Permit Status of (Open) as of Report Date: 03/04/2020 10:34 am
Permit Details Permit Number: 12-00542
410 W 1st N - Carriage Cove Short Stay Rehabilitation
410 W 1st N
New Commercial Building
Permit Issued Date: 02/10/2014
Permit Inspection Statistics
60Total Inspections Completed:
51Total Inspections Passed:
Inspection Pass Rate: 85.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
05/02/2013PassDale PickeringFire Underground Inspection
0935 200psi
1135 200psi
Ok to cover
Inspector Comments:
05/22/2014PassJoel GrayPublic Works Final Inspection
OKInspector Comments:
02/13/2015PassNatalie PowellPlanning and Zoning Final Inspection
Building Inspection Type
06/07/2013PassQuinton OwensFooting Inspection
5/2,QO: SE corner around North side to West courtyard. All #5 (2 cont. and
across at 12" oc)
5/6,QO: South ftg reinforced as per plans.
5/8,QO: SE (final exterior section) reinforced per plans.
5/21,QO Interior courtyard reinforced per plans
5/31,QO: Interior footings
5/22,QO: Stair ftg done as per plans.
5/31,QO: West end interior ftgs and spot footings reinforced per plans.
6/6,QO: Some interior spot footings and int. wall footings at admin offices and by
NE corner of courtyard.
6/7,QO: Several Spot footings done most 5 #5 rebar each way.
Inspector Comments:
09/24/2013PassQuinton OwensFoundation Inspection
5/3,QO: #5 rebar at 12" oc ea way w/ 2 in top and bottom
5/6, QO: NW section Reinforced per plans
5/7,QO: Partial Fnd. ok to pour.
5/8,QO: SE (final exterior) section reinforced per plans.
5/22,QO: Interior courtyard and stair foundation rebar as per plans
6/7,QO: Interior Foundation walls by admin. offices and off NE corner of
courtyard.
6/27,QO: Concrete - slab only (int ftgs dome) *did not inspect* AP
9/24,QO: Replaced conc.entry across street (needed to access underground
hookups).
Inspector Comments:
Page 1 of 7
(Continued)
Permit Details Permit Number: 12-00542
410 W 1st N - Carriage Cove Short Stay Rehabilitation
410 W 1st N
New Commercial Building
Permit Status of (Open) as of Report Date: 03/04/2020 10:34 am
Permit
Inspection
Summary
12/18/2013Fail Insulation Inspection
insulate around windows
need some headers repaired. u .33 solar heat gain .25
Inspector Comments:
12/20/2013PassQuinton OwensCommercial Insulation Inspection
Reinspection of steel frame headers and window perimeters.Inspector Comments:
01/16/2014FailQuinton OwensFraming/Structure Inspection
fire blocking in walls over 10'. Tighten anchor bolts (various locations int. walls)
Not all penetrations protected as needed.
Inspector Comments:
01/23/2014PassTed DyeFraming/Structure Inspection
General Progress Reinspect - Grid 1-5 fire caulks in hall complete.
Bolts tightened.
Inspector Comments:
01/29/2014PassQuinton OwensSheetrock/Drywall Inspection
NW wing ok to tape (patient rooms done)
cw8a (int walls) #5 vert 14"o.c. ea way 2 #5 top & bottom
cw14a (outside N&E) #4 at 10" o.c. (each face) ea way (2) #6 top & bottom
cw16a (nw corner) vert #5 at 10"o.c. vert ins face out face
#4 at 10" o.c.
hor #4 at 9" o.c. each face 2#6 top & bottom
Inspector Comments:
02/05/2014PassQuinton OwensSheetrock/Drywall Inspection
2/5/14 - Drywall Screw - Drywall in patient rooms. East side of north wing
approved for taping. Hallway grid 1-5 North Ok to hang drywall on clg's.
Inspector Comments:
02/11/2014PassQuinton OwensSheetrock/Drywall Inspection
Drywall West end of North wing corridor and patient rooms on East end of North
wing. Approved for taping.
Inspector Comments:
02/21/2014PassQuinton OwensSheetrock/Drywall Inspection
North East section Drywall (mech room, laundry, custodial, etc.). Add missing
screws as indicated (exterior wall by door to last room, and in custodial closet).
Some penetrations in firewalls still to be firecaulked and will be inspected later.
Inspector Comments:
04/14/2014FailQuinton OwensFraming/Structure Inspection
Fire Barriers have several penetrations not fire rated throughout building.Inspector Comments:
04/17/2014FailQuinton OwensFraming/Structure Inspection
Inspection of all Fire barriers: Fire caulked most penetrations in NE corner Fire
barriers. Large vacant opening between storage and Mechanical room. Fire
dampers missing on 2 ducts between 130 & 126. Fire caulk penetrations in 325,
213, 211, 116, 108, 123 (Reception), and above Fire doors by 125 and corridor
C02-A.
