Loading...
HomeMy WebLinkAboutFIRE ALARM SYSTEMS - 13-00274, 13-00341, & 13-00342 - 650 S 1st W - BYUI Student AptsNelson I d I Ll I Systems FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 www.nelsonfire.com BYU-Idaho Student Housing Buildings A -B -C Fire Alarm System Submittal Data Sheets 19-0 011113 411 3 1Z BjUI �,Whn} tPsinq Firs Alarm *ns: .1ggj.. . I {�' � .�,y11 i" nn .� l�{i�g1.: 'il .;� .� . � F' .1ggj.. . I {�' � .�,y11 i" nn .� l�{i�g1.: 'il BYU-IDAHO STUDENT HOUSING BUILDING A -B -C FIRE ALARM SYSTEM SUBMITTAL DATA SHEETS Equipment Manufacturer: Gamewell-FCI Authorized Distributor: Nelson Fire Systems 1481 South Major Street Salt Lake City, UT 84115 801-468-8300 Data Sheet Part No. Description Gamewell-FCI E3 Series Emergency Evacuation System Gamewell-FCI ILI-MB-E3 E3 Series Intelligent Loop Main Board Gamewell-FCI ILI-S-E3 E3 Series Intelligent Loop Expansion Board Gamewell-FCI PM -9 E3 Series Power Supply Gamewell-FCI LCD -E3 E3 Series Remote Annunciator Gamewell-FCI ASM -16 E3 Series Addressable Switch Module Gamewell-FCI ANX-SR Addressable Node Expander Gamewell-FCI RPT -E3 -UTP Network Repeater Gamewell-FCI FSL-E3 Single Mode Fiver Module Gamewel-FCI FP -Gate -3 Focal Point Gateway Gamewell-FCI ASD-PL2F Addressable Photo Smoke Detector Gamewell-FCI ATD-RL2F Addressable Heat Detector Gamewell-FCI B200S Audible Base Gamewell-FCI MCS-COF Carbon Monoxide Detector Gamewell-FCI DNR Addressable Duct Detector Gamewell-FC] MS-7AF Addressable Pull Station Gamewell-FCI AMM -417 Addressable Monitor Module Gamewell-FCI AOM-2RF Addressable Control Module Gamewell-FCI AOM-2SF Addressable Control Module Gamewell-FCI PR -3 Auxiliary Relay Gamewell-FCI P2W Horn/Strobe-Wall Mount Gamewell-FCI HPFF8 NAC Power Supply FIRE CONTROL INSTRUMENTS by Honeywell Description The E3 Series" Expandable Emergency Evacuation System by FCI is in the forefront of the latest generation of fire alarm control panels. Employing the new high-speed Velociti" sensors, the E3 Series" provides previously unreachable polling speed and response together with the flexibility demanded by today's emergency evacuation systems. In addition to their high-speed polling rate, the VelocitiTN series of sensors feature bi-polar LEDs that flash green for normal polling, and light red steadily to indicate an alarm. The E3 Series" is equipped with an 80 -character LCD -E3 alphanumeric LCD display that allows 40 characters to be user -defined for customizing installa- tions. Up to six (6), keyboard LCD displays may also be remotely located in addition to five of the familiar LCD -7100 remote displays, allowing for instant system status information to be available in any desired area of an installation. The use of a high-speed 32-bit processor easily tackles a wide array of applications from small office buildings to sophisticated high rise installations. 64 -node networking is made possible by 625K baud/ ARCNET communications using twisted -pair copper cable, fiber-optic cable, or a combination of both. The basic E3 Series" is equipped with an ILI-MB-E3 Intelligent Loop Interface -Main Board and ASM -16 Addressable Switch Module that features sixteen (16), software programmable switches, each accompanied by red, green and yellow LEDs that can be programmed to indicate operation of the switches. Sixteen (16) additional optional ASM -16 modules may be added to expand the operation to a plateau previously unimagined. The Intelligent Loop Interface - Expansion Board (ILI-S-E3) provides the E3 SeriesTN control panel with two (2), additional signaling line circuits. The layout is similar to the ILI-MB-E3 with the exception that a number of components are omitted. When the ILI-S-E3 is used with the RPT -E3 Repeater, it occupies one node on the Broadband network. E3 Series" and Velociti10 are trademarks of Fire Control Instruments. E3 SerleSTI Control Pane Expandable Emergenc Evacuation Syster E3 Senesm- Features • Two to 128 SLCs each supporting 99 sensors and modules per circuit. • 625K baud ARCNET communications using wi fiber, or mixed configurations for installation flexibili • High-speed 32 bit processor. • 4100 event history log. • Advanced Boolean logic -based programming such AND, OR, NOT, time delay and calendar functic configurable via computer programming. • Supports up to sixteen (16), ASM -16 addressa' switch modules. • Supports up to sixteen (16), ANU-48 LED driver modules. • Two (2), Class A, Style Z or Class B, Style Y, notification appliance circuits rated at 2.0 am per circuit. • Integral city connection. • Flexible 115,200 baud high speed RS -232 interface • 40 character user -defined text per device. • Styles 4, 6, or 7` signaling line circuits. • Supports up to five (5), LCD -7100 displays and (6), LCD -E3 keyboard displays. • Listed under UL Standard 864, 9th Edition. *Style 7 wiring requires the use of System Sen: M50OX Isolator Modules. An ISO 9000-2000 Company SIGNALING City of Chicago &<S> MEA 0 Approved City of OSTED—.S rowmee • class 1 DENVER 51869 3025415 PENDING 77650694 268 • Class 2 Approved 71650894 269 • High Was FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090—Tel 781-471-3000—Fax: 781-471-3099 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Fire Control Instruments for their use. 0200.5 Fire Control Instruments. All rights reserved. www.flrecontrolinstruments.com 9020-0637 Rev. C page 1 of Description (continued) As many as sixteen (16), ANU-48 remote LED modules may also be added, furnishing hundreds of LEDs for remote annunciation. The ANU-48 modules may be installed in any Listed remote annunciator. It can be remotely located via an RS -485 serial interface. An array of cabinets allows for neat, compact, attractive installations. Installation The E3 Series" expandable emergency evacuation system offers four (4), cabinet size options. A typical cabinet includes a backbox, an inner door, and an outer door. The E3 Series' cabinet assembly is a compact 19" wide wall -mounted enclosure. Cabinet A includes two options: a two or three -bay outer door mounted to the backbox. The backbox typically houses one (1) LCD -E3, or one (1) NGA, and one (1) or two (2), ASM -16 modules. Cabinet B contains a space for the ILI-MB-E3, PM -9 modules and batteries set inside the backbox. Additional module options mounted on the backbox include the DACT-E3, RPT -E3 and ILI-S-E3. The 2 -Bay inner door houses one (1), LCD -E3 module and one (1), ASM -16 module. Both Cabinets C and D include the following: • Pre -assembled outer door panels that contain an enclosure for the fire fighter's phone handset and a microphone voice messaging system. • Two inner door panel selections that may contain optional modules to meet the facility operation requirements. • Inner Door Panel 1 accommodates up to eleven (11), ASM -16 modules and one LCD -E3 module. • Inner Door Panel 2 houses up to sixteen (16), ASM -16 modules, one (1), LCD -E3 or one (1), NGA. For instructions on installing any of the above E3 Series" cabinets, refer to the E3 Series`" Expand- able Emergency Evacuation Installation/Operating Manual Part Number: 9000-0574. Specifications Operating Voltage: 24 VDC Operating Not to exceed the range of Temperature: 32' to 120 F (0 to 49 C) Relative Not to exceed 93% Humidity: Non -condensing at 90' F (32 C) Dimensions: Cabinet A:19 1/4'W x 10" L x 3" D (49 x 25 x 7.6 cm) Cabinet B:19 3/8" W x 19 3/8" L x 4.5 D (49 x 49 x 11 cm) Cabinet C:19 3/8" W x 30" L x 4.5" D (49 x 76 x 11 cm) Cabinet D:19 3/8' W x 41" L x 4.5" D (49 x 104 x 11 cm) Ordering Information Model Description F��ILI-MB-E3 Intelligent