Inspection
Summary
Permit Status of (Open) as of Report Date: 12/31/2019 2:44 pm
Permit Details Permit Number: 12-00050
34 N 5th W - Duplex
34 N 5th W
Single Family - Basement Finish
Permit Issued Date: 07/10/2014
Permit Inspection Statistics
15Total Inspections Completed:
11Total Inspections Passed:
Inspection Pass Rate: 73.33%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
02/24/2012FailQuinton OwensFraming/Structure Inspection
move hall smoke det. near bottom of stairs AND end of hallway (make it
photoelectric) OR add smoke det at top of stairway. One hour ceiling separation
to extend to foundation wall or make ext.walls of basement 1 hr rated (protecting
penetrations). Walls along dropped ceiling to be 1 hr rated because of
unprotected dropped ceiling. Caulk overcuts on windows.
Told framer that outside stairs will need to be updated to code. They were not
indicated on plans.
Inspector Comments:
02/27/2012FailQuinton OwensInsulation Inspection
Joist cavities at exterior walls to be insulated same as ext. framed wall above
grade (R-20 min). Empty area at floor joist at south wall where electrical work
was done. Finish fire-blocking at dropped ceilings (see N.E. bedroom).
Inspector Comments:
02/29/2012PassQuinton OwensFraming/Structure Inspection
No fire separation done yet. Work was done before permit was issued. Tops of
furred out walls shall be sealed off with 1hr rating as well as dropped ceilings.
OR 1hr rating required on exterior walls and walls next to dropped ceilings and
protect penetrations.
Inspector Comments:
02/29/2012PassQuinton OwensInsulation Inspection
Fixed Insulation items.Inspector Comments:
03/05/2012FailQuinton OwensSheetrock/Drywall Inspection
Drywall needed behind pipe in mech. room (attach from bath side). Patch gap
behind tub before tile. 5/8" needed at lower portion of ceiling over stairs.
Firestop rings needed at final around drain penetrations into wall.
Inspector Comments:
03/07/2012PassQuinton OwensSheetrock/Drywall Inspection
Drywall all 5/8" type x, Mechanical closet done on walls open to above. Drywall
installed behind plastic pipe in mech closet.
Inspector Comments:
Page 1 of 2
(Continued)
Permit Details Permit Number: 12-00050
34 N 5th W - Duplex
34 N 5th W
Single Family - Basement Finish
Permit Status of (Open) as of Report Date: 12/31/2019 2:44 pm
Permit
Inspection
Summary
04/12/2012FailQuinton OwensBuilding Final
Exterior landing/stairs/handrail/guardrail non-compliant; all stair handrails must
be 34-38" above front of tread; egress needed from window wells (44" max
depth); Seal all joints and concrete cuts around exterior of basement windows;
seal between tile & window in bathroom and at base of tub; Fire separation ring
needed around bathroom sink drain (no openings); firecaulk around bathroom
waterlines under sink, around dryer vent, at penetration in mech room, and pipe
in closet at top of stairs; Photoelectric smoke detector at bottom of stairs (on
order).
Inspector Comments:
04/26/2012PassQuinton OwensBuilding Final
Install exterior light at basement apt. entrance. Done 5/2, QuintonInspector Comments:
Electrical Inspection Type
02/24/2012PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
Approved for cover in the basement unit-no work is going to be done in the
upstairs unit.
Inspector Comments:
03/08/2012PassBret StoddardResidential Electrical Service Inspection
Approved to be energized for permanent power.Inspector Comments:
04/04/2012PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Approved for a final and C.O.(basement remodel)-upstairs is existing entirely and
nothing was changed.
Inspector Comments:
Mechanical Inspection Type
02/29/2012PassQuinton OwensHVAC Rough-in
Standard "duct tape" not allowed for ducts. Has not called in for Mech. inspection
yet (2-27).
Duct tape is in addition to straps which are ok.
Inspector Comments:
04/05/2012PassQuinton OwensHVAC Final Inspection
Plumbing Inspection Type
02/27/2012PassDon AllenPlumbing Rough-in
all good to coverInspector Comments:
04/12/2012PassDon AllenPlumbing Final Inspection
ALL GOOD FOR THE C/OInspector Comments: