HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00406 - Mesa Falls Apts Bldg #9Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/14/2020 10:31 am
Permit Details Permit Number: 12-00406
Mesa Falls Apts Bldg #9
940 S 5th W
New Multi-Family Residence
Permit Issued Date: 09/12/2014
Permit Inspection Statistics
38Total Inspections Completed:
25Total Inspections Passed:
Inspection Pass Rate: 65.79%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
09/17/2014PassTed DyeCommercial Footing Inspection
09/18/2014PassTed DyeFoundation Inspection
10/20/2014PassTed DyeCommercial Footing Inspection
02/06/2015FailTed DyeSheeting
Units 9107, 108, 202, 203, 204, 205, 206, 207, 208, 304, 305 and 308 are
approved.
-Units 9101, 102, 103, 104, 105, 301, 302, 303, 306 and 307 had sheeting that
had not been nailed to the studs.
- Unit 103 had nails from straps that had missed the backing.
Inspector Comments:
02/18/2015FailTed DyeSheeting
Sheeting that missed being nailed are in the following locations:
-9101 One stud in the kitchen area.
-105 In last bedroom under the window.
-407 Stud between separation walls..
Inspector Comments:
03/13/2015FailTed DyeCommercial Framing/Structure Inspection
03/16/2015Pass Commercial Framing/Structure Inspection
03/16/2015PassTed DyeCommercial Insulation Inspection
03/18/2015PassTed DyeCommercial Insulation Inspection
Insulation was not ready around exterior concrete wallsInspector Comments:
03/20/2015FailTed DyeCommercial Insulation Inspection
This ticket entered by mistake please disregardInspector Comments:
03/20/2015FailTed DyeCommercial Insulation Inspection
In units 206 bedroom and 205 2nd bedroom, There is foam insulation missing
around windows.
In unit 104 There is drywall missing flue chase (concealed location).
Inspector Comments:
03/20/2015PassTed DyeCommercial Sheetrock/Drywall Inspection
03/24/2015PassTed DyeCommercial Insulation Inspection
all items completedInspector Comments:
Page 1 of 4
(Continued)
Permit Details Permit Number: 12-00406
Mesa Falls Apts Bldg #9
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 10:31 am
Permit
Inspection
Summary
03/24/2015PassTed DyeResidential Sheetrock/Drywall Inspection
Inspected units 101, 102, 105, 106, 107 and 108 and they are approved to tape
and texture.
Inspector Comments:
03/30/2015PassTed DyeCommercial Sheetrock/Drywall Inspection
Units 9103, 104, 201,202, 203, 204, 205, 206-207 and 208 Approved to tape and
texture.
Inspector Comments:
04/06/2015PassTed DyeSheeting
Sheeting reinspect done with the framing inspection.
This ticket is for your records and ours to close out the sheeting inspection
Inspector Comments:
06/15/2015PassTed DyeResidential Sheetrock/Drywall Inspection
All units inspected for 1" around "B" vent.
All Passed.
Inspector Comments:
06/15/2015Fail Sidewalk Inspection
Inspected East side along S. Millhollow Rd. Apprx. 12" of Granular fill.
Also inspected city side walk across the driveway. 12" granular fill.
Remainder of front sidewalk and around the corner on Millow hollow
to approximatly the front of the house, did not have fill in place and
ready for inspection .
Call for an additional inspection for 8 am in the morning, as disussed
with Straight Arrow construction.
Inspector Comments:
06/15/2015Fail Sidewalk Inspection
Inspection failed because of all granular base not being in place.Inspector Comments:
Page 2 of 4
(Continued)
Permit Details Permit Number: 12-00406
Mesa Falls Apts Bldg #9
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 10:31 am
Permit
Inspection
Summary
07/01/2015FailTed DyeCommercial Building Final
Units passed; 9101, 103, 201, 202, 203, 301, 302, 303, 105, 106, 205, 207
102.
102-Smoke detector in 1st bedroom is communicating with others.
104-Fire caulk drain and supplies under master sink
- Master bath;Clean out on wall needs to be metal.
202-Second bedroom smoke detector is not communicating with others.
204-Fire caulk around drain in master bath.
-Fire caulk around sprinkler head in furnace.
304-The bottom strap is loose on the water heater.
-Fire caulk around drain in Master bath.
107-Seal along bottom of tub.
108-Seal along bottom of tub.
205-Sprinkler in Mechanical room is to low and thus the beauty ring does not fit
and leave an opening in the ceiling.
Either raise the sprinkler head or fire caulk opening.
206-Fire caulk thermostat wire in furnace room
208-Seal along bottom of tub.
305-Seal along bottom of tub.
306-Seal along bottom of tub.
307-Seal along bottom of tub.
308-Seal along bottom of tub. Both (bathrooms)
Inspector Comments:
07/14/2015FailTed DyeCommercial Building Final
Unit 104 needs a metal cover on clean out, on the separation wall in the
bathroom,located next to toilet.
fire caulk supply for toilet in same bathroom.
Inspector Comments:
07/16/2015FailTed DyeCommercial Building Final
Unit 104 items completedInspector Comments:
07/28/2015PassQuinton OwensCommercial Building Final
Electrical Inspection Type
03/11/2015PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/13/2015PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
03/13/2015PassBret StoddardCOM & MFR Electrical Service Inspection
06/09/2015PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Page 3 of 4
(Continued)
Permit Details Permit Number: 12-00406
Mesa Falls Apts Bldg #9
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 10:31 am
Permit
Inspection
Summary
Fire Inspection Type
03/10/2015FailBret StoddardFire Sprinkler Rough-in
03/23/2015PassDale PickeringFire Sprinkler Rough-in
05/07/2015PassDale PickeringFire Sprinkler Hydro
06/11/2015PassBret StoddardFire Alarm Final Inspection
Mechanical Inspection Type
03/17/2015FailDon AllenHVAC Rough-in
03/19/2015PassDon AllenHVAC Rough-in
06/15/2015FailDon AllenHVAC Final Inspection
APT. 9307 THE TOP 90 ON THE WATER HEATR NEEDS TO BE DOUBLE WALL.Inspector Comments:
06/23/2015PassDon AllenHVAC Final Inspection
Good for the c/oInspector Comments:
Plumbing Inspection Type
09/29/2014PassDon AllenPlumbing Underground Inspection
All good to cover the undergroundInspector Comments:
03/09/2015PassDon AllenPlumbing Rough-in
Good to cover the plumbing roughinInspector Comments:
06/30/2015FailDon AllenPlumbing Final Inspection
APT.9103 NEEDS T&P DROP
APT. 9305 NEEDS FAUCET FIKED IN THE KITCHEN.
Inspector Comments:
02/16/2016PassDon AllenPlumbing Final Inspection
Page 4 of 4