Permit Inspection History *Refer to Individual Inspection Report for more Details
Mechanical Inspection Type
03/26/2013PassQuinton OwensHVAC Rough-in
Furnace replacement onlyInspector Comments:
03/26/2013PassQuinton OwensHVAC Final Inspection
Non-direct vent Furnace & WH input = 94k btu. 2 comb. air vents with 4" diam.
good for 75k btu. Mech room over 116 sf needed for remaining comb. air
(1000btu/50cf).
Inspector Comments: