HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00111 - 820 W 7th S - Rockwell Court Apts Bldg #9Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 01/06/2020 12:02 pm
Permit Details Permit Number: 12-00111
820 W 7th S - Rockwell Court Apts Bldg #9
820 W 7th S
New Multi-Family Residence
Permit Issued Date: 04/02/2014
Permit Inspection Statistics
22Total Inspections Completed:
18Total Inspections Passed:
Inspection Pass Rate: 81.82%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
02/14/2013PassQuinton OwensFooting Inspection
Rebar (3) #4 cont
supported w. clearances
ok to pour
Spec. insp. on site.
Inspector Comments:
02/15/2013PassQuinton OwensFoundation Inspection
Ufer installed. 4 #4 horiz. bars & Vert #4 at 16" ocInspector Comments:
04/18/2013FailQuinton OwensSheeting
sheer wall - exterior walls - missed locations - marked with crayon on studs.
(to be reinspected with framing).
Inspector Comments:
05/08/2013PassQuinton OwensSheeting
05/08/2013PassQuinton OwensFraming/Structure Inspection
OK to Insulate.Inspector Comments:
05/10/2013PassQuinton OwensInsulation Inspection
R-21 in walls
R-11 in floors (sound) and party walls
Windows V-.30
Vent Baffles in
Attic Duct = R-8
Inspector Comments:
5/22,QO: 2nd floor approved. Noted to fasten drywall 24" max o.c. at each stud.Inspector Comments:
05/28/2013PassQuinton OwensSheetrock/Drywall Inspection
5/28,QO: Main level doneInspector Comments:
07/15/2013FailQuinton OwensBuilding Final
Pull insulation back from crwl spc vents.Inspector Comments:
07/25/2013PassQuinton OwensBuilding Final
Page 1 of 2
(Continued)
Permit Details Permit Number: 12-00111
820 W 7th S - Rockwell Court Apts Bldg #9
820 W 7th S
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 01/06/2020 12:02 pm
Permit
Inspection
Summary
Electrical Inspection Type
05/08/2013PassBret StoddardCommercial Electrical Rough-in
Approved for cover-SER cable is not installed yet-will inspect on the service
inspection.
Inspector Comments:
05/20/2013PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power-5 meters.Inspector Comments:
07/24/2013PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.-inspected this building entirely on 7/18, this is a
re-inspect.
Inspector Comments:
Fire Inspection Type
05/02/2013PassDale PickeringFire Sprinkler Rough-in
900 - 1000 -200 psi
ok to cover.
Inspector Comments:
07/24/2013PassBret StoddardFire Alarm Final Inspection
Approved for a final and C.O.-witnessed fire alarm test 24 hour 5 minute, flow
test-35 seconds, DB witnessed at 80 DB at pillow level in bedrooms, smoke
detectors tested, final report from fire alarm contractor is in permit 12-103.
Inspector Comments:
Mechanical Inspection Type
05/02/2013FailQuinton OwensHVAC Rough-in
firecaulk around dryer vents jpenetrating floor/ceiling assemblies.
finish dryer vent in lower right unit
firecaulk all holes in lower level bath fans.
Inspector Comments:
05/10/2013PassQuinton OwensHVAC Rough-in
07/15/2013PassQuinton OwensHVAC Final Inspection
mech final OKInspector Comments:
Plumbing Inspection Type
05/28/2013PassDon AllenPlumbing Rough-in
5/7/13 DA: 900 all good to cover rough in.Inspector Comments:
07/09/2013PassDon AllenPlumbing Water
Good to cover water line for apt. 1,2,3,7,8,9,Inspector Comments:
07/15/2013FailDon AllenPlumbing Final Inspection
07/19/2013PassDon AllenPlumbing Sewer
07/19/2013PassDon AllenPlumbing Final Inspection
Page 2 of 2