Loop Interface -Mai Bo r ILI-S-E3 Intelligent Loop Interface -Expansion Board LCD -E3 LCD -E3, LCD Keypad Dis la RPT -E3 -FO Network Repeater Module RPT -E3 -UTP DACT-E3 Digital Alarm Communicator Transmitter ANU-48 ANU-48 LED Driver Module ASM -16 Addressable Switch Module NGA LCD Network Graphic Annunciator PM -9 Power Supply Module LCD -7100 Remote LCD Display Cabinet A E3BB-BA Backbox with Door, (Black) E3BB-RA Backbox with Door, (Red) E31D2-A Cabinet A, Inner Door, 2 Slots E31D3-A Cabinet A, Inner Door, 3 Slots Cabinet B E3 -BB -BB Backbox with Door (Black) E3 -BB -RB Backbox with Door (Red) E31D2-B Cabinet B, Inner Door, 2 Slots Cabinet C E3BB-BC/INCC Cabinet C, Backbox Enclosure, Command Center (Black) E3BB-RC/INCC Cabinet C, Backbox Enclosure, Command Center (Red) E3BB-BC/INX Cabinet C, Black Enclosure, Transponder E3BB-RC/INX Cabinet C, Red Enclosure, Transponder E31D2-C Cabinet C, Inner Door, Command Center, 7 Slots E31D3-C Cabinet C, Inner Door, Command Center, 8 Slots Cabinet D E3BB-BD Backbox with Door, (Black) E3BB-RD Backbox with Door, (Red) E31D2-D Cabinet D, Inner Door, 13 Slots (11 single and 2 double slots) E31D3-D Cabinet D, Inner Door, 14 Slots (12 single and one double slots) FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090—Tel 781-471-3000—Fax: 781-471-3099 www.firecontrolinstruments.com 9020-0637 Rev. C page 2 of 2 ^Gamewell IN�STCRUOMEMS by Honeywell Description The E3 Series® Expandable Emergency Evacuation Sys- tem by Gamewell-FCI offers several cabinet size options. These cabinet options allow for neat, sturdy, attractive installations. The E3 Series cabinet assembly is a com- pact, wall -mounted enclosure. A typical cabinet includes a backbox and an outer locking door. In addition, there are several inner door choices and mounting plates to accom- modate a variety of E3 sub -assemblies. Each cabinet backbox includes mounting patterns or plates to aid the installer in arranging and securing the sub -assemblies to the backbox. Backbox knockouts are also positioned at numerous points to allow a conduit access into the enclosure. Four (4) Annunciator Cabinet sizes provide maximum flex- ibility that can meet any application. • Cabinet A or AA offers 2 slot and 3 slot options to accommodate either of the following configurations: - Cabinet A or AA, 2 slot allows space for one (1) LCD -E3 and one (1) NGA or one (1) ASM -16/ ANU-48. - Cabinet A or AA, 3 slot provides space for either one NGA and two ASM -16S or three ASM-16s/ANU-48s. • Cabinet Al houses one NGA or one ASM-16/ANU-48. • Cabinet A2 accommodates a single LCD -E3 display. Cabinet B contains a space for the ILI-MB-E3, PM-9/PM- 9G sub -assemblies and batteries set inside the backbox. Additional sub -assembly options mounted on the backbox include the DACT-E3 and RPT -E3. The 2 slot inner door houses the following options: • one (1) LCD -E3 module and • either one (1) ASM-16/ANU-48 or one (1) NGA module Both C and D size Command Center cabinets house a variety of E3 Broadband sub -assemblies in multiple con- figurations that provide a solution to a wide range of appli- cations. Two (2), flexible inner door panel selections are available for C and D size Command Center cabinets that may con- tain a fire fighter's phone handset, a microphone, and optional modules to meet the facility operation require- ments. ('Note: See Inner and Backbox Mounting Capacities on page 3). E3 Series® is a registered trademark of Honeywell International Inc. Laron® Is a registered trademark of GE Plastics, a subsidiary of General Electric Company. E3 Series(' Cabinet: Cabinets for the E3 Series E3 Series® Cabinets Features 16 -gauge steel backbox Removable outer and inner doors Inner door bonding strap used to provide electrical continuity for grounding Backbox and door ground studs provide positive grounding. 