Permit Status of (Open) as of Report Date: 01/23/2020 8:12 am
Permit Details Permit Number: 12-00201
374 E 4th N - Dr. Andy Summers Orthodontics
374 E 4th N
New Commercial Building
Permit Issued Date: 07/23/2014
Permit Inspection Statistics
25Total Inspections Completed:
22Total Inspections Passed:
Inspection Pass Rate: 88.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
07/12/2012PassPLL ADMINCommercial Footing Inspection
As per Jon Berry. Looked goodInspector Comments:
07/16/2012PassPLL ADMINFoundation Inspection
As per Jon Berry. ok
7/26 foundation re-pour ok
Inspector Comments:
10/09/2012PassPLL ADMINCommercial Framing/Structure Inspection
As per Jon Berry.
8/13 Exterior sheathing and shearwalls ok to cover.
10/9 east wall south end needs type x drywall due to property line
Inspector Comments:
10/09/2012PassPLL ADMINCommercial Insulation Inspection
As per Jon Berry. Exterior wall insulation OK to cover after drying.Inspector Comments:
10/16/2012PassPLL ADMINCommercial Sheetrock/Drywall Inspection
As per Jon Berry. Drywall OK to cover.Inspector Comments:
12/06/2012PassQuinton OwensSidewalk Inspection
Done (unsure of any inspection?)Inspector Comments:
12/06/2012FailQuinton OwensCommercial Building Final
Building Address #'s missing. Finish front handrails.(ramp & steps). South steps
approved w/out handrail per Jon B. (Contr. told would be ok, but shown on
plans). Toilet paper dispenser not in (back ordered). Brett Jensen informed of
location requirements - no reinspect of T.P. holder required. Handrail required.
Inspector Comments:
02/07/2013FailQuinton OwensCommercial Building Final
Only one handrail installed. Non-public entrance (no exception found in IBC); 2nd
handrail per plans needed and required for commercial.
Inspector Comments:
02/25/2013PassQuinton OwensCommercial Building Final
Page 1 of 3
(Continued)
Permit Details Permit Number: 12-00201
374 E 4th N - Dr. Andy Summers Orthodontics
374 E 4th N
New Commercial Building
Permit Status of (Open) as of Report Date: 01/23/2020 8:12 am
Permit
Inspection
Summary
Electrical Inspection Type
10/04/2012PassBret StoddardCommercial Electrical Rough-in
Approved for cover-also inspected the service on this inspection.Inspector Comments:
10/04/2012PassBret StoddardCOM & MFR Electrical Service Inspection
7/16/12 - As per Jon Berry. 20' rebar uffer installed.
10/4/12 - Approved to be energized for permanent power-inspected the service
on the rough-in therefore no seperate inspection ticket was written for the
service.
Inspector Comments:
12/06/2012FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Wire in the vacuum room needs blank cover, need to strap A/C unit conduits, air
compressor needs to be on smaller breaker-20A, GFCI protection required for
receptacle next to the sink in the break room, blank covers needed for the lights
outside(3), sign not complete, call for a re-inspect when ready.
Inspector Comments:
02/13/2013PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.Inspector Comments:
Fire Inspection Type
10/18/2012PassPLL ADMINFire Underground Inspection
As per Jon Berry. N/AInspector Comments:
10/18/2012PassPLL ADMINFire Alarm Rough-in
As per Jon Berry. N/AInspector Comments:
10/18/2012PassPLL ADMINFire Department Final Inspection
As per Jon Berry. N/AInspector Comments:
10/18/2012PassPLL ADMINFire Sprinkler Final Inspection
As per Jon Berry, N/AInspector Comments:
10/18/2012PassPLL ADMINFire Alarm Final Inspection
As per Jon Berry: N/AInspector Comments:
Mechanical Inspection Type
10/09/2012PassPLL ADMINHVAC Rough-in
As per Jon Berry.Inspector Comments:
12/06/2012PassQuinton OwensHVAC Final Inspection
Page 2 of 3
(Continued)
Permit Details Permit Number: 12-00201
374 E 4th N - Dr. Andy Summers Orthodontics
374 E 4th N
New Commercial Building
Permit Status of (Open) as of Report Date: 01/23/2020 8:12 am
Permit
Inspection
Summary
Plumbing Inspection Type
10/15/2012PassDon AllenPlumbing Underground Inspection
10/15/2012PassDon AllenPlumbing Rough-in
All good to cover the plumbingInspector Comments:
12/14/2012PassDon AllenPlumbing Sewer
12/14/2012PassDon AllenPlumbing Water
12/14/2012PassDon AllenPlumbing Final Inspection
All good for C/OInspector Comments: