HomeMy WebLinkAboutPLANS - 20-00180 - BYU-Idaho Benson Fume HoodSHEET INDEX SHEET NO. SHEET TITLE REVISION M0.00 GENERAL NOTES, SHEET INDEX, LEGEND MD1.10 MECHANICAL DEMO PLAN M1.10 MECHANICAL FLOOR PLAN M5.10 TYPICAL DETAILS, SCHEMATICS AND SEQUENCE OF OPERATIONS. TOTAL NO. OF SHEETS: 4 G M T H MECHANICAL LEGEND 18/12 SUPPLY DIFFUSER RETURN GRILLE EXHAUST GRILLE RETURN AIR DUCT SECTION RETURN AIR DUCT TURNED UP RETURN AIR DUCT DOWN SUPPLY AIR DUCT SECTION SUPPLY AIR DUCT TURNED UP SUPPLY AIR DUCT DOWN EXHAUST AIR DUCT SECTION EXHAUST AIR DUCT TURNED UP EXHAUST AIR DUCT DOWN ACCESS PANEL MANUAL VOLUME DAMPER GRAVITY BACKDRAFT DAMPER MOTORIZED DAMPER FIRE DAMPER COMBINATION FIRE/SMOKE DAMPER DUCT SIZE (FIRST FIGURE IS SIZE SHOWN) BURIED OR UNDERFLOOR DUCT DUCT W/ ACOUSTICAL LINING FLEXIBLE DUCT (HELICAL) FLEXIBLE DUCT CONNECTION DUCT TRANSITION ELBOW W/ TURNING VANES TEE W/45 DEGREE ENTRY WYE W/ 45 DEGREE ENTRY THERMOSTAT OR TEMP SENSOR HUMIDISTAT OR HUMIDITY SENSOR FD FSD STANDARD ABBREVIATIONS GATE VALVE BALL VALVE BUTTERFLY VALVE MOTORIZED VALVE OPERATOR CHECK VALVE (SWING OR LIFT AS REQ'D) SOLENOID VALVE AUTOMATIC CONTROL VALVE (2-WAY) AUTOMATIC CONTROL VALVE (3-WAY) PRESSURE REDUCING VALVE P & T RELIEF VALVE AIR VENT (AUTOMATIC) STRAINER AUTOMATIC FLOW CONTROL VALVE VENTURI FLOW METER REDUCER VALVE PET COCK OR GAUGE COCK PRESSURE GAUGE W/GAUGE COCK THERMOMETER TEMPERATURE & PRESSURE TEST PLUG PUMP FLOW SWITCH TEMPERATURE SENSOR HOSE BIB OR SILLCOCK YARD HYDRANT/ROOF HYDRANT FLOOR DRAIN FLOOR SINK WALL CLEANOUT (WCO) FLOOR CLEANOUT (FCO) EXPANSION JOINT FLEXIBLE PIPE CONNECTION REDUCED PRESSURE BACKFLOW PREVENTER DOUBLE CHECK BACKFLOW PREVENTER WATER HAMMER ARRESTOR ELBOW DOWN ELBOW UP PIPE CAP TEE DOWN UNION F T M CLEANOUT TO GRADE (CTG) GLOBE VALVE SHEET# SEC# (TEMP)°F CD RD OD STORM DRAIN SD FS NG CHS CHR CWS CWR HWS HWR S RL RS OVERFLOW ROOF DRAIN DOMESTIC COLD WATER (DCW) DOMESTIC HOT WATER (DHW) DOMESTIC HOT WATER RECIRC. (DHWR) DOMESTIC HOT WATER (SPECIFIED TEMP.) SANITARY VENT (VT) SANITARY SEWER ABOVE GRADE (SS) SANITARY SEWER BELOW GRADE (SS) CONDENSATE DRAIN ROOF DRAIN SECTION CUT LINE FIRE SPRINKLER SERVICE NATURAL GASHEAT TRACING CHILLED WATER SUPPLY CHILLED WATER RETURN CONDENSER WATER SUPPLY CONDENSER WATER RETURN HEATING WATER SUPPLY HEATING WATER RETURN STEAM REFRIGERANT LIQUID REFRIGERANT SUCTION POINT OF REMOVAL FROM EXISTING POINT OF CONNECTION TO EXISTING DETAIL TAG KEYED NOTE DET# SHT# M## LP LIQUID PROPANE PIPING BELOW GRADE (**SYS. ABR.)** (E) EXISTING (N) NEW AFF ABOVE FINISHED FLOOR AI ANALOG INPUT ALT ALTERNATE AO ANALOG INPUT APD AIR PRESSURE DROP BOD BOTTOM OF DUCT BOP BOTTOM OF PIPE BTU/H BRITISH THERMAL UNITS PER HOUR CAP. CAPACITY CFM CUBIC FEET PER MINUTE CV CONSTANT VOLUME DB DRY BULB DI DIGITAL INPUT DIA OR Ø DIAMETER DO DIGITAL OUTPUT EA EXHAUST AIR EAT ENTERING AIR TEMPERATURE EFF EFFICIENCY ELEV ELEVATION ESP EXTERNAL STATIC PRESSURE EWT ENTERING WATER TEMPERATURE FA FREE AREA FPM FEET PER MINUTE FT FEET FV FACE VELOCITY FW FRESH WATER GA GAUGE GAL GALLON GPM GALLONS PER MINUTE HP HORSEPOWER HR HOUR HT HEIGHT IAQ INDOOR AIR QUALITY IN. INCH INWC INCHES OF WATER COLUMN INWG INCHES OF WATER GAUGE LAT LEAVING AIR TEMPERATURE LBS POUNDS LWT LEAVING WATER TEMPERATURE MAX MAXIMUM MBH THOUSAND BRITISH THERMAL UNITS/HOUR MECH MECHANICAL MIN MINIMUM MVD MANUAL VOLUME DAMPER NC NOISE CRITERIA NIC NOT IN CONTRACT NO. NUMBER NOM NOMINAL NTS NOT TO SCALE OBD OPPOSED BLADE DAMPER OSA OUTSIDE AIR PD PRESSURE DROP PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE RA RETURN AIR SA SUPPLY AIR SEN SENSIBLE SL SEA LEVEL SP STATIC PRESSURE SQ FT SQUARE FEET SS SERVICE SINK OR STAINLESS STEEL TOD TOP OF DUCT TSP TOTAL STATIC PRESSURE UNO UNLESS NOTED OTHERWISE VAV VARIABLE AIR VOLUME VFD VARIABLE FREQUENCY DRIVE VOL VOLUME W/ WITH W/O WITHOUT WB WET BULB WPD WATER PRESSURE DROP WT WEIGHT NOTE: NOT ALL SYMBOLS MAY BE USED TH E S E P L A N S , D R A W I N G S A N D D E S I G N S A R E T H E E X C L U S I V E P R O P E R T Y O F E N G I N E E R I N G S Y S T E M S O L U T I O N S . A N D S H A L L N O T B E R E P R O D U C E D I N A N Y F O R M W I T H O U T W R I T T E N C O N SE N T . A L L R I G H T S A R E R E S E R V E D . C O P Y R I G H T 2 0 1 5 E N G IN E E R I N G S Y S T E M S O L U T I O N S . PR O J E C T : SH E E T T I T L E : SE A L : DRAWN:CHECKED: 16 7 7 E U R E K A R O A D S T E . # 1 0 2 RO S E V I L L E , C A 9 5 6 6 1 PH O N E : ( 9 1 6 ) 7 8 0 - 2 0 3 0 36 3 2 N R A N C H O D R I V E LA S V E G A S , N V 8 9 1 3 0 PH O N E : ( 7 0 2 ) 6 1 6 - 3 1 0 7 49 4 3 N O R T H 2 9 T H E A S T , S T E A ID A H O F A L L S , I D A H O 8 3 4 0 1 PH O N E : ( 2 0 8 ) 5 5 2 - 9 8 7 4 EN G I N E E R I N G S Y S T E M S O L U T I O N S ST R U C T U R A L • M E P • B U I L D I N G C O M M I S S I O N I N G ww w . e s 2 e n g . c o m BU I L D I N G R E L A T I O N S H I P S EX C E E D I N G E X P E C T A T I O N S SHEET NUMBER: PROJECT NUMBER: SE A L : REVISIONS: ISSUE: M0.00 GE N E R A L N O T E S , S H E E T I N D E X , L E G E N D 20 2 0 B E N F u m e H o o d E x h a u s t S y s t e m R e p l a c e m e n t BR I N G H A M Y O U N G U N V E R S I T Y I D A H O CB JJ 19.3025 #/###AIR DEVICE TAG MARK/CFM GENERAL REQUIREMENTS CONTRACTOR INSTALL ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH THE ADOPTED VERSIONS OF THE INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL FUEL GAS CODE, INTERNATIONAL ENERGY CONSERVATION CODE, AND UNIFORM PLUMBING CODE AND ALL OTHER LOCAL CODES AND ADOPTED ORDINANCES. CLOSELY COORDINATE ALL MECHANICAL WITH ELECTRICAL, ARCHITECTURAL, AND STRUCTURAL. DUCTWORK AND PIPING IS APPROXIMATE AND DIAGRAMMATIC AND IS NOT TO BE SCALED. PROVIDE ALTERNATE ROUTING, OFFSETS, AND TRANSITIONS AS REQUIRED FOR COORDINATION OF ALL WORK WITHOUT ADDITIONAL COST TO THE OWNER. FIELD VERIFY ALL MECHANICAL PRIOR TO COMMENCING NEW WORK. DO NOT FABRICATE OR INSTALL ANY MECHANICAL BEFORE VERIFYING DIMENSIONS AND ROUTING WITH BUILDING CONDITIONS AND ALL OTHER TRADES. CONTRACTOR IS RESPONSIBLE FOR ALL APPLICABLE PERMITS AND FEES. IF DISCREPANCIES EXIST BETWEEN BUILDING CODES, DRAWINGS, NOTES, AND SPECIFICATIONS, THE MOST STRINGENT REQUIREMENT WILL BE REQUIRED UNLESS CLARIFIED BY PROJECT ENGINEER IN AN OFFICIAL ADDENDUM OR SUPPLEMENTAL INSTRUCTION. REQUESTS FOR INFORMATION: THE CONTRACTOR ACKNOWLEDGES ITS RESPONSIBILITY TO BE FAMILIAR WITH THE CONTRACT DOCUMENTS. REQUESTS FOR INFORMATION (RFI'S) WILL BE RESPONDED TO WITHIN FIVE WORKING DAYS OF RECEIPT. TIME SPENT REVIEWING RFI'S IN WHICH THE INFORMATION REQUESTED IS CLEARLY INCLUDED IN THE DRAWINGS OR SPECIFICATIONS WILL BE CHARGED TO THE CONTRACTOR AT ENGINEERING SYSTEM SOLUTIONS' STANDARD BILLING RATES. INSTALLATION PROVIDE SEISMIC RESTRAINTS FOR HVAC EQUIPMENT, DUCTWORK, AND PIPING TO COMPLY WITH SEISMIC DESIGN CRITERIA LISTED IN THE STRUCTURAL GENERAL NOTES. IF NOT AVAILABLE PROVIDE RESTRAINTS IN ACCORDANCE WITH ASCE/SEI 7-10 AND INTERNATIONAL BUILDING CODE WITH SEISMIC DESIGN CATEGORY D, SITE CLASS D, RISK CATEGORY II, SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCELERATION COEFFICIENT SDS=0.368, ONE SECOND PERIOD DESIGN SPECTRAL RESPONSE ACCELERATION COEFFICIENT SD1=0.22, AND IMPORTANCE FACTOR 1.0. PIPING SUPPORTED WITHIN 12" OF STRUCTURE DOES NOT REQUIRE SEISMIC BRACING. DUCTS SUPPORTED WITHIN 12" OF STRUCTURE OR DUCTS LESS THAN 6 SQ. FT. CROSS-SECTIONAL AREA DO NOT REQUIRE SEISMIC BRACING. PIPING, DUCTWORK, AND EQUIPMENT HANGERS CENTERED ON STEEL I-BEAMS (CONCENTRIC HANGERS) ARE PREFERRED OVER HANGERS SUPPORTED FROM A SINGLE SIDE OF THE BOTTOM I-BEAM FLANGE. IF USING HANGERS SUPPORTED FROM A SINGLE SIDE OF THE BOTTOM FLANGE, THE MAXIMUM WEIGHT LIMIT PER HANGER IS 200 POUNDS UNLESS DIRECTED OTHERWISE BY THE PROJECT STRUCTURAL ENGINEER. CAULK AND SEAL ALL PENETRATIONS THROUGH CEILINGS, WALLS, AND FLOORS. PROVIDE ESCUTCHEON COVERS OR SHEET METAL FLANGES ON ALL VISIBLE PENETRATIONS. ALL DETAILS INCLUDED IN DESIGN DRAWINGS MUST BE APPLIED TO ALL RELEVANT INSTALLATIONS REFERRED TO IN THE DETAIL. EACH DETAIL WILL NOT BE SPECIFICALLY REFERENCED ON THE DRAWINGS. DUCTWORK AND PIPING MAY DIFFER IN DIMENSIONS THAN WHAT IS INDICATED ON DRAWINGS BASED ON EASIER PROCUREMENT, CONSISTENT SIZES, OR FIELD INSTALLATION CONDITIONS. PIPING MUST BE LARGER THAN WHAT IS INDICATED ON THE DRAWINGS AND THE CONTRACTOR MUST COORDINATE ROUTING OF LARGER PIPING WITH FIELD CONDITIONS. THE INSIDE FREE AREA FOR ALL DUCTWORK MUST MATCH OR EXCEED THE INSIDE FREE AREA OF THE DUCTWORK ON THE DRAWINGS AND EXHIBIT THE SAME OR BETTER PRESSURE LOSS CHARACTERISTICS. THE ASPECT RATIO OF MODIFIED DUCT MUST NOT EXCEED 3 TO 1 WITHOUT PRIOR ENGINEER APPROVAL. ROUTING FOR ALL MODIFIED DUCTWORK MUST BE COORDINATED WITH ALL FIELD CONDITIONS. EQUIPMENT ACCESS PROVIDE ACCESS PANELS FOR ALL EQUIPMENT, DAMPERS, ACTUATORS, AND FILTERS. ENSURE ADEQUATE ACCESS TO ALL SYSTEM COMPONENTS FOR MAINTAINABILITY. ELECTRICAL REQUIREMENTS COORDINATE ALL ELECTRICAL AND CONTROL REQUIREMENTS WITH ELECTRICIAN. PROVIDE STARTERS AND CONTACTORS NECESSARY TO OPERATE ALL MECHANICAL EQUIPMENT. COORDINATE ALL REQUIREMENTS WITH ELECTRICAL. CONTRACTOR MUST COORDINATE ALL ELECTRICAL REQUIREMENTS FOR ALL EQUIPMENT WITH ELECTRICAL CONTRACTOR ONCE REVIEWED SUBMITTALS ARE RECEIVED. CONTRACTOR IS RESPONSIBLE FOR ALL LOW VOLTAGE WIRING CONDUIT. CONDUIT IS REQUIRED FOR ALL INACCESSIBLE LOCATIONS INCLUDING INSIDE WALLS, ABOVE HARD CEILINGS, AND IN FLOORS. REFER TO ELECTRICAL PLANS AND SPECIFICATIONS FOR ALL CONDUIT REQUIREMENTS. SOME LOW VOLTAGE CONDUIT MAY BE SPECIFIED IN ELECTRICAL DRAWINGS. GENERAL REQUIREMENTS PROVIDE ONE YEAR PARTS AND LABOR WARRANTY ON INSTALLATION. PROVIDE SUBMITTALS ON ITEMS LISTED IN SCHEDULES TO ENGINEER FOR REVIEW PRIOR TO ORDER, PURCHASE, OR INSTALLATION. PROVIDE ALL HVAC CONSTRUCTION COSTS FOR ENGINEER DATA BASE AS PART OF SUBMITTALS. ALL MANUFACTURER SUBSTITUTIONS MUST BE SUBMITTED THROUGH ARCHITECT AND APPROVED THROUGH AN ADDENDUM. PRIOR APPROVALS MUST BE SUBMITTED 10 DAYS PRIOR TO BID DATE. PROVIDE OPERATIONS AND MAINTENANCE MANUAL INCLUDING ALL HVAC EQUIPMENT. COORDINATE EXACT LOCATION OF THERMOSTATS/SENSORS WITH ARCHITECT PRIOR TO INSTALLATION. PROVIDE VENTILATED LOCKABLE COVERS FOR ALL THERMOSTATS AND SENSORS LOCATED IN PUBLIC ACCESSIBLE LOCATIONS. PROVIDE AND INSTALL CONTROL WIRING BETWEEN THERMOSTAT/SENSOR AND AIR HANDLING EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR FULLY FUNCTIONING AND COMPLETE MECHANICAL SYSTEMS INCLUDING ALL INSTALLATION REQUIREMENTS, SERVICE AND MAINTENANCE REQUIREMENTS, CONTROL AND OPERATION REQUIREMENTS, ETC. INSTALLATION INSTALL ALL EQUIPMENT AND DEVICES PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE CONDENSATE DRAINS PIPED FULL SIZE TO FLOOR DRAIN FOR ALL AIR CONDITIONING EQUIPMENT AND HIGH EFFICIENCY FURNACES AND BOILERS. SLOPE ALL CONDENSATE AT MIN 1/8" PER FT. ALL CONDENSATE PIPING TO BE 3/4" DIA. UNLESS NOTED OTHERWISE. REFER TO MANUFACTURER’S RECOMMENDATIONS FOR CONDENSATE TRAPPING REQUIREMENTS. DUCTWORK INSTALLATION INSTALL AND SUPPORT ALL DUCTWORK PER SMACNA AND INTERNATIONAL MECHANICAL CODE REQUIREMENTS. CLOSE ENDS OF DUCTWORK AND PIPING AND COVER FLOOR DRAINS DURING CONSTRUCTION. CLEAN ALL EQUIPMENT, PIPING, AND DUCTWORK AT COMPLETION OF PROJECT. PROVIDE MINIMUM 2.5 WHEEL DIAMETERS OF STRAIGHT DUCT BEFORE OFFSETS OR BENDS FOR ALL INLET AND OUTLET DUCTWORK FOR FANS. COMPLY WITH SMACNA REQUIREMENTS FOR ALL DUCT SUPPORT SIZING, SPACING, AND MATERIAL. ALL HANGERS IN CORROSIVE ENVIRONMENTS TO BE ELECTROGALVANIZED ALL-THREAD RODS. PROVIDE EXPANSION JOINTS FOR ALL DUCT WORK PER SMACNA AND MECHANICAL CODE REQUIREMENTS BASED ON FINAL FIELD ROUTING. MATERIALS ALL DUCT TO BE CONSTRUCTED OF GALVANIZED METAL UNLESS NOTED OTHERWISE. ALL ROUND EXPOSED DUCT TO BE SPIRAL DUCT. CONSTRUCT ALL DUCT TO THE FOLLOWING SMACNA STANDARDS: 1. MEDIUM PRESSURE SUPPLY DUCT (ALL DUCT UPSTREAM OF VAV BOX OR ZONE DAMPER) - 4" W.G. PRESSURE CLASS AND SEAL CLASS A. 2. LOW PRESSURE SUPPLY DUCT AND RETURN DUCT - 2" W.G. PRESSURE CLASS AND SEAL CLASS B. 3. EXHAUST DUCT - 1" W.G. PRESSURE CLASS AND SEAL CLASS B. ALL DUCTS ABOVE RATED CEILINGS TO BE MINIMUM 24-GAUGE SHEET METAL. ACCESS PROVIDE ACCESS PANELS FOR ALL EQUIPMENT, DAMPERS, ACTUATORS, AND FILTERS. ENSURE ADEQUATE ACCESS TO ALL SYSTEM COMPONENTS FOR MAINTAINABILITY. PROVIDE DOUBLE WALL DUCT ACCESS DOORS FOR ALL MOTORIZED DAMPERS, FIRE/SMOKE DAMPERS, FIRE DAMPERS, FILTERS, DUCT COILS, TURNING VANES, DUCTWORK CONNECTING TO LOUVERS, AND OTHER DEVICES THAT REQUIRE ACCESS. DOORS TO BE 12" SQUARE FOR TWO HAND ACCESS AND 25"X14" FOR BODY ACCESS. INSULATION AND LINER LINE ALL LOW PRESSURE RECTANGULAR SUPPLY AND RETURN DUCT A MINIMUM OF 20 FEET FROM AIR HANDLING EQUIPMENT/VAV BOX. LINE ALL RETURN AIR TRANSFERS AND GRILLE PLENUM BOXES. DUCT LINER TO BE MINIMUM R-6. TRIM AND SEAL JOINTS. INSULATE ALL CONCEALED UNLINED SUPPLY DUCT WITH MINIMUM R-6 (INSTALLED) FIBERGLASS DUCT WRAP. INSULATE ALL OUTSIDE AIR DUCT WITH MINIMUM R-6 (INSTALLED) FIBERGLASS DUCT WRAP. INSULATION TO BE UL LISTED AND MEET NFPA 220. ALL DUCT LOCATED IN UNCONDITIONED SPACE TO BE INSULATED WITH MINIMUM R-12 (INSTALLED). ALL DUCT LOCATED OUTSIDE TO BE DOUBLE WALL AND INSULATED WITH MINIMUM R-12 (INSTALLED). TEST AND BALANCE BALANCE ALL HVAC EQUIPMENT AND AIR DEVICES PER PLAN BY AN APPROVED INDEPENDENT TEST AND BALANCE CONTRACTOR. BALANCE REPORT TO BE GIVEN TO ENGINEER, OWNER, AND O&M MANUAL. EXHAUST VENTURI VALVE (XV, HV) MARK ROOM NUMBER SYSTEM SERVED AIRFLOW RANGE (CFM)SASH CFM PRESSURE RANGE (IN WC) MANUFACTURER & MODEL NOTES HV-01 285 FUME HOOD 940 940 0.6 - 3.0 ANTEC VV 1,2 HV-02 285A FUME HOOD 940 940 0.6 - 3.0 ANTEC VV 1,2 HV-03 285A FUME HOOD 940 940 0.6 - 3.0 ANTEC VV 1,2 HV-06 283 FUME HOOD 940 940 0.6 - 3.0 ANTEC VV 1,2 HV-07 281 FUME HOOD 940 940 0.6 - 3.0 ANTEC VV 1,2 XV-01 286 EXHAUST 1025 - 2050 - 0.6 - 3.0 ANTEC VV 1 XV-02 285 EXHAUST 360 - 770 - 0.6 - 3.0 ANTEC VV 1 XV-03 280B EXHAUST 405 - 970 - 0.6 - 3.0 ANTEC VV 1 XV-04A 280A EXHAUST 520 - 1040 - 0.6 - 3.0 ANTEC VV 1 XV-04B 282 EXHAUST 30 - 60 - 0.6 - 3.0 ANTEC VV 1 XV-05A 280B EXHAUST 35 - 100 - 0.6 - 3.0 ANTEC VV 1 XV-05B 280B EXHAUST 30 - 70 - 0.6 - 3.0 ANTEC VV 1 XV-06A 285A EXHAUST 0 - 500 - 0.6 - 3.0 ANTEC VV 1 XV-06B 285A EXHAUST 35 - 125 - 0.6 - 3.0 ANTEC VV 1 XV-07 280 EXHAUST 930 - 2050 - 0.6 - 3.0 ANTEC VV 1 XV-08 283 EXHAUST 390 - 1230 - 0.6 - 3.0 ANTEC VV 1 XV-09 281 EXHAUST 210 - 750 - 0.6 - 3.0 ANTEC VV 1 NOTES: 1. TSI AND ANTEC ARE APPROVED MANUFACTURER'S. REFER TO MANUFACTURER AND MODEL FOR BASIS OF DESIGN. 2. PROVIDE SIDE WALL FLOW SENSOR AND PRESSURE SENSOR IN FUME HOOD INTEGRATED WITH FUME HOOD CONTROLLER. PROVIDE WITH QUICK REACTION ACTUATOR. SUPPLY VENTURI VALVE (SV) MARK ROOM NUMBER SYSTEM SERVED AIRFLOW RANGE (CFM) PRESSURE RANGE (IN WC) HOT WATER HEATING SECTION MANUFACTURER & MODEL NOTESEAT (°F) MIN LAT (°F) HEATING CFM EWT/LWT (°F)GPM MAX W.P.D. (FT) SV-01 286 SUPPLY 1090 - 1860 0.6 - 3.0 54 100 1270 180/145 4 9.3 ANTEC VV 1,2,3,4,6 SV-02 285 SUPPLY 1170 - 1550 0.6 - 3.0 54 110 1100 180/145 3 5.9 ANTEC VV 1,2,3,4,6 SV-03 284 SUPPLY 360 - 880 0.6 - 3.0 54 110 780 180/145 2 3.0 ANTEC VV 1,2,3,4,6 SV-04 284 SUPPLY 500 - 1020 0.6 - 3.0 54 110 720 180/145 2 3.0 ANTEC VV 1,2,3,4,6 SV-05A 282 SUPPLY 30 - 90 0.6 - 3.0 54 110 90 180/145 1 0.6 ANTEC VV 1,2,3,4,6 SV-05B 282 SUPPLY 30 - 60 0.6 - 3.0 54 110 60 180/145 1 0.6 ANTEC VV 1,2,3,4,6 SV-06A 285A SUPPLY 1530 - 1710 0.6 - 3.0 54 115 965 180/145 3 5.9 ANTEC VV 1,2,3,4,6 SV-06B 285B SUPPLY 105 - 240 0.6 - 3.0 54 120 105 180/170 1 0.6 ANTEC VV 1,2,3,4,6 SV-06C 285C SUPPLY 40 - 180 0.6 - 3.0 54 125 95 180/170 1 0.6 ANTEC VV 1,2,3,4,6 SV-06D 285C SUPPLY 50 - 140 0.6 - 3.0 54 130 50 180/170 1 0.6 ANTEC VV 1,3,4,5,6 SV-07 280 SUPPLY 840 - 1860 0.6 - 3.0 54 110 1280 180/145 4 10.2 ANTEC VV 1,2,3,4,6 SV-08 283 SUPPLY 1200 - 1970 0.6 - 3.0 54 115 960 180/140 3.5 8.2 ANTEC VV 1,2,3,4,6 SV-09A 281 SUPPLY 1010 - 1250 0.6 - 3.0 54 110 1010 180/155 4 7.2 ANTEC VV 1,2,3,4,6 SV-09B 281A SUPPLY 80 - 290 0.6 - 3.0 54 130 80 180/170 1 0.6 ANTEC VV 1,2,3,4,6 NOTES: 1. TSI AND ANTEC ARE APPROVED MANUFACTURER'S. REFER TO MANUFACTURER AND MODEL FOR BASIS OF DESIGN. 2. PROVIDE 2-ROW COIL WITH ACCESS DOOR. 3. REFER TO SEQUENCE OF OPERATION AND SCHEMATIC ON M5.10 FOR ADDITIONAL REQUIREMENTS. 4. PROVIDE WITH WALL MOUNTED TEMPERATURE SENSOR IN EACH ROOM AND A DUCT MOUNTED TEMPERATURE SENSOR IN THE DUCT JUST PAST EACH HOT WATER COIL. 5. PROVIDE 1-ROW COIL WITH ACCESS DOOR. 6. PROVIDE WITH HOT WATER COIL (VVHWC OR EQUAL) AND HARDWARE FOR ATTACHMENT TO VENTURI VALVE. J U S T I R J U D Y 11 5 1 3 P R O F E S S I O N A L E N G I N E E R I D A HO O F S T A T E R E G I S T E R E D N 02 / 2 5 / 2 0 2 0 (E) 16"x16" (E) 10"x16" (E) 8"x10" (E) 10"ø (E) 14"ø (E) 20"x12" (E) 12"x12" (E) 9"ø(E) 9"ø (E) 12"ø (E) 24"x18" (E) 20"x24" (E) 8"x12"(E) 16"x12" (E) 26"x12" (E) 10"ø (E) 14"ø (E) 19"ø (E) 12"ø(E) 10"ø (E) 10"ø (E) 12"ø (E) 13"ø (E) 5"ø (E) 10"ø (E) 18"x12" (E) 12"x10" (E) 10"ø (E) 10"ø (E) 10"ø (E) 10"ø (E) 10"ø (E) 16"ø (E) 12"ø (E) 9"ø(E) 9"ø (E) 24"x12" (E) 5"ø (E) 8"ø (E) 6"ø (E) 4"ø (E) 4"ø (E) 6"ø (E) 9"ø (E) 9"ø (E) 9"ø(E) 9"ø (E) 9"ø (E) 10"x8" (E) 24"x12" (E) 20"x12" (E) 12"x12" (E) 10"ø (E) 10"ø (E) 6"ø (E) 10"ø (E) 10"ø (E) 14"ø (E) 12"ø (E) 12"ø (E) 18"ø (E) 18"ø (E) 12"ø (E) 12"ø (E) 20"ø (E) 6"ø (E) 6"ø (E) 12"ø (E) 12"ø (E) VAV (E) 14"ø (E) 20"ø (E) 12"ø (E) 12"ø (E) 12"ø (E) 9"ø (E) 12"ø (E) 12"ø (E) 12"ø (E) 6"ø (E) 8"ø M6 M7 M4 M4 M7 M7 M4 M7 M7 M6 M6 M6 M6 M4 M4 M7 M7 M6 M6 M4 M6 M6 M7 (E) 11"ø (E) 24"x12" (E) 16"x12" (E) 12"x12" (E) 9"ø (E) 9"ø (E) 9"ø (E) 9"ø (E) 9"ø (E) 9"ø (E) 16"ø (E) 18"ø (E) 