HomeMy WebLinkAboutGARAGE LATERAL CALCULATIONS (12-6-19) - 19-00708 - Reeser - 1196 Torrey Ln - New SFR HUNTER RESIDENCE PARTIAL STRUCTURAL DESIGN CALCULATIONS FOR THE LATERAL DESIGN OF THE GARAGE AREA ONLY TO BE LOCATED AT THE CORNER OF FOXHILL DRIVE & PLEASANT RUN CIRCLE RIGBY, IDAHO Prepared For: Stoker Contracting Rigby, Idaho Designed By: Mark D. Andrus, PE Project #19244 TABLE OF CONTENTS DESCRIPTION SHEET General Design Criteria 1.1 Reduced Copy of Redlines 2.1 Lateral Design (seismic & wind) 3.1 – 3.14 G & S Structural Engineers 505 Lindsay Boulevard Idaho Falls, ID 83402 Telephone: (208) 523-6918 E-mail: gs@gsengineers.net Fax: (208) 523-6922 12-6-19 G & S Structural Engineers 505 Lindsay Boulevard Idaho Falls, ID 83402 Telephone: (208) 523-6918 E-mail: gs@gsengineers.net Fax: (208) 523-6922 GENERAL DESIGN CRITERIA Project: Hunter Residence (Project 19244) Location: Rigby, Idaho Building Code: 2015 International Building Code (IBC) Design Loads: Roof: Snow Load (SL): 35 PSF Dead Load (DL): 20 PSF Garage: 4” concrete slab on grade Wind: 115 mph 3-second wind gust (Ultimate) 90-mph 3-second gust (Nominal) Exposure C Risk Category II Seismic: SS = 43.6 % g SDS = 0.422 g S1 = 15.3 % g SD1 = 0.223 g Site class D Design Category D Risk Category II Importance Factor: IE = 1.0 R = 6.5, Light framed wood bearing shear walls with OSB wall sheathing V = 0.065 W 20% of snow weight was considered for seismic load calculations Sheet 2.1 Co p y r i g h t S u n d a n c e D r a f t i n g & D e s i g n 2 0 1 7 Main Floor Scale: 1/4"=1'-0" D Size Paper Scale: 1/8"=1'-0" B Size Paper Header Notes: Headers 4' or less use 1 Ply 9.50 or 2 Ply 2x10 Dim. Lumber Headers 6' or less use 2 Ply 9.50 Headers 8' or less use 3 Ply 9.50 or 2 Ply 11.88 ML Headers 10' or less use 3 Ply 11.88 or 2 Ply 14.00 ML Headers 10' or more refer to TJXpert Layout 3' Hallway Clearance 2012 IRC, Section R106 and R311.6 Saftey Glazing 2012 IRC, Sections R106 and R308.4.5 Exhaust and Ventilation: Whole House Fan 80 CFM Kitchen Fan 100 CFM Laundry 50 CFM Bathrooms 50 CFM Bedrooms 10 CFM fresh air Living Areas 10 CFM fresh air Contractor to indicate location of fans if not indicated on plans already. Furnace: Location of furnace and water heater 2012 IRC, Section R106, and M1305 Elevate all sources of ignition in the garage a min. of 18" above the floor 2012 IRC, Sections R106, and M1307.3 Provide a protection post in the garage to prevent vehicle damage to furnace and water heater. 2012 IRC, Section R106, M1307.3.1 Crawl Space: Through Floor min 18"x24" or through perimeter wall min 16"x24" required crawl space opening. If applicable, refer to mechanical code for access requirements where mechanical equipment is located under floors. 2012 IRC, Section R106, R408.4 M1305.1.4 Smoke Alarms 2012 IRC Code Section 106. R314 All smoke alarms shall be listed in accordance with UL 217 & installed in accordance with NFPA 72 -One in each sleeping area -Outside of each separate sleeping area in the immediate vicinity of the bedrooms -On each additional story including un-finish & finished basements and habitable attics but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with splits levels and without an intervening door between the adjacent levels a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. -Alarm devices shall be interconnected with battery backup that the actuation of one alarm will activate all of the alarms S Carbon Monoxide Alarms 2012 IRC Section 106 & R315.1 New Construction an approved carbon monoxide alarm installed outside of each sleeping area in the immediate vicinity of bedroom and dwelling units. They shall be listed as complying with UL 2034 and installed accordingly CM 4'Nailing or Screws 7" O.C. Max Horiz. & Vert. Blocks at Drywall Joints for 7" O.C. Screws of Nails Drywall is shown cutaway Overlapped Double Plate 2x6 Exterior wall @16"O.C. with 7/16" Waferboard Drywall & Waterboard not Shown for clarity 2x4 Interior Wall @16" O.C. 4'x8' Shear Panel on Both Sides 4' 8'x8' Shear Panel on Single Side 48 . 