HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00399 - Mesa Falls Apts Bldg # 1Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/19/2020 9:08 am
Permit Details Permit Number: 12-00399
Mesa Falls Apts Bldg # 1
940 S 5th W
New Multi-Family Residence
Permit Issued Date: 02/27/2014
Permit Issued Date: 05/20/2015
Permit Inspection Statistics
27Total Inspections Completed:
24Total Inspections Passed:
Inspection Pass Rate: 88.89%
Permit Inspection History *Refer to Individual Inspection Report for more Details
05/24/2013PassDale PickeringFire Underground Inspection
Underground hydro - bldgs 6,1,15,16 all pass.Inspector Comments:
Building Inspection Type
04/16/2013PassTed DyeFoundation Inspection
Middle section approved. (outside foundation to be inspected)Inspector Comments:
04/17/2013PassQuinton OwensFoundation Inspection
4/17, QO: outer buildings approved to pour. Ufer placed in footing after
inspection.
Inspector Comments:
05/09/2013PassQuinton OwensFooting Inspection
2 #4 rebar cont. and supported. clearances good. Ufer not in at time of
inspection.
5/9, QO: Interior footings - 2 #4 rebar supported on chairs.
Inspector Comments:
8/8,QO: Finish firecaulking interior wall plates (mainly at dryer vents and phone
line). Fireblock plate penetrations in rated walls. Add stud by door to laundry
(305). Fix clg joist in lndry (306).
Inspector Comments:
8/21,QO: 2nd Floor - finish Fireclk (205,208,202,203). Bad stud in bearing wall
(205). Fireclk penetrations into rated washer box area (203,206). Fire caulk tub
drain above 201.
Inspector Comments:
8/23,QO: previous items not completed- Frclk & frblk, add stud by
laundry (305)
Inspector Comments:
8/27, TD: 1st floor - open hope (101 hole filled with fire block, need's caulk),
concealed area above tum rm101 drywall hanging & rm108
Inspector Comments:
8/29,QO: 2nd & 3rd Floor items done.(sent Ted for re-inspection)Inspector Comments:
8/29 TD: 2nd floor - 208 seal around patio door (DA)Inspector Comments:
08/30/2013PassQuinton OwensFraming/Structure Inspection
8/30/13 TD: rm. 101 Approved , 208 approvedInspector Comments:
08/30/2013PassQuinton OwensInsulation Inspection
8/23,QO: 3rd Floor approved.
8/27,QO: 2nd Floor - Seal around patio doors.
8/29,QO: All floors done.
Inspector Comments:
8/27,QO: 3rd Floor, 5/8" type x required on walls dividing vaulted space and attic
space in addition to fire partitions.(corrected 8/30,QO)
Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 12-00399
Mesa Falls Apts Bldg # 1
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/19/2020 9:08 am
Permit
Inspection
Summary
8/29 QO: 1st floor insuation good. r-19 walls (ext.) r-13 int. walls, v-.34 windows,
floor- blown fbrgls wndow/dr perm. sealed.
Inspector Comments:
8/30/13 208,207,205,and 206 approved for taping
207 had one side missing screws they did them shortly after i inspected it.
Inspector Comments:
9/4,QO: 1st floor approved.Inspector Comments:
12/26/2013PassQuinton OwensSheetrock/Drywall Inspection
8/30 TD: 208 - drywall approved taping.
207 - drywall screws missing kitchen area.
205- drywall approved for taping.
206- need shear wall and drywall.
Inspector Comments:
12/26/2013PassTed DyeSidewalk Inspection
12/30/2013PassTed DyeBuilding Final
1101through 108 passed final
1201 through 208 passed final
1301 through 308 passed final
Inspector Comments:
02/27/2014PassPLL ADMINFraming/Structure Inspection
7/2,QO: Sheathing- missed nailing at marked locations. (Reinspect with Framing)Inspector Comments:
Electrical Inspection Type
08/05/2013PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power(2 locations)-inspected the
electrical services on the rough-in inspection.
Inspector Comments:
08/05/2013PassBret StoddardCommercial Electrical Rough-in
Approved for cover entire building-inspected the electrical service and fire alarm
wiring on this inspection.
Inspector Comments:
12/12/2013PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.-electrical only.Inspector Comments:
Fire Inspection Type
08/05/2013PassBret StoddardFire Alarm Rough-in
Approved for cover entire building-fire alarm wiring-inspected on the same
inspection as the electrical wiring.
Inspector Comments:
09/06/2013PassDale PickeringFire Sprinkler Hydro
Bldg # 1; Hydro at #200 psi - PassInspector Comments:
12/19/2013PassBret StoddardFire Alarm Final Inspection
Approved for a final and C.O.-fire alarm only, witnessed all signalling and
initiating device operation, 24 hour/5minute test from 3:15PM 12/18 to 3:30PM
12/19 for AC restored, flow switch(36 seconds) and tamper switches(2)
operational-witnessed, panel had 2 hour delay for AC loss because of dip switch
#6 on panel as per Gary with Omni, report in file.
Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 12-00399
Mesa Falls Apts Bldg # 1
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/19/2020 9:08 am
Permit
Inspection
Summary
Mechanical Inspection Type
08/29/2013PassQuinton OwensHVAC Rough-in
8/8,QO: fix separation in bath vent (301). B-vents not finished. Dryer vents very
long (post effective dryer length).
8/21,QO: 2nd Floor- firecaulk gaps at B-vent at ceiling leve (207,204,201) & wall
(201,208). 3rd floor done.
8/23,QO: Post effective dryer lengths before final.
8/27,QO: 1st floor-seal plenums (101,102,106). Finish 2nd floor items.
8/29,QO: 1st & 2nd floor done.
Inspector Comments:
12/20/2013FailQuinton OwensHVAC Final Inspection
Gas odor by regulator in 1102,1301, and 1108. Fix bath fan in 1203. Hazard:
strap for water heater by light switch in pantry (middle units) might cut
someone's hand when reaching for the switch. Don't lose tags to regulators; they
need to stay on them.
Inspector Comments:
12/27/2013PassQuinton OwensHVAC Final Inspection
12/24: Gas odor still by regulator in 1301.
12/27: all units approved.
Inspector Comments:
Plumbing Inspection Type
04/29/2013PassDon AllenPlumbing Underground Inspection
all good to cover groundworkInspector Comments:
05/28/2013PassDon AllenPlumbing Underground Inspection
07/16/2013FailDon AllenPlumbing Rough-in
need to strap the water lines ever 32"Inspector Comments:
07/17/2013FailDon AllenPlumbing Water
need to install the y straner and the meter
need to strap the water lines ever 32"
Inspector Comments:
12/18/2013PassDon AllenPlumbing Final Inspection
all good for the C/OInspector Comments:
12/24/2013PassDon AllenPlumbing Sewer
12/24/2013PassDon AllenPlumbing Water
12/24/2013PassDon AllenPlumbing Rough-in