HomeMy WebLinkAboutINSPECTION SUMMARY - 12-00107 - 820 W 7th S - Rockwell Court Apts Bldg #5Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 01/03/2020 11:36 am
Permit Details Permit Number: 12-00107
820 W 7th S - Rockwell Court Apts Bldg #5
820 W 7th S
New Multi-Family Residence
Permit Issued Date: 04/02/2014
Permit Inspection Statistics
24Total Inspections Completed:
22Total Inspections Passed:
Inspection Pass Rate: 91.67%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
3/22: Partial (North and East side) 3 #4 rebar cont.- approved, QOInspector Comments:
3/26: SW corner of Exterior footing approved for pour. - QOInspector Comments:
3/27: Interior footings (all units except north end).approved - QOInspector Comments:
03/29/2013PassQuinton OwensFooting Inspection
3/29: North end unit interior ftgs approved.Inspector Comments:
3/26: North and East all (all but SW corner) ok to pour
4#4 horx cont. and #4 vert at 16 "o.c.
Inspector Comments:
03/29/2013PassQuinton OwensFoundation Inspection
3/29: Remaining fnd walls approved for pourInspector Comments:
5/24,QO: Sheathing- Fix missed locations as marked. Re-inspect w/ framing.Inspector Comments:
9/10: Tape attic party walls. Patch holes in attic (5203, 5202). Add fireclk under
tub drain- 1/8" thick is insufficient (front 5202, back 5203).
Inspector Comments:
09/10/2013FailQuinton OwensFraming/Structure Inspection
9/16,QO: middle units ok to drywall. Extend vent baffles to terminate above
insulation (5101,5104)
gap in attic drywall (5101). firecaulk sprinkler line into stairwell (5203)
Inspector Comments:
09/16/2013PassQuinton OwensFraming/Structure Inspection
09/19/2013FailQuinton OwensInsulation Inspection
End units- vents not extended above insulation level between lower & upper attic
(will be blocked with insul)
Inspector Comments:
09/23/2013PassQuinton OwensInsulation Inspection
9/23,QO: Secure sheetrock above tub in back (5202), sheet missing screws in
field on ceiling in front bdrm, front bthrm by door and wall across from tub.
Inspector Comments:
10/03/2013PassPLL ADMINSheetrock/Drywall Inspection
10/3,QO: DoneInspector Comments:
10/24/2013PassTed DyeBuilding Final
Page 1 of 3
(Continued)
Permit Details Permit Number: 12-00107
820 W 7th S - Rockwell Court Apts Bldg #5
820 W 7th S
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 01/03/2020 11:36 am
Permit
Inspection
Summary
Electrical Inspection Type
09/09/2013PassBret StoddardCommercial Electrical Rough-in
Approved for cover-inspected the electrical service and the fire alarm wiring on
this inspection also-as per Jane Shaw.
Inspector Comments:
09/09/2013PassBret StoddardCOM & MFR Electrical Service Inspection
Approved to be energized for permanent power-inspected the electrical service
on the rough-in inspection-as per Jane Shaw.
Inspector Comments:
10/22/2013PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O. #500. (Put sticker on electrical service-Jane
inspected and didn't have one).
Inspector Comments:
Fire Inspection Type
09/09/2013PassBret StoddardFire Alarm Rough-in
Approved for cover-inspected the fire alarm wiring on the electrical rough-in
inspection-as per Jane Shaw.
Inspector Comments:
9/6/13 DP: 10am hydro 200psi
walked around aprts for rough in.
12am hydro 205psi
Action required: 4 supports needed, on in each apartments utility room.
Inspector Comments:
09/23/2013PassDale PickeringFire Sprinkler Hydro
9/23/13 DP: Bldg # 500: Hydro 2 hours @ #200 -Pass, sprinkler rough-in -PassInspector Comments:
10/07/2013PassDale PickeringFire Sprinkler Final Inspection
Flow test - 37 secs - pass
Sprinklers - pass
Inspector Comments:
10/08/2013PassDale PickeringFire Underground Inspection
10/24/2013PassDale PickeringFire Department Final Inspection
Storz fittings on the hydrants - Ord 1063
Please call for any questions.
Inspector Comments:
10/24/2013PassBret StoddardFire Alarm Final Inspection
Approved for a final and C.O. #500, 24 hour/5 minute test witnessed, flow switch
operation witnessed at 38 seconds, A/C power loss at 3:00PM 10/23 and A/C
restored at 3:50PM 10/24, witnessed operation of all horn strobes and smoke
detectors, witnessed operation of CO detectors(2), report in file.
Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 12-00107
820 W 7th S - Rockwell Court Apts Bldg #5
820 W 7th S
New Multi-Family Residence
Permit Status of (Open) as of Report Date: 01/03/2020 11:36 am
Permit
Inspection
Summary
Mechanical Inspection Type
07/30/2013PassDon AllenHVAC Rough-in
All good to cover HVAC rough in.Inspector Comments:
10/24/13 DA: need to hook up microwaves
need to finish up fan in bathroom
need to change out T&P drops in water heaters.
Inspector Comments:
10/25/2013PassDon AllenHVAC Final Inspection
10/25/13 DA: all good for the C/OInspector Comments:
Planning & Zoning
10/23/2013PassVal ChristensenPlanning and Zoning Final Inspection
Landscaping complete
P&Z final complete.
Inspector Comments:
Plumbing Inspection Type
07/09/2013PassDon AllenPlumbing Water
Good to cover water line for apt 1,2,3,7,8,9.Inspector Comments:
08/19/2013PassDon AllenPlumbing Rough-in
07/9/13 DA: Approved.
8/19/13 DA: all good to cover rough in.
Inspector Comments:
09/03/2013PassDon AllenPlumbing Sewer
10/25/2013PassDon AllenPlumbing Final Inspection
10/23/13 DA: all good for c/o when tubs and shower are trenal out.
10/27/13 DA: all good for the C/O.
Inspector Comments:
Page 3 of 3