data (heating, cooling, blower): Building plan #:NoYesManual D Friction Rate Worksheet: NoYesDuct distribution sketch: Home address (Street or Lot#, Block, Subdivision):555 Mikn, Unit5 HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Front Door faces SouthBuildingWinter Design Conditions North, East, West, South, Northeast, Northwest, Southeast, SouthwestOrientation:°F-13Outdoor temperature: °F70Indoor temperature: 0Number of bedrooms:Btuh16265Total heat loss: ft²637Conditioned floor area: 2Number of occupants:Summer Design Conditions °F97Outdoor temperature: Windows°F75Indoor temperature: ft0Eave overhang depth:% RH50gr/lb @-22Grains difference: Blinds, drapes, etc.noneInternal shade:Btuh12330Sensible heat gain: Btuh0Latent heat gain: 0Number of skylights:Btuh12330Total heat gain: HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Blower DataCooling Equipment Data 593Heating cfm:Air Conditioner, Heat pump, etc.Split ACEquipment type:Furnace, Heat pump, Boiler, etc.Gas furnaceEquipment type: 593Cooling cfm: Fan's rated external static pressure for design airflow in H2O0.80Static pressure:TraneModel:TraneModel: S9X1B040U2PS***4TTR3018H1+GMU2APB30 Btuh0Total cooling capacity:Heat pumps - capacity at winter design outdoor conditionsBtuh39000Heating output capacity: Btuh0Sensible cooling capacity: Btuh0Latent cooling capacity:Btuh0Aux. heating output capacity: HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Duct Materials Usedft228Longest supply duct:cfm593Design airflow: Sheet metalTrunk duct:ft141Longest return duct:in H2O0.80Equipment design ESP: ft369Total effective length (TEL):in H2O-0.4Total device pressure losses: Sheet metal, Stud/joist spaceBranch duct:Friction Rate = ASP ÷ (TEL x 100)in/100ft0.111Friction rate:in H2O0.41Available static pressure (ASP): I declare the load calculation, equipment, equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature:Date: Reserved for County, Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Mar 17, 2020Date:Entire House By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Information InfiltrationClgHtg SimplifiedMethod97-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2283Design TD (°F) H-Daily range 5050Inside humidity (%) -2263Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Unit2 d 637 10583 11226 600 600 Unit1 d 637 14158 12080 600 600 Unit3 d 637 10503 11170 593 593 Unit4 d 637 10583 11226 593 593 Unit5 d 637 13839 11944 593 593 Entire House d 3183 59665 57644 2980 2980 Other equip loads 13699 3643 Equip. @ 1.02 RSM 62575 Latent cooling 1104 TOTALS 3183 73364 63679 2980 2980 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Information InfiltrationClgHtg SimplifiedMethod97-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2283Design TD (°F) H-Daily range 5050Inside humidity (%) -2263Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade TRANE Trade TRANE Model S9X1B040U2PS***Cond 4TTR3018H1 AHRI ref 202555287 Coil 4GXCB004AC6HUA AHRI ref 10350056 Efficiency 95 AFUE Efficiency 11.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh14400 Heating output Btuh39000 Latent cooling Btuh3600 Temperature rise °F70 Total cooling Btuh18000 Actual air flow cfm600 Actual air flow cfm600 Air flow factor cfm/Btuh0.042 Air flow factor cfm/Btuh0.050 Static pressure in H2O0.80 Static pressure in H2O0.80 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) 1Bed 150 3287 2001 139 99 1Bath 42 778 216 33 11 1Clos 36 0 0 0 0 1Living 163 4278 3860 181 192 1Kit 108 321 1331 14 66 1Stair 30 0 0 0 0 1Foy 18 3796 2507 161 125 1Ldr 32 1698 2165 72 108 1Mech 18 0 0 0 0 1DStair 40 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Unit1 d 637 14158 12080 600 600 Other equip loads 2426 645 Equip. @ 1.02 RSM 12992 Latent cooling 0 TOTALS 637 16584 12992 600 600 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Information InfiltrationClgHtg SimplifiedMethod97-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2283Design TD (°F) H-Daily range 5050Inside humidity (%) -2263Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade TRANE Trade TRANE Model S9X1B040U2PS***Cond 4TTR3018H1 AHRI ref 202555287 Coil TMM4A0B18S21SA AHRI ref 8593277 Efficiency 95 AFUE Efficiency 11.5 EER, 13.5 SEER Heating input Btuh40000 Sensible cooling Btuh14400 Heating output Btuh39000 Latent cooling Btuh3600 Temperature rise °F70 Total cooling Btuh18000 Actual air flow cfm600 Actual air flow cfm600 Air flow factor cfm/Btuh0.057 Air flow factor cfm/Btuh0.053 Static pressure in H2O0.80 Static pressure in H2O0.80 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) 2Bed 150 2120 1754 120 94 2Bath 42 778 216 44 12 2Clos 36 0 0 0 0 2Living 163 2259 3337 128 178 2Stair 30 0 0 0 0 2Kit 108 321 1330 18 71 2Ldr 32 1698 2164 96 116 2Foy 18 3408 2424 193 130 2DStair 40 0 0 0 0 2Mech 18 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Unit2 d 637 10583 11226 600 600 Other equip loads 2949 784 Equip. @ 1.02 RSM 12262 Latent cooling 0 TOTALS 637 13532 12262 600 600 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Information InfiltrationClgHtg SimplifiedMethod97-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2283Design TD (°F) H-Daily range 5050Inside humidity (%) -2263Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade TRANE Trade TRANE Model S9X1B040U2PS***Cond 4TTR3018H1 AHRI ref 202555287 Coil GMU2APB30 AHRI ref 202410016 Efficiency 95 AFUE Efficiency 11.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh14240 Heating output Btuh39000 Latent cooling Btuh3560 Temperature rise °F71 Total cooling Btuh17800 Actual air flow cfm593 Actual air flow cfm593 Air flow factor cfm/Btuh0.056 Air flow factor cfm/Btuh0.053 Static pressure in H2O0.80 Static pressure in H2O0.80 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) 3Bed 150 2040 1630 115 87 3Foy 18 3408 2441 192 130 3DStair 40 0 0 0 0 3Mech 18 0 0 0 0 3Stair 30 0 0 0 0 3Kit 108 321 1340 18 71 3Living 163 2259 3361 128 178 3Ldr 32 1698 2180 96 116 3Bath 42 778 218 44 12 3Clos 36 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 7 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Unit3 d 637 10503 11170 593 593 Other equip loads 2949 784 Equip. @ 1.02 RSM 12205 Latent cooling 0 TOTALS 637 13452 12205 593 593 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 8 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Information InfiltrationClgHtg SimplifiedMethod97-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2283Design TD (°F) H-Daily range 5050Inside humidity (%) -2263Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade TRANE Trade TRANE Model S9X1B040U2PS***Cond 4TTR3018H1 AHRI ref 202555287 Coil GMU2APB30 AHRI ref 202410016 Efficiency 95 AFUE Efficiency 11.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh14240 Heating output Btuh39000 Latent cooling Btuh3560 Temperature rise °F71 Total cooling Btuh17800 Actual air flow cfm593 Actual air flow cfm593 Air flow factor cfm/Btuh0.056 Air flow factor cfm/Btuh0.053 Static pressure in H2O0.80 Static pressure in H2O0.80 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) 4Living 163 2259 3337 127 176 4DStair 40 0 0 0 0 4Mech 18 0 0 0 0 4Foy 18 3408 2424 191 128 4Ldr 32 1698 2164 95 114 4Kit 108 321 1330 18 70 4Clos 36 0 0 0 0 4Stair 30 0 0 0 0 4Bed 150 2120 1754 119 93 4Bath 42 778 216 44 11 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 9 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Unit4 d 637 10583 11226 593 593 Other equip loads 2949 784 Equip. @ 1.02 RSM 12262 Latent cooling 0 TOTALS 637 13532 12262 593 593 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 10 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Load Short Form Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Information InfiltrationClgHtg SimplifiedMethod97-13Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces2283Design TD (°F) H-Daily range 5050Inside humidity (%) -2263Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade TRANE Trade TRANE Model S9X1B040U2PS***Cond 4TTR3018H1 AHRI ref 202555287 Coil GMU2APB30 AHRI ref 202410016 Efficiency 95 AFUE Efficiency 11.5 EER, 13 SEER Heating input Btuh40000 Sensible cooling Btuh14240 Heating output Btuh39000 Latent cooling Btuh3560 Temperature rise °F71 Total cooling Btuh17800 Actual air flow cfm593 Actual air flow cfm593 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.050 Static pressure in H2O0.80 Static pressure in H2O0.80 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) 5Living 163 2259 3346 97 166 5DStair 40 0 0 0 0 5Foy 18 3796 2512 163 125 5Mech 18 0 0 0 0 5Clos 36 0 0 0 0 5Bed 150 2279 1792 98 89 5Stair 30 0 0 0 0 5Kit 108 1821 1651 78 82 5Bath 42 1597 390 68 19 5Ldr 32 2087 2252 89 112 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 11 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Unit5 d 637 13839 11944 593 593 Other equip loads 2426 645 Equip. @ 1.02 RSM 12853 Latent cooling 0 TOTALS 637 16265 12853 593 593 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Load Multizone Summary Report Mar 17, 2020Date: By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Infiltration Summary Heating Cooling ZONE NAME Volume ACH AVF HTM Volume ACH AVF HTM ft³cfm Btuh/ft²ft³cfm Btuh/ft² 0.5 18 0.19 5729 3.2 34 0.36 5729Unit1 0.5 12 0.12 5729 3.2 22 0.23 5729Unit2 0.5 12 0.12 5729 3.2 22 0.23 5729Unit3 0.5 12 0.12 5729 3.2 22 0.23 5729Unit4 0.5 18 0.19 5729 3.2 34 0.36 5729Unit5 Entire House 28643 0.28 134 3.2 28643 0.15 72 0.5 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Load and AVF Summary ROOM NAME Area Htg load Clg load Htg AVF Clg AVF ft²Btuh Btuh cfm cfm 99 139 2001 3287 1501Bed 11 33 216 778 421Bath 0 0 0 0 361Clos 192 181 3860 4278 1631Living 66 14 1331 321 1081Kit 0 0 0 0 301Stair 125 161 2507 3796 181Foy 108 72 2165 1698 321Ldr 0 0 0 0 181Mech 0 0 0 0 401DStair 600 600 12080 14158 637Unit1 94 120 1754 2120 1502Bed 12 44 216 778 422Bath 0 0 0 0 362Clos 178 128 3337 2259 1632Living 0 0 0 0 302Stair 71 18 1330 321 1082Kit 116 96 2164 1698 322Ldr 130 193 2424 3408 182Foy 0 0 0 0 402DStair 0 0 0 0 182Mech 600 600 11226 10583 637Unit2 87 115 1630 2040 1503Bed 130 192 2441 3408 183Foy 0 0 0 0 403DStair 0 0 0 0 183Mech 0 0 0 0 303Stair 71 18 1340 321 1083Kit 178 128 3361 2259 1633Living 116 96 2180 1698 323Ldr 12 44 218 778 423Bath 0 0 0 0 363Clos 593 593 11170 10503 637Unit3 176 127 3337 2259 1634Living 0 0 0 0 404DStair 0 0 0 0 184Mech 128 191 2424 3408 184Foy 114 95 2164 1698 324Ldr 70 18 1330 321 1084Kit 0 0 0 0 364Clos 0 0 0 0 304Stair 93 119 1754 2120 1504Bed 11 44 216 778 424Bath 593 593 11226 10583 637Unit4 166 97 3346 2259 1635Living 0 0 0 0 405DStair 125 163 2512 3796 185Foy 0 0 0 0 185Mech 0 0 0 0 365Clos 89 98 1792 2279 1505Bed 0 0 0 0 305Stair 82 78 1651 1821 1085Kit 19 68 390 1597 425Bath 112 89 2252 2087 325Ldr 593 593 11944 13839 637Unit5 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Entire House 3183 59665 57644 2980 2980 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Mar 17, 2020Date:Entire House By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Other Infiltration Ventilation % of loadBtuhBtuh/ft²Component 27.9204717.6Walls 23.01686347.4Glazing 4.6340332.4Doors 10.274522.7Ceilings 1.712133.23.2Floors 14.0102643.2Infiltration 00Ducts00Piping00Humidification18.713699Ventilation0Adjustments100.073364Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 8.551981.9Walls 48.72984583.8Glazing 1.7106910.2Doors 7.344481.6Ceilings 0.53220.8Floors 2.414620.5Infiltration 00Ducts5.93643Ventilation25.015300Internal gains 00Blower0Adjustments100.061288Total Latent Cooling Load = 1104 BtuhOverall U-value = 0.094 Btuh/ft²-°F Data entries checked. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Other Infiltration Ventilation % of loadBtuhBtuh/ft²Component 32.654117.6Walls 22.3369547.4Glazing 4.168132.4Doors 9.014902.7Ceilings 1.52433.23.2Floors 15.926393.2Infiltration 00Ducts00Piping00Humidification14.62426Ventilation0Adjustments100.016584Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 10.813741.9Walls 48.0610278.2Glazing 1.721410.2Doors 7.08901.6Ceilings 0.5640.8Floors 3.03760.5Infiltration 00Ducts5.1645Ventilation24.03060Internal gains 00Blower0Adjustments100.012725Total Latent Cooling Load = 0 BtuhOverall U-value = 0.096 Btuh/ft²-°F Data entries checked. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Other Infiltration Ventilation % of loadBtuhBtuh/ft²Component 23.631917.6Walls 24.5331647.4Glazing 5.068132.4Doors 11.014902.7Ceilings 1.82433.23.2Floors 12.316623.2Infiltration 00Ducts00Piping00Humidification21.82949Ventilation0Adjustments100.013532Total Cooling Walls Glazing Other Ceilings Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 6.78101.9Walls 49.5595185.0Glazing 1.821410.2Doors 7.48901.6Ceilings 0.5640.8Floors 2.02370.5Infiltration 00Ducts6.5784Ventilation25.53060Internal gains 00Blower0Adjustments100.012010Total Latent Cooling Load = 0 BtuhOverall U-value = 0.094 Btuh/ft²-°F Data entries checked. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Other Infiltration Ventilation % of loadBtuhBtuh/ft²Component 23.832067.6Walls 23.9322147.4Glazing 5.168132.4Doors 11.114902.7Ceilings 1.82433.23.2Floors 12.416623.2Infiltration 00Ducts00Piping00Humidification21.92949Ventilation0Adjustments100.013452Total Cooling Walls Glazing Other Ceilings Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 6.88141.9Walls 49.3589186.6Glazing 1.821410.2Doors 7.48901.6Ceilings 0.5640.8Floors 2.02370.5Infiltration 00Ducts6.6784Ventilation25.63060Internal gains 00Blower0Adjustments100.011954Total Latent Cooling Load = 0 BtuhOverall U-value = 0.093 Btuh/ft²-°F Data entries checked. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Other Infiltration Ventilation % of loadBtuhBtuh/ft²Component 23.631917.6Walls 24.5331647.4Glazing 5.068132.4Doors 11.014902.7Ceilings 1.82433.23.2Floors 12.316623.2Infiltration 00Ducts00Piping00Humidification21.82949Ventilation0Adjustments100.013532Total Cooling Walls Glazing Other Ceilings Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 6.78101.9Walls 49.5595185.0Glazing 1.821410.2Doors 7.48901.6Ceilings 0.5640.8Floors 2.02370.5Infiltration 00Ducts6.5784Ventilation25.53060Internal gains 00Blower0Adjustments100.012010Total Latent Cooling Load = 0 BtuhOverall U-value = 0.094 Btuh/ft²-°F Data entries checked. 2020-Mar-20 14:34:52 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Building Analysis Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation:5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F)SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Other Infiltration Ventilation % of loadBtuhBtuh/ft²Component 33.654717.6Walls 20.4331647.4Glazing 4.268132.4Doors 9.214902.7Ceilings 1.52433.23.2Floors 16.226393.2Infiltration 00Ducts00Piping00Humidification14.92426Ventilation0Adjustments100.016265Total Cooling Walls Glazing Other Ceilings Infiltration Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.013891.9Walls 47.3595185.0Glazing 1.721410.2Doors 7.18901.6Ceilings 0.5640.8Floors 3.03760.5Infiltration 00Ducts5.1645Ventilation24.33060Internal gains 00Blower0Adjustments100.012589Total Latent Cooling Load = 0 BtuhOverall U-value = 0.093 Btuh/ft²-°F Data entries checked. 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:Entire House By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 5641.9222197.5613.00.091294n 15301.9260277.5613.00.091797e 5791.9222807.5613.00.091302s 25251.9299447.5613.00.0911315w 51981.92204717.5613.00.0912707all Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 18623.237947.400.5708n 377065.0274747.400.57058e 1885065.01373647.400.570290w 2280664.11686347.400.570356all Doors11D0: Door, wd sc type 106910.2340332.400.390105w Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 44481.5974522.6630.00.0322803 Floors 19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 3220.8512133.1919.00.049380 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 5641.9222197.5613.00.091294n 3051.9212027.5613.00.091159e 5051.9219897.5613.00.091263w 13741.9254117.5613.00.091716all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 18623.237947.400.5708n 78065.056847.400.57012e 377065.0274747.400.57058w 473660.7369547.400.57078all Doors11D0: Door, wd sc type 21410.268132.400.39021w Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 8901.5914902.6630.00.032561 Floors 19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 640.852433.1919.00.04976 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 3051.9212027.5613.00.091159e 5051.9219897.5613.00.091263w 8101.9231917.5613.00.091422all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 78065.056847.400.57012e 377065.0274747.400.57058w 455065.0331647.400.57070all Doors11D0: Door, wd sc type 21410.268132.400.39021w Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 8901.5914902.6630.00.032561 Floors 19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 640.852433.1919.00.04976 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 3091.9212177.5613.00.091161e 5051.9219897.5613.00.091263w 8141.9232067.5613.00.091424all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 65065.047447.400.57010e 377065.0274747.400.57058w 442065.0322147.400.57068all Doors11D0: Door, wd sc type 21410.268132.400.39021w Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 8901.5914902.6630.00.032561 Floors 19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 640.852433.1919.00.04976 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 3051.9212027.5613.00.091159e 5051.9219897.5613.00.091263w 8101.9231917.5613.00.091422all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 78065.056847.400.57012e 377065.0274747.400.57058w 455065.0331647.400.57070all Doors11D0: Door, wd sc type 21410.268132.400.39021w Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 8901.5914902.6630.00.032561 Floors 19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 640.852433.1919.00.04976 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 3051.9212027.5613.00.091159e 5791.9222807.5613.00.091302s 5051.9219897.5613.00.091263w 13891.9254717.5613.00.091724all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 78065.056847.400.57012e 377065.0274747.400.57058w 455065.0331647.400.57070all Doors11D0: Door, wd sc type 21410.268132.400.39021w Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 8901.5914902.6630.00.032561 Floors 19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 640.852433.1919.00.04976 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 7...