5 " t o c n t r IBWP 3 Interior Braced Wall Panel IBWP 2012 IRC Section 602.10.1 BWP 3-Interior Braced Wall Method 3 (IRC R602.10) 2x4 Studs @ 16" O.C. w/7/16" OSB Nailed 5" O.C. and 10" Field IBWP 5-Interior Braced Wall Method 5 1/2" min. Gypsum board 48" length applied to both sides OR 96" to one side covering 3 studs spaced 16" or 2 studs spaced 24" apart, blocked Screwed @7"/7" w/1" Drywall Screws All Vert Joints occur over stud All Hori. Joints blocked w/2x4 blocking Braced Wall Panel BWP 3' Braced Walls at each strap with 7/16" OSB one side, blocked in all joints Nailed @ 6"/12" w/ 8d or Stapled @ 4"/8" w 16 ga. All joints must occur over raming member 6" at edge 12" in field 4' 8d @ 12" O.C. in field 8d Nails @ 6" O.C. @ edge Braced Wall Panel Detail BWP IBWP 5 All exterior wall are braced walls. IBWP 5_________ APA SIMPLIFIED WALL BRACING IBWP 5-Interior Braced Wall Method 5 1/2" min. Gypsum See plan for length 2 studs spaced 24" apart, blocked Screwed @7"/7" w/1" Drywall Screws All Vert Joints occur over stud All Hori. Joints blocked w/2x4 blocking Above each IBWP3 a 2x4 Truss block is required as well at each corner, not over window ALL EXTERIOR WALLS ARE BRACED WALLS Header Notes: Headers 4' or less use 1 Ply 9.50 or 2 Ply 2x10 Dim. Lumber Headers 6' or less use 2 Ply 9.50 Headers 8' or less use 3 Ply 9.50 or 2 Ply 11.88 ML Headers 10' or less use 3 Ply 11.88 or 2 Ply 14.00 ML Headers 10' or more refer to TJXpert Layout 3' Hallway Clearance 2012 IRC, Section R106 and R311.6 Saftey Glazing 2012 IRC, Sections R106 and R308.4.5 Exhaust and Ventilation: Whole House Fan 80 CFM Kitchen Fan 100 CFM Laundry 50 CFM Bathrooms 50 CFM Bedrooms 10 CFM fresh air Living Areas 10 CFM fresh air Contractor to indicate location of fans if not indicated on plans already. A3 Su n d a n c e dr a f t i n g & d e s i g n PAGE LAYOUT A1-Elevations A2-Foundation/Basement Plan A3-Floor Plan A4-Cross Section A5-Plot Plan Sundance Drafting and Design tries to provide the most accurate information for your house design as possible, if design information is not provided correctly Sundance is not liable. Many factors occur in construction during the building process that change the continuity of this drawing. Due to these factors if the plan is not followed or changes occur after the final print has been given, Sundance Drafting and Design is not liable for those items. Read through all pages provided. Review all the notations and labels on each page. Engineering supersedes all drafting notations. Labeling by County or City Inspectors have to be followed. Footing, Foundation, Rebar, and Shear walls are specified and have to be followed. Floor Layouts and Truss Details are separate from these pages but need to be kept together and followed. If any problems with the plans, please notify Sundance Drafting and Design. The undersigned has looked through these pages and agrees that all discussed between Client/Contractor and Sundance Drafting and Design is noted and correct Please Initial Here 1. For a permit you will need 2 sets of the following: House plans, Floor Layout, Truss Details, Rescheck, Heat Loss Analysis, and Engineer Stamp (if needed). 2. Review entire set of plans including the above described with owner/contractor. 3. This drawing is drawn by an AutoCad Design Specialist not an Architect. All Details should be looked over and approved by contractor before construction begins. Sundance Drafting and Design is not liable for construction mistakes. 