180° opening door with full clearance Available in either black or red Lexan® windows appear on the doors of most cabine except the Cabinet "C" and " D" INX cabinets which u: louvered doors 900 opening door with zero clearance Keylock with quarter turn latch Trim Ring accessories available An ISO 9000-2000 Company sicca uwa L FM Ciy AMEA c6""of icflp City of usreo MPROWD �� ro cwnwr 51669 3025416 23144E 7165-0103:125 cW2 APProvea H". GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Swilcations are for information only, are not Intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ®2909 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0649 Rev. J page 1 of Irdering Information 1rt Number Description abinet "A" & "AA" Size M -BA Enclosure, Black, "A" Size 3BB-RA Enclosure, Red, "A" Size 3BB-BAA Enclosure, Black, "AA" (LOC) Size 3BB-RAA Enclosure, Red, "AA" (LOC) Size 3102-A Inner Door, 2 Slots, "A" Size 3103-A Inner Door, 3 Slots, "A" Size abinet "Al" & "A2" Size: 3BB-BA1 Remote Enclosure, Al Size, Black Trim kit for "A2" size enclosure, black (include inner door) 3BB-RA1 Remote Enclosure, Al Size, Red Trim kit for "C" size enclosure, black (include inner door) MB-BA2 Remote Enclosure, A2 Size, Black (include inner door) 3BB-RA2 Remote Enclosure, A2 Size, Red (include inner door) abinet "B" Size: 3BB-1313 Enclosure, Black, "B" Size 3BB-RB Enclosure, Red, "B" Size 3102-13 Inner Door, 2 Slots, "B" Size abinet "C" Size: 3BB-BC/INCL Enclosure, Command Center, Black, "C" Size 3BB-RC/INCC Enclosure, Command Center, Red, "C" Size 3102-C Inner Door, Command Center, 2 Slots Specifications "C" Size 31D3 -C Inner Door, Command Center, 3 Slots Cabinet "C" Size 3BB-BC/INX Enclosure, Transponder, Black, "C" Size 3BB-RC/INX Enclosure, Transponder, Red, "C" Size !-INCC-CPLATE Command Center module mounting plate, "C" Size !-INX-CPLATE Transponder module mounting plate, "C" Size 3-ILI-CPLATE Intelligent loop module mounting plate "C" Size abinet "D" Size: 3BB-BD/INCC Enclosure, Command Center, Black, "D" Size 3BB-RD/INCC Enclosure, Command Center, Red, "D" Size 31D2 -D Inner Door, 2 Slots, "D" Size 3103-D Inner Door, 3 Slots, "D" Size 3BB-BD/INX Enclosure, Transponder, Black "D" Size 3BB-RD/INX Enclosure, Transponder, Red, "D" Size !-INCC-DPLATE Command Center module mounting (49 cm) (104 cm) (11 cm) plate, "D" Size 3-INX-DPLATE Transponder module mounting plate, "D" Size ptional Accessories art Number Description 00-0450 Command Center, blank plate, single size 3 -BP Inner door panel, blank, double size 1375 PM-9/PM-9G Adapter Plate Kit, Audio coupling transformer, for audio Hardware,E3-INX 3-TRIMKIT-A Trim kit for "A"f'AW size enclosure, black 3-TRIMKIT-A1 Trim kit for "Al" size enclosure, black 3-TRIMKIT-A2 Trim kit for "A2" size enclosure, black 3-TRIMKIT-B Trim kit for "B" size enclosure, black 3-TRIMKIT-C Trim kit for "C" size enclosure, black Ordering Information (Continued) Bulk Amplification Part Number Description E3-TRIMKIT-D Trim kit for "D" size enclosure, black AA -100 Audio Amplifier, 10OW @70.7 VRMS w/ built-in tone generator, 120 VAC AA -120 Audio Amplifier, 120W @25 VRMS w/ built-in tone generator, 120 VAC ACT -1 Audio coupling transformer, for audio systems w/multiple supplies FCI-CHG-120 Battery Charger, 25-120 A/H sealed lead -acid, mounts in an FCI-LBB box FCI-LBB Battery box, accommodates batteries up to 55 Aft (Black) Cabinet C: FCI-DR-C4B Blank door, lock & keys, for backbox accepting 3 chassis, (Black) FCI-DR-C4BR Blank door, lock & keys, for backbox accepting 3 chassis, (Red) SBB-C4 Backbox, 3 chassis, (Black) Cabinet D: FCI-DR-D4B Blank door, lock & keys, for backbox accepting 4 chassis, (Black) FCI-DR-D4BR Blank door, lock & keys, for backbox accepting 4 chassis, (Red) SBB-D4 