HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00132 - 600 Tanglewood Dr - SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 01/09/2020 4:26 pm
Permit Details Permit Number: 12-00132
600 Tanglewood Dr - SFR
600 Tanglewood Dr
New Single Family Residence
Permit Issued Date: 07/17/2014
Permit Issued Date: 10/26/2012
Permit Inspection Statistics
26Total Inspections Completed:
17Total Inspections Passed:
Inspection Pass Rate: 65.38%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
04/16/2012PassQuinton OwensFooting Inspection
Basement ftg approved (4/16, QO)- rebar supported (must have 3" clearance
underneath)
Inspector Comments:
05/22/2012PassQuinton OwensFoundation Inspection
4/24/12 - Basement foundation needs 2 rebar in top 12" of wall. Rebar spacing
OK. Extra full length rebar on site. (call attempted, left message 4/25, QO)
4/26 AM: foundation poured , no more rebar on site, assumed used in top of
foundation.
5/22/12 - Garage: rebar verticals 48" oc horizontal 2 ft oc
Inspector Comments:
07/26/2012FailPLL ADMINFraming/Structure Inspection
As per Jon Berry.
Attic stairs are not per code R/T
add header under trusses at attic stairs
Add 2 studs under girder trusses at attic stairs
Maintain 6'-8" headroom for attic stairs.
Add stud by light at bottom of basement stairs under header.
Inspector Comments:
07/30/2012FailQuinton OwensFraming/Structure Inspection
Open up roof vents in attic. Items done except stairs to attic. (no decision on fix)
- no door at bottom without landing. OK to insulate.
Inspector Comments:
08/07/2012PassQuinton OwensFraming/Structure Inspection
Stairs to attic corrected.Inspector Comments:
08/07/2012PassQuinton OwensSheetrock/Drywall Inspection
Finish garage common wall. Add screws to missed locations in house as
indicated.
Inspector Comments:
09/11/2012FailQuinton OwensSidewalk Inspection
only 3-4" base. 6" required.Inspector Comments:
09/12/2012PassQuinton OwensSidewalk Inspection
OK to pour. 6" baseInspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 12-00132
600 Tanglewood Dr - SFR
600 Tanglewood Dr
New Single Family Residence
Permit Status of (Open) as of Report Date: 01/09/2020 4:26 pm
Permit
Inspection
Summary
10/18/2012FailQuinton OwensBuilding Final
House #'s needed. Handrail needed for lower section of basement stairs. Back
steps not approved (key lock door from inside). CO detector outside bedrooms.
5/8" drywall separation on garage side to floor. Egress ladder or 44" max deep
window well (at least 1)
Bonus room: light switch at top of stairs, handrail, guardrail, window not
tempered at top of stairs.
Inspector Comments:
10/19/2012PassQuinton OwensBuilding Final
Room above garage not to be used for any purpose until approved (see
conditions)
Inspector Comments:
12/04/2012PassSAUREY AMANDAInsulation Inspection
Blown Cellulose in walls; ICF foundation; Attic vents maintained through bonus
room ceiling.
Add insulation to thin areas of floor perimeter. Floor over garage still to insulate.
Seal around basement windows.
Inspector Comments:
Electrical Inspection Type
06/25/2012PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power.Inspector Comments:
07/26/2012FailBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Outlets not installed upstairs, floor outlet required by railing, inter-system
bonding termination required by main panel, tamper resistant receptacles
required throughout the residence for the final, garage door opener does not
have a receptacle installed, some items are notes for the final as a reminder as
per the request of the owner, unfinished basement, call for a re-inspect when
ready.
Inspector Comments:
08/03/2012PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover-main level, unfinished basement and bonus room.Inspector Comments:
10/11/2012FailBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
GFCI protection required in the laundry room by the sink and any basement
receptacles, intersystem bonding termination required by the main panel, fridge
has reversed polarity, spark rings required for devices in the kitchen behind
cabinets (3), need to cover the NM cable in the cabinet on the peninsula and
install a TR receptacle, open ground on the receptacles in the entry and front
bedroom, closet light to close to the shelving in the master closet, shower trim is
not rated for shower installation, cover needed for the switch in the hallway in
the basement, call for a re-inspect when ready.
Inspector Comments:
10/12/2012PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Approved for a final and C.O.-unfinished basement.Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 12-00132
600 Tanglewood Dr - SFR
600 Tanglewood Dr
New Single Family Residence
Permit Status of (Open) as of Report Date: 01/09/2020 4:26 pm
Permit
Inspection
Summary
Mechanical Inspection Type
07/30/2012PassQuinton OwensHVAC Rough-in
Mech rough in approved.Inspector Comments:
10/10/2012FailQuinton OwensHVAC Final Inspection
Strap water heater at upper and lower thirds.
High eff. furnace: cap holes on side to seal comb. chamber.
Seal ends of R.A. floor plenums.
Inspector Comments:
10/18/2012PassQuinton OwensHVAC Final Inspection
Plumbing Inspection Type
05/07/2012FailDon AllenPlumbing Rough-in
need to put backflow device on basement toilet, bathtub, and floor drain.Inspector Comments:
05/14/2012PassDon AllenPlumbing Sewer
05/14/2012PassDon AllenPlumbing Water
Check back water valves. All good to cover.Inspector Comments:
05/14/2012PassDon AllenPlumbing Underground Inspection
07/30/2012PassDon AllenPlumbing Rough-in
all good to cover the rough in.Inspector Comments:
10/11/2012FailDon AllenPlumbing Final Inspection
Need shut off valve on cold side of water heater.Inspector Comments:
10/19/2012PassDon AllenPlumbing Final Inspection
All good for C/OInspector Comments:
Page 3 of 3