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Bed By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 2071.928177.5613.00.091108n 1931.927607.5613.00.091101e 4001.9215777.5613.00.091209all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 78065.056847.400.57012e Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2381.593992.6630.00.032150 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 8...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Bath By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1121.924427.5613.00.09159e Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 671.591122.6630.00.03242 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 9...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Clos By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 571.59952.6630.00.03236 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 10...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Living By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 2871.9211317.5613.00.091150n 601.922387.5613.00.09132w 3481.9213697.5613.00.091181all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 18623.237947.400.5708n Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2581.594322.6630.00.032163 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 11...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Kit By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 1711.592872.6630.00.032108 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 12...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Stair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 721.922847.5613.00.09138w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 195065.0142147.400.57030w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 481.59802.6630.00.03230 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 13...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Bed By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1931.927607.5613.00.091101e Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 78065.056847.400.57012e Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2381.593992.6630.00.032150 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 14...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Bath By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1121.924427.5613.00.09159e Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 671.591122.6630.00.03242 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 15...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Clos By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 571.59952.6630.00.03236 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 16...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Living By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 601.922387.5613.00.09132w Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2581.594322.6630.00.032163 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 17...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Kit By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 1711.592872.6630.00.032108 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 18...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Stair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 721.922847.5613.00.09138w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 195065.0142147.400.57030w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 481.59802.6630.00.03230 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 19...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Ldr By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1231.924847.5613.00.09164w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 52065.037947.400.5708w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 511.59852.6630.00.03232 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 20...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Bed By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1971.927757.5613.00.091103e Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 65065.047447.400.57010e Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2381.593992.6630.00.032150 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 21...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Bath By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1121.924427.5613.00.09159e Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 671.591122.6630.00.03242 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 22...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Clos By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 571.59952.6630.00.03236 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 23...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Living By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 601.922387.5613.00.09132w Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2581.594322.6630.00.032163 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 24...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Kit By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 1711.592872.6630.00.032108 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 25...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Stair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 721.922847.5613.00.09138w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 195065.0142147.400.57030w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 481.59802.6630.00.03230 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 26...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Ldr By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1231.924847.5613.00.09164w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 52065.037947.400.5708w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 511.59852.6630.00.03232 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 27...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Bed By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1931.927607.5613.00.091101e Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 78065.056847.400.57012e Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2381.593992.6630.00.032150 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 28...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Bath By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1121.924427.5613.00.09159e Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 671.591122.6630.00.03242 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 29...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Clos By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 571.59952.6630.00.03236 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 30...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Living By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 601.922387.5613.00.09132w Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2581.594322.6630.00.032163 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 31...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Kit By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls (none) Partitions(none) Windows(none) Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 1711.592872.6630.00.032108 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 32...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Stair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 721.922847.5613.00.09138w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 195065.0142147.400.57030w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 481.59802.6630.00.03230 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 33...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Ldr By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1231.924847.5613.00.09164w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 52065.037947.400.5708w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 511.59852.6630.00.03232 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 34...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Bed By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1931.927607.5613.00.091101e Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 78065.056847.400.57012e Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2381.593992.6630.00.032150 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 35...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Bath By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1121.924427.5613.00.09159e 1121.924427.5613.00.09159s 2251.928857.5613.00.091117all Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 671.591122.6630.00.03242 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 36...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Clos By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 951.923747.5613.00.09150s Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 571.59952.6630.00.03236 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 37...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Living By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 601.922387.5613.00.09132w Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2581.594322.6630.00.032163 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 38...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Kit By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 2331.929197.5613.00.091122s Partitions(none) Windows (none) Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 1711.592872.6630.00.032108 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 39...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Stair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 721.922847.5613.00.09138w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 195065.0142147.400.57030w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 481.59802.6630.00.03230 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 40...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Ldr By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 691.922727.5613.00.09136s 1231.924847.5613.00.09164w 1921.927567.5613.00.091100all Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 52065.037947.400.5708w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 511.59852.6630.00.03232 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 41...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Foy By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 371.921477.5613.00.09120w Partitions(none) Windows (none) Doors 11D0: Door, wd sc type 21410.268132.400.39021w Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 42...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Ldr By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1231.924847.5613.00.09164w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 52065.037947.400.5708w Doors (none) Ceilings16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 511.59852.6630.00.03232 Floors(none) 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 43...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1Mech By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 691.922727.5613.00.09136n 781.923067.5613.00.09141w 1471.925797.5613.00.09177all Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 44...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:1DStair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1341.925297.5613.00.09170w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 130065.094747.400.57020w Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 340.851283.1919.00.04940 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 45...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Foy By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 371.921477.5613.00.09120w Partitions(none) Windows (none) Doors 11D0: Door, wd sc type 21410.268132.400.39021w Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 46...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2Mech By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 781.923067.5613.00.09141w Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 47...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:2DStair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1341.925297.5613.00.09170w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 130065.094747.400.57020w Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 340.851283.1919.00.04940 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 48...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Foy By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 371.921477.5613.00.09120w Partitions(none) Windows (none) Doors 11D0: Door, wd sc type 21410.268132.400.39021w Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 49...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3Mech By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 781.923067.5613.00.09141w Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 50...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:3DStair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1341.925297.5613.00.09170w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 130065.094747.400.57020w Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 340.851283.1919.00.04940 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 51...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Foy By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 371.921477.5613.00.09120w Partitions(none) Windows (none) Doors 11D0: Door, wd sc type 21410.268132.400.39021w Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 52...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4Mech By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 781.923067.5613.00.09141w Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 53...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:4DStair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1341.925297.5613.00.09170w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 130065.094747.400.57020w Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 340.851283.1919.00.04940 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 54...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Foy By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 691.922727.5613.00.09136s 371.921477.5613.00.09120w 1071.924207.5613.00.09156all Partitions(none) Windows (none) Doors 11D0: Door, wd sc type 21410.268132.400.39021w Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 55...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5Mech By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 781.923067.5613.00.09141w Partitions(none) Windows (none) Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 150.85573.1919.00.04918 2020-Mar-20 14:34:52Right-Suite® Universal 2019 19.0.13 RSU12258 Page 56...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Component Constructions Mar 17, 2020Date:5DStair By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) SimplifiedMethod)H(35-Daily range (°F) AverageConstruction quality64-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1341.925297.5613.00.09170w Partitions(none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.56); 6.67 ft head ht 130065.094747.400.57020w Doors (none) Ceilings(none) Floors19A-19bscp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, tight bsmt ovr 340.851283.1919.00.04940 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Project Summary Mar 17, 2020Date:Entire House By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F97Inside db °F70 Inside db °F75Design TD °F83 Design TD °F22Daily range HRelative humidity %50Moisture difference gr/lb-22 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh59665 Structure Btuh57644DuctsBtuh0DuctsBtuh0Central vent (178 cfm)13699 Btuh Central vent (178 cfm)Btuh3643 Humidification Btuh0 Blower Btuh0PipingBtuh0Equipment load Btuh73364 Use manufacturer's data nRate/swing multiplier 1.02InfiltrationEquipment sensible load Btuh62575 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh1104DuctsBtuh0Central vent (178 cfm)Btuh-2232CoolingHeating31833183Area (ft²)Equipment latent load Btuh11042864328643Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh63679Equiv. AVF (cfm)72134 Req. total capacity at 0.70 SHR ton7.4 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTraden/a Trade n/aModeln/a Cond n/aAHRI ref n/a Coil n/aAHRI ref n/aEfficiencyn/a Efficiency n/aHeating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Project Summary Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F97Inside db °F70 Inside db °F75Design TD °F83 Design TD °F22Daily range HRelative humidity %50Moisture difference gr/lb-22 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh14158 Structure Btuh12080DuctsBtuh0DuctsBtuh0Central vent (32 cfm)2426 Btuh Central vent (32 cfm)Btuh645Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh16584 Use manufacturer's data nRate/swing multiplier 1.02InfiltrationEquipment sensible load Btuh12992 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh170DuctsBtuh0Central vent (32 cfm)Btuh-395CoolingHeatingOutside air637637Area (ft²)Equipment latent load Btuh057295729Volume (ft³)Air changes/hour 0.190.36 Equipment Total Load (Sen+Lat)Btuh12992Equiv. AVF (cfm)1834 Req. total capacity at 0.80 SHR ton1.4 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTradeTRANETradeTRANEModelS9X1B040U2PS***Cond 4TTR3018H1AHRI ref 202555287 Coil 4GXCB004AC6HUAAHRI ref 10350056Efficiency95 AFUE Efficiency 11.5 EER, 13 SEERHeating input Btuh40000 Sensible cooling Btuh14400Heating output Btuh39000 Latent cooling Btuh3600Temperature rise °F70 Total cooling Btuh18000Actual air flow cfm600 Actual air flow cfm600Air flow factor cfm/Btuh0.042 Air flow factor cfm/Btuh0.050Static pressure in H2O0.80 Static pressure in H2O0.80Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Project Summary Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F97Inside db °F70 Inside db °F75Design TD °F83 Design TD °F22Daily range HRelative humidity %50Moisture difference gr/lb-22 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh10583 Structure Btuh11226DuctsBtuh0DuctsBtuh0Central vent (38 cfm)2949 Btuh Central vent (38 cfm)Btuh784Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh13532 Use manufacturer's data nRate/swing multiplier 1.02InfiltrationEquipment sensible load Btuh12262 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh255DuctsBtuh0Central vent (38 cfm)Btuh-480CoolingHeatingOutside air637637Area (ft²)Equipment latent load Btuh057295729Volume (ft³)Air changes/hour 0.120.23 Equipment Total Load (Sen+Lat)Btuh12262Equiv. AVF (cfm)1222 Req. total capacity at 0.80 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTradeTRANETradeTRANEModelS9X1B040U2PS***Cond 4TTR3018H1AHRI ref 202555287 Coil TMM4A0B18S21SAAHRI ref 8593277Efficiency95 AFUE Efficiency 11.5 EER, 13.5 SEERHeating input Btuh40000 Sensible cooling Btuh14400Heating output Btuh39000 Latent cooling Btuh3600Temperature rise °F70 Total cooling Btuh18000Actual air flow cfm600 Actual air flow cfm600Air flow factor cfm/Btuh0.057 Air flow factor cfm/Btuh0.053Static pressure in H2O0.80 Static pressure in H2O0.80Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Project Summary Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F97Inside db °F70 Inside db °F75Design TD °F83 Design TD °F22Daily range HRelative humidity %50Moisture difference gr/lb-22 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh10503 Structure Btuh11170DuctsBtuh0DuctsBtuh0Central vent (38 cfm)2949 Btuh Central vent (38 cfm)Btuh784Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh13452 Use manufacturer's data nRate/swing multiplier 1.02InfiltrationEquipment sensible load Btuh12205 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh255DuctsBtuh0Central vent (38 cfm)Btuh-480CoolingHeatingOutside air637637Area (ft²)Equipment latent load Btuh057295729Volume (ft³)Air changes/hour 0.120.23 Equipment Total Load (Sen+Lat)Btuh12205Equiv. AVF (cfm)1222 Req. total capacity at 0.80 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTradeTRANETradeTRANEModelS9X1B040U2PS***Cond 4TTR3018H1AHRI ref 202555287 Coil GMU2APB30AHRI ref 202410016Efficiency95 AFUE Efficiency 11.5 EER, 13 SEERHeating input Btuh40000 Sensible cooling Btuh14240Heating output Btuh39000 Latent cooling Btuh3560Temperature rise °F71 Total cooling Btuh17800Actual air flow cfm593 Actual air flow cfm593Air flow factor cfm/Btuh0.056 Air flow factor cfm/Btuh0.053Static pressure in H2O0.80 Static pressure in H2O0.80Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Project Summary Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F97Inside db °F70 Inside db °F75Design TD °F83 Design TD °F22Daily range HRelative humidity %50Moisture difference gr/lb-22 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh10583 Structure Btuh11226DuctsBtuh0DuctsBtuh0Central vent (38 cfm)2949 Btuh Central vent (38 cfm)Btuh784Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh13532 Use manufacturer's data nRate/swing multiplier 1.02InfiltrationEquipment sensible load Btuh12262 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh255DuctsBtuh0Central vent (38 cfm)Btuh-480CoolingHeatingOutside air637637Area (ft²)Equipment latent load Btuh057295729Volume (ft³)Air changes/hour 0.120.23 Equipment Total Load (Sen+Lat)Btuh12262Equiv. AVF (cfm)1222 Req. total capacity at 0.80 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTradeTRANETradeTRANEModelS9X1B040U2PS***Cond 4TTR3018H1AHRI ref 202555287 Coil GMU2APB30AHRI ref 202410016Efficiency95 AFUE Efficiency 11.5 EER, 13 SEERHeating input Btuh40000 Sensible cooling Btuh14240Heating output Btuh39000 Latent cooling Btuh3560Temperature rise °F71 Total cooling Btuh17800Actual air flow cfm593 Actual air flow cfm593Air flow factor cfm/Btuh0.056 Air flow factor cfm/Btuh0.053Static pressure in H2O0.80 Static pressure in H2O0.80Space thermostat Load sensible heat ratio 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Project Summary Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor:555 Mikn, Rexburg, ID 83440 Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-13 Outside db °F97Inside db °F70 Inside db °F75Design TD °F83 Design TD °F22Daily range HRelative humidity %50Moisture difference gr/lb-22 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh13839 Structure Btuh11944DuctsBtuh0DuctsBtuh0Central vent (32 cfm)2426 Btuh Central vent (32 cfm)Btuh645Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh16265 Use manufacturer's data nRate/swing multiplier 1.02InfiltrationEquipment sensible load Btuh12853 Method Latent Cooling Equipment Load SizingSimplifiedConstruction quality Average0Fireplaces Structure Btuh170DuctsBtuh0Central vent (32 cfm)Btuh-395CoolingHeatingOutside air637637Area (ft²)Equipment latent load Btuh057295729Volume (ft³)Air changes/hour 0.190.36 Equipment Total Load (Sen+Lat)Btuh12853Equiv. AVF (cfm)1834 Req. total capacity at 0.80 SHR ton1.3 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTradeTRANETradeTRANEModelS9X1B040U2PS***Cond 4TTR3018H1AHRI ref 202555287 Coil GMU2APB30AHRI ref 202410016Efficiency95 AFUE Efficiency 11.5 EER, 13 SEERHeating input Btuh40000 Sensible cooling Btuh14240Heating output Btuh39000 Latent cooling Btuh3560Temperature rise °F71 Total cooling Btuh17800Actual air flow cfm593 Actual air flow cfm593Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.050Static pressure in H2O0.80 Static pressure in H2O0.80Space thermostat Load sensible heat ratio 1.00 2020-Mar-20 14:34:53 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Mar 17, 2020Date:Entire House By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F))H(35-Daily range (°F) 64-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 5,000 10,000 15,000 20,000 25,000 30,000 35,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 67.3%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 7039 Btuh (PFG - 1.3*AFG) 2020-Mar-20 14:34:53 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F))H(35-Daily range (°F) 64-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 64.5%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1366 Btuh (PFG - 1.3*AFG) 2020-Mar-20 14:34:53 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F))H(35-Daily range (°F) 64-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 67.3%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1401 Btuh (PFG - 1.3*AFG) 2020-Mar-20 14:34:53 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F))H(35-Daily range (°F) 64-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 70.4%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1471 Btuh (PFG - 1.3*AFG) 2020-Mar-20 14:34:53 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F))H(35-Daily range (°F) 64-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 67.3%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1401 Btuh (PFG - 1.3*AFG) 2020-Mar-20 14:34:53 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:AED Assessment Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F))H(35-Daily range (°F) 64-Wet bulb (°F)7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gla z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 67.3%. Zone does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 1401 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Entire House By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Entire House Unit2 2 Exposed wall 352.0 ft 57.0 ft3Room height 9.0 dft 9.0 dft 4 Room dimensions 5 Room area 3182.5 ft²636.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 302 294 2219 564 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 8 0 379 186 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 855 797 6027 1530 171 159 1202 305 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 58 0 2747 3770 12 0 568 780 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 302 302 2280 579 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 1710 1315 9944 2525 342 263 1989 505 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 290 0 13736 18850 58 0 2747 3770DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 105 105 3403 1069 21 21 681 214 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 2803 2803 7452 4448 561 561 1490 890FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 380 380 1213 322 76 76 243 64 6 c) AED excursion 7039 1401 Envelope loss/gain 49401 40882 8920 7929 12 a)Infiltration 10264 1462 1662 237 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 10 2300 2 460 Appliances/other 13000 2600 Subtotal (lines 6 to 13)59665 57644 10583 11226 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal59665576441058311226 15 Duct loads 0%0%0 0 0%0%0 0 Total room load 59665 57644 10583 11226 Air required (cfm)Air required (cfm)2980 2980 600 600 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Entire House By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Unit1 Unit3 2 Exposed wall 90.5 ft 57.0 ft3Room height 9.0 dft 9.0 dft 4 Room dimensions 5 Room area 636.5 ft²636.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 302 294 2219 564 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 8 0 379 186 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 171 159 1202 305 171 161 1217 309 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 12 0 568 780 10 0 474 650 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 342 263 1989 505 342 263 1989 505 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 58 0 2747 3770 58 0 2747 3770DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 21 21 681 214 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 561 561 1490 890 561 561 1490 890FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 76 76 243 64 76 76 243 64 6 c) AED excursion 1366 1471 Envelope loss/gain 11519 8644 8841 7873 12 a)Infiltration 2639 376 1662 237 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 2 460 Appliances/other 2600 2600 Subtotal (lines 6 to 13)14158 12080 10503 11170 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal14158120801050311170 15 Duct loads 0%0%0 0 0%0%0 0 Total room load 14158 12080 10503 11170 Air required (cfm)Air required (cfm)600 600 593 593 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Entire House By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Unit4 Unit5 2 Exposed wall 57.0 ft 90.5 ft3Room height 9.0 dft 9.0 dft 4 Room dimensions 5 Room area 636.5 ft²636.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 171 159 1202 305 171 159 1202 305 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 12 0 568 780 12 0 568 780 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 0 0 0 0 302 302 2280 579 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 342 263 1989 505 342 263 1989 505 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 58 0 2747 3770 58 0 2747 3770DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 21 21 681 214 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 561 561 1490 890 561 561 1490 890FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 76 76 243 64 76 76 243 64 6 c) AED excursion 1401 1401 Envelope loss/gain 8920 7929 11200 8508 12 a)Infiltration 1662 237 2639 376 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 2 460 Appliances/other 2600 2600 Subtotal (lines 6 to 13)10583 11226 13839 11944 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution000014Subtotal10583112261383911944 15 Duct loads 0%0%0 0 0%0%0 0 Total room load 10583 11226 13839 11944 Air required (cfm)Air required (cfm)593 593 593 593 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Unit1 1Bed 2 Exposed wall 90.5 ft 24.5 ft3Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft12.0x12.5 5 Room area 636.5 ft²150.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 302 294 2219 564 108 108 817 207.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 8 0 379 186 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 171 159 1202 305 113 101 760 193 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 12 0 568 780 12 0 568 780 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 342 263 1989 505 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 58 0 2747 3770 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 561 561 1490 890 150 150 399 238FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 76 76 243 64 0 0 0 0 6 c) AED excursion 1366 4 Envelope loss/gain 11519 8644 2544 1423 12 a)Infiltration 2639 376 714 102 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 2 460 Appliances/other 2600 0 Subtotal (lines 6 to 13)14158 12080 3258 1985 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00281614Subtotal141581208032872001 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 14158 12080 3287 2001 Air required (cfm)Air required (cfm)600 600 139 99 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 1Bath 1Clos 2 Exposed wall 6.5 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.5x6.5 ft5.5x6.5 5 Room area 42.3 ft²35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 59 59 442 112 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 42 42 112 67 36 36 95 57FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -9 -2 Envelope loss/gain 555 170 95 54 12 a)Infiltration 190 27 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)744 197 95 54 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution3319-95 -5414Subtotal77821600 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 778 216 0 0 Air required (cfm)Air required (cfm)33 11 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 1Living 1Kit 2 Exposed wall 21.0 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft162.5x1.0 ft13.5x8.0 5 Room area 162.5 ft²108.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 158 150 1131 287 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 8 0 379 186 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 32 32 238 60 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 163 163 432 258 108 108 287 171FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -78 -60 Envelope loss/gain 2180 714 287 112 12 a)Infiltration 612 87 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 900 1200 Subtotal (lines 6 to 13)2792 1701 287 1312 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution14862159331914Subtotal427838603211331 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4278 3860 321 1331 Air required (cfm)Air required (cfm)181 192 14 66 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 7...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 1Stair 1Foy 2 Exposed wall 7.5 ft 4.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x7.5 ft4.0x4.5 5 Room area 30.0 ft²18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 68 38 284 72 41 20 147 37 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 30 0 1421 1950 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 21 21 681 214 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 30 30 80 48 0 0 0 0FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 18 18 57 15 6 c) AED excursion 810 -12 Envelope loss/gain 1784 2879 885 254 12 a)Infiltration 219 31 131 19 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2003 2911 1017 273 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-2003 -2911 2780 223414Subtotal0037962507 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 3796 2507 Air required (cfm)Air required (cfm)0 0 161 125 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 8...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 1Ldr 1Mech 2 Exposed wall 8.0 ft 8.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x8.0 ft4.0x4.5 5 Room area 32.0 ft²18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 7.567.56 1.921.92 0 0 0 0 36 36 272 69.GG 1D-c2ov1D-c2ov 0.5700.570 nn 47.3747.37 23.2323.23 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 72 64 484 123 41 41 306 78 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 8 0 379 520 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 32 32 85 51 0 0 0 0FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 18 18 57 15 6 c) AED excursion 187 -9 Envelope loss/gain 948 881 636 154 12 a)Infiltration 233 33 248 35 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)1181 1414 884 189 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution517751-884 -18914Subtotal1698216500 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1698 2165 0 0 Air required (cfm)Air required (cfm)72 108 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 9...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 1DStair 2 Exposed wall 10.0 ft3Room height 9.0 heat/coolft 4 Room dimensions ft4.0x10.0 5 Room area 40.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12C-0sw 0.091 n 7.56 1.92 0 0 0 0.G 1D-c2ov 0.570 n 47.37 23.23 0 0 0 0.W 12C-0sw 0.091 e 7.56 1.92 0 0 0 0 .G 1D-c2ov 0.570 e 47.37 65.00 0 0 0 0 11 W 12C-0sw 0.091 s 0.00 0.00 0 0 0 0 W 12C-0sw 0.091 w 7.56 1.92 90 70 529 134 G 1D-c2ov 0.570 w 47.37 65.00 20 0 947 1300D11D00.390 w 32.41 10.18 0 0 0 0 C 16B-30ad 0.032 -2.66 1.59 0 0 0 0F19A-19bscp 0.049 -3.19 0.85 40 40 128 34 6 c) AED excursion 535 Envelope loss/gain 1604 2003 12 a)Infiltration 292 42 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)1896 2045 Less external load 0 0 Less transfer 0 0Redistribution-1896 -204514Subtotal00 15 Duct loads -0%0%0 0 Total room load 0 0 Air required (cfm)0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 10...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Unit2 2Bed 2 Exposed wall 57.0 ft 12.5 ft3Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft12.0x12.5 5 Room area 636.5 ft²150.