Inspector Comments:
Page 2 of 7
(Continued)
Permit Details Permit Number: 12-00542
410 W 1st N - Carriage Cove Short Stay Rehabilitation
410 W 1st N
New Commercial Building
Permit Status of (Open) as of Report Date: 03/04/2020 10:34 am
Permit
Inspection
Summary
04/29/2014FailQuinton OwensBuilding Final
Smoke partitions under sink penetrations to be sealed: 102, 103, 104, 106, 108,
110, 111, 113, 115, 218, 219, 222, 227,228,
Under sink pipe protection missing in all patient bathrooms (except 101)
Sprinkler head in "soiled linen" & Bathroom in kitchen area not trimmed out.
Bathroom door in 233 catches on floor, opening width may not be enough.
Dryer vents not done in Clean linen, 136.
Lock control from inside walk in freezer for egress?
Maxitrol R500S regulator not vented outside, not horizontal (need one or the
other).
2nd fire damper between custodian room 130 & room 126 (duct through fire
barrier).
uncover sprinkler over stairway.
Finish seal on Aluminum Grease duct cover on roof
Fire caulk duct penetrations in North fire barrier wall in Attic room, A03
Duct not sealed around sensor rod through duct in Attic, A01.
West wall of 108 designated as fire barrier- is window above door rated?
Maximum reach height for items above bathroom counters is 44" above floor.
Handicap bathroom door closer (only one installed so far) by dining closes too
fast.
Inspector Comments:
05/07/2014FailQuinton OwensBuilding Final
Maxitrol regulators not vented outside, not horizontal (need one or the
other).Behind cooking range & dryers.
Finish sealing exterior grease duct cover on roof.
Handicap bathroom door closer by dining closes too fast (only one of two
installed so far).
Inspector Comments:
05/09/2014PassQuinton OwensBuilding Final
Final Building items complied with.Inspector Comments:
Page 3 of 7
(Continued)
Permit Details Permit Number: 12-00542
410 W 1st N - Carriage Cove Short Stay Rehabilitation
410 W 1st N
New Commercial Building
Permit Status of (Open) as of Report Date: 03/04/2020 10:34 am
Permit
Inspection
Summary
Electrical Inspection Type
01/29/2013PassBret StoddardCommercial Electrical Rough-in
Approved for cover in room units only in section A, 5 to 7 (7 units), for electrical
and fire alarm wiring and conduits.
Inspector Comments:
11/13/2013PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power.Inspector Comments:
12/02/2013FailBret StoddardCommercial Electrical Rough-in
Need to install "green" MC cable for all patient care areas as specified in the
electrical plans-(lighting below 7'6"), nail plates and K.O. seals needed
throughout, call for a re-inspect when ready.
Inspector Comments:
12/18/2013PassBret StoddardCommercial Electrical Rough-in
Approved for cover in gridline 5 to the west in the assisted living wing for
electrical and fire alarm wiring and conduit.
Inspector Comments:
12/23/2013PassBret StoddardCommercial Electrical Rough-in
Approved for cover in the south side from gridline 5 to 7(assisted living portion)
for electrical and fire alarm wiring/conduit.
Inspector Comments:
01/08/2014PassBret StoddardCommercial Electrical Rough-in
Approved for cover in the exterior walls only in the 7 north west end units.Inspector Comments:
01/16/2014PassBret StoddardCommercial Electrical Rough-in
Approved for cover for electrical and fire alarm wiring in the areas from 0-5 lines
on the north portion (skilled nursing wing) in all units, soffits in the 0-7 line
(assist. living wing), and room 250 between the two wings hallway. Also
approved for cover upstairs in the communications room-all other areas upstairs
were fished in the walls after sheetrock was installed.
Inspector Comments:
02/05/2014PassBret StoddardCommercial Electrical Rough-in
Approved for cover in resident room #301, hair salon 126, library 124,
multipurpose room 122, toilet room 120 and 118, 107, 105, 103, 102, 106, and
104 for electrical and fire alarm wiring/conduit.
Inspector Comments:
02/11/2014PassBret StoddardCommercial Electrical Rough-in
02/18/2014PassBret StoddardCommercial Electrical Rough-in
02/24/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
02/26/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
04/21/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved to install the ceiling tiles in all corridors and rooms with grid ceilings.Inspector Comments:
04/23/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final in the north wing-skilled nursing only-electrical.Inspector Comments:
Page 4 of 7
(Continued)
Permit Details Permit Number: 12-00542
410 W 1st N - Carriage Cove Short Stay Rehabilitation
410 W 1st N
New Commercial Building
Permit Status of (Open) as of Report Date: 03/04/2020 10:34 am
Permit
Inspection
Summary
04/24/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
GFCI protection required for all 125V receptacles in kitchen area.Inspector Comments:
04/25/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.Inspector Comments:
Fire Inspection Type
12/18/2013PassBret StoddardFire Alarm Rough-in
Approved for cover in gridline 5 to the west in the assisted living wing for
electrical and fire alarm wiring and conduit.
Inspector Comments:
12/23/2013PassBret StoddardFire Alarm Rough-in
Approved for cover in the south side from gridline 5 to 7(assisted living portion)
for electrical and fire alarm wiring/conduit.
Inspector Comments:
01/16/2014PassBret StoddardFire Alarm Rough-in
Approved for cover for electrical and fire alarm wiring in the areas from 0-5 lines
on the north portion (skilled nursing wing) in all units, soffits in the 0-7 line
(assist. living wing), and room 250 between the two wings hallway.
Inspector Comments:
02/05/2014PassBret StoddardFire Alarm Rough-in
Approved for cover in resident room #301, hair salon 126, library 124,
multipurpose room 122, toilet room 120 and 118, 107, 105, 103, 102, 106, and
104 for electrical and fire alarm wiring/conduit.
Inspector Comments:
04/16/2014N/ABret StoddardFire Alarm Final Inspection
04/23/2014PassSAUREY AMANDAFire Sprinkler Rough-in
3/7 Underground flush, Pass, DD
4/7 #220 Hydro, wet, #210 @ 1130, #215 @ 1330
dry, #211 @ 1130, #210 @ 1330
Above grid wet & attic dry, OK to cover, DP
Inspector Comments:
04/23/2014PassSAUREY AMANDAFire Sprinkler Final Inspection
04/23/2014PassBret StoddardFire Alarm Final Inspection
05/29/2014PassDale PickeringFire Department Final Inspection
Page 5 of 7
(Continued)
Permit Details Permit Number: 12-00542
410 W 1st N - Carriage Cove Short Stay Rehabilitation
410 W 1st N
New Commercial Building
Permit Status of (Open) as of Report Date: 03/04/2020 10:34 am
Permit
Inspection
Summary
Mechanical Inspection Type
01/16/2014PassQuinton OwensHVAC Rough-in
north b wing - mech rough in good.Inspector Comments:
02/11/2014PassQuinton OwensHVAC Rough-in
Ductwork over physical therapy area and connecting rooms. Sealed and
approved.
Inspector Comments:
02/20/2014PassQuinton OwensHVAC Rough-in
Walk through for HVAC rough on North side rooms & hall. Approved (finish duct
insulation)
Inspector Comments:
03/10/2014PassQuinton OwensHVAC Rough-in
Grease duct light test. Found 4 initial holes. 2 holes still found at re-inspection. All
holes repaired during inspection and duct approved for wrap.
Inspector Comments:
03/28/2014PassQuinton OwensHVAC Rough-in
3/25: Grease duct section above roof. Light bulb test in sunlight? or arrange
different time. Visual inspection of welds showed potential holes and need to
verify.
3/28: Reinspected. holes found (with sunlight outside and inspecting inside duct
through access opening) and fixed. Did visual inspection to recheck. Approved
Inspector Comments:
04/02/2014PassQuinton OwensHVAC Rough-in
Grease duct above roof approved for cover. South portion of mech floor ducts
sealed and ready for cover.
Inspector Comments:
04/14/2014PassDon AllenHVAC Final Inspection
All good for c/oInspector Comments:
Page 6 of 7
(Continued)
Permit Details Permit Number: 12-00542
410 W 1st N - Carriage Cove Short Stay Rehabilitation
410 W 1st N
New Commercial Building
Permit Status of (Open) as of Report Date: 03/04/2020 10:34 am
Permit
Inspection
Summary
Plumbing Inspection Type
06/07/2013PassDon AllenPlumbing Underground Inspection
all good to cover groundworkInspector Comments:
06/27/2013PassDon AllenPlumbing Underground Inspection
07/11/2013PassDon AllenPlumbing Underground Inspection
all good to cover ground workInspector Comments:
07/18/2013PassDon AllenPlumbing Underground Inspection
good to cover ground work.Inspector Comments:
11/14/2013PassDon AllenPlumbing Rough-in
1/2 south b wing good to coverInspector Comments:
01/21/2014PassDon AllenPlumbing Rough-in
north east wing all good to coverInspector Comments:
01/30/2014PassDon AllenPlumbing Rough-in
all good on hallways done.Inspector Comments:
02/20/2014FailDon AllenPlumbing Rough-in
02/25/2014PassDon AllenPlumbing Rough-in
all goodInspector Comments:
04/14/2014PassDon AllenPlumbing Final Inspection
All good for c/oInspector Comments:
Page 7 of 7