HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00496 - Rockcreek Townhomes #101-108Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/25/2020 4:05 pm
Permit Details Permit Number: 12-00496
Rockcreek Townhomes #101-108
565 Pioneer Rd
New Single Family Residence
Permit Issued Date: 08/06/2014
Permit Inspection Statistics
38Total Inspections Completed:
17Total Inspections Passed:
Inspection Pass Rate: 44.74%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
11/13/2012PassQuinton OwensResidential Footing Inspection
Footing OK to pour. Ufer installed (north side)Inspector Comments:
11/20/2012PassQuinton OwensFoundation Inspection
11-16 (QO) Lengthwise foundation walls and end walls ok.
Cross walls between units and remaining interior footings ok (11-20)
Inspector Comments:
04/25/2013FailTed DyeResidential Framing/Structure Inspection
Sheathing: Some locations missed - partial to full studs, marked inside with paint
or crayon. Corner holddowns on garage popouts not nailed to double studs.
6,7,8 inspected
violations:
-type all units, Holes through sheetrock in gables need to be repaired
-type all units, Overburns some are incomplete and need finished of patched
typical all units,
-Truss notched under tub drains. talk to manufactor for repair spec's**
-information given on fix for notched truss. 3' plywood patch on one side
Inspector Comments:
06/14/2013PassTed DyeResidential Framing/Structure Inspection
5/3/13 - reinspected at insulation inspection.all units had party wall patched in
trusses. 105, 106, 107,108 framing complete
6/14/13 - 6 units from south still need floor truss repair.
Inspector Comments:
06/14/2013PassTed DyeResidential Insulation Inspection
5/2/13 - 105, 106, 107, 108 units approved to cover with drywall
5/8/13 - *other ticket approved*
6/14/13 - 101,102,103&104 main floor and second story OK to cover.
Crawl spaces are not insulated yet
Inspector Comments:
06/20/2013PassTed DyeResidential Sheetrock/Drywall Inspection
5/13/13 - Drywall OK to cover. Party walls in garage needs to have a 2 hr wall @
floor joists (no drywall all the way through rim joist) five caulk any penetration
through party wall.
6/20/13 - 1,2,3 OK to tape. 4 already taped.
Inspector Comments:
Page 1 of 5
(Continued)
Permit Details Permit Number: 12-00496
Rockcreek Townhomes #101-108
565 Pioneer Rd
New Single Family Residence
Permit Status of (Open) as of Report Date: 02/25/2020 4:05 pm
Permit
Inspection
Summary
07/18/2013FailTed DyeResidential Building Final
#108: missing handrail. Need access to crawl space. Dishwasher missing
ownerselect. Main floor smoke / CO detector wont test OK.
Inspector Comments:
08/05/2013FailTed DyeResidential Building Final
3107: Smoke / CO detector needed outside bedrooms. House # missing above
garage.
Inspector Comments:
08/08/2013PassTed DyeSidewalk Inspection
no inspection made at time of pour
grade and base looked at at side of sidewalk look to be good
Inspector Comments:
08/27/2013FailTed DyeResidential Building Final
#102: Insulation in crawl space falling out.Inspector Comments:
09/19/2013FailTed DyeResidential Building Final
#105: Smoke detector outside bedrooms is not communicating with others it also
is required to be a smoke / CO combination detector.
Inspector Comments:
12/03/2013FailTed DyeResidential Building Final
#101: Handrails missing. Smoke / CO detector needed outside bedroom. Smoke
detector inside of bedroom is not working with other smoke detectors. Insulate
around edge of exterior walls.
Inspector Comments:
01/09/2014FailQuinton OwensResidential Building Final
#104: R-30 required for floors over uncond. space. Riser heights should be even
in garage. Insulation certification by installer? Condensate drain placed in a way
the sub floor may get wet. (extend pipe into floor drain or protect subfloor from
condensate.)
Inspector Comments:
01/22/2014PassTed DyeResidential Building Final
8/1/13 - #108 handrail installed.
8/8/13 - #107 approved
8/29/13 - #102 approved
9/20/13 - #105 fixed while I was here.
9/20/13 - #105 approved.
10/22/13 - #103 OK while there. Approved.
12/5/13 - #101 Approved.
1/21/14 - #104 Approved.
Inspector Comments:
Page 2 of 5
(Continued)
Permit Details Permit Number: 12-00496
Rockcreek Townhomes #101-108
565 Pioneer Rd
New Single Family Residence
Permit Status of (Open) as of Report Date: 02/25/2020 4:05 pm
Permit
Inspection
Summary
Electrical Inspection Type
06/10/2013PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power-(2)-also inspected for rough-in
on the same ticket and inspection.
Inspector Comments:
06/12/2013PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
07/12/2013FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Island missing receptacle in kitchen, dispose-all and microwave receptacles
missing covers and recessed, recessed can trim missing front, water heater not
wired in, call for a re-inspect when ready.
Inspector Comments:
08/09/2013FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Water heater not wired, wires in island not protected for receptacle, need to
strap conduits for the main service, call for a re-inspect when ready.
Inspector Comments:
08/27/2013FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Closet light to close to shelving, island receptacle-no power, north bedroom
upstairs on north wall receptacle is loose, call for a re-inspect when ready-unit
#102 only.
Inspector Comments:
09/13/2013FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Disposeall, dishwasher and microwave receptacles not installed, island receptacle
not installed, GFCI cover plate broken outside front patio, recessed can trim not
installed outside, furnace missing cover, water heater not wired, call for a
re-inspect when ready.
Inspector Comments:
09/19/2013FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
GFCI receptacle outside on the west side of the building has a broken cover,
island NM-B cable is not protected from physical damage, furnace switch is
missing cover upstairs, call for a re-inspect when ready-unit #105.
Inspector Comments:
10/03/2013FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Unit #101-Need to GFCI protect the receptacles in the garage and outside,
kitchen receptacle not GFCI protected near sink, door bell transformer has
exposed wires, need to strap flex in island for receptacle, need to install box on
exposed wires near meter bases on north end, call for a re-inspect when ready.
Inspector Comments:
10/21/2013FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Outside receptacle on the west side of the building not installed, garage not
done, stair light covered and not installed, call for a re-inspect when ready.
Inspector Comments:
01/10/2014FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Fridge breaker not functional, recessed can trim in front porch not installed,
switch cover missing in garage, master bath fan doesn't work, switches for
master bath, furnace, and closet upside down, master bath shower can doesn't
work, receptacle on the north end of the building not installed, transformer for
door bell has exposed wire and no cover, no A/C unit installed(30A OCPD), call
for a re-inspect when ready.
Inspector Comments:
Page 3 of 5
(Continued)
Permit Details Permit Number: 12-00496
Rockcreek Townhomes #101-108
565 Pioneer Rd
New Single Family Residence
Permit Status of (Open) as of Report Date: 02/25/2020 4:05 pm
Permit
Inspection
Summary
01/10/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
7/17/13 - Approved for a final and C.O. #106, 103 only.
8/8/13 - Approved for a final and C.O. #107, 105 only.
8/13/13 - Approved for a final and C.O. #108 only.
8/29/13 - Approved for a final and C.O. in unit #102 closet light changed to
flourescent type.
9/19/13 - Approved for a final and C.O. #105 only.
10/22/13 - Approved for a final and C.O. #103 only.
12/5/13 - Approved for a final and C.O.#101 only. North receptacle on building
outside not done and will re-inspect on the final #104(final unit in this building).
1/10/14 - Approved for a final and C.O. in unit #104, no A/C unit is installed(30A
OCPD).
Inspector Comments:
Fire Inspection Type
10/21/2013PassDale PickeringFire Sprinkler Final Inspection
Mechanical Inspection Type
04/10/2013FailQuinton OwensHVAC Rough-in
Bath Fans or vents not installed.Inspector Comments:
07/17/2013FailDon AllenHVAC Final Inspection
Need water in to sinks. Trim out shower / upstairs tub. Washer box trim out. Ice
box needs trimmed out.
Inspector Comments:
07/23/2013FailDon AllenHVAC Final Inspection
106 - Need valve on gas line for dryer and stove.
107 - Needs to be finished / gas hooked up and registers put in
Inspector Comments:
09/13/2013FailDon AllenHVAC Final Inspection
HVAC needs to put register cover in upstairs. Call for reinspect.Inspector Comments:
10/18/2013FailDon AllenHVAC Final Inspection
Mech: need to finish mech fan in bathroom.Inspector Comments:
12/02/2013PassDon AllenHVAC Final Inspection
7/23/13 - 108 All good for C/O
8/8/13 - HVAC all good for C/O
8/27/13 - All good for the C/O
9/19/13 - All good for the C/O
12/2/13 - All good for C/O on mech
Inspector Comments:
Page 4 of 5
(Continued)
Permit Details Permit Number: 12-00496
Rockcreek Townhomes #101-108
565 Pioneer Rd
New Single Family Residence
Permit Status of (Open) as of Report Date: 02/25/2020 4:05 pm
Permit
Inspection
Summary
Plumbing Inspection Type
12/14/2012PassDon AllenPlumbing Water
07/17/2013FailDon AllenPlumbing Final Inspection
106 need to trim the tub and shower
106 need water turned on to check sinks
106 washer box and ice box need trimmed out
Inspector Comments:
07/24/2013PassDon AllenPlumbing Final Inspection
7/19/13 - All good for C/O
8/8/13 - Plumbing all good for C/O (#107)
8/23/13 - All good for C/O (#102)
9/13/13 - Plumbing is all good for the C/O (#105)
10/18/13 - Plumbing all good for C/O (#103)
12/2/13 - All good for C/O (#101)
1/9/14 - All good for C/O All good on apt.104 (#104)
Inspector Comments:
09/03/2013PassDon AllenPlumbing Rough-in
09/24/2013PassDon AllenPlumbing Sewer
09/24/2013PassDon AllenPlumbing Underground Inspection
Page 5 of 5