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 171 159 1202 305 113 101 760 193 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 12 0 568 780 12 0 568 780 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 342 263 1989 505 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 58 0 2747 3770 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 561 561 1490 890 150 150 399 238FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 76 76 243 64 0 0 0 0 6 c) AED excursion 1401 15 Envelope loss/gain 8920 7929 1727 1226 12 a)Infiltration 1662 237 364 52 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 2 460 Appliances/other 2600 0 Subtotal (lines 6 to 13)10583 11226 2092 1738 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00281614Subtotal105831122621201754 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 10583 11226 2120 1754 Air required (cfm)Air required (cfm)600 600 120 94 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 11...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 2Bath 2Clos 2 Exposed wall 6.5 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft6.5x6.5 ft5.5x6.5 5 Room area 42.3 ft²35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 59 59 442 112 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 42 42 112 67 36 36 95 57FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -9 -2 Envelope loss/gain 555 170 95 54 12 a)Infiltration 190 27 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)744 197 95 54 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution3319-95 -5414Subtotal77821600 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 778 216 0 0 Air required (cfm)Air required (cfm)44 12 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 12...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 2Living 2Stair 2 Exposed wall 3.5 ft 7.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft162.5x1.0 ft4.0x7.5 5 Room area 162.5 ft²30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 32 32 238 60 68 38 284 72 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 30 0 1421 1950DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 163 163 432 258 30 30 80 48FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -54 809 Envelope loss/gain 670 264 1784 2878 12 a)Infiltration 102 15 219 31 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)772 1179 2003 2910 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution14862159-2003 -291014Subtotal2259333700 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2259 3337 0 0 Air required (cfm)Air required (cfm)128 178 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 13...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 2Kit 2Ldr 2 Exposed wall 0 ft 8.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.5x8.0 ft4.0x8.0 5 Room area 108.0 ft²32.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 0 0 0 0 72 64 484 123 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 8 0 379 520DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 108 108 287 171 32 32 85 51FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -60 186 Envelope loss/gain 287 111 948 880 12 a)Infiltration 0 0 233 33 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1200 500 Subtotal (lines 6 to 13)287 1311 1181 1413 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution331951775114Subtotal321133016982164 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 321 1330 1698 2164 Air required (cfm)Air required (cfm)18 71 96 116 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 14...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 2Foy 2DStair 2 Exposed wall 4.5 ft 10.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x4.5 ft4.0x10.0 5 Room area 18.0 ft²40.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 41 20 147 37 90 70 529 134 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 20 0 947 1300DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 0 0 0 0 0 0 0 0FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 18 18 57 15 40 40 128 34 6 c) AED excursion -13 534 Envelope loss/gain 885 254 1604 2003 12 a)Infiltration 131 19 292 42 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1017 273 1896 2044 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution23912151-1896 -204414Subtotal3408242400 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3408 2424 0 0 Air required (cfm)Air required (cfm)193 130 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 15...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 2Mech 2 Exposed wall 4.5 ft3Room height 9.0 heat/coolft 4 Room dimensions ft4.0x4.5 5 Room area 18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12C-0sw 0.091 n 0.00 0.00 0 0 0 0.G 1D-c2ov 0.570 n 0.00 0.00 0 0 0 0.W 12C-0sw 0.091 e 7.56 1.92 0 0 0 0 .G 1D-c2ov 0.570 e 47.37 65.00 0 0 0 0 11 W 12C-0sw 0.091 s 0.00 0.00 0 0 0 0 W 12C-0sw 0.091 w 7.56 1.92 41 41 306 78 G 1D-c2ov 0.570 w 47.37 65.00 0 0 0 0D11D00.390 w 32.41 10.18 0 0 0 0 C 16B-30ad 0.032 -2.66 1.59 0 0 0 0F19A-19bscp 0.049 -3.19 0.85 18 18 57 15 6 c) AED excursion -5 Envelope loss/gain 364 88 12 a)Infiltration 131 19 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)495 107 Less external load 0 0 Less transfer 0 0Redistribution-495 -10714Subtotal00 15 Duct loads -0%0%0 0 Total room load 0 0 Air required (cfm)0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 16...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Unit3 3Bed 2 Exposed wall 57.0 ft 12.5 ft3Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft12.0x12.5 5 Room area 636.5 ft²150.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 171 161 1217 309 113 103 775 197 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 10 0 474 650 10 0 474 650 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 342 263 1989 505 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 58 0 2747 3770 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 561 561 1490 890 150 150 399 238FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 76 76 243 64 0 0 0 0 6 c) AED excursion 1471 17 Envelope loss/gain 8841 7873 1648 1102 12 a)Infiltration 1662 237 364 52 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 2 460 Appliances/other 2600 0 Subtotal (lines 6 to 13)10503 11170 2012 1614 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution00281614Subtotal105031117020401630 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 10503 11170 2040 1630 Air required (cfm)Air required (cfm)593 593 115 87 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 17...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 3Foy 3DStair 2 Exposed wall 4.5 ft 10.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x4.5 ft4.0x10.0 5 Room area 18.0 ft²40.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 41 20 147 37 90 70 529 134 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 20 0 947 1300DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 0 0 0 0 0 0 0 0FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 18 18 57 15 40 40 128 34 6 c) AED excursion -11 549 Envelope loss/gain 885 256 1604 2017 12 a)Infiltration 131 19 292 42 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1017 275 1896 2059 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution23912167-1896 -205914Subtotal3408244100 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3408 2441 0 0 Air required (cfm)Air required (cfm)192 130 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 18...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 3Mech 3Stair 2 Exposed wall 4.5 ft 7.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x4.5 ft4.0x7.5 5 Room area 18.0 ft²30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 41 41 306 78 68 38 284 72 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 30 0 1421 1950DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 0 0 0 0 30 30 80 48FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 18 18 57 15 0 0 0 0 6 c) AED excursion -4 830 Envelope loss/gain 364 89 1784 2899 12 a)Infiltration 131 19 219 31 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)495 108 2003 2930 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-495 -108 -2003 -293014Subtotal0000 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 19...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 3Kit 3Living 2 Exposed wall 0 ft 3.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.5x8.0 ft162.5x1.0 5 Room area 108.0 ft²162.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 0 0 0 0 32 32 238 60 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 108 108 287 171 163 163 432 258FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -51 -46 Envelope loss/gain 287 120 670 273 12 a)Infiltration 0 0 102 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1200 900 Subtotal (lines 6 to 13)287 1320 772 1187 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution33191486217414Subtotal321134022593361 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 321 1340 2259 3361 Air required (cfm)Air required (cfm)18 71 128 178 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 20...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 3Ldr 3Bath 2 Exposed wall 8.0 ft 6.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x8.0 ft6.5x6.5 5 Room area 32.0 ft²42.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 59 59 442 112 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 72 64 484 123 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 8 0 379 520 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 32 32 85 51 42 42 112 67FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion 196 -8 Envelope loss/gain 948 890 555 172 12 a)Infiltration 233 33 190 27 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)1181 1423 744 199 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution517756331914Subtotal16982180778218 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1698 2180 778 218 Air required (cfm)Air required (cfm)96 116 44 12 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 21...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 3Clos 2 Exposed wall 0 ft3Room height 9.0 heat/coolft 4 Room dimensions ft5.5x6.5 5 Room area 35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12C-0sw 0.091 n 0.00 0.00 0 0 0 0.G 1D-c2ov 0.570 n 0.00 0.00 0 0 0 0.W 12C-0sw 0.091 e 7.56 1.92 0 0 0 0 .G 1D-c2ov 0.570 e 47.37 65.00 0 0 0 0 11 W 12C-0sw 0.091 s 0.00 0.00 0 0 0 0 W 12C-0sw 0.091 w 7.56 1.92 0 0 0 0 G 1D-c2ov 0.570 w 47.37 65.00 0 0 0 0D11D00.390 w 32.41 10.18 0 0 0 0 C 16B-30ad 0.032 -2.66 1.59 36 36 95 57F19A-19bscp 0.049 -3.19 0.85 0 0 0 0 6 c) AED excursion -2 Envelope loss/gain 95 55 12 a)Infiltration 0 0 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)95 55 Less external load 0 0 Less transfer 0 0Redistribution-95 -5514Subtotal00 15 Duct loads -0%0%0 0 Total room load 0 0 Air required (cfm)0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 22...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Unit4 4Living 2 Exposed wall 57.0 ft 3.5 ft3Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft162.5x1.0 5 Room area 636.5 ft²162.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 171 159 1202 305 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 12 0 568 780 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 342 263 1989 505 32 32 238 60 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 58 0 2747 3770 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 561 561 1490 890 163 163 432 258FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 76 76 243 64 0 0 0 0 6 c) AED excursion 1401 -54 Envelope loss/gain 8920 7929 670 264 12 a)Infiltration 1662 237 102 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 2600 900 Subtotal (lines 6 to 13)10583 11226 772 1179 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution001486215914Subtotal105831122622593337 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 10583 11226 2259 3337 Air required (cfm)Air required (cfm)593 593 127 176 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 23...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 4DStair 4Mech 2 Exposed wall 10.0 ft 4.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x10.0 ft4.0x4.5 5 Room area 40.0 ft²18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 90 70 529 134 41 41 306 78 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 20 0 947 1300 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 0 0 0 0 0 0 0 0FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 40 40 128 34 18 18 57 15 6 c) AED excursion 534 -5 Envelope loss/gain 1604 2003 364 88 12 a)Infiltration 292 42 131 19 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1896 2044 495 107 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-1896 -2044 -495 -10714Subtotal0000 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 24...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 4Foy 4Ldr 2 Exposed wall 4.5 ft 8.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x4.5 ft4.0x8.0 5 Room area 18.0 ft²32.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 41 20 147 37 72 64 484 123 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 8 0 379 520DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 0 0 0 0 32 32 85 51FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 18 18 57 15 0 0 0 0 6 c) AED excursion -13 186 Envelope loss/gain 885 254 948 880 12 a)Infiltration 131 19 233 33 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1017 273 1181 1413 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution2391215151775114Subtotal3408242416982164 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3408 2424 1698 2164 Air required (cfm)Air required (cfm)191 128 95 114 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 25...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 4Kit 4Clos 2 Exposed wall 0 ft 0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.5x8.0 ft5.5x6.5 5 Room area 108.0 ft²35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 108 108 287 171 36 36 95 57FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -60 -2 Envelope loss/gain 287 111 95 54 12 a)Infiltration 0 0 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1200 0 Subtotal (lines 6 to 13)287 1311 95 54 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution3319-95 -5414Subtotal321133000 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 321 1330 0 0 Air required (cfm)Air required (cfm)18 70 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 26...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 4Stair 4Bed 2 Exposed wall 7.5 ft 12.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x7.5 ft12.0x12.5 5 Room area 30.0 ft²150.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 113 101 760 193 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 12 0 568 780 11 WW 12C-0sw12C-0sw 0.0910.091 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 68 38 284 72 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 30 0 1421 1950 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 30 30 80 48 150 150 399 238FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion 809 15 Envelope loss/gain 1784 2878 1727 1226 12 a)Infiltration 219 31 364 52 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13)2003 2910 2092 1738 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-2003 -2910 28 1614Subtotal0021201754 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 2120 1754 Air required (cfm)Air required (cfm)0 0 119 93 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 27...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 4Bath 2 Exposed wall 6.5 ft3Room height 9.0 heat/coolft 4 Room dimensions ft6.5x6.5 5 Room area 42.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12C-0sw 0.091 n 0.00 0.00 0 0 0 0.G 1D-c2ov 0.570 n 0.00 0.00 0 0 0 0.W 12C-0sw 0.091 e 7.56 1.92 59 59 442 112 .G 1D-c2ov 0.570 e 47.37 65.00 0 0 0 0 11 W 12C-0sw 0.091 s 0.00 0.00 0 0 0 0 W 12C-0sw 0.091 w 7.56 1.92 0 0 0 0 G 1D-c2ov 0.570 w 47.37 65.00 0 0 0 0D11D00.390 w 32.41 10.18 0 0 0 0 C 16B-30ad 0.032 -2.66 1.59 42 42 112 67F19A-19bscp 0.049 -3.19 0.85 0 0 0 0 6 c) AED excursion -9 Envelope loss/gain 555 170 12 a)Infiltration 190 27 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)744 197 Less external load 0 0 Less transfer 0 0Redistribution331914Subtotal778216 15 Duct loads -0%0%0 0 Total room load 778 216 Air required (cfm)44 11 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 28...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name Unit5 5Living 2 Exposed wall 90.5 ft 3.5 ft3Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft162.5x1.0 5 Room area 636.5 ft²162.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 171 159 1202 305 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 12 0 568 780 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 302 302 2280 579 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 342 263 1989 505 32 32 238 60 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 58 0 2747 3770 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 21 21 681 214 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 561 561 1490 890 163 163 432 258FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 76 76 243 64 0 0 0 0 6 c) AED excursion 1401 -51 Envelope loss/gain 11200 8508 670 267 12 a)Infiltration 2639 376 102 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 2600 900 Subtotal (lines 6 to 13)13839 11944 772 1182 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution001486216414Subtotal138391194422593346 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 13839 11944 2259 3346 Air required (cfm)Air required (cfm)593 593 97 166 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 29...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 5DStair 5Foy 2 Exposed wall 10.0 ft 8.