HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00420 - Maverik Country Store - Service Change OutPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/18/2020 9:12 am
Permit Details Permit Number: 12-00420
Maverik Country Store - Service Change Out
12 S 2nd W
Commercial Electrical Misc.
Permit Issued Date: 07/03/2014
Permit Inspection Statistics
2Total Inspections Completed:
2Total Inspections Passed:
Inspection Pass Rate: 100.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Electrical Inspection Type
09/26/2012PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power-changed out 200A for a 400A
service. Available fault current as per RMP is 9800A-breakers are rated at 10,000
and 25,000A on 240V-2 200A breaker installed.
Inspector Comments:
09/26/2012PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final-service change. Approved to close the permit.Inspector Comments: