HomeMy WebLinkAboutINSPECTION REPORTS - 13-00104 - 538 S 2nd W - The Mountain LoftsINSPECTION REPORT
CommunityDevelopment
Department
Phone (208)359-3020
Inspection Hotline:
208)372-2344
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELE-FINAL
Permit Number
Address:
Project
13-00104
The Mountain Lofts - Bldg #1; 93
Units
538 S 2nd W
Inspection Date
6/23/2014
PASSInspectionResult:
Inspector's Comments
Approved for a final in units #1410, 1304, 1305, 1310,
1306,1307, 1308, 1321, 1322, 1317, 1316, and 1323 for
electrical only.
Inspector:Bret Stoddard
INSPECTION REPORT
CommunityDevelopment
Department
Phone (208)359-3020
Inspection Hotline:
208)372-2344
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELEROUGH
Permit Number
Address:
Project
13-00104
The Mountain Lofts - Bldg #1; 93
Units
538 S 2nd W
Inspection Date
6/26/2014
PASSInspectionResult:
Inspector's Comments
Approved for cover in unit #1105 and corridors in
sequence 2, 3, 4 and 5 on bottom level-level 1 for
electrical and fire alarm wiring.
Inspector:Bret Stoddard
INSPECTION REPORT
CommunityDevelopment
Department
Phone (208)359-3020
Inspection Hotline:
208)372-2344
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELE-FINAL
Permit Number
Address:
Project
13-00104
The Mountain Lofts - Bldg #1; 93
Units
538 S 2nd W
Inspection Date
7/8/2014
PASSInspectionResult:
Inspector's Comments
Approved for a final in units
1210,1205,1206,1209,1225,1226,1214,1213,1212,1224
1215,1211,1203,1204,1221 and 1218.
Inspector:Bret Stoddard
INSPECTION REPORT
CommunityDevelopment
Department
Phone (208)359-3020
Inspection Hotline:
208)372-2344
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELEFINAL-R
Permit Number
Address:
Project
13-00104
The Mountain Lofts - Bldg #1; 93
Units
538 S 2nd W
Inspection Date
7/15/2014
PASSInspectionResult:
Inspector's Comments
Approved for a final for electrical only in units #1208,
1207, 1219, 1220, 1115, 1114, 1101, 1113, 1102, 1103
and 1112.
Inspector:Bret Stoddard
Community Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELEFINAL-R
Permit Number
Address: 538 S 2nd W
Project
13-00104 The Mountain Lofts - Bldg #1; 93
Units
Inspection Date
7/22/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Positioning of boxes intended to be flush
with combustible and noncombustible
finished surfaces. 314.20
COMPLETED
Gaps around boxes in walls. 314.21 COMPLETED
Polarity of devices and luminaires.
200.10(B), 200.11, 410.23, 406.9
COMPLETED
Unused openings in boxes and other
enclosures are closed. 110.12, 314.17(A),
312.5(A)
COMPLETED
Spacing of receptacles for walls and
countertops, including islands and
peninsulas. 210.52(A) and (C)
COMPLETED
Countertop receptacles are provided with
GFCI protection. 210.8(A)(6)
COMPLETED
Bathroom receptacles are GFCI protected.
210.8(A)(1)
COMPLETED
Arc-fault circuit-interrupter (AFCI)
protection on bedroom circuits. 210.12
COMPLETED
Proper identification of all overcurrent
devices and disconnects. 110.22,
230.70(B), 408.4
COMPLETED
Open spaces in panelboard fronts. 110.12 COMPLETED
Approved for a final and C.O. in the noted
levels.
Final for electrical only in units #1104,
1106, 1107, 1109, 1110, 1111, 1118,
1119 and 1120.
COMPLETED
Inspector: Bret Stoddard
Community Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELEFINAL-R
Permit Number:
Address: 538 S 2nd W
Project:
13-00104 The Mountain Lofts - Bldg #1; 93
Units
Inspection Date
8/12/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Gaps around boxes in walls. 314.21 COMPLETED
Polarity of devices and luminaires.
200.10(B), 200.11, 410.23, 406.9
COMPLETED
Proper use of connectors and fittings and
for protection of cables. 300.15
COMPLETED
Bushings or equivalent protection for
cables entering boxes and other
enclosures. 300.4(F), 314.17, 314.42
COMPLETED
Disconnecting means on both permanently
connected and cord- and plug-connected
appliances. Article 422 Part III
COMPLETED
Properly sized circuits are provided for
specific kitchen appliances, such as
dishwashers, disposals, ranges, cooktops,
trash compactors, and the like. 210.23,
422.10
COMPLETED
Proper identification of all overcurrent
devices and disconnects. 110.22,
230.70(B), 408.4
COMPLETED
Open spaces in panelboard fronts. 110.12 COMPLETED
Approved for a final and C.O. in the noted
levels.