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x10.0 ft4.0x4.5 5 Room area 40.0 ft²18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 0 0 0 0 36 36 272 69 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 90 70 529 134 41 20 147 37 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 20 0 947 1300 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 21 21 681 214 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 0 0 0 0 0 0 0 0FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 40 40 128 34 18 18 57 15 6 c) AED excursion 540 -15 Envelope loss/gain 1604 2008 1158 320 12 a)Infiltration 292 42 248 35 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1896 2050 1406 356 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-1896 -2050 2391 215714Subtotal0037962512 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 3796 2512 Air required (cfm)Air required (cfm)0 0 163 125 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 30...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 5Mech 5Clos 2 Exposed wall 4.5 ft 5.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft4.0x4.5 ft5.5x6.5 5 Room area 18.0 ft²35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 0 0 0 0 50 50 374 95 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 41 41 306 78 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 0 0 0 0 36 36 95 57FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 18 18 57 15 0 0 0 0 6 c) AED excursion -5 -7 Envelope loss/gain 364 88 469 145 12 a)Infiltration 131 19 160 23 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)495 107 630 167 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution-495 -107 -630 -16714Subtotal0000 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 31...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 5Bed 5Stair 2 Exposed wall 12.5 ft 7.5 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft12.0x12.5 ft4.0x7.5 5 Room area 150.0 ft²30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 113 101 760 193 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 12 0 568 780 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 0 0 0 0 68 38 284 72 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 30 0 1421 1950DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 150 150 399 238 30 30 80 48FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion 20 816 Envelope loss/gain 1727 1231 1784 2886 12 a)Infiltration 364 52 219 31 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 2 460 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2092 1743 2003 2917 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution18750-2003 -291714Subtotal2279179200 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2279 1792 0 0 Air required (cfm)Air required (cfm)98 89 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 32...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 5Kit 5Bath 2 Exposed wall 13.5 ft 13.0 ft3Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft13.5x8.0 ft6.5x6.5 5 Room area 108.0 ft²42.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.GG 1D-c2ov1D-c2ov 0.5700.570 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0.WW 12C-0sw12C-0sw 0.0910.091 ee 7.567.56 1.921.92 0 0 0 0 59 59 442 112 .GG 1D-c2ov1D-c2ov 0.5700.570 ee 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0 11 WW 12C-0sw12C-0sw 0.0910.091 ss 7.567.56 1.921.92 122 122 919 233 59 59 442 112 WW 12C-0sw12C-0sw 0.0910.091 ww 7.567.56 1.921.92 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 47.3747.37 65.0065.00 0 0 0 0 0 0 0 0DD11D011D00.3900.390 ww 32.4132.41 10.1810.18 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --2.662.66 1.591.59 108 108 287 171 42 42 112 67FF19A-19bscp19A-19bscp 0.0490.049 --3.193.19 0.850.85 0 0 0 0 0 0 0 0 6 c) AED excursion -69 -14 Envelope loss/gain 1206 336 997 277 12 a)Infiltration 394 56 379 54 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1200 0 Subtotal (lines 6 to 13)1600 1592 1376 331 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0RedistributionRedistribution221592215914Subtotal182116511597390 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1821 1651 1597 390 Air required (cfm)Air required (cfm)78 82 68 19 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:53Right-Suite® Universal 2019 19.0.13 RSU12258 Page 33...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Room name 5Ldr 2 Exposed wall 12.0 ft3Room height 9.0 heat/coolft 4 Room dimensions ft4.0x8.0 5 Room area 32.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12C-0sw 0.091 n 0.00 0.00 0 0 0 0.G 1D-c2ov 0.570 n 0.00 0.00 0 0 0 0.W 12C-0sw 0.091 e 7.56 1.92 0 0 0 0 .G 1D-c2ov 0.570 e 47.37 65.00 0 0 0 0 11 W 12C-0sw 0.091 s 7.56 1.92 36 36 272 69 W 12C-0sw 0.091 w 7.56 1.92 72 64 484 123 G 1D-c2ov 0.570 w 47.37 65.00 8 0 379 520D11D00.390 w 32.41 10.18 0 0 0 0 C 16B-30ad 0.032 -2.66 1.59 32 32 85 51F19A-19bscp 0.049 -3.19 0.85 0 0 0 0 6 c) AED excursion 187 Envelope loss/gain 1220 949 12 a)Infiltration 350 50 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 500 Subtotal (lines 6 to 13)1570 1499 Less external load 0 0 Less transfer 0 0Redistribution51775314Subtotal20872252 15 Duct loads -0%0%0 0 Total room load 2087 2252 Air required (cfm)89 112 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Entire House By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Entire House Unit2 2 Running Feet of Exposed Wall 352.0 ft 57.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²13860.0ft 9.0 ft²2772.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²3182.5 ft²636.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²3182.5°0 ft²636.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 302 2219 564 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 8 379 186 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 855 6027 1530 171 1202 305 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 58 2747 3770 12 568 780 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 302 2280 579 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 1710 9944 2525 342 1989 505 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 290 13736 18850 58 2747 3770DoorDoor11D011D0ww32.4132.41 10.1810.18 105 3403 1069 21 681 214 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 2803 7452 4448 561 1490 890FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 380 1213 322 76 243 64 Infiltration Heating Load (Btuh)0.280.28 10264 1662EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 1462 1.00 2370.150.15 Latent Load (Btuh)-896 -145 Internal a Occupants at 230 and 200 Btuh 10 2300 2000 2 460 400 b Scenario number 13000 2600 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 59665 57644 1104 10583 11226 255 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 178178 E CfmE Cfm 178178 13699 3643 -2232 2949 784 -480 17 Winter Humidification Load Gal/Day 00 0 0 18 Piping Load 0 0 19 Blower Heat 0 0 20 AED Excursion & Latent Moisture Migration Load 7039 1401 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 73364 61288 1104 13532 12010 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Entire House By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Unit1 Unit3 2 Running Feet of Exposed Wall 90.5 ft 57.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²2772.0ft 9.0 ft²2772.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²636.5 ft²636.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²636.5°0 ft²636.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 302 2219 564 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 8 379 186 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 171 1202 305 171 1217 309 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 12 568 780 10 474 650 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 342 1989 505 342 1989 505 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 58 2747 3770 58 2747 3770DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 21 681 214 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 561 1490 890 561 1490 890FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 76 243 64 76 243 64 Infiltration Heating Load (Btuh)0.280.28 2639 1662EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 376 1.00 2370.150.15 Latent Load (Btuh)-230 -145 Internal a Occupants at 230 and 200 Btuh 2 460 400 2 460 400 b Scenario number 2600 2600 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 14158 12080 170 10503 11170 255 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 178178 E CfmE Cfm 178178 2426 645 -395 2949 784 -480 17 Winter Humidification Load Gal/Day 00 0 0 18 Piping Load 0 0 19 Blower Heat 0 0 20 AED Excursion & Latent Moisture Migration Load 1366 1471 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 16584 12725 0 13452 11954 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Entire House By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Unit4 Unit5 2 Running Feet of Exposed Wall 57.0 ft 90.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²2772.0ft 9.0 ft²2772.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²636.5 ft²636.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²636.5°0 ft²636.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 171 1202 305 171 1202 305 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 12 568 780 12 568 780 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 0 0 0 302 2280 579 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 342 1989 505 342 1989 505 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 58 2747 3770 58 2747 3770DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 21 681 214 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 561 1490 890 561 1490 890FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 76 243 64 76 243 64 Infiltration Heating Load (Btuh)0.280.28 1662 2639EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 237 1.00 3760.150.15 Latent Load (Btuh)-145 -230 Internal a Occupants at 230 and 200 Btuh 2 460 400 2 460 400 b Scenario number 2600 2600 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 10583 11226 255 13839 11944 170 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 178178 E CfmE Cfm 178178 2949 784 -480 2426 645 -395 17 Winter Humidification Load Gal/Day 00 0 0 18 Piping Load 0 0 19 Blower Heat 0 0 20 AED Excursion & Latent Moisture Migration Load 1401 1401 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 13532 12010 0 16265 12589 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Unit1 1Bed 2 Running Feet of Exposed Wall 90.5 ft 24.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²2772.0ft 9.0 ft²441.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²636.5 12.5 x 12.0 ft ft²150.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²636.5°0 ft²150.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 302 2219 564 108 817 207.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 8 379 186 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 171 1202 305 113 760 193 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 12 568 780 12 568 780 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 342 1989 505 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 58 2747 3770 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 561 1490 890 150 399 238FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 76 243 64 0 0 0 Infiltration Heating Load (Btuh)0.360.36 2639 714EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 376 0.27 1020.190.19 Latent Load (Btuh)-230 Internal a Occupants at 230 and 200 Btuh 2 460 400 2 460 400 b Scenario number 2600 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 14158 12080 170 3287 2001 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 2426 645 -395 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1366 4 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 16584 12725 0 3287 2001 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 1Bath 1Clos 2 Running Feet of Exposed Wall 6.5 ft 0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²234.0ft 9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)6.5 x 6.5 ft ft²42.3 6.5 x 5.5 ft ft²35.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²42.3°0 ft²35.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 59 442 112 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 0 0 0 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 42 112 67 36 95 57FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.360.36 190 0EffectWARWAR 12 Sensible Load (Btuh)ACH 0.07 27 0 00.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 778 216 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -9 -2 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 778 216 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 1Living 1Kit 2 Running Feet of Exposed Wall 21.0 ft 0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²513.0ft 9.0 ft²387.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 162.5 ft ft²162.5 8.0 x 13.5 ft ft²108.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²162.5°0 ft²108.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 158 1131 287 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 8 379 186 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 32 238 60 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 163 432 258 108 287 171FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.360.36 612 0EffectWARWAR 12 Sensible Load (Btuh)ACH 0.23 87 0 00.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 900 1200 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 4278 3860 321 1331 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -78 -60 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 4278 3860 321 1331 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 7...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 1Stair 1Foy 2 Running Feet of Exposed Wall 7.5 ft 4.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²207.0ft 9.0 ft²153.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)7.5 x 4.0 ft ft²30.0 4.5 x 4.0 ft ft²18.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²30.0°0 ft²18.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 68 284 72 41 147 37 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 30 1421 1950 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 21 681 214 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 30 80 48 0 0 0FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 18 57 15 Infiltration Heating Load (Btuh)0.360.36 219 131EffectWARWAR 12 Sensible Load (Btuh)ACH 0.08 31 0.05 190.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 3796 2507 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 810 -12 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 3796 2507 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 8...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 1Ldr 1Mech 2 Running Feet of Exposed Wall 8.0 ft 8.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²216.0ft 9.0 ft²153.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.0 x 4.0 ft ft²32.0 4.5 x 4.0 ft ft²18.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²32.0°0 ft²18.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 7.567.56 1.921.92 0 0 0 36 272 69.GlazGlaz 1D-c2ov1D-c2ov nn 47.3747.37 23.2323.23 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 72 484 123 41 306 78 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 8 379 520 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 32 85 51 0 0 0FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 18 57 15 Infiltration Heating Load (Btuh)0.360.36 233 248EffectWARWAR 12 Sensible Load (Btuh)ACH 0.09 33 0.09 350.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 500 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1698 2165 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 187 -9 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1698 2165 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 9...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit1 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 1DStair 2 Running Feet of Exposed Wall 10.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²252.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)10.0 x 4.0 ft ft²40.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²40.0° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12C-0sw n 7.56 1.92 0 0 0.Glaz 1D-c2ov n 47.37 23.23 0 0 0.Wall 12C-0sw e 7.56 1.92 0 0 0 .Glaz 1D-c2ov e 47.37 65.00 0 0 0 11 Wall 12C-0sw s 0.00 0.00 0 0 0 Wall 12C-0sw w 7.56 1.92 90 529 134 Glaz 1D-c2ov w 47.37 65.00 20 947 1300Door11D0w32.41 10.18 0 0 0 Ceil 16B-30ad -2.66 1.59 0 0 0Flor19A-19bscp -3.19 0.85 40 128 34 Infiltration Heating Load (Btuh)0.36 292EffectWAR 12 Sensible Load (Btuh)ACH 0.11 420.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 b Scenario number 0 13 c Default Adjustments d Custom Appliances 0 0ePlants0 14 Subtotals Sum lines 6 through 12 0 0 Duct EHLF & ESGF 0 0 0 015Loads ELG 0 Vent Cfm16Ventilation Loads 32 E Cfm 32 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 535 21 Total Load Sum lines 13 through 19 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 10...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Unit2 2Bed 2 Running Feet of Exposed Wall 57.0 ft 12.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²2772.0ft 9.0 ft²441.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²636.5 12.5 x 12.0 ft ft²150.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²636.5°0 ft²150.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 171 1202 305 113 760 193 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 12 568 780 12 568 780 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 342 1989 505 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 58 2747 3770 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 561 1490 890 150 399 238FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 76 243 64 0 0 0 Infiltration Heating Load (Btuh)0.230.23 1662 364EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 237 0.22 520.120.12 Latent Load (Btuh)-145 Internal a Occupants at 230 and 200 Btuh 2 460 400 2 460 400 b Scenario number 2600 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 10583 11226 255 2120 1754 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 2949 784 -480 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1401 15 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 13532 12010 0 2120 1754 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 11...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 2Bath 2Clos 2 Running Feet of Exposed Wall 6.5 ft 0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²234.0ft 9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)6.5 x 6.5 ft ft²42.3 6.5 x 5.5 ft ft²35.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²42.3°0 ft²35.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 59 442 112 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 0 0 0 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 42 112 67 36 95 57FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.230.23 190 0EffectWARWAR 12 Sensible Load (Btuh)ACH 0.11 27 0 00.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 778 216 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -9 -2 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 778 216 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 12...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 2Living 2Stair 2 Running Feet of Exposed Wall 3.5 ft 7.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²513.0ft 9.0 ft²207.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 162.5 ft ft²162.5 7.5 x 4.0 ft ft²30.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²162.5°0 ft²30.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 32 238 60 68 284 72 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 30 1421 1950DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 163 432 258 30 80 48FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.230.23 102 219EffectWARWAR 12 Sensible Load (Btuh)ACH 0.06 15 0.13 310.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 900 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2259 3337 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -54 809 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2259 3337 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 13...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 2Kit 2Ldr 2 Running Feet of Exposed Wall 0 ft 8.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²387.0ft 9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.0 x 13.5 ft ft²108.0 8.0 x 4.0 ft ft²32.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²108.0°0 ft²32.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 0 0 0 72 484 123 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 8 379 520DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 108 287 171 32 85 51FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.230.23 0 233EffectWARWAR 12 Sensible Load (Btuh)ACH 0 0 0.14 330.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 1200 500 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 321 1330 1698 2164 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -60 186 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 321 1330 1698 2164 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 14...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 2Foy 2DStair 2 Running Feet of Exposed Wall 4.5 ft 10.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²153.0ft 9.0 ft²252.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)4.5 x 4.0 ft ft²18.0 10.0 x 4.0 ft ft²40.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²18.0°0 ft²40.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 41 147 37 90 529 134 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 20 947 1300DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 0 0 0 0 0 0FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 18 57 15 40 128 34 Infiltration Heating Load (Btuh)0.230.23 131 292EffectWARWAR 12 Sensible Load (Btuh)ACH 0.08 19 0.18 420.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 3408 2424 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -13 534 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 3408 2424 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 15...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit2 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 2Mech 2 Running Feet of Exposed Wall 4.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²153.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)4.5 x 4.0 ft ft²18.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²18.0° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12C-0sw n 0.00 0.00 0 0 0.Glaz 1D-c2ov n 0.00 0.00 0 0 0.Wall 12C-0sw e 7.56 1.92 0 0 0 .Glaz 1D-c2ov e 47.37 65.00 0 0 0 11 Wall 12C-0sw s 0.00 0.00 0 0 0 Wall 12C-0sw w 7.56 1.92 41 306 78 Glaz 1D-c2ov w 47.37 65.00 0 0 0Door11D0w32.41 10.18 0 0 0 Ceil 16B-30ad -2.66 1.59 0 0 0Flor19A-19bscp -3.19 0.85 18 57 15 Infiltration Heating Load (Btuh)0.23 131EffectWAR 12 Sensible Load (Btuh)ACH 0.08 190.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 b Scenario number 0 13 c Default Adjustments d Custom Appliances 0 0ePlants0 14 Subtotals Sum lines 6 through 12 0 0 Duct EHLF & ESGF 0 0 0 015Loads ELG 0 Vent Cfm16Ventilation Loads 38 E Cfm 38 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -5 21 Total Load Sum lines 13 through 19 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 16...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Unit3 3Bed 2 Running Feet of Exposed Wall 57.0 ft 12.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²2772.0ft 9.0 ft²441.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²636.5 12.5 x 12.0 ft ft²150.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²636.5°0 ft²150.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 171 1217 309 113 775 197 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 10 474 650 10 474 650 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 342 1989 505 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 58 2747 3770 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 561 1490 890 150 399 238FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 76 243 64 0 0 0 Infiltration Heating Load (Btuh)0.230.23 1662 364EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 237 0.22 520.120.12 Latent Load (Btuh)-145 Internal a Occupants at 230 and 200 Btuh 2 460 400 2 460 400 b Scenario number 2600 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 10503 11170 255 2040 1630 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 2949 784 -480 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1471 17 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 13452 11954 0 2040 1630 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 17...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 3Foy 3DStair 2 Running Feet of Exposed Wall 4.5 ft 10.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²153.0ft 9.0 ft²252.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)4.5 x 4.0 ft ft²18.0 10.0 x 4.0 ft ft²40.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²18.0°0 ft²40.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 41 147 37 90 529 134 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 20 947 1300DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 0 0 0 0 0 0FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 18 57 15 40 128 34 Infiltration Heating Load (Btuh)0.230.23 131 292EffectWARWAR 12 Sensible Load (Btuh)ACH 0.08 19 0.18 420.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 3408 2441 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -11 549 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 3408 2441 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 18...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 3Mech 3Stair 2 Running Feet of Exposed Wall 4.5 ft 7.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²153.0ft 9.0 ft²207.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)4.5 x 4.0 ft ft²18.0 7.5 x 4.0 ft ft²30.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²18.0°0 ft²30.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 41 306 78 68 284 72 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 30 1421 1950DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 0 0 0 30 80 48FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 18 57 15 0 0 0 Infiltration Heating Load (Btuh)0.230.23 131 219EffectWARWAR 12 Sensible Load (Btuh)ACH 0.08 19 0.13 310.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -4 830 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 19...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 3Kit 3Living 2 Running Feet of Exposed Wall 0 ft 3.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²387.0ft 9.0 ft²513.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.0 x 13.5 ft ft²108.0 1.0 x 162.5 ft ft²162.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²108.0°0 ft²162.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 0 0 0 32 238 60 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 108 287 171 163 432 258FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.230.23 0 102EffectWARWAR 12 Sensible Load (Btuh)ACH 0 0 0.06 150.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 1200 900 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 321 1340 2259 3361 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -51 -46 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 321 1340 2259 3361 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 20...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 3Ldr 3Bath 2 Running Feet of Exposed Wall 8.0 ft 6.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²216.0ft 9.0 ft²234.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.0 x 4.0 ft ft²32.0 6.5 x 6.5 ft ft²42.3 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²32.0°0 ft²42.3° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 59 442 112 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 72 484 123 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 8 379 520 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 32 85 51 42 112 67FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.230.23 233 190EffectWARWAR 12 Sensible Load (Btuh)ACH 0.14 33 0.11 270.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 500 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1698 2180 778 218 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 196 -8 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1698 2180 778 218 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 21...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit3 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 3Clos 2 Running Feet of Exposed Wall 0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)6.5 x 5.5 ft ft²35.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²35.8° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12C-0sw n 0.00 0.00 0 0 0.Glaz 1D-c2ov n 0.00 0.00 0 0 0.Wall 12C-0sw e 7.56 1.92 0 0 0 .Glaz 1D-c2ov e 47.37 65.00 0 0 0 11 Wall 12C-0sw s 0.00 0.00 0 0 0 Wall 12C-0sw w 7.56 1.92 0 0 0 Glaz 1D-c2ov w 47.37 65.00 0 0 0Door11D0w32.41 10.18 0 0 0 Ceil 16B-30ad -2.66 1.59 36 95 57Flor19A-19bscp -3.19 0.85 0 0 0 Infiltration Heating Load (Btuh)0.23 0EffectWAR 12 Sensible Load (Btuh)ACH 0 00.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 b Scenario number 0 13 c Default Adjustments d Custom Appliances 0 0ePlants0 14 Subtotals Sum lines 6 through 12 0 0 Duct EHLF & ESGF 0 0 0 015Loads ELG 0 Vent Cfm16Ventilation Loads 38 E Cfm 38 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -2 21 Total Load Sum lines 13 through 19 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 22...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Unit4 4Living 2 Running Feet of Exposed Wall 57.0 ft 3.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²2772.0ft 9.0 ft²513.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²636.5 1.0 x 162.5 ft ft²162.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²636.5°0 ft²162.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 171 1202 305 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 12 568 780 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 342 1989 505 32 238 60 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 58 2747 3770 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 561 1490 890 163 432 258FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 76 243 64 0 0 0 Infiltration Heating Load (Btuh)0.230.23 1662 102EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 237 0.06 150.120.12 Latent Load (Btuh)-145 Internal a Occupants at 230 and 200 Btuh 2 460 400 0 0 0 b Scenario number 2600 900 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 10583 11226 255 2259 3337 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 2949 784 -480 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1401 -54 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 13532 12010 0 2259 3337 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 23...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 4DStair 4Mech 2 Running Feet of Exposed Wall 10.0 ft 4.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²252.0ft 9.0 ft²153.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)10.0 x 4.0 ft ft²40.0 4.5 x 4.0 ft ft²18.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²40.0°0 ft²18.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 90 529 134 41 306 78 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 20 947 1300 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 0 0 0 0 0 0FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 40 128 34 18 57 15 Infiltration Heating Load (Btuh)0.230.23 292 131EffectWARWAR 12 Sensible Load (Btuh)ACH 0.18 42 0.08 190.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 534 -5 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 24...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 4Foy 4Ldr 2 Running Feet of Exposed Wall 4.5 ft 8.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²153.0ft 9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)4.5 x 4.0 ft ft²18.0 8.0 x 4.0 ft ft²32.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²18.0°0 ft²32.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 41 147 37 72 484 123 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 8 379 520DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 0 0 0 32 85 51FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 18 57 15 0 0 0 Infiltration Heating Load (Btuh)0.230.23 131 233EffectWARWAR 12 Sensible Load (Btuh)ACH 0.08 19 0.14 330.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 500 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 3408 2424 1698 2164 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -13 186 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 3408 2424 1698 2164 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 25...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 4Kit 4Clos 2 Running Feet of Exposed Wall 0 ft 0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²387.0ft 9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.0 x 13.5 ft ft²108.0 6.5 x 5.5 ft ft²35.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²108.0°0 ft²35.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 0 0 0 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 108 287 171 36 95 57FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.230.23 0 0EffectWARWAR 12 Sensible Load (Btuh)ACH 0 0 0 00.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 1200 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 321 1330 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -60 -2 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 321 1330 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 26...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 4Stair 4Bed 2 Running Feet of Exposed Wall 7.5 ft 12.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²207.0ft 9.0 ft²441.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)7.5 x 4.0 ft ft²30.0 12.5 x 12.0 ft ft²150.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²30.0°0 ft²150.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 113 760 193 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 12 568 780 11 WallWall 12C-0sw12C-0sw ss 0.000.00 0.000.00 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 68 284 72 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 30 1421 1950 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 30 80 48 150 399 238FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.230.23 219 364EffectWARWAR 12 Sensible Load (Btuh)ACH 0.13 31 0.22 520.120.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 2 460 400 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 2120 1754 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3838 E CfmE Cfm 3838 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 809 15 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 2120 1754 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 27...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit4 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 4Bath 2 Running Feet of Exposed Wall 6.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²234.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)6.5 x 6.5 ft ft²42.3 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²42.3° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12C-0sw n 0.00 0.00 0 0 0.Glaz 1D-c2ov n 0.00 0.00 0 0 0.Wall 12C-0sw e 7.56 1.92 59 442 112 .Glaz 1D-c2ov e 47.37 65.00 0 0 0 11 Wall 12C-0sw s 0.00 0.00 0 0 0 Wall 12C-0sw w 7.56 1.92 0 0 0 Glaz 1D-c2ov w 47.37 65.00 0 0 0Door11D0w32.41 10.18 0 0 0 Ceil 16B-30ad -2.66 1.59 42 112 67Flor19A-19bscp -3.19 0.85 0 0 0 Infiltration Heating Load (Btuh)0.23 190EffectWAR 12 Sensible Load (Btuh)ACH 0.11 270.12 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 b Scenario number 0 13 c Default Adjustments d Custom Appliances 0 0ePlants0 14 Subtotals Sum lines 6 through 12 778 216 Duct EHLF & ESGF 0 0 0 015Loads ELG 0 Vent Cfm16Ventilation Loads 38 E Cfm 38 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -9 21 Total Load Sum lines 13 through 19 778 216 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 28...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room Unit5 5Living 2 Running Feet of Exposed Wall 90.5 ft 3.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²2772.0ft 9.0 ft²513.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²636.5 1.0 x 162.5 ft ft²162.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²636.5°0 ft²162.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 171 1202 305 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 12 568 780 0 0 0 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 302 2280 579 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 342 1989 505 32 238 60 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 58 2747 3770 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 21 681 214 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 561 1490 890 163 432 258FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 76 243 64 0 0 0 Infiltration Heating Load (Btuh)0.360.36 2639 102EffectWARWAR 12 Sensible Load (Btuh)ACH 1.00 376 0.04 150.190.19 Latent Load (Btuh)-230 Internal a Occupants at 230 and 200 Btuh 2 460 400 0 0 0 b Scenario number 2600 900 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 13839 11944 170 2259 3346 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 2426 645 -395 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 1401 -51 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 16265 12589 0 2259 3346 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 29...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 5DStair 5Foy 2 Running Feet of Exposed Wall 10.0 ft 8.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²252.0ft 9.0 ft²153.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)10.0 x 4.0 ft ft²40.0 4.5 x 4.0 ft ft²18.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²40.0°0 ft²18.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 0 0 0 36 272 69 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 90 529 134 41 147 37 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 20 947 1300 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 21 681 214 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 0 0 0 0 0 0FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 40 128 34 18 57 15 Infiltration Heating Load (Btuh)0.360.36 292 248EffectWARWAR 12 Sensible Load (Btuh)ACH 0.11 42 0.09 350.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 3796 2512 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 540 -15 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 3796 2512 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 30...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 5Mech 5Clos 2 Running Feet of Exposed Wall 4.5 ft 5.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²153.0ft 9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)4.5 x 4.0 ft ft²18.0 6.5 x 5.5 ft ft²35.8 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²18.0°0 ft²35.8° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 0 0 0 50 374 95 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 41 306 78 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 0 0 0 36 95 57FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 18 57 15 0 0 0 Infiltration Heating Load (Btuh)0.360.36 131 160EffectWARWAR 12 Sensible Load (Btuh)ACH 0.05 19 0.06 230.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -5 -7 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 31...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 5Bed 5Stair 2 Running Feet of Exposed Wall 12.5 ft 7.5 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²441.0ft 9.0 ft²207.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)12.5 x 12.0 ft ft²150.0 7.5 x 4.0 ft ft²30.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²150.0°0 ft²30.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 113 760 193 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 12 568 780 0 0 0 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 0 0 0 68 284 72 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 30 1421 1950DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 150 399 238 30 80 48FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.360.36 364 219EffectWARWAR 12 Sensible Load (Btuh)ACH 0.14 52 0.08 310.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 2 460 400 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2279 1792 0 0 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 20 816 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2279 1792 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 32...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 5Kit 5Bath 2 Running Feet of Exposed Wall 13.5 ft 13.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²387.0ft 9.0 ft²234.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.0 x 13.5 ft ft²108.0 6.5 x 6.5 ft ft²42.3 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²108.0°0 ft²42.3° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 0.000.00 0.000.00 0 0 0 0 0 0.GlazGlaz 1D-c2ov1D-c2ov nn 0.000.00 0.000.00 0 0 0 0 0 0.WallWall 12C-0sw12C-0sw ee 7.567.56 1.921.92 0 0 0 59 442 112 .GlazGlaz 1D-c2ov1D-c2ov ee 47.3747.37 65.0065.00 0 0 0 0 0 0 11 WallWall 12C-0sw12C-0sw ss 7.567.56 1.921.92 122 919 233 59 442 112 WallWall 12C-0sw12C-0sw ww 7.567.56 1.921.92 0 0 0 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 47.3747.37 65.0065.00 0 0 0 0 0 0DoorDoor11D011D0ww32.4132.41 10.1810.18 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --2.662.66 1.591.59 108 287 171 42 112 67FlorFlor19A-19bscp19A-19bscp --3.193.19 0.850.85 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.360.36 394 379EffectWARWAR 12 Sensible Load (Btuh)ACH 0.15 56 0.14 540.190.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 1200 0 13 c Default Adjustments d Custom Appliances 0 0 0 0ePlants00 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1821 1651 1597 390 Duct EHLF & ESGF 00 00 0 0 0 015Loads ELG 0 0 Vent CfmVent Cfm16Ventilation Loads 3232 E CfmE Cfm 3232 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -69 -14 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1821 1651 1597 390 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:55Right-Suite® Universal 2019 19.0.13 RSU12258 Page 33...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Right-J8® Form J1 Mar 17, 2020Date:Unit5 By:JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com 1 Name of Room 5Ldr 2 Running Feet of Exposed Wall 12.0 ft3Ceiling Ht (Ft) and Gross Wall Area (SqFt)9.0 ft²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)8.0 x 4.0 ft ft²32.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²32.0° Type of Exposure Const., Number Panel Faces HTM Area or Length Btuh Area or Length Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12C-0sw n 0.00 0.00 0 0 0.Glaz 1D-c2ov n 0.00 0.00 0 0 0.Wall 12C-0sw e 7.56 1.92 0 0 0 .Glaz 1D-c2ov e 47.37 65.00 0 0 0 11 Wall 12C-0sw s 7.56 1.92 36 272 69 Wall 12C-0sw w 7.56 1.92 72 484 123 Glaz 1D-c2ov w 47.37 65.00 8 379 520Door11D0w32.41 10.18 0 0 0 Ceil 16B-30ad -2.66 1.59 32 85 51Flor19A-19bscp -3.19 0.85 0 0 0 Infiltration Heating Load (Btuh)0.36 350EffectWAR 12 Sensible Load (Btuh)ACH 0.13 500.19 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 b Scenario number 500 13 c Default Adjustments d Custom Appliances 0 0ePlants0 14 Subtotals Sum lines 6 through 12 2087 2252 Duct EHLF & ESGF 0 0 0 015Loads ELG 0 Vent Cfm16Ventilation Loads 32 E Cfm 32 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 187 21 Total Load Sum lines 13 through 19 2087 2252 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:57 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Mar 17, 2020Date:Entire House By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) )H(35-Daily range (°F) 64-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)55506 52682 47727 58234 62575 52568 41750 49805 Latent Load (Btuh)1104 1104 1104 1104 1104 1104 1104 1104 Total Load (Btuh)56611 53786 48832 59338 63679 53672 42854 50909 Heating AVF (cfm)2980 2980 2980 2980 2980 2980 2980 2980 Cooling AVF (cfm)2980 2980 2980 2980 2980 2980 2980 2980 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 20000 40000 60000 80000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces SouthHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:57 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) )H(35-Daily range (°F) 64-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)11716 11237 10243 12358 12992 11055 9131 10705 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)11716 11237 10243 12358 12992 11055 9131 10705 Heating AVF (cfm)600 600 600 600 600 600 600 600 Cooling AVF (cfm)600 600 600 600 600 600 600 600 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces SouthHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:57 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) )H(35-Daily range (°F) 64-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)10832 10293 9233 11337 12262 10241 8025 9656 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)10832 10293 9233 11337 12262 10241 8025 9656 Heating AVF (cfm)600 600 600 600 600 600 600 600 Cooling AVF (cfm)600 600 600 600 600 600 600 600 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces SouthHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:57 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) )H(35-Daily range (°F) 64-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)10703 10248 9194 11274 12205 10200 7952 9542 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)10703 10248 9194 11274 12205 10200 7952 9542 Heating AVF (cfm)593 593 593 593 593 593 593 593 Cooling AVF (cfm)593 593 593 593 593 593 593 593 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces SouthHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:57 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) )H(35-Daily range (°F) 64-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)10832 10293 9233 11337 12262 10241 8025 9656 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)10832 10293 9233 11337 12262 10241 8025 9656 Heating AVF (cfm)593 593 593 593 593 593 593 593 Cooling AVF (cfm)593 593 593 593 593 593 593 593 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces SouthHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:57 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Loads for Multiple Orientations Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)Idaho Falls Rgnl, ID, US 2283Design TD (°F)ft4744Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-21.962.8Moisture difference (gr/lb)CoolingHeating Infiltration:97-13Dry bulb (°F) )H(35-Daily range (°F) 64-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)11423 10884 9824 11928 12853 10832 8616 10247 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)11423 10884 9824 11928 12853 10832 8616 10247 Heating AVF (cfm)593 593 593 593 593 593 593 593 Cooling AVF (cfm)593 593 593 593 593 593 593 593 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 N NE E SE S SW W NW Front Door faces SouthCurrent Orientation: Front Door faces SouthHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Mar 17, 2020Date:Entire House By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Supporting Detail Project Name:Mar 17, 2020Eden Townhomes Date: Address:555 Mikn, Rexburg, ID 83440 Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Idaho Falls Rgnl, ID, US 444744Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%50 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-13°F Hgr/lb-22°F97 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F22°F83 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Supporting Detail Project Name:Mar 17, 2020Eden Townhomes Date: Address:555 Mikn, Rexburg, ID 83440 Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Idaho Falls Rgnl, ID, US 444744Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%50 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-13°F Hgr/lb-22°F97 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F22°F83 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Supporting Detail Project Name:Mar 17, 2020Eden Townhomes Date: Address:555 Mikn, Rexburg, ID 83440 Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Idaho Falls Rgnl, ID, US 444744Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%50 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-13°F Hgr/lb-22°F97 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F22°F83 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Supporting Detail Project Name:Mar 17, 2020Eden Townhomes Date: Address:555 Mikn, Rexburg, ID 83440 Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Idaho Falls Rgnl, ID, US 444744Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%50 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-13°F Hgr/lb-22°F97 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F22°F83 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Supporting Detail Project Name:Mar 17, 2020Eden Townhomes Date: Address:555 Mikn, Rexburg, ID 83440 Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Idaho Falls Rgnl, ID, US 444744Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%50 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-13°F Hgr/lb-22°F97 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F22°F83 CTD =HTD = Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:J1 Form - Worksheet A Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Supporting Detail Project Name:Mar 17, 2020Eden Townhomes Date: Address:555 Mikn, Rexburg, ID 83440 Phone:Job ID: Worksheet A Location and Design Conditions Weather Location:Idaho Falls Rgnl, ID, US 444744Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%50 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-13°F Hgr/lb-22°F97 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F22°F83 CTD =HTD = Job #: Performed for: Eden Townhomes 555 Mikn Rexburg, ID 83440 JM Mechanical 3775 N. Hwy 91 Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 balmond@jmmech.com Scale: 1 : 161 Page 1 Right-Suite® Universal 2019 19.0.13 RSU12258 2020-Mar-20 14:35:25 ...ightsoft HVAC\Eden Townhomes.rup N Upper 1Bed 1Bath 1Clos 1Living 1Kit 1Stair 1Ldr 2Bed 2Bath 2Clos 2Living 2Kit 2Stair 2Ldr 3Bed 3Bath 3Clos 3Living 3Kit 3Stair 3Ldr 4Bed 4Bath 4Clos 4Living 4Kit 4Stair 4Ldr 5Bed 5Bath 5Clos 5Living 5Kit 5Stair 5Ldr 139 cfm 108 cfm 33 cfm 434 cfm 236 cfm 192 cfm 120 cfm 44 cfm 308 cfm 600 cfm 178 cfm 71 cfm 126 cfm 160 cfm 115 cfm 44 cfm 178 cfm 71 cfm 116 cfm 119 cfm 44 cfm 385 cfm 176 cfm 114 cfm 98 cfm 68 cfm 249 cfm 344 cfm 256 cfm 166 cfm 112 cfm116 cfm 66 cfm 70 cfm 82 cfm Job #: Performed for: Eden Townhomes 555 Mikn Rexburg, ID 83440 JM Mechanical 3775 N. Hwy 91 Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 balmond@jmmech.com Scale: 1 : 161 Page 2 Right-Suite® Universal 2019 19.0.13 RSU12258 2020-Mar-20 14:35:25 ...ightsoft HVAC\Eden Townhomes.rup N Main 1Gar 1Foy1Mech1DStair 2Gar 2Foy2Mech2DStair 3Gar 3Foy3Mech3DStair 4Gar 4Foy4Mech4DStair 5Gar 5Foy5Mech5DStair 193 cfm161 cfm 192 cfm 191 cfm 163 cfm 2-14x3.253-14x3.25 6 " 7 "8 " 7 " 6 " 6 " 2-14x3.253-14x3.25 3-14x3.25 6 " 6 " 6 " 7 " 7 " 6 " 14x3.25 2-14x3.25 14x3.25 6 " 6 " 6 " 7 " 7 " 6 " 16 x 8 2-14x3.252-14x3.25 16 x 816 x 88 x 814 x 8 6 " 6 " 7 " 7 " 6 " 14 x 816 x 814 x 8 6 " 10 x 8 6 " 6 " 7 " 7 " 7 " 6 " 4" OA 4" OA 4" OA 4" OA4" OA Bold/italic values have been manually overridden 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 CoolingHeating External static pressure in H2O0.80in H2O0.80 Pressure losses in H2O0.39in H2O0.39 Available static pressure in H2O0.41in H2O0.41 Supply / return available pressure 0.254 / 0.156 in H2O in H2O0.254 / 0.156 Lowest friction rate in/100ft0.111in/100ft0.111 Actual air flow cfm600cfm600 Total effective length (TEL)ft369 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st5190.038.5ShMt0x06.00.1111133778h1Bath st5195.031.0ShMt0x07.00.112991393287h1Bed st5180.018.0ShMt0x07.00.1281251613796h1Foy st5170.023.5ShMt0x06.00.13166141331c1Kit st5105.019.5ShMt0x06.00.204108722165c1Ldr 95.07.5ShMt0x07.00.2481921813860c1Living Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st5 Peak AVF 419 408 0.111 754 9.7 10x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb2 0x 4340 364 140.0 0.111 458 9.9 3-3.25x14 3-10x27 SJSp rt6 rb7 0x 1660 236 125.5 0.124 373 7.7 2-3.25x14 2-10x18 SJSp rt6 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt6 Peak AVF 600 600 0.111 675 11.1 16x8 ShtMetl 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 CoolingHeating External static pressure in H2O0.80in H2O0.80 Pressure losses in H2O0.39in H2O0.39 Available static pressure in H2O0.41in H2O0.41 Supply / return available pressure 0.283 / 0.127 in H2O in H2O0.283 / 0.127 Lowest friction rate in/100ft0.126in/100ft0.126 Actual air flow cfm600cfm600 Total effective length (TEL)ft326 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st4180.038.0ShMt0x06.00.1301244778h2Bath st4195.029.5ShMt0x06.00.126941202120h2Bed st4105.021.5ShMt0x07.00.2241301933408h2Foy st4190.019.0ShMt0x06.00.13571181330c2Kit st4170.020.0ShMt0x06.00.149116962164c2Ldr st4160.07.0ShMt0x07.00.1691781283337c2Living Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 600 600 0.126 771 10.9 14x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb8 0x 6000 600 101.0 0.126 633 10.9 3-3.25x14 3-10x27 SJSp 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 CoolingHeating External static pressure in H2O0.80in H2O0.80 Pressure losses in H2O0.39in H2O0.39 Available static pressure in H2O0.41in H2O0.41 Supply / return available pressure 0.274 / 0.136 in H2O in H2O0.274 / 0.136 Lowest friction rate in/100ft0.122in/100ft0.122 Actual air flow cfm593cfm593 Total effective length (TEL)ft336 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st3180.037.5ShMt0x06.00.1261244778h3Bath