24"ø (E) 16"ø (E) 16"ø (E) 16"x10" (E) 8"ø (E) 10"x10" (E) 14"x14" (E) 10"x10" (E) 8"ø (E) 12"ø (E) 7"ø(E) 7"ø (E) 12"ø (E) 12"ø 286 280A 280B 280C 280D 280 284 282 285 285A 285B 285C 283 281 M10 SCALE: 1/8" = 1'-0" MECHANICAL DEMO PLAN TH E S E P L A N S , D R A W I N G S A N D D E S I G N S A R E T H E E X C L U S I V E P R O P E R T Y O F E N G I N E E R I N G S Y S T E M S O L U T I O N S . A N D S H A L L N O T B E R E P R O D U C E D I N A N Y F O R M W I T H O U T W R I T T E N C O N SE N T . A L L R I G H T S A R E R E S E R V E D . C O P Y R I G H T 2 0 1 5 E N G IN E E R I N G S Y S T E M S O L U T I O N S . PR O J E C T : SH E E T T I T L E : SE A L : DRAWN: CHECKED: 16 7 7 E U R E K A R O A D S T E . # 1 0 2 RO S E V I L L E , C A 9 5 6 6 1 PH O N E : ( 9 1 6 ) 7 8 0 - 2 0 3 0 36 3 2 N R A N C H O D R I V E LA S V E G A S , N V 8 9 1 3 0 PH O N E : ( 7 0 2 ) 6 1 6 - 3 1 0 7 49 4 3 N O R T H 2 9 T H E A S T , S T E A ID A H O F A L L S , I D A H O 8 3 4 0 1 PH O N E : ( 2 0 8 ) 5 5 2 - 9 8 7 4 EN G I N E E R I N G S Y S T E M S O L U T I O N S ST R U C T U R A L • M E P • B U I L D I N G C O M M I S S I O N I N G ww w . e s 2 e n g . c o m BU I L D I N G R E L A T I O N S H I P S EX C E E D I N G E X P E C T A T I O N S SHEET NUMBER: PROJECT NUMBER: SE A L : REVISIONS: ISSUE: MD1.10 ME C H A N I C A L D E M O P L A N 20 2 0 B E N F u m e H o o d E x h a u s t S y s t e m R e p l a c e m e n t BR I N G H A M Y O U N G U N V E R S I T Y I D A H O Author Checker 19.3025 A. REMOVE EQUIPMENT, DUCT, AIR DEVICES, ACCESSORIES, AND PIPING AS SHOWN ON PLANS. REMOVE ALL PNEUMATIC TUBING BACK TO SOURCE FOR ALL REMOVED PNEUMATIC CONTROL DEVICES. COORDINATE FINAL REMOVAL AND DISPOSAL OF EQUIPMENT AND DUCTWORK WITH BUILDING OPERATION MANAGER. B. CAP AND SEAL ALL MEDIUM PRESSURE DUCTWORK TO 4" W.C. PRESSURE CLASS AT POINT OF DISCONNECT. CAP AND SEAL ALL LOW PRESSURE DUCTWORK TO 2" W.C. PRESSURE CLASS AT POINT OF DISCONNECT. C. CAP AND SEAL ALL HYDRONIC PIPING AT POINT OF DISCONNECT. D. REMOVE SENSORS/CONTROLS CORRELATED WITH ALL VENTURI VALVES THAT ARE BEING REMOVED. COORDINATE ALL CONTROL REQUIREMENTS WITH CONTROL CONTRACTOR. E. COORDINATE ELECTRICAL REQUIREMENTS FOR ALL REMOVED EQUIPMENT AND ACCESSORIES WITH ELECTRICAL CONTRACTOR. F. EXISTING DUCTWORK IN ACCEPTABLE CONDITION MAY BE RE-USED AS LONG AS THE INTERNAL FREE AREA IS GREATER THAN WHAT IS SHOWN ON THE NEW DUCTWORK PLANS. PLAN NOTES KEYNOTES M4 EXISTING HOOD, VENTURI VALVE AND ALL ASSOCIATED EQUIPMENT AND CONTROLS TO BE REMOVED. CAP AND SEAL GAS AND WATER PIPES FOR USE WITH NEW EQUIPMENT. MAINTAIN DUCT WORK AND ELECTRICAL CIRCUITING FOR USE WITH NEW EQUIPMENT. M6 REMOVE EXISTING SUPPLY AIR VENTURI VALVE AND EXISTING HOT WATER COIL. M7 REMOVE EXISTING EXHAUST VENTURI VALVE. M10 REMOVE EXISTING VALVE AND DUCT BACK TO MAIN AND CAP AND SEAL. J U S T I R J U D Y 11 5 1 3 P R O F E S S I O N A L E N G I N E E R I D A HO O F S T A T E R E G I S T E R E D N 02 / 2 5 / 2 0 2 0 (E) 16"x16" (E) 10"x16"(E) 8"x10" (E) 10"ø (E) 14"ø (E) 20"x12"(E) 12"x12" (E) 9"ø(E) 9"ø (E) 12"ø (E) 24"x18" (E) 20"x24" (E) 8"x12"(E) 16"x12" (E) 26"x12" (E) 10"ø (E) 14"ø (E) 19"ø (E) 12"ø(E) 10"ø (E) 10"ø (E) 12"ø (E) 13"ø (E) 5"ø (E) 10"ø (E) 18"x12" (E) 12"x10" (E) 10"ø (E) 10"ø (E) 10"ø (E) 10"ø (E) 10"ø (E) 16"ø (E) 12"ø (E) 9"ø(E) 9"ø (E) 24"x12" (E) 5"ø (E) 8"ø (E) 6"ø (E) 4"ø (E) 4"ø (E) 6"ø (E) 9"ø (E) 9"ø (E) 9"ø(E) 9"ø (E) 9"ø (E) 10"x8" (E) 24"x12" (E) 20"x12" (E) 12"x12" (E) 10"ø (E) 10"ø (E) 6"ø (E) 10"ø (E) 10"ø XV-02 SV-02 (E) 14"ø HV-01 FUME HOOD (E) 12"ø (E) 12"ø (E) 18"ø XV-06A (E) 18"ø HV-02FUME HOOD (E) 12"ø (E) 12"ø (E) 20"ø SV-06B SV-06C SV-06DSV-06A HV-03 (E) 6"ø (E) 6"ø XV-06B FUME HOOD XV-08 HV-06 FUME HOOD (E) 12"ø (E) 12"ø (E) VAV SV-08 XV-09 (E) 14"ø (E) 20"ø FUME HOOD (E) 12"ø HV-07 SV-09A SV-09B (E) 16"ø(E) 16"ø (E) 9"ø (E) 12"ø (E) 12"ø (E) 12"ø (E) 6"ø (E) 8"ø M1 M1 M1 M1 M1 M2 M2 M2 M2 M2 M2 M2 M2 M3 M3 M3 M3 M3 M3 M3 M3 M3 M3 M8 M8 M8 M8 M9M9M9 M9 SV-07 XV-07M3 M2 M8 286 280A 280B 280C 280D 280 284 282 285 285A 285B 285C 283 281 M8 M8 M8 SV-01 XV-01 SV-03 SV-04 SV-05A SV-05B XV-03 XV-04A XV-05A XV-05B XV-04B M9 M9 M11M11 M11 M11 M11 M11 A. DURING REPLACEMENT OF EXISTING EQUIPMENT, SALVAGE AS MUCH PIPING AND DUCTWORK AS POSSIBLE TO RECONNECT TO NEW EQUIPMENT. PROVIDE NEW DUCTING OR PIPING AS REQUIRED TO INSTALL NEW EQUIPMENT. NEW DUCTING AND PIPING TO MATCH EXISTING SIZE