Inspected levels 3, 4 and 5 corridors and
commons areas. Need to cover NM-B
cabling above panels where exposed,
need to cover NM-B on level 3 west
corridor server room up high, will
re-inspect on other level corridors.
COMPLETED
Inspector: Bret Stoddard
Community Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELEFINAL-R
Permit Number:
Address: 538 S 2nd W
Project:
13-00104 The Mountain Lofts - Bldg #1; 93
Units
Inspection Date
8/13/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Polarity of devices and luminaires.
200.10(B), 200.11, 410.23, 406.9
COMPLETED
Unused openings in boxes and other
enclosures are closed. 110.12, 314.17(A),
312.5(A)
COMPLETED
Bushings or equivalent protection for
cables entering boxes and other
enclosures. 300.4(F), 314.17, 314.42
COMPLETED
Installation of listed equipment for
compliance with manufacturer’s
instructions. 110.3(B)
COMPLETED
Disconnecting means on both permanently
connected and cord- and plug-connected
appliances. Article 422 Part III
COMPLETED
Approved for a final and C.O. in common
areas.
In levels 1 and 2 corridors and commons
areas for electrical only.
COMPLETED
Inspector: Bret Stoddard
Community Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELECOMSERV
Permit Number:
Address: 538 S 2nd W
Project:
13-00104 The Mountain Lofts - Bldg #1; 93
Units
Inspection Date
8/13/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Each building has only one service or
justified for more than one. 230.2
COMPLETED
Underground fed services have proper
strapping and expansion fittings.
352.30(A)(B), 352.44
COMPLETED
Services are grouped together and limited
to six disconnects. 230.71, 230.72
COMPLETED
Unused openings have been closed. (K.O.
seals, etc.) 110.12(A), 408.7
COMPLETED
Proper clearances about electrical
equipment indoors and outdoors. 110.26
A), (E),(E)(2) and (F)
COMPLETED
Proper labeling of panels, switchgear, and
similar equipment. 110.22, 408.4
COMPLETED
Grounding electrode system installed-ufer,
ground rods, metal water piping, etc.
250.52(A)(4-7)
COMPLETED
Grounding electrode system conductors
sized and protected appropriately. 250.66,
250.64(F), 250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved
methods. 250.64(C)(F)
COMPLETED
Main bonding jumper sized to 250.28(D),
and all panels bonded together using an
equipment bonding conductor sized in
accordance with 250.122 or 250.66 as
appropriate.
COMPLETED
Approved to be energized for permanent
power (will send permit to utility).
To remain energized for permanent
power.
COMPLETED
Inspector: Bret Stoddard
Community Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELEFINAL-R
Permit Number:
Address: 538 S 2nd W
Project:
13-00104 The Mountain Lofts - Bldg #1; 93
Units
Inspection Date
8/15/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Approved for a final and C.O. in the noted
levels.
For preliminary final only entire building. A
few items remaining awaiting paint and
other trades.
COMPLETED
Inspector: Bret Stoddard
Community Development Department
Phone (208)359-3020
Inspection Hotline: (208)372-2344
INSPECTION
REPORT
Inspection Type Building Type Inspection
ELECTRICAL BLD-MFR ELEFINAL-R
Permit Number:
Address: 538 S 2nd W
Project:
13-00104 The Mountain Lofts - Bldg #1; 93
Units
Inspection Date
8/20/2014
Inspection Result: PASS
D ESCRIPTIO N CO MMEN TS STATUS
Bushings or equivalent protection for
cables entering boxes and other
enclosures. 300.4(F), 314.17, 314.42
COMPLETED
Disconnecting means on both permanently
connected and cord- and plug-connected
appliances. Article 422 Part III
COMPLETED
Circuits for mechanical equipment have
correct conductor size and overcurrent
protection. Articles 422, 424, 430, and 440
COMPLETED
Proper receptacle ratings based on
branch-circuit ratings, including
receptacles for electric dryers. 210.21,
210.24, 250.140
COMPLETED
Outdoor receptacles are GFCI protected
unless they are not readily accessible and
are supplied by circuits for deicing or
snow-melting equipment(GFPE required
otherwise with a disconnecting
means-breaker lock). 210.8(A)(3), 426.28,
426.50(A)
COMPLETED
Proper identification of all overcurrent
devices and disconnects. 110.22,
230.70(B), 408.4
COMPLETED
Open spaces in panelboard fronts. 110.12 COMPLETED
Approved for a final and C.O.Approved for a final and TEMPORARY
C.O. only-need to finish labeling units,
meters and fire alarm devices. Also need
to finish up loose ends throughout-Jack
has list of these items. This does not give
consent that people can move into the
units to live. This will be done later this
week or first part of next.
COMPLETED
Page 1 of 2
Inspector: Bret Stoddard
Page 2 of 2