HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00400 - Mesa Falls Apts Bldg #15Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/14/2020 8:12 am
Permit Details Permit Number: 12-00400
Mesa Falls Apts Bldg #15
940 S 5th W
New Multi-Family Residence
Permit Issued Date: 02/26/2014
Permit Inspection Statistics
30Total Inspections Completed:
22Total Inspections Passed:
Inspection Pass Rate: 73.33%
Permit Inspection History *Refer to Individual Inspection Report for more Details
05/24/2013PassDale PickeringFire Underground Inspection
underground hydro - pass on buildings 6,1,15 & 16.Inspector Comments:
Building Inspection Type
11/27/2012PassQuinton OwensFoundation Inspection
11/26, QO: Middle section - 2 #4 horiz & #4 vert's at 32"oc.
11/27, QO: East & West section (same)
Inspector Comments:
05/09/2013FailQuinton OwensFraming/Structure Inspection
Sheathing a few spots missed (marked with orange paint) Submit design change
on bldg straps. Studs to be 24" oc max.
Inspector Comments:
05/16/2013PassQuinton OwensFraming/Structure Inspection
3 spots missed, ok to wrap after fixing above locations.Inspector Comments:
06/04/2013FailQuinton OwensFraming/Structure Inspection
6/4: Fire separation needed at concealed locations on ceiling or fire rated walls.
Fire dampers on ceiling vents. Backing for HC grab bars. Some stud spacing
greater than 24". Firecaulking and fireblking at top & bottom plates. Fire
separation at tub drains (upper flrs). Some washer boxes (not rated) in rated
partitions. Interior shear or bearing walls? Would require anchors with square
washers as on exterior walls.
Inspector Comments:
06/14/2013FailQuinton OwensFraming/Structure Inspection
Framing Pre Insulation - 6/14,QO: Finish firecaulk and fireblock as required
Exterior ok to insulate. Need to inspect concealed openings at ceiling/floor for
rated separation
Inspector Comments:
06/18/2013PassQuinton OwensFraming/Structure Inspection
6/18: Ok to drywall except at concealed locations for inspection of rated
separation.
Inspector Comments:
06/18/2013FailQuinton OwensInsulation Inspection
6/18: 3rd floor- R19 in walls,windows U=0.32, doors and windows sealed.
Insulate headers.
6/18L Leave concealed locations at floor and ceiling open for inspection of
firetaing.
Action required: need 3/8" gap around pvc pipe through plates for fire caulk.
Inspector Comments:
6/19: No ready for inspection. *did not inspect.Inspector Comments:
Page 1 of 4
(Continued)
Permit Details Permit Number: 12-00400
Mesa Falls Apts Bldg #15
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 8:12 am
Permit
Inspection
Summary
06/20/2013PassQuinton OwensInsulation Inspection
6/20: 2nd Flr - Insulation good.Inspector Comments:
6/20,QO: 2nd floor Insulation approved (same as 3rd level, flr/clg blown
fiberglass)
Inspector Comments:
06/21/2013PassQuinton OwensInsulation Inspection
6/21,QO: 1st flr insulation approved (same as 2nd level)Inspector Comments:
06/27/2013PassQuinton OwensSheetrock/Drywall Inspection
6/25: 4 units approved for taping. Do not cover concealed fire separations until
inspected.
6/26,QO: 204,102,101 approved for taping.(104 and west side to be inspected)
6/27,QO: 104, and west side 1st floor approved.
Inspector Comments:
9/9 TD - 103 - opening behind dry on party wall need caulk.
206 - fire caulk around dryer vent.
Inspector Comments:
9/10 TD - 203 - opening behind dryer needs fire caulk & sheetrocked.
All 3's and 6's need sheet rock on sides, if not a round hold around dryer vent,
fire caulk corners.
Inspector Comments:
9/10,QO: remove clips on sprinkler heads in furnace closets
(308,305,205,207,208,108,107,106 & 204)
Inspector Comments:
09/11/2013FailQuinton OwensBuilding Final
9/11, QO: Dryer vent boxes not rated yet. 103-sheetrock at gap. 203-Firecaulk
around PVC pipe. 306-Firecaulk corners at vent. 303-sheetrock over gap.
206-Firecaulk corners at vent and small gap in back of box.
Inspector Comments:
10/02/2013PassQuinton OwensBuilding Final
12/17/2013PassQuinton OwensFooting Inspection
11/21, QO: East & Middle section - 2, #4 bar cont. (spot ftgs 3 ea way) 2 Ufers
installed.
11/26 West section (same) with 2 Ufer ground bars installed.
12/20: Middle section interior footings - 2, #4 rebar supported on chairs. Ground
blanketed prior.
Inspector Comments:
Page 2 of 4
(Continued)
Permit Details Permit Number: 12-00400
Mesa Falls Apts Bldg #15
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 8:12 am
Permit
Inspection
Summary
Electrical Inspection Type
06/10/2013PassBret StoddardCommercial Electrical Rough-in
Approved for cover in the entire building-24 units-the electrical contractor needs
to add receptacles on the short walls in the end units in the bedroom, will
re-inspect this on the electrical service inspection. Fire alarm wiring and electrical
wiring on the same inspection.
Inspector Comments:
06/26/2013PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power-2 services.Inspector Comments:
09/06/2013PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a temporary C.O. in the entire building. Closet lights are to close to
the shelving and are not fully enclosed, breezeway lights are not damp location
rated, call for a re-inspect when ready for a full final and C.O.
Inspector Comments:
10/03/2013PassQuinton OwensCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O. building #15 only.Inspector Comments:
Fire Inspection Type
09/09/2013Pass Fire Department Final Inspection
"riser room" not identified, knox box key, head covered in 15103, head
replacement 15204, 15201
notification incomplete in 15302, 15304
Inspector Comments:
09/10/2013PassQuinton OwensFire Alarm Final Inspection
Approved for a final and C.O.-fire alarm system. Witnessed all initiating and
signalling devices operation, witnessed 24hour 5 minute test, test/certification
report from Omni is in file-As per Quinton.
Inspector Comments:
Mechanical Inspection Type
06/04/2013FailQuinton OwensHVAC Rough-in
Fire damper at ceiling penetrations.Inspector Comments:
07/12/2013PassQuinton OwensHVAC Rough-in
Bath vents - added fire dampers and fire caulkInspector Comments:
09/10/2013FailQuinton OwensHVAC Final Inspection
Need fire dampers on return air vents 201,202,101,102,104,208,107,108. 1"
clearance (all) and rate penetrations (ceiling) around B-vent. Slope condensate
DOWN to drain (203).
10/2,QO: F. damprs done except 201,208,108.
Inspector Comments:
10/03/2013PassQuinton OwensHVAC Final Inspection
Page 3 of 4
(Continued)
Permit Details Permit Number: 12-00400
Mesa Falls Apts Bldg #15
940 S 5th W
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 02/14/2020 8:12 am
Permit
Inspection
Summary
Plumbing Inspection Type
12/11/2012PassDon AllenPlumbing Underground Inspection
partial ground - all good to cover groundworkInspector Comments:
12/14/2012PassDon AllenPlumbing Underground Inspection
all good to cover ground workInspector Comments:
09/03/2013FailDon AllenPlumbing Final Inspection
need to have 6" of clearnce around the water heater vents
need to hook up the manifold on the main water room
Inspector Comments:
09/18/2013PassDon AllenPlumbing Final Inspection
approved for c/oInspector Comments:
09/24/2013PassDon AllenPlumbing Rough-in
7/12,QO: 108 & 205 bath fans done. (Return air dampers for final not done yet)Inspector Comments:
09/24/2013PassDon AllenPlumbing Sewer
Page 4 of 4