Permit Status of (Open) as of Report Date: 02/03/2020 4:47 pm
Permit Details Permit Number: 12-00244
Pizza Hut, Rigby - Tenant Finish
205 Stockhman Blvd. Ste A-1 - Rigby
Commercial Tenant Finish Rigby
Permit Issued Date: 06/18/2014
Permit Inspection Statistics
15Total Inspections Completed:
14Total Inspections Passed:
Inspection Pass Rate: 93.33%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
07/12/2012PassQuinton OwensFraming/Structure Inspection
7/6 QO: Fire rated wall not required above ceiling.(based on all B-occupancies,
typ). 5/8" drywall installed up to roof deck anyway on Pizza Hut side.
7/12 QO: framing ok
Inspector Comments:
07/17/2012PassQuinton OwensInsulation Inspection
7/9, QO: R-19 Insulation installed behind Cooler location (NW corner)
7-17, QO: Walls R-19 done.
Inspector Comments:
07/18/2012PassQuinton OwensSheetrock/Drywall Inspection
Drywall OK to tape.Inspector Comments:
08/09/2012PassPLL ADMINInsulation Inspection
8/1 Duct Insulation - JB - Grease duct fire wrap looks good.
HVAC ducting looks good
3in fire barrier.
8/9 insulation completed
As per Jon Berry.
Inspector Comments:
09/05/2012PassPLL ADMINBuilding Final
Bldg final completed
As per Jon Berry.
Inspector Comments:
Page 1 of 2
(Continued)
Permit Details Permit Number: 12-00244
Pizza Hut, Rigby - Tenant Finish
205 Stockhman Blvd. Ste A-1 - Rigby
Commercial Tenant Finish Rigby
Permit Status of (Open) as of Report Date: 02/03/2020 4:47 pm
Permit
Inspection
Summary
Electrical Inspection Type
07/13/2012PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
Approved for cover-need to strap up the MC cabling through out the ceiling-will
re-inspect on the final through the ceiling tile.
Inspector Comments:
08/09/2012FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Panels not labeled, time clock needs a connector installed to protect wires, GFCI
protection required for receptacles within 6' from the edge of the sink(3), 60A
breaker installed in panel for A/C units and the units show a 50A max, signs are
UL listed and labeled and have disconnects installed on the sides of each sign,
call for a re-inspect when ready.
Inspector Comments:
08/10/2012PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.Inspector Comments:
Fire Inspection Type
09/05/2012PassPLL ADMINFire Department Final Inspection
as per Jon Berry.Inspector Comments:
Mechanical Inspection Type
08/01/2012PassPLL ADMINHVAC Rough-in
HVAC ducting looked good. Quinton checked insulation and grease ducting both
hoods. (7/30)
Grease duct insulation looked good. 2 layers 3M on both hoods.
As per Jon Berry.
Inspector Comments:
Plumbing Inspection Type
07/16/2012PassDon AllenPlumbing Underground Inspection
7/5/12 DA: all good to cover.Inspector Comments:
08/10/2012PassDon AllenPlumbing Rough-in
All good to cover.Inspector Comments:
08/10/2012PassDon AllenPlumbing Final Inspection
All good for the C/O.Inspector Comments:
08/10/2012PassDon AllenPlumbing Sewer
08/10/2012PassDon AllenPlumbing Water