HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00364 - LDS Rexburg 19th Stake - New BuildingPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/13/2020 2:29 pm
Permit Details Permit Number: 12-00364
LDS Rexburg 19th Stake - New Building
2332 W 2000 S
New Commercial Building
Permit Issued Date: 08/04/2014
Permit Inspection Statistics
27Total Inspections Completed:
22Total Inspections Passed:
Inspection Pass Rate: 81.48%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
10/03/2012PassQuinton OwensCommercial Footing Inspection
Spot footings approx. 8" oc ea way. 3 bars cont. front and partial side.
2 bars cont. in back and partial side
Verticals about 16" oc
11/5 North interior footings OK
Inspector Comments:
10/12/2012PassPLL ADMINFoundation Inspection
As per Jon Berry. Foundation and rebar look good.Inspector Comments:
03/05/2013PassQuinton OwensCommercial Framing/Structure Inspection
Hold downs ok. Sheathing (staples 3 to 4" in field, more on edges) ok. Joist
hangers nailed (finish lobbies). Anchor bolts tightened (w/ large washers) ok.
NEED SOME BLOCKING ON MECHANICAL LEVEL (any walls over 10 ft)
Inspector Comments:
03/27/2013PassQuinton OwensCommercial Insulation Inspection
3/20: East side ceiling, R38 batts.
3/25: Ceiling insulation all but Mech room and some gables: some locations
missed or have gaps.
3/27: Remaining insulation over mechanical room and gables (entry & mech) -
approved.
Inspector Comments:
05/07/2013PassQuinton OwensCommercial Sheetrock/Drywall Inspection
4/18,QO: Chapel area ok to tape.
4/30,QO: (Exterior classrooms and hall) Several locations missed on ceiling and
walls.
5/6,QO: Bathrooms and remaining classrooms and previous items are done
(Stage area left)
5/7,QO: Last of drywall completed.
Inspector Comments:
09/06/2013FailQuinton OwensCommercial Building Final
Parking and paving not done. Restroom dispensers not installed. Handrails to
mech room are too low. Sprinkler heads covered at north and south end attic. Fix
& seal exhaust pipe on far right furnace on mech platform. Covered return air
vents terminate under cabinets? One exit sign in primary room not working.
Verifying non-direct venting of instant water heater. Seal hole on top side of
furnace (NE end)
Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 12-00364
LDS Rexburg 19th Stake - New Building
2332 W 2000 S
New Commercial Building
Permit Status of (Open) as of Report Date: 02/13/2020 2:29 pm
Permit
Inspection
Summary
09/26/2013PassQuinton OwensCommercial Building Final
9/17: Parking lot not done yet. Toilet paper dispensers not located per ANSI 117
(2003)
9/26,QO: Final completed.
Inspector Comments:
Electrical Inspection Type
10/30/2012PassBret StoddardElectrical Underground Inspection
Groundwork/ Uffer - Approved to backfill throughout the building.Inspector Comments:
06/11/2013PassBret StoddardCommercial Electrical Rough-in
3/13/13 - Approved for cover in all exterior walls only.
3/27/13 - approved cover in/outside portions classroom
4/4/13 - Approved for cover-all except gym area done-as per Jane Shaw.
4/9/13 - Approved for cover in the corridors, primary room, relief society room
and bathrooms on the north end of building. Also inspected the fire alarm wiring
throughout the building as well-Approved for cover-no seperate ticket was
written for this.
4/18/13 - Approved for cover-classrooms around the perimeter of
building-ceilings only.
4/24/13 - Approved for cover in the primary room and the platform area ceilings.
6/11/13 - Approved for cover under the rostrum conduits and north side storage
shed, inspected the electrical service on this inspection also and no seperate
ticket was written.
Inspector Comments:
06/11/2013PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power-inspected the electrical service
on the rough-in inspection for the rostrum.
Inspector Comments:
08/15/2013FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Storage shed not inspected-concrete being poured, energy recovery units have
breakers to large for nameplate ratings, drinking fountains not GFCI protected
and must be, outside receptacles not weather rated, call for a re-inspect when
ready.
Inspector Comments:
08/27/2013FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Lift not wired for platform, call for a re-inspect when ready.Inspector Comments:
09/05/2013PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.-lift inspected by DBS.Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 12-00364
LDS Rexburg 19th Stake - New Building
2332 W 2000 S
New Commercial Building
Permit Status of (Open) as of Report Date: 02/13/2020 2:29 pm
Permit
Inspection
Summary
Fire Inspection Type
04/09/2013PassBret StoddardFire Alarm Rough-in
See rough-in inspection for electrical inspection-no seperate ticket was written.Inspector Comments:
04/19/2013PassDale PickeringFire Sprinkler Hydro
200 PSI from 11:10-1:20. OK to cover.Inspector Comments:
08/27/2013FailBret StoddardFire Alarm Final Inspection
Not monitored with phone line, index not in panel, need report from Peak Alarm
before final completion, blank cover missing on east side, wire needs strapped in
west side of mezanine deck area, witnessed 24 hour/5 minute test from 10:31AM
8/26 to 10:31AM 8/27, AC power restored at 10:44AM 8/27, flow switch operated
in 41 seconds for water gong, witnessed operation of all devices on system, call
for a re-inspect when these items are done.
Inspector Comments:
08/30/2013PassBret StoddardFire Alarm Final Inspection
Approved for a final and C.O. for fire alarm only, verified dispatch was called
(Wes), items from previous inspection are done.
Inspector Comments:
10/21/2013PassDale PickeringFire Underground Inspection
10/21/13 - Fire sprinker as well.Inspector Comments:
10/21/2013PassDale PickeringFire Sprinkler Final Inspection
10/21/2013PassDale PickeringFire Department Final Inspection
Mechanical Inspection Type
08/28/2013FailQuinton OwensHVAC Final Inspection
Seal holes on Dir. vent Furnaces. Instant Hot water heater installed as non-direct
vent - Need to verify special requirements for approval (Model NRC1111-DV).
Inspector Comments:
9/17: Grid cover missing as part of approved intake for water heater.Inspector Comments:
08/20/2014PassQuinton OwensHVAC Final Inspection
Due to C/O being issued, we can now sign off on this milestone.
*approved*
Inspector Comments:
Plumbing Inspection Type
10/31/2012PassDon AllenPlumbing Underground Inspection
All good to cover groundwork.Inspector Comments:
09/03/2013PassDon AllenPlumbing Sewer
09/03/2013PassDon AllenPlumbing Water
09/03/2013PassDon AllenPlumbing Rough-in
09/03/2013PassDon AllenPlumbing Final Inspection
All good for C/OInspector Comments:
Page 3 of 3