AND MATERIAL. REPLACE ANY AND ALL DAMAGED DUCT AND PIPING. B. ALL NEW BACNET CONTROLS TO BE INTERFACED WITH THE EXISTING BMS. C. CLEAN AND FLUSH ALL NEW PIPING. ADJUST CHEMICAL CONCENTRATION FOR ENTIRE SYSTEM. D. TEST & BALANCE CONTRACTOR TO ENSURE THE SUPPLY AND EXHAUST SYSTEMS FOR EACH SPACE OPERATES AT STABLE OPERATING CONDITIONS WHEN SYSTEM OPERATES AT MINIMUM AND MAXIMUM SETPOINTS OF THE AIR SUPPLY VALVE. ROOM AND HOOD EXHAUST VALVES ARE INTENDED TO OPERATE TO MAINTAIN A NEGATIVE ROOM PRESSURE. IF ISSUES ARE OBSERVED, CONTACT THE DESIGN ENGINEER TO DISCUSS NEW AIRFLOW SETPOINTS. REFER TO TABLE FOR APPROXIMATE AIRFLOW SETPOINTS. PLAN NOTES TH E S E P L A N S , D R A W I N G S A N D D E S I G N S A R E T H E E X C L U S I V E P R O P E R T Y O F E N G I N E E R I N G S Y S T E M S O L U T I O N S . A N D S H A L L N O T B E R E P R O D U C E D I N A N Y F O R M W I T H O U T W R I T T E N C O N SE N T . A L L R I G H T S A R E R E S E R V E D . C O P Y R I G H T 2 0 1 5 E N G IN E E R I N G S Y S T E M S O L U T I O N S . PR O J E C T : SH E E T T I T L E : SE A L : DRAWN: CHECKED: 16 7 7 E U R E K A R O A D S T E . # 1 0 2 RO S E V I L L E , C A 9 5 6 6 1 PH O N E : ( 9 1 6 ) 7 8 0 - 2 0 3 0 36 3 2 N R A N C H O D R I V E LA S V E G A S , N V 8 9 1 3 0 PH O N E : ( 7 0 2 ) 6 1 6 - 3 1 0 7 49 4 3 N O R T H 2 9 T H E A S T , S T E A ID A H O F A L L S , I D A H O 8 3 4 0 1 PH O N E : ( 2 0 8 ) 5 5 2 - 9 8 7 4 EN G I N E E R I N G S Y S T E M S O L U T I O N S ST R U C T U R A L • M E P • B U I L D I N G C O M M I S S I O N I N G ww w . e s 2 e n g . c o m BU I L D I N G R E L A T I O N S H I P S EX C E E D I N G E X P E C T A T I O N S SHEET NUMBER: PROJECT NUMBER: SE A L : REVISIONS: ISSUE: M1.10 ME C H A N I C A L F L O O R P L A N 20 2 0 B E N F u m e H o o d E x h a u s t S y s t e m R e p l a c e m e n t BR I N G H A M Y O U N G U N V E R S I T Y I D A H O CB JJ 19.3025 KEYNOTES M1 PROVIDE WITH AN AIR BYPASS LOW FLOW, CONSTANT AIR VOLUME FUME HOOD (HEMCO UNIFLOW SE AIRESTREAM CAV, 60" WIDE). HOOD TO HAVE A FACE VELOCITY OF 80-100 FPM. FUME HOOD TO HAVE DUAL WALL CONSTRUCTION WITH NON-METALLIC CHEMICAL, CORROSION AND FIRE RESISTANT COMPOSITE RESIN. SASH TO BE VERTICAL SLIDE TEMPERED GLASS WITH CHEMICAL RESISTANT PVC SASH FRAME, TRACK AND AERODYNAMIC SASH LIFT. FUME HOOD LIGHT TO BE VAPOR PROOF LED WITH CONTROL SWITCH PRE-WIRED TO A SINGLE POINT JUNCTION BOX. FUME HOOD TO BE UL 1805 CLASSIFIED. CONNECT NEW HOOD TO EXISTING EXHAUST SYSTEM AND EXISTING PIPING SYSTEMS (PIPING TO MATCH EXISTING PIPING), INCLUDING ACID VENT (AV), LABORATORY COLD WATER (LCW), LABORATORY HOT WATER (LHW) REVERSE OSMOSIS WATER (RO), LABORATORY GAS (LG), AND LABORATORY COMPRESSED AIR (LA). PROVIDE WITH FUME HOOD DISPLAY (ANTEC FHC+ OR EQUAL).REFER TO SHEET M5.10 FOR SEQUENCE OF OPERATION. M2 PROVIDE NEW SUPPLY AIR VENTURI VALVE. REFER TO SCHEDULE ON SHEET M0.00 FOR SPECIFICATIONS. CONNECT NEW VALVE TO EXISTING DUCTWORK. PROVIDE NEW HOT WATER COIL AND CONNECT TO EXISTING HOT WATER LINES. REFER TO TYPICAL WATER COIL DETAIL FOR ADDITIONAL REQUIREMENTS. ALL ITEMS IN DETAIL ARE TO BE PROVIDED NEW. M3 PROVIDE NEW EXHAUST VENTURI VALVE. REFER TO SCHEDULE ON SHEET M0.00 FOR SPECIFICATIONS. CONNECT NEW VALVE TO EXISTING DUCTWORK. M8 PROVIDE WITH ROOM PRESSURE MONITOR (ANTEC PMT), AND ROOM CONTROLLER (PACE+). M9 PROVIDE WITH ROOM CONTROLLER (PACE+). M1 1 ROOM INTENDED TO BE POSITIVE PRESSURED. REFER TO THE SUPPLY ONLY SECTION IN THE SEQUENCE OF OPERATION ON SHEET M5.10. SCALE: 1/8" = 1'-0" MECHANICAL FLOOR PLAN J U S T I R J U D Y 11 5 1 3 P R O F E S S I O N A L E N G I N E E R I D A HO O F S T A T E R E G I S T E R E D N 02 / 2 5 / 2 0 2 0 V E N T U R I V A L V E KEYNOTES: 1. EXISTING DUCT 2. FLEX DUCT CONNECTION. 3. CONTROL COVER. PROVIDE 42" CLEARANCE IN FRONT. 4. MINIMUM 3 DIAMETERS OF STRAIGHT RIGID DUCT IMMEDIATELY AHEAD OF CONNECTION AT BOX. DUCT SIZE TO BE ONE SIZE LARGER THAN VAV INLET SIZE UNLESS NOTED OTHERWISE. 5. EXISTING MEDIUM PRESSURE SUPPLY DUCT. 6. HEATING COIL WHERE SCHEDULED. REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS FOR FINAL HEATING COIL LOCATION. NOTES: A. PROVIDE ADEQUATE MAINTENANCE ACCESS TO ALL VENTURI VALVES. CLEARANCE REQUIREMENTS TO BE BASED ON MANUFACTURERS INSTALLATION INSTRUCTIONS. ACCESS DOORS SHALL BE PROVIDED IN CEILING CONSTRUCTION WHERE NECESSARY. PROVIDE RATED ACCESS DOORS WHERE REQUIRED. 2 3 4 5 6 1 KEYNOTES: 1. MANUAL AIR VENTS AT HIGH POINT. 2. P&T TEST PLUG (TYP). PROVIDE MINIMUM 50% OF COILS WITH THERMOMETERS AND 25% OF COILS WITH PRESSURE GUAGES. 3. UNION (TYP). 4. 3/4" BALL VALVE WITH HOSE THREAD DRAIN CONNECTION. PROVIDE WITH PLUG. 5. STRAINER WITH BALL VALVE AND HOSE END CONNECTION. PROVIDE WITH PLUG. 6. NEW ISOLATION VALVE (TYP). 7. CALIBRATED BALANCING VALVE (TYP). 8. 3-WAY MODULATING CONTROL VALVE. 9. EXISTING ISOLATION VALVE. REMOVE HANDLE AFTER INSTALLATION OF NEW ISOLATION VALVES. 10. BRAIDED STAINLESS STEEL FLEXIBLE METAL HOSE. NOTES: A. FOR MULTIPLE COILS: COIL HEADER PIPING TO BE ARRANGED SO ALL FLOW CIRCUITS HAVE EXACTLY THE SAME NUMBER OF ELBOWS AND TEES FROM HEADER THROUGH COIL AND BACK TO HEADER. COIL 1 8 7 1 6 5 3 4 2 9 10 DCS SRPS PMT FHC FHCFHC FHC SWS SIDEWALL SENSOR FUME HOOD PRESSURE SENSOR SIDEWALL SENSOR FUME HOOD PRESSURE SENSOR FUME HOOD EXHAUST 1 FUME HOOD EXHAUST 1 SWS PACEPACE GENERAL EXHAUSTSUPPLY VV VV VV VV HWV HWCES-DT ES-RM-LCD-BTN CKJ TO NEXT BACNET MS/TP CONNECTION TO NEXT BACNET MS/TP CONNECTION ES-RM-LCD-BTN CKJ RIN ES-DT HWV HWC VV PACE 2P SWS FHI FHC FHN DCS CAT5e (PUNCH DOWN) KEYSTONE JACK ROOM INFORMATION NETWORK DUCT TEMPERATURE SENSOR MODULATING (0-10V) REHEAT VALVE HOT WATER REHEAT COIL VENTURI VALVE PACE CONTROLLER 2-POSITION ACTUATOR SIDEWALL FACE VELOCITY SENSOR DOOR CONTACT SWITCH FUME HOOD INTERFACE FHIFHI FUME CONTROLLER FUME HOOD NETWORK FEILD WIRING FACTORY WIRING LEGEND: ROOM TEMPERATURE SENSOR WITH DISPLAY, PUSH-BUTTON SETPOINT ADJUSTMENT PMT TOUCHSCREEN ROOM PRESSURE MONITOR SRSP SIN ROOM PRESSURE SENSORE TH E S E P L A N S , D R A W I N G S A N D D E S I G N S A R E T H E E X C L U S I V E P R O P E R T Y O F E N G I N E E R I N G S Y S T E M S O L U T I O N S . A N D S H A L L N O T B E R E P R O D U C E D I N A N Y F O R M W I T H O U T W R I T T E N C O N SE N T . A L L R I G H T S A R E R E S E R V E D . C O P Y R I G H T 2 0 1 5 E N G IN E E R I N G S Y S T E M S O L U T I O N S . PR O J E C T : SH E E T T I T L E : SE A L : DRAWN: CHECKED: 16 7 7 E U R E K A R O A D S T E . # 1 0 2 RO S E V I L L E , C A 9 5 6 6 1 PH O N E : ( 9 1 6 ) 7 8 0 - 2 0 3 0 36 3 2 N R A N C H O D R I V E LA S V E G A S , N V 8 9 1 3 0 PH O N E : ( 7 0 2 ) 6 1 6 - 3 1 0 7 49 4 3 N O R T H 2 9 T H E A S T , S T E A ID A H O F A L L S , I D A H O 8 3 4 0 1 PH O N E : ( 2 0 8 ) 5 5 2 - 9 8 7 4 EN G I N E E R I N G S Y S T E M S O L U T I O N S ST R U C T U R A L • M E P • B U I L D I N G C O M M I S S I O N I N G ww w . e s 2 e n g . c o m BU I L D I N G R E L A T I O N S H I P S EX C E E D I N G E X P E C T A T I O N S SHEET NUMBER: PROJECT NUMBER: SE A L : REVISIONS: ISSUE: M5.10 TY P I C A L D E T A I L S , S C H E M A T I C S A N D S E Q U E N C E O F O P E R A T I ON S . 20 2 0 B E N F u m e H o o d E x h a u s t S y s t e m R e p l a c e m e n t BR I N G H A M Y O U N G U N V E R S I T Y I D A H O CB JJ 19.3025 NO SCALEM5.10 TYPICAL VENTURI VALVE INSTALLATION4 NO SCALEM5.10 TYPICAL COIL PIPING (3-WAY)3 NO SCALEM5.10 TYPICAL LABORATORY CONTROL SCHEMATIC2 SEQUENCE OF OPERATION PRESSURE CONTROL: SUPPLY ONLY: THE ACS WILL MEASURE THE DIFFERENTIAL PRESSURE BETWEEN THE ROOM AND THE REFERENCE SPACE AND WILL MODULATE THE AIRFLOW TO MEET THE REQUIRED ROOM PRESSURE TARGET. WITH ADDITIONAL CONTROL SEQUENCES, THE SEQUENCE WITH THE HIGHEST DEMAND FOR AIRFLOW WILL TAKE PRIORITY. IF DOOR SWITCHES ARE PRESENT, THE PRESSURE CONTROL ALGORITHM WILL PAUSE WHEN THE DOOR IS OPEN, AND WILL RESUME AFTER THE DOOR IS CLOSED. SUPPLY AND GENERAL EXHAUST: THE AIRFLOW CONTROL SYSTEM (ACS) WILL MEASURE THE DIFFERENTIAL PRESSURE BETWEEN THE ROOM AND THE REFERENCE SPACE AND WILL MODULATE THE SUPPLY AIR DEVICE TO MEET THE REQUIRED ROOM PRESSURE TARGET. WITH NO THERMAL DEMAND, THE SUPPLY WILL BE MAINTAINED AT THE MINIMUM SCHEDULED VALUE. AS AIRFLOW DEMAND INCREASES (SEE SECTION: TEMPERATURE CONTROL) THE SUPPLY AND GENERAL EXHAUST WILL BE INCREASED SIMULTANEOUSLY TO MAINTAIN THE SCHEDULED PRESSURE. IF DOOR SWITCHES ARE PRESENT, THE PRESSURE CONTROL ALGORITHM WILL PAUSE WHEN THE DOOR IS OPEN, AND WILL RESUME AFTER THE DOOR IS CLOSED. SUPPLY, GENERAL EXHAUST, AND FUME HOODS: THE ACS WILL MEASURE THE DIFFERENTIAL PRESSURE BETWEEN THE ROOM AND THE REFERENCE SPACE AND WILL MODULATE THE AIRFLOW TO MEET THE REQUIRED ROOM PRESSURE TARGET. WITH NO THERMAL DEMAND, THE ACS WILL MAINTAIN ROOM AIRFLOW AT THE MINIMUM SCHEDULED VALUE. AS AIRFLOW DEMAND INCREASES (SEE SECTION: TEMPERATURE CONTROL) THE SUPPLY AND GENERAL EXHAUST WILL BE INCREASED TO MAINTAIN THE SCHEDULED ROOM PRESSURE. WITH ADDITIONAL CONTROL SEQUENCES, THE SEQUENCE WITH THE HIGHEST DEMAND FOR AIRFLOW WILL TAKE PRIORITY. IF DOOR SWITCHES ARE PRESENT, THE PRESSURE CONTROL ALGORITHM WILL PAUSE WHEN THE DOOR IS OPEN, AND WILL RESUME AFTER THE DOOR IS CLOSED. TEMPERATURE CONTROL: THE CONTROLLER WILL MEASURE THE SPACE TEMPERATURE FROM A WALL MOUNTED ROOM TEMPERATURE SENSOR. IF THE SPACE TEMPERATURE FALLS BELOW THE ADJUSTABLE ROOM TEMPERATURE SETPOINT, THE AIRFLOW WILL INITIALLY BE MAINTAINED AT THE MINIMUM SCHEDULED HEATING AIRFLOW (OR THE VALUE DICTATED BY OTHER DEMANDS, E.G. FUME HOODS) AND THE REHEAT COIL OUTPUT WILL BE INCREASED. ONCE THE DISCHARGE TEMPERATURE REACHES THE ADJUSTABLE MAXIMUM VALUE, THE REHEAT OUTPUT WILL BE MAINTAINED. IF THE ROOM TEMPERATURE DOES NOT RISE TO THE ROOM TEMPERATURE SETPOINT, THE AIRFLOW WILL THEN BE INCREASED (IF SCHEDULED) TOWARDS THE MAXIMUM SCHEDULED HEATING AIRFLOW, ALLOWING THE REHEAT OUTPUT TO INCREASE WHILE MAINTAINING THE MAXIMUM DISCHARGE TEMPERATURE. IF THE SPACE TEMPERATURE RISES ABOVE THE ADJUSTABLE ROOM TEMPERATURE SETPOINT, THE REHEAT OUTPUT WILL BE DECREASED. ONCE THE DISCHARGE TEMPERATURE REACHES THE ADJUSTABLE MINIMUM VALUE, THE REHEAT OUTPUT WILL BE MAINTAINED. THE AIRFLOW WILL INITIALLY BE MAINTAINED AT THE MINIMUM SCHEDULED COOLING AIRFLOW (OR VALUE DICTATED BY OTHER DEMANDS). IF THE ROOM TEMPERATURE DOES NOT DECREASE TO THE ROOM TEMPERATURE SETPOINT, THE AIRFLOW WILL BE INCREASED TOWARDS THE MAXIMUM SCHEDULED COOLING AIRFLOW. MODES OF OPERATION: OCCUPIED MODE: OCCUPIED MODE MAY BE ACTIVATED BY A CONTACT INPUT OR COMMAND BY BUILDING MANAGEMENT SYSTEM. A LOCAL OCCUPANCY SENSOR SHALL BE GIVEN PRIORITY OVER A BUILDING MANAGEMENT SYSTEM COMMAND ALLOWING THE USER TO OVERRIDE THE OCCUPANCY MODE AND SET THE SPACE TO “OCCUPIED” FOR A PREDETERMINED INTERVAL. WHILE IN OCCUPIED MODE THE CONTROLLER WILL TARGET THE SCHEDULED OCCUPIED AIRFLOWS. UNOCCUPIED MODE: UNOCCUPIED MODE MAY BE ACTIVATED BY A CONTACT INPUT OR COMMAND BY BUILDING MANAGEMENT SYSTEM. WHILE IN UNOCCUPIED MODE THE CONTROLLER WILL TARGET THE UNOCCUPIED SETPOINTS. EMERGENCY PURGE MODE: THE EMERGENCY PURGE MODE MAY BE ACTIVATED BY A CONTACT INPUT OR COMMAND BY BUILDING MANAGEMENT SYSTEM. WHILE IN THE EMERGENCY PURGE MODE, THE ROOM AIR CHANGE RATE WILL BE INCREASED. ROOM VOLUMETRIC OFFSET WILL BE MAINTAINED. PRESSURE MONITORING: A ROOM PRESSURE SENSOR WILL MEASURE THE DIFFERENTIAL PRESSURE BETWEEN THE ROOM AND ADJOINING SPACE. THE DIFFERENTIAL PRESSURE IS DISPLAYED ON THE WALL MOUNTED INTERFACE. LOW AND HIGH ROOM PRESSURE ALARMS AND CAUTIONS CAN BE ENABLED FOR LOCAL VISUAL AND AUDIBLE ALERT. ROOM DIFFERENTIAL PRESSURE AND ALARMS ARE AVAILABLE TO THE BUILDING MANAGEMENT SYSTEM. FUME HOOD CONTROL: SIDEWALL VELOCITY CONTROL: A VELOCITY SENSOR WILL MEASURE THE FACE VELOCITY OF THE FUME HOOD. UPON A MEASURED DECREASE IN FACE VELOCITY, THE CONTROLLER WILL INCREASE THE EXHAUST AIR VOLUME UNTIL THE MEASURED FACE VELOCITY IS EQUAL TO THE TARGET FACE VELOCITY. ON AN INCREASE IN MEASURED FACE VELOCITY, THE CONTROLLER WILL INCREASE THE EXHAUST AIR VOLUME UNTIL THE MEASURED FACE VELOCITY IS EQUAL TO THE TARGET FACE VELOCITY. A MINIMUM AIRFLOW IS MAINTAINED AT ALL TIMES WHEN THE SASH IS CLOSED TO ENSURE THE PROPER FUME HOOD AIR CHANGE RATE. ALARMS: AN AUDIBLE AND VISUAL ALARM WILL BE ACTIVATED IF: • THE MEASURED FACE VELOCITY DROPS BELOW THE ADJUSTABLE LOW ALARM LIMIT, OR RISES ABOVE THE ADJUSTABLE HIGH ALARM LIMIT • WHILE THE UNIT IS IN ALARM, THE LED LIGHT BARS WILL BE RED. THE AUDIBLE ALARM CAN BE SILENCED BUT WILL RE-ENGAGE AFTER AN ADJUSTABLE TIME DELAY. FUME HOOD EMERGENCY PURGE: AN EMERGENCY PURGE FEATURE WILL BE ACTIVATED WHEN THE “EMERGENCY” BUTTON ON THE FUME HOOD INTERFACE IS PRESSED. THE AIR DEVICE WILL MODULATE TO ITS FULLY OPEN POSITION TO PURGE THE FUME HOOD. A VISUAL AND AUDITORY ALARM WILL ACTIVATE TO INDICATE THAT THE FUME HOOD IS BEING PURGED. BUILDING NETWORK COMMUNICATION THE AIRFLOW CONTROL SYSTEM (ACS) WILL COMMUNICATE OVER A NATIVE BACNET MS/TP TRUNK TO THE BUILDING AUTOMATION NETWORK. ALL POINTS ARE AVAILABLE TO THE BMS WITH NO NETWORK GATEWAY REQUIRED. J U S T I R J U D Y 11 5 1 3 P R O F E S S I O N A L E N G I N E E R I D A HO O F S T A T E R E G I S T E R E D N 02 / 2 5 / 2 0 2 0