st3195.029.5ShMt0x06.00.122871152040h3Bed st3105.021.0ShMt0x07.00.2181301923408h3Foy st3190.019.0ShMt0x06.00.13171181340c3Kit st3170.019.5ShMt0x06.00.145116962180c3Ldr st3160.07.0ShMt0x07.00.1641781283361c3Living Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 593 593 0.122 762 10.9 14x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb4 0x 3070 308 111.0 0.122 488 8.5 2-3.25x14 2-10x18 SJSp rb9 0x 1260 126 96.0 0.141 399 5.9 3.25x14 10x9 SJSp rt3 rb10 0x 1600 159 110.5 0.123 506 6.7 3.25x14 10x9 SJSp rt3 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt3 Peak AVF 286 285 0.123 644 8.3 8x8 ShtMetl 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 CoolingHeating External static pressure in H2O0.80in H2O0.80 Pressure losses in H2O0.39in H2O0.39 Available static pressure in H2O0.41in H2O0.41 Supply / return available pressure 0.311 / 0.099 in H2O in H2O0.311 / 0.099 Lowest friction rate in/100ft0.071in/100ft0.071 Actual air flow cfm593cfm593 Total effective length (TEL)ft582 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2225.037.5ShMt0x06.00.1191144778h4Bath st2160.029.5ShMt0x06.00.164931192120h4Bed st2420.021.5ShMt0x08.00.0711281913408h4Foy st2355.022.0ShMt0x06.00.08370181330c4Kit st2290.019.5ShMt0x07.00.101114952164c4Ldr st2160.06.5ShMt0x07.00.1871761273337c4Living Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 593 593 0.071 668 12.2 16x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb5 0x 3850 345 140.0 0.071 406 10.3 3-3.25x14 3-10x27 SJSp rt2 rb11 0x 2090 249 125.0 0.079 394 8.6 2-3.25x14 2-10x18 SJSp rt2 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 7 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 593 593 0.071 668 12.2 16x8 ShtMetl 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 8 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 CoolingHeating External static pressure in H2O0.80in H2O0.80 Pressure losses in H2O0.39in H2O0.39 Available static pressure in H2O0.41in H2O0.41 Supply / return available pressure 0.254 / 0.156 in H2O in H2O0.254 / 0.156 Lowest friction rate in/100ft0.111in/100ft0.111 Actual air flow cfm593cfm593 Total effective length (TEL)ft369 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1190.038.0ShMt0x06.00.11119681597h5Bath st1195.029.0ShMt0x06.00.11389982279h5Bed st1105.021.0ShMt0x07.00.2011251633796h5Foy st1170.020.5ShMt0x06.00.13382781651c5Kit st1180.019.5ShMt0x06.00.127112892252c5Ldr st1160.06.0ShMt0x07.00.153166973346c5Living Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 593 593 0.111 763 11.1 14x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb6 0x 3440 337 140.5 0.111 545 9.0 2-3.25x14 2-10x18 SJSp rt1 rb12 0x 2490 256 125.0 0.125 406 7.9 2-3.25x14 2-10x18 SJSp rt1 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 9 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 593 593 0.111 668 11.1 16x8 ShtMetl 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct system multi orientation report Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Group 1: ( N, NE, E, SE, S, SW, W, NW) Duct Name (SE)(E)(NE)(N) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 1Bath 612x433 h612x433 h612x433 h612x433 h 1Bed 712x4139 h712x4139 h712x4139 h712x4139 h 1Foy 712x4161 h712x4161 h712x4161 h712x4161 h 1Kit 612x482 c612x471 c612x475 c612x486 c 1Ldr 612x487 c612x497 c612x495 c612x491 c 1Living 712x4192 c712x4189 c712x4204 c712x4217 c Supply Trunks st5 10x8419 h10x8419 h10x8419 h10x8419 h Return Branches rb2 0x030x8434 h0x030x8434 h0x030x8434 h0x030x8434 h rb7 0x030x8218 c0x030x8223 c0x030x8223 c0x030x8227 c Return Trunks rt6 16x8600 c16x8600 c16x8600 c16x8600 c Friction Rates Heating FR 0.1110.1110.1110.111 Cooling FR 0.1110.1110.1110.111 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name (NW)(W)(SW)(S) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 1Bath 612x433 h612x433 h612x433 h612x433 h 1Bed 712x4139 h712x4139 h712x4139 h712x4139 h 1Foy 712x4161 h712x4161 h712x4161 h712x4161 h 1Kit 612x471 c612x466 c612x477 c612x499 c 1Ldr 612x4103 c612x4108 c612x497 c612x479 c 1Living 712x4205 c712x4192 c712x4194 c712x4199 c Supply Trunks st5 10x8419 h10x8419 h10x8419 h10x8419 h Return Branches rb2 0x030x8434 h0x030x8434 h0x030x8434 h0x030x8434 h rb7 0x030x8233 c0x030x8236 c0x030x8229 c0x030x8218 c Return Trunks rt6 16x8600 c16x8600 c16x8600 c16x8600 c Friction Rates Heating FR 0.1110.1110.1110.111 Cooling FR 0.1110.1110.1110.111 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name SmalestLargest Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 1Bath 612x433 h612x433 h 1Bed 712x4139 h712x4139 h 1Foy 712x4161 h712x4161 h 1Kit 612x466 c612x499 c 1Ldr 612x479 c612x4108 c 1Living 712x4189 c712x4217 c Supply Trunks st5 10x8419 h10x8419 h Return Branches rb2 0x030x8434 h0x030x8434 h rb7 0x030x8218 c0x030x8236 c Return Trunks rt6 16x8600 c16x8600 c Friction Rates Heating FR 0.1110.111 Cooling FR 0.1110.111 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct system multi orientation report Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Group 1: ( N, NE, E, SW, W, NW) Group 2: (SE, S) Duct Name (SE)(E)(NE)(N) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 2Bath 612x444 h612x444 h612x444 h612x444 h 2Bed 712x4129 c612x4120 h612x4120 h612x4120 h 2Foy 712x4193 h712x4193 h712x4193 h712x4193 h 2Kit 612x493 c612x478 c612x485 c612x4101 c 2Ldr 612x499 c612x4107 c612x4108 c612x4108 c 2Living 712x4160 c712x4167 c712x4170 c712x4173 c Supply Trunks st4 14x8600 c14x8600 c14x8600 c14x8600 c Return Branches rb8 0x030x8600 c0x030x8600 c0x030x8600 c0x030x8600 c Friction Rates Heating FR 0.1260.1260.1260.126 Cooling FR 0.1260.1260.1260.126 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name (NW)(W)(SW)(S) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 2Bath 612x444 h612x444 h612x444 h612x444 h 2Bed 612x4120 h612x4120 h612x4120 h712x4127 c 2Foy 712x4193 h712x4193 h712x4193 h712x4193 h 2Kit 612x480 c612x471 c612x486 c612x4116 c 2Ldr 612x4115 c612x4116 c612x4108 c612x496 h 2Living 712x4179 c712x4178 c712x4170 c712x4155 c Supply Trunks st4 14x8600 c14x8600 c14x8600 c14x8600 c Return Branches rb8 0x030x8600 c0x030x8600 c0x030x8600 c0x030x8600 c Friction Rates Heating FR 0.1260.1260.1260.126 Cooling FR 0.1260.1260.1260.126 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 6 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name SmalestLargest Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 2Bath 612x444 h612x444 h 2Bed 612x4120 h712x4129 c 2Foy 712x4193 h712x4193 h 2Kit 612x471 c612x4116 c 2Ldr 612x496 h612x4116 c 2Living 712x4155 c712x4179 c Supply Trunks st4 14x8600 c14x8600 c Return Branches rb8 0x030x8600 c0x030x8600 c Friction Rates Heating FR 0.1260.126 Cooling FR 0.1260.126 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 7 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct system multi orientation report Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Group 1: ( N, NE, E, SW, W, NW) Group 2: (SE, S) Duct Name (SE)(E)(NE)(N) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 3Bath 612x444 h612x444 h612x444 h612x444 h 3Bed 712x4119 c612x4115 h612x4115 h612x4115 h 3Foy 712x4192 h712x4192 h712x4192 h712x4192 h 3Kit 612x494 c612x479 c612x486 c612x4100 c 3Ldr 612x4100 c612x4107 c612x4108 c612x4107 c 3Living 712x4161 c712x4168 c712x4171 c712x4172 c Supply Trunks st3 14x8593 c14x8593 c14x8593 c14x8593 c Return Branches rb4 0x030x8315 c0x030x8316 c0x030x8308 c0x030x8307 h rb9 0x030x8144 c0x030x8131 c0x030x8138 c0x030x8154 c rb10 0x030x8160 h0x030x8160 h0x030x8160 h0x030x8160 h Return Trunks rt3 8x8286 h8x8286 h8x8286 h8x8298 c Friction Rates Heating FR 0.1120.1120.1120.112 Cooling FR 0.1120.1120.1120.112 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 8 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name (NW)(W)(SW)(S) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 3Bath 612x444 h612x444 h612x444 h612x444 h 3Bed 612x4115 h612x4115 h612x4115 h712x4120 c 3Foy 712x4192 h712x4192 h712x4192 h712x4192 h 3Kit 612x479 c612x471 c612x486 c612x4116 c 3Ldr 612x4115 c612x4116 c612x4108 c612x496 h 3Living 712x4179 c712x4178 c712x4170 c712x4156 c Supply Trunks st3 14x8593 c14x8593 c14x8593 c14x8593 c Return Branches rb4 0x030x8307 h0x030x8308 c0x030x8308 c0x030x8307 h rb9 0x030x8134 c0x030x8126 h0x030x8138 c0x030x8165 c rb10 0x030x8160 h0x030x8160 h0x030x8160 h0x030x8160 h Return Trunks rt3 8x8291 c8x8286 h8x8286 h8x8288 c Friction Rates Heating FR 0.1120.1220.1120.112 Cooling FR 0.1120.1220.1120.112 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 9 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name SmalestLargest Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 3Bath 612x444 h612x444 h 3Bed 612x4115 h712x4120 c 3Foy 712x4192 h712x4192 h 3Kit 612x471 c612x4116 c 3Ldr 612x496 h612x4116 c 3Living 712x4156 c712x4179 c Supply Trunks st3 14x8593 c14x8593 c Return Branches rb4 0x030x8307 h0x030x8316 c rb9 0x030x8126 h0x030x8165 c rb10 0x030x8160 h0x030x8160 h Return Trunks rt3 8x8286 h8x8298 c Friction Rates Heating FR 0.1120.122 Cooling FR 0.1120.122 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 10 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct system multi orientation report Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Group 1: ( N, S) Group 2: (NE, E, SE, SW) Group 3: ( W, NW) Duct Name (SE)(E)(NE)(N) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 4Bath 612x444 h612x444 h612x444 h612x444 h 4Bed 612x4128 c612x4119 h612x4119 h612x4119 h 4Foy 812x4191 h812x4191 h812x4191 h812x4191 h 4Kit 612x492 c612x477 c612x484 c712x4100 c 4Ldr 612x498 c612x4105 c612x4107 c612x4106 c 4Living 712x4158 c712x4165 c712x4169 c712x4171 c Supply Trunks st2 16x8593 c16x8593 c16x8593 c16x8593 c Return Branches rb5 0x030x8385 h0x030x8385 h0x030x8385 h0x030x8385 h rb11 0x030x8242 c0x030x8240 c0x030x8249 c0x030x8262 c Return Trunks rt2 16x8593 c16x8593 c16x8593 c16x8593 c Friction Rates Heating FR 0.0710.0710.0710.071 Cooling FR 0.0710.0710.0710.071 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 11 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name (NW)(W)(SW)(S) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 4Bath 612x444 h612x444 h612x444 h612x444 h 4Bed 612x4119 h612x4119 h612x4119 h612x4126 c 4Foy 812x4191 h812x4191 h812x4191 h812x4191 h 4Kit 612x479 c612x470 c612x485 c712x4115 c 4Ldr 712x4114 c712x4114 c612x4107 c612x495 h 4Living 712x4177 c712x4176 c712x4168 c712x4154 c Supply Trunks st2 16x8593 c16x8593 c16x8593 c16x8593 c Return Branches rb5 0x030x8385 h0x030x8385 h0x030x8385 h0x030x8385 h rb11 0x030x8255 c0x030x8249 c0x030x8249 c0x030x8251 c Return Trunks rt2 16x8593 c16x8593 c16x8593 c16x8593 c Friction Rates Heating FR 0.0710.0710.0710.071 Cooling FR 0.0710.0710.0710.071 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 12 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name SmalestLargest Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 4Bath 612x444 h612x444 h 4Bed 612x4119 h612x4128 c 4Foy 812x4191 h812x4191 h 4Kit 612x470 c712x4115 c 4Ldr 612x495 h712x4114 c 4Living 712x4154 c712x4177 c Supply Trunks st2 16x8593 c16x8593 c Return Branches rb5 0x030x8385 h0x030x8385 h rb11 0x030x8240 c0x030x8262 c Return Trunks rt2 16x8593 c16x8593 c Friction Rates Heating FR 0.0710.071 Cooling FR 0.0710.071 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 13 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Duct system multi orientation report Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Group 1: ( N, NE, E, SW, W, NW) Group 2: (SE) Group 3: ( S) Duct Name (SE)(E)(NE)(N) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 5Bath 612x468 h612x468 h612x468 h612x468 h 5Bed 712x4120 c612x4112 c612x4100 c612x498 h 5Foy 712x4163 h712x4163 h712x4163 h712x4163 h 5Kit 612x4106 c612x490 c612x497 c612x4114 c 5Ldr 612x496 c612x4103 c612x4104 c612x4104 c 5Living 712x4146 c712x4155 c712x4157 c712x4158 c Supply Trunks st1 14x8593 c14x8593 c14x8593 c14x8593 c Return Branches rb6 0x030x8344 h0x030x8344 h0x030x8344 h0x030x8344 h rb12 0x030x8252 c0x030x8249 c0x030x8258 c0x030x8271 c Return Trunks rt1 16x8593 c16x8593 c16x8593 c16x8593 c Friction Rates Heating FR 0.1110.1110.1110.111 Cooling FR 0.1110.1110.1110.111 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 14 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name (NW)(W)(SW)(S) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 5Bath 612x468 h612x468 h612x468 h612x468 h 5Bed 612x498 h612x498 h612x4100 c712x4117 c 5Foy 712x4163 h712x4163 h712x4163 h712x4163 h 5Kit 612x491 c612x482 c612x498 c712x4129 c 5Ldr 612x4111 c612x4112 c612x4104 c612x490 c 5Living 712x4166 c712x4166 c712x4157 c712x4140 c Supply Trunks st1 14x8593 c14x8593 c14x8593 c14x8593 c Return Branches rb6 0x030x8344 h0x030x8344 h0x030x8344 h0x030x8344 h rb12 0x030x8263 c0x030x8256 c0x030x8258 c0x030x8263 c Return Trunks rt1 16x8593 c16x8593 c16x8593 c16x8593 c Friction Rates Heating FR 0.1110.1110.1110.111 Cooling FR 0.1110.1110.1110.111 2020-Mar-20 14:34:58 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 15 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Duct Name SmalestLargest Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches 5Bath 612x468 h612x468 h 5Bed 612x498 h712x4120 c 5Foy 712x4163 h712x4163 h 5Kit 612x482 c712x4129 c 5Ldr 612x490 c612x4112 c 5Living 712x4140 c712x4166 c Supply Trunks st1 14x8593 c14x8593 c Return Branches rb6 0x030x8344 h0x030x8344 h rb12 0x030x8249 c0x030x8271 c Return Trunks rt1 16x8593 c16x8593 c Friction Rates Heating FR 0.1110.111 Cooling FR 0.1110.111 2020-Mar-20 14:34:59 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 1 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Static Pressure and Friction Rate Mar 17, 2020Date:Unit1 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.800.80External static pressure Pressure losses 0.300.30Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 0.030.03Filter 00Humidifier 00Balancing damper 00Other device 0.410.41Available static pressure Total Effective Length ReturnSupply (ft)(ft) 1426Measured length of run-out 213Measured length of trunk 125190Equivalent length of fittings 140229Total length 369Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.111OK0.111Supply Ducts OK0.111OK0.111Return Ducts Fitting Equivalent Length Details 4AD=60, 2I3=95, 1A=35: TotalEL=190Supply 6M=20, 6B3=40, 5A=40, 6BB=25: TotalEL=125Return 2020-Mar-20 14:34:59 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 2 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Static Pressure and Friction Rate Mar 17, 2020Date:Unit2 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.800.80External static pressure Pressure losses 0.300.30Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 0.030.03Filter 00Humidifier 00Balancing damper 00Other device 0.410.41Available static pressure Total Effective Length ReturnSupply (ft)(ft) 2124Measured length of run-out 06Measured length of trunk 80195Equivalent length of fittings 101225Total length 326Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.126OK0.126Supply Ducts OK0.126OK0.126Return Ducts Fitting Equivalent Length Details 4AD=60, 2I4=100, 1C=35: TotalEL=195Supply 6M=20, 8B3=20, 5A=40: TotalEL=80Return 2020-Mar-20 14:34:59 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 3 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Static Pressure and Friction Rate Mar 17, 2020Date:Unit3 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.800.80External static pressure Pressure losses 0.300.30Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 0.030.03Filter 00Humidifier 00Balancing damper 00Other device 0.410.41Available static pressure Total Effective Length ReturnSupply (ft)(ft) 3124Measured length of run-out 06Measured length of trunk 80195Equivalent length of fittings 111225Total length 336Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.122OK0.122Supply Ducts OK0.122OK0.122Return Ducts Fitting Equivalent Length Details 4AD=60, 2I4=100, 1C=35: TotalEL=195Supply 6M=20, 8B3=20, 5A=40: TotalEL=80Return 2020-Mar-20 14:34:59 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 4 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Static Pressure and Friction Rate Mar 17, 2020Date:Unit4 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.800.80External static pressure Pressure losses 0.300.30Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 0.030.03Filter 00Humidifier 00Balancing damper 00Other device 0.410.41Available static pressure Total Effective Length ReturnSupply (ft)(ft) 145Measured length of run-out 217Measured length of trunk 125420Equivalent length of fittings 140442Total length 582Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.071OK0.071Supply Ducts OK0.071OK0.071Return Ducts Fitting Equivalent Length Details 4AD=60, 2I0=65, 9K=65, 9K=65, 9K=65, 9K=65, 1A=35: TotalEL=420Supply 6M=20, 6B3=40, 5A=40, 6BB=25: TotalEL=125Return 2020-Mar-20 14:34:59 Right-Suite® Universal 2019 19.0.13 RSU12258 Page 5 ...CH\Documents\Wrightsoft HVAC\Eden Townhomes.rup Calc = MJ8 Front Door faces: S Job:Static Pressure and Friction Rate Mar 17, 2020Date:Unit5 By: JM Mechanical 3775 N. Hwy 91, Hyde Park, UT 84318 Phone: 435-563-6267 Fax: 435-563-7025 Email: balmond@jmmech.com Project Information Eden Townhomes, Kartchner HomesFor: 555 Mikn, Rexburg, ID 83440 Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.800.80External static pressure Pressure losses 0.300.30Coil 00Heat exchanger 0.030.03Supply diffusers 0.030.03Return grilles 0.030.03Filter 00Humidifier 00Balancing damper 00Other device 0.410.41Available static pressure Total Effective Length ReturnSupply (ft)(ft) 1424Measured length of run-out 214Measured length of trunk 125190Equivalent length of fittings 141228Total length 369Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.111OK0.111Supply Ducts OK0.111OK0.111Return Ducts Fitting Equivalent Length Details 4AD=60, 2I3=95, 1C=35: TotalEL=190Supply 6M=20, 6B3=40, 5A=40, 6BB=25: TotalEL=125Return