4. This drawing is not to be duplicated without written or verbal consent by Tiffany Stoddart. GENERAL NOTES: 1/4"=1'-0" UNO St o k e r C o n s t r u c t i o n Hu n t e r R e s i d e n c e A5of 03-06-17 Co p y r i g h t S u n d a n c e D r a f t i n g & D e s i g n 2 0 1 7 Copyright Sundance Drafting and Design 2017 Copyright Sundance Drafting and Design 2017 1/8"=1'-0" UNO 9' Main Walls 8'-4" Basement Foundation Walls Garage to Match Main TYP TOTAL SQ. FTG.= 3399 MAIN FLOOR=1714 BASEMENT =1685 /1568 INTERIOR GARAGE =1075 20 8 . 5 2 4 . 2 8 8 0 N EE D AH OU S E P LA N . C O M 14'-10" 45 ' 11'12'-2" 27'-2" 42' 14 ' - 2 " 5' 13 ' - 4 " 12 ' - 6 " 16'-3"6'-7"4'-4" 6'-8"2'-8" 10 ' - 1 0 " 3' - 5 " 3' - 9 " 3' - 8 " 4' 6'-1"5'-3"3'-6" 10 ' - 1 0 " 3'-8"3' 5'-6"5'-6"6'-1"6'-1" 2'-0 1/2"5'-7" 17 ' - 1 0 " 5' Great Room Dining Entry Bedroom 1 Bedroom 2 Master Bedroom 3068 2 8 6 8 DOWN STAIRS 3050 SH 5050 SV 5050 SV 14'-4" 37'-6"32' 30 6 8 4'-1"3'-4"3'-6"3'-3"2'-10" 3' - 3 " 2' 2' - 6 " 2' - 6 " 2' - 4 " 9' Ceiling 9' Ceiling 9' Ceiling 33 ' 69'-6" 8'-10"6' 3 ' - 0 1 / 2 " 2'-10" 2' - 1 0 " 2' - 4 " Porch 3'-8" 2 ' - 1 0 " 2' - 8 " S S 246 8 4040 T 9' - 3 " 8'-6"3'-3"3'-1" 9' Flat Ceiling 2' - 4 " 3 ' - 8 1 / 2 " 4040 SV T 3050 SH 2' - 6 " 11 ' - 1 0 " 11' x 10'-2" 10'-8"x 11' 26 6 8 17'-8"x18' 11'-8"x10' 5'-2"9'-10" 2668 286 8 Pantry 14'-4"x15' M. Bath 9' Flat Ceiling 9' Flat Ceiling Hall LN 4010 SV 28 6 8 S 4' 50 CFM 10 0 C F M 50 CFM 10 CFM Fresh Air 10 CFM Fresh Air 10 CFM Fresh Air 10 CFM Fresh Air WIC 3050 3'-4" 26 6 8 26 6 8 26 6 8 26 6 8 5010 TRA 14'-10" 14'-8" 15 ' - 4 " IBWP IB W P BWP BWP BWP BWP BW P 5006 w 6" Arch Above w/12 SLS 6' 7'-8" 12 ' - 1 0 " 3068 3' - 5 " 3' - 4 " 5'-10"2'-4"4'6'5' 2' Utility 8'-8" x 11'-8"9' Flat Ceiling 50 CFM 80 WHF Bath 11" Min. Step 206 8 2 0 6 8 2 0 6 8 2 0 6 8 3 0 6 8 DW 4'-6" 6' 3'4' 4'6' 16 ' - 6 " 19 ' 17 ' - 2 " 9x8 OH Garage Door 12'-6"19'-6" 1'-6"1'-6"9'2' 16x8 OH Garage Door 16'2' 27'-6" 24'-2"3'-4" 12 ' - 6 " 4' - 8 " 2' - 6 " 2' - 2 " 2' 2' 30503050 3050 3050 Vapor Barrier OC GAS FP 40 4 0 16 ' - 6 " 16 ' - 6 " 2'1'-11"2'-5" 3068 11 " M i n 11 " M i n 5' 14 ' 2' - 6 " 5' 5'-4" 5' - 6 " 4'-8" 11 ' - 8 " 2'-6" 2' - 1 0 " 3' 1' - 2 " 5'-8" 3' - 8 " 5'-6" Double Wall 6' - 2 " 2468 O 2x6 Wall 3 Car Garage 1075 Square Feet 3' - 6 " Contractor to locate exact location of req'd 22" x 30" Attic Access Point Min. 30" Vert. Head Room Clearance (2009-R807.1) 2x6 Wall 20min Fire Rated 1-3/8" Solid Door or Equal 8' - 1 0 " 2'-1 1 1 / 2 " 6'-1 1/2" 3' x 3 ' M i n S CM 1' - 7 " 1 ' - 5 " 8'-9 1/2" 8x8 Post 6" ST H D 1 4 ST H D 1 4 ST H D 1 4 ST H D 1 4 S T H D 1 4 S T H D 1 4 S T H D 1 4 S T H D 1 4 At front wall provide 7/16" OSB on each side of wall. Fasten with either 8d nails spaced at 6" o/c at panel edges and 12" o/c at intermediate studs or 16 gage staples at 4" and 12" o/c respectfully. Block horizontal panel joints with minimum 2x4 flat blocking. Provide minimum (2)5/8" or (3)1/2" diameter anchor bolts per wall segment with 3x3x1/4 plate washers and 2x pressure treated sill plate. Provide 7/16" OSB on exterior side of wall. Fasten with either 8d nails spaced at 6" o/c at panel edges and 12" o/c at intermediate studs or 16 gage staples at 6" and 12" o/c respectfully. Block horizontal panel joints with minimum 2x4 flat blocking. Provide minimum 5/8" or 1/2" diameter anchor bolts at 4'-0" o/c with 3x3x1/4 plate washers and 2x pressure treated sill plate. Simpson Strap-tie holdown with double 2x stud column. Typical 8 places Hunter Residence Partial Lateral Design - Garage Only Redlined by G&S Structural Engineers Project #19244 Mark Andrus 208-523-6918 December 6, 2019 S h e e t 2 . 1 Sheet 3.1 Sheet 3.2 Sheet 3.3 Sheet 3.4 Sheet 3.5 Sheet 3.6 Garage Roof Framing layout used for design Sheet 3.7 Sheet 3.8 Sheet 3.9 Sheet 3.10 Sheet 3.11 Sheet 3.12 Sheet 3.13 Sheet 3.14