HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00401 - Mesa Falls Apts Bldg #14Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/14/2020 8:49 am
Permit Details Permit Number: 12-00401
Mesa Falls Apts Bldg #14
940 S 5th W
New Multi-Family Residence
Permit Issued Date: 08/06/2014
Permit Inspection Statistics
33Total Inspections Completed:
23Total Inspections Passed:
Inspection Pass Rate: 69.70%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
08/06/2014PassTed DyeCommercial Footing Inspection
08/07/2014PassTed DyeFoundation Inspection
Pouring the center section only.Inspector Comments:
09/10/2014PassTed DyeCommercial Footing Inspection
12/03/2014FailTed DyeSheeting
13108 sheeting missed being to stud on west wall.
13301 nail sheeting located at the top plate on the north wall on east side of that
wall.
13305 repair sheeting under window.
13307 sheeting missed being nailed to stud in furnace closeet.
Inspector Comments:
12/15/2014FailTed DyeCommercial Framing/Structure Inspection
concealed area's are not all sealed up and need fire caulked.
Some sprinkler lines need sealed.
All electrical has been sealed.
Inspector Comments:
12/16/2014PassTed DyeCommercial Framing/Structure Inspection
3rd floor passed for insulation
1st and 2nd floor yet to be inspected( not ready ).
Inspector Comments:
12/18/2014FailTed DyeCommercial Framing/Structure Inspection
Inspected levels 1st and 2nd floor.Inspector Comments:
12/18/2014PassTed DyeCommercial Insulation Inspection
12/22/2014FailTed DyeCommercial Framing/Structure Inspection
window missing in 101Inspector Comments:
12/22/2014FailTed DyeCommercial Insulation Inspection
insulation has not been pushed back at top of rim joist
insulation should be tight against top plate
Inspector Comments:
12/22/2014PassTed DyeCommercial Sheetrock/Drywall Inspection
12/22/2014Fail Commercial Framing/Structure Inspection
12/29/2014PassTed DyeCommercial Sheetrock/Drywall Inspection
12/29/2014PassTed DyeCommercial Framing/Structure Inspection
Page 1 of 3
(Continued)
Permit Details Permit Number: 12-00401
Mesa Falls Apts Bldg #14
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 8:49 am
Permit
Inspection
Summary
12/29/2014PassTed DyeCommercial Insulation Inspection
01/03/2015FailQuinton OwensCommercial Sheetrock/Drywall Inspection
1st floor apartments onlyInspector Comments:
01/07/2015PassTed DyeCommercial Sheetrock/Drywall Inspection
04/01/2015FailTed DyeCommercial Building Final
Those units needing 1" around the "B" vent are; 14101, 102, 201, 202, 203, 204,
105, 107 and 207.
There are "B" vents that have the ring around held on by screws that can not be
inspected. They
are 105, 106, 107, 108 and 205.
The pop off tube for the water heater needs to exten over to the floor drain in
units 104 and108.
Unit 305 needs a combination SD/CO detector out side the bedrooms.
Unit 108 has a gas smell in the laundry room.
Units that passed are 103, 206, 208, 301, 302, 303, 304, 306, 307 and 308.
Inspector Comments:
04/08/2015N/ATed DyeSidewalk Inspection
Private sidewalkInspector Comments:
04/08/2015FailTed DyeCommercial Building Final
All previous items corrected
ONLY landscaping to finish up.
Temp C.O. may be issued with the stipulation that the landscaping be done by
6/1/15
Inspector Comments:
06/12/2015PassTed DyeCommercial Building Final
Electrical Inspection Type
10/22/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
12/01/2014PassBret StoddardCOM & MFR Electrical Service Inspection
12/12/2014PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
03/17/2015PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Fire Inspection Type
12/10/2014PassDale PickeringFire Sprinkler Rough-in
01/13/2015PassDale PickeringFire Sprinkler Hydro
03/19/2015PassBret StoddardFire Alarm Final Inspection
Page 2 of 3
(Continued)
Permit Details Permit Number: 12-00401
Mesa Falls Apts Bldg #14
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 8:49 am
Permit
Inspection
Summary
Mechanical Inspection Type
12/15/2014PassDon AllenHVAC Rough-in
Gas presser held at 70 lb on all 24 apt.Inspector Comments:
03/19/2015PassDon AllenHVAC Final Inspection
All good for the c/oInspector Comments:
Plumbing Inspection Type
08/29/2014PassDon AllenPlumbing Underground Inspection
12/15/2014PassDon AllenPlumbing Rough-in
03/20/2015PassDon AllenPlumbing Final Inspection
Good for c/oInspector Comments:
Page 3 of 3