HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00199 - 760 Griffin St - SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 01/22/2020 10:39 am
Permit Details Permit Number: 12-00199
760 Griffin St - SFR
760 Griffin St
New Single Family Residence
Permit Issued Date: 07/23/2014
Permit Inspection Statistics
22Total Inspections Completed:
17Total Inspections Passed:
Inspection Pass Rate: 77.27%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
05/17/2012PassPLL ADMINResidential Footing Inspection
As per Jon Berry. Footings and rebar look good.Inspector Comments:
05/17/2012PassQuinton OwensFoundation Inspection
Missing 2nd bar in top 12" of bsmt wall. (completed at 7:30, QO)Inspector Comments:
06/22/2012PassPLL ADMINResidential Framing/Structure Inspection
As per Jon Berry.
6/22/12- Framing ok gasline union in garage will need access door.
6/14/12 - Sheathing stapled 3-4" on edges and 6" in field. Finish nailing tie down
in back of house (6-14,QO)
Inspector Comments:
06/28/2012FailQuinton OwensResidential Insulation Inspection
clearance required around B-vent. Basement windows not sealed. Main floor
windows have gaps/holes in foam seal.
Inspector Comments:
06/28/2012PassQuinton OwensResidential Insulation Inspection
07/02/2012PassQuinton OwensCommercial Sheetrock/Drywall Inspection
Drywall ok to tape.Inspector Comments:
08/08/2012PassPLL ADMINSidewalk Inspection
As per Jon Berry.Inspector Comments:
08/13/2012PassQuinton OwensResidential Building Final
Bldg ok
Smoke at bottom of stairs ?????
Inspector Comments:
Page 1 of 2
(Continued)
Permit Details Permit Number: 12-00199
760 Griffin St - SFR
760 Griffin St
New Single Family Residence
Permit Status of (Open) as of Report Date: 01/22/2020 10:39 am
Permit
Inspection
Summary
Electrical Inspection Type
05/29/2012FailBret StoddardResidential Electrical Service Inspection
Meter not mounted or ready, call for a re-inspect when ready.Inspector Comments:
05/30/2012FailBret StoddardResidential Electrical Service Inspection
Meter not mounted or ready, call for a re-inspect when ready.Inspector Comments:
05/31/2012PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power.Inspector Comments:
06/22/2012PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover-unfinished basement.Inspector Comments:
08/08/2012PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Approved for a final and C.O.-unfinished basement entirely-A/C unit not installed-
(30A OCPD).
Inspector Comments:
Mechanical Inspection Type
06/22/2012PassPLL ADMINHVAC Rough-in
As per Jon Berry. Gasline union in garage will need access cover.Inspector Comments:
08/08/2012FailPLL ADMINHVAC Final Inspection
As per Jon Berry. Water hearer and furnace not completed. Move insulation from
water heater vent. Thermostat not installed.
Inspector Comments:
08/13/2012PassQuinton OwensHVAC Final Inspection
Previous items per JB completed: B vent clearance, thermostat done, Furnace
installed.
Inspector Comments:
Plumbing Inspection Type
05/22/2012FailDon AllenPlumbing Underground Inspection
Water line needs to be moved 10' away from the sewer line.Inspector Comments:
06/04/2012PassDon AllenPlumbing Underground Inspection
5/24/12 - All good.
6/4/12 - 20#
Inspector Comments:
08/06/2012PassDon AllenPlumbing Sewer
08/06/2012PassDon AllenPlumbing Water
08/06/2012PassDon AllenPlumbing Rough-in
All good to cover.Inspector Comments:
08/06/2012PassDon AllenPlumbing Final Inspection
All good for the C/OInspector Comments:
Page 2 of 2