HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00307 - 626 Tanglewood Dr - SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 02/11/2020 1:11 pm
Permit Details Permit Number: 12-00307
626 Tanglewood Dr - SFR
626 Tanglewood Dr
New Single Family Residence
Permit Issued Date: 06/26/2014
Permit Inspection Statistics
23Total Inspections Completed:
19Total Inspections Passed:
Inspection Pass Rate: 82.61%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
07/25/2012PassPLL ADMINFooting Inspection
Layout looks good.
Footing and Rebar ok
As per Jon Berry.
Inspector Comments:
07/26/2012PassBret StoddardFoundation Inspection
Approved to place concrete for the foundation-2 #4 rebars installed at the top
portion of the walls and the rest of the rebar is spaced on 2 foot center grid, ufer
is installed next to the conduits.
Inspector Comments:
11/15/2012PassQuinton OwensSheeting
Hold downs nailed
Sheathing approved.
OK to cover.
Inspector Comments:
11/16/2012FailQuinton OwensFraming/Structure Inspection
Truss details do not match installed trusses.
Anchor bolts needed in bsmt bearing walls.
A35 ties missing at cantilevers (per engineer)
ties for trusses at bay windows missing.
Inspector Comments:
11/29/2012PassQuinton OwensFraming/Structure Inspection
11/21 basement framing (bdrm & family room)
11/29 - Items for reinspect completed.
Inspector Comments:
11/29/2012PassQuinton OwensInsulation Inspection
Wndw U-factor=.34; R-19 in basement. Wndws & doors sealed.Walls blown
fiberglass.
1" clearance req'd between B-vent and insulation.
Inspector Comments:
12/11/2012PassQuinton OwensSheetrock/Drywall Inspection
12/11: living space approved; Garage not done.Inspector Comments:
12/13/2012PassQuinton OwensSidewalk Inspection
7/12/13 - Sidewalk finished. Approved as per Tedd Dye.Inspector Comments:
02/06/2013PassQuinton OwensBuilding Final
Page 1 of 2
(Continued)
Permit Details Permit Number: 12-00307
626 Tanglewood Dr - SFR
626 Tanglewood Dr
New Single Family Residence
Permit Status of (Open) as of Report Date: 02/11/2020 1:11 pm
Permit
Inspection
Summary
Electrical Inspection Type
08/22/2012PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power.Inspector Comments:
11/16/2012PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover-unfinished basement entirely.Inspector Comments:
11/26/2012PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover in the basement bedroom and living room-west side of the
stairs room is not wired.
Inspector Comments:
02/06/2013PassQuinton OwensSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Approved for a final and C.O.-west room in the basement is not finished, the
remaining portions are finished, no A/C unit was installed-15A breaker was
installed for it.
Inspector Comments:
Mechanical Inspection Type
11/16/2012PassQuinton OwensHVAC Rough-in
02/06/2013PassQuinton OwensHVAC Final Inspection
Plumbing Inspection Type
02/06/2012FailDon AllenPlumbing Final Inspection
-Need to clean out bottom of meter pit, need to see curb stop.
-Need to fix centers waist under kitchen sink (change out slip gaskets) (no tape)
-Need to cut 30'' clean clearance in grunt of water heater.
Inspector Comments:
02/08/2012PassDon AllenPlumbing Final Inspection
All good for the c/o.Inspector Comments:
07/30/2012FailDon AllenPlumbing Underground Inspection
sewer and warter need a 10 foot searpationInspector Comments:
08/16/2012PassPLL ADMINPlumbing Sewer
Sewer looks good as per Nathan Wood.Inspector Comments:
08/16/2012PassPLL ADMINPlumbing Water
Water looks good.
As per Nathan Wood.
Inspector Comments:
08/16/2012PassPLL ADMINPlumbing Underground Inspection
As per Nathan Wood.Inspector Comments:
11/16/2012FailDon AllenPlumbing Rough-in
toilet in the master bath is over 135 deg. with no cleanoutInspector Comments:
11/27/2012PassDon AllenPlumbing Rough-in
Rough in is good to cover.Inspector Comments:
Page 2 of 2