Backbox, 4 chassis, (Black) Specifications Dimensions: Cabinet Width Height Depth Cabinet 191/4" 10" 3" (49 cm) (25 cm) (7.6 cm) Cabinet AA 191/4" 10" 41/2' 8475" 101,25 311 cm) Cabinet Al: Backbox (22.2 cm) (25 cm) (7.6 cm) Cabinet A2: 13.25" 10" 3" Backbox (33.6 cm) (25 cm) (7.6 cm) Cabinet B 19 3/8" 3/8" 4 1/2" (19 9 21 4111/2 Cabinet C 193/8,' 3/8" 19 471cm) Cabinet D 4111//22' 3/1 (49 cm) (104 cm) (11 cm) GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0649 Rev. J page 2 of 3 www.gamewell-fci.com Inner Door Mounting Capacity Number Components Cabinet A E31D2-A, Cabinet A, Inner Door, 2 Slots 1 LCD -E3 Display and 1 ASM-16/ANU-48 E31D3-A, Cabinet A. Inner Door, 3 Slots 1 NGA or ASM -16 2 ASM-16s/ANU-48s Cabinet AA 1 Microphone Cabinet Al E31D-A1 Cabinet A1, Inner Door, (Included with Box) 1 NGA Cabinet A2 E31D-A2 Cabinet A2, Inner Door, (Included with Box) 1 LCD -E3 Cabinet B E302 -B, Cabinet B, Inner Door, (Included with Box) 1 LCD -E3 Display and one (1) ASM-16/ANU-48 1 NGA and one (1) ASM -1 6/AN U-48 Cabinet C E302 -C, Cabinet C, Inner Door, 2 Slots 1 LCD -E3 Display and 5 Any combination of ASM-16/ANU-48, NGA or Microphone Assemblies 1 Telephone Assembly E303 -C, Cabinet C, Inner Door, 3 Slots 7 Any Combination of ASM-16/ANU48, NGA, or Microphone Assemblies 1 Telephone Assembly Cabinet D E302 -D, Cabinet D, Inner Door, 2 Slots 1 LCD -E3 Display 11 Any Combination of ASM-16/ANU48, or NGA or Microphone and 1 Telephone Assembly E303 -D, Cabinet D, Inner Door, 3 Slots 13 Any Combination of ASM-16/ANU48, NGA or Microphone Assemblies 1 Telephone Assembly Backbox Mounting Capacity Number Components E3BB-BAA, Enclosure, "AA' (LOC) Size, Black 1 INI-VG Series Voice Gateway E3BB-BA1, At Size Box/Door, Black 1 RPT -E3 Network Repeater E3BB-BB, B Size Box/Door, Black 1 PM-9/PM-9G Power Supply 1 ILI-MB-E3 Loop Interface and 1 Additional ILI-MB-E3 Loop Interface or 1 DACT-E3 Digital Communicator and 1 RPT -E3 Network Repeater E3-INCC-C Plate 1 PM-9/PM-9G Power Supply 1 INI-VG Series Voice Gateway 1 ILI-MB-E3 Loop Interface and Backbox Mounting Capacity Number Components E3-INCC-C Plate (Continued) 1 Additional ILI-MB-E3 Loop Interface or 1 DACT-E3 Digital Communicator and 1 RPT -E3 Network Repeater 1 Optional AM -50 -Plate E3-ILI-C Plate 1 PM-9/PM-9G Power Supply 1 ILI-MB-E3 Loop Interface 2 Additional ILI-MB-E3 or ILI-S-E3 1 DACT-E3 1 RPT -E3 E3-INX-C Plate 1 PM-9/PM-9G Power Supply with one (1) 1 PM -9G Adapter Plate 1 INI-VGX Voice Gateway 1 ILI-MB-E3 Loop Interface and 1 Additional ILI-MB-E3 Loop Interface or DACT-E3 Digital Communicator and RPT -E3 Network Repeater AM -50 Amplifier E3-INCC-D Plate 1 PM-9/PM-9G Power Supply 1 ILI-MB-E3 or ILI95-MB-E3 Loop Interface 4 Additional ILI-E3 Series or ILI95-E3 Series 1 DACT-E3 Digital Communicator 1 RPT -E3 Network Repeater 1 INI-VG Series E3-INX-D Plate 1 PM-9/PM-9G Power Supply 1 ILI-MB-E3 or ILI95-MB-E3 Loop Interface 1 DACT-E3 Digital Communicator 1 RPT -E3 Network Repeater 1 INI-VG Series 4 AM -50 Amplifier E3BB-BD, D Size Box/Command Center (Voice), Black 1 PM-9/PM-9G Power Supply 1 INI-VG Series Voice Gateway 4 ILI-MB-E3 Loop Interface and 1 Additional ILI-MB-E3 Loop Interface or 1 DACT-E3 Digital Communicator and 1 RPT -E3 Network Repeater E3BB-BD, D Size Box/Command Center, Black 1 PM-9/PM-9G Power Supply 7 ILI-MB-E3 Loop Interface and 1 Additional ILI-MB-E3 Loop Interface or 1 DACT-E3 Digital Communicator and 1 RPT -E3 Network Repeater GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA - Tel: (203) 484-7161 • Fax: (203) 484-7118 www.ga,'PWOII-fci.com 9020-0649 Rev. J page 3 of 3 FIRE CONTROL INSTRUMENTS by Honeywell Description ILI-MB-E3 The Intelligent Loop Interface -Main Board (ILI-MB- E3) is the main interface for the E3 SeriesTIA product line. With its state-of-the-art 32 bit RISC processor, this compact "panel on a board" pro- vides a powerful addition to FCI's single pair con- ductor solutions. This intuitive design provides two (2), signaling line circuits, two (2), notification ap- plication circuits, local energy city box output, aux- iliary relay functions, and auxiliary power out. These features, combined with built-in network and serial protocols, allow this module to support a host of new and existing products, resulting in a building block approach to fire alarm panel design. The ILI-MB-E3 is network ready and occupies one of 64 nodes, operating at 625K baud. When this sub -assembly is integrated with proven Broadband components, the result is a flexible yet powerful integrated audio solution. When transmitting to remote locations, the optional RPT -E3 provides the ILI-MB-E3 with valuable signal boosting and transient protection, as well as connectivity using both wire and fiber-optic cables. It provides two (2), signaling line circuits and termi- nals for the connections of all the E3 sub- assemblies. This board can support up to a total of sixteen (16), ASM -16 and/or sixteen (16), ANU-48 remote LED driver modules. The ILI-MB-E3 relay outputs include system alarm, supervisory, and system trouble contacts. The ILI- MB-E3 provides output for a local energy city mas- ter box or remote location which is non power - limited. All other wiring is power -limited. E3 Sedes. is a trademark of Fire Control Instruments. ILIABli Series Intelligent Loop Interface -Main Board ILI-MB-E3 Features ILI-MB-E3 and ILI-S-E3: • Network ready integral 625K baud ARCNET. • 115.2K baud RS -232. • Signaling line circuits with: - Two (2), Class A, Style 6, 7 or Class B,Style 4 circuits. - 40 Character user -defined text per device. - Style 4, 6, or 7" operation. - Capacity of 99 sensors and 99 addressable devices per circuit. • Notification appliance circuits with: - Two (2), Class "A", Style Z, Class B, Style Y, Notification appliance circuits rated at 2.0 amps. per circuit, Styles Y and Z. • 4100 event history log. • Listed under UL Standard 864, 9th Edition. 'Style 7 wiring requires the use of System Sensor M50OX Isolator Modules. ILI-MB-E3 Only: • RS -485 supporting sixteen (16), ASM -16 switch modules and/or ANU-48 LED driver modules. • Alarm, trouble, and supervisory dry contacts Form "C", rated at 2 amp. @ 30 VDC (resistive). • Supports six (6), local/remote LCD -E3 annunciators and five (5), LCD -7100 annunciators. An ISO 9000-2000 Company SWAM City of uL Chicago ase Approved City of TED6 0 LISMEA .Class? DENVER staff 302541E PENDING 7785089425E -Classl Approved 7185089425'. •Nigh Rise FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090—Tel 781-471-3000—Fax: 781-471-3099 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Fire Control Inshumenls for their use. 02005 Fire Control Instruments. All rights reserved, www.flrecontrolinstruments.com 9020-0605 Rev.0 page oft ILI-S-E3 ILI-S-E3 The Intelligent Loop Interface - Expansion Board (ILI-S-E3) provides the E3 SeriesTM control panel with two (2), additional signaling line circuits. The layout is similar to the ILI-MB-E3 except a number of components are omitted. The ILI-S-E3 occupies one node on the Broadband network. The Intelligent Loop Interface - Expansion Board (ILI-S-E3) pro- vides the E3 SerieSTM control panel with two (2), additional signaling line circuits. The layout is similar to the ILI-MB-E3 except a number of components are omitted. The ILI-S-E3 occupies one node on the Broadband network. Installation Typically, the ILI-MB-E3 or ILI-S-E3 can be mounted in the following E3 Series TM cabinets: • Cabinet B and D, backbox. • Cabinet C. INX-E3 sub -assembly plate. • Cabinet C, INCC-E3 sub -assembly plate. Note: More than one ILI-MB-E3 or ILI-S-E3 can be mounted in Cabinet D. For instructions on installing the ILI-MB-E3 or ILI-S-E3, refer to the E3 Series" Expandable Emer- gency Evacuation Installation/Operating Manual, Part Number: 9000-0574, the ILI-MB-E3 Installation Instructions, Part Number: 9000-0579, or the ILI-S-E3 Installation Instructions, Part Number: 9000-0569. Specifications Operating Voltage: Operating Current: Alarm Current: Operating Temperature: Relative Humidity: 24 VDC FWR (from PM -9 Power Supply) 0.081 amp. 0.150 amp. max. 32° to 120° F (0° to 49° C) 0 to 93%, non -condensing at 90° F (32° C) 40 Ohms maximum line impedance. 0.5 pf maximum line capacitance. Ordering Information Model Description ILI-MB-E3 Intelligent Loop Interface -Main Board ILI-S-E3 Intelligent Loop Interface -Expansion Boar( FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090—Tel: 781-471-3000—Fax: 781-471-3099 www.firecontrolinstruments.com 9020-0605 Rev. C page 2 of 2' ^Gamewell Q � FIRECONTROL INSTRUMENTS by Honeywell PM=9 Description PM -9 Power Supply The PM -9 Power Supply is a component of NetSOLOO and E3 Series® fire alarm and voice evacuation systems. It provides power to the INX Transponder assembly and all E3 Series components. The PM -9 is a switching power supply that provides 9 amperes of filtered and regulated 24 VDC (nominal). It has an internal battery charging circuit capable of maintaining up to fifty-five (55), A/H batteries. This module is designed for use with the Gamewell-FCI distributed audio networks. Installation Typically, the PM -9 Module can be mounted in the follow- ing E3 Series cabinets: • Cabinet B and D, backbox • Cabinet C, INX-E3 sub -assembly plate • Cabinet C, INCC-E3 sub -assembly plate • Cabinet D, E3-INX-D Plate • Cabinet D, E3-ILI-D Plate For instructions on installing the PM -9, refer to the E3 Series® Expandable Emergency Evacuation Installation/ Operation Manual, Part Number: 9000-0574 or the PM -9 Installation Instructions, Part Number: 9000-0548. Specifications Input Voltage: 120 VAC 60 Hz Input Current: 4.6 amps max. @ 120 VAC 60 Hz Output Voltage: 24 VDC (nominal) FWR Output Current: 9 amperes Alarm max. continuous Output Current: 5 amperes Standby max. continuous (See Note 1) Alarm Current: 0.050 amp Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 0 to 93% (non -condensing) at 90° F (32° C) Supervised Non Power -Limited Dimensions: 10 1/2" W x 5"H x 2" D (27 IN x 13 H x 5 D cm) Note 1: Continuous standby loads in excess of .560 Amps up to 5 Amps may require Generator backup or load shed- ding during an AC power failure. E3 Sedes® and NetSOLO® are registered trademarks of Honeywell International Inc. UL® Is a registered trademark Undellwoters Laboratories Inc. PM -9 Features Listed under UL® Standard 864, 9th Edition 9 ampere, filtered, regulated power supply Energy and space saving switching technology Integral battery charger capable of recharging up to fifty-five (55), AH batteries (Batteries not furnished) Ordering Information Part Number Descrintion PM -9 Power supply An ISO 9000.2000 Company acanuxc Cit of 11 TL fM Chicago A(l9= City Of class i U6povEeatl SlM�Wr 4 M117416e 7166.170):125 Class2 51919vol.19 Higher. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for infor.-- ;nn only, are not intended for installation purposes, and are subject to change YALhout notice. No responsibility is assumed by Gamewell-M for their use. `®2009by Honeywelllntematbnall^ „Ildghlsmserved. www.gamewell-fcl.com 9020-0555 Rev. J page 1 of 1 J 0 " FIRE CONTROL INSTRUMENTS by Honeywell Description The LCD -E3 provides the main panel display of the E3 SeriesTm Expandable Emergency Evacuation System with indicating LEDs and operating switches. Up to six (6), LCD -E3 displays may be locally or remotely located from the panel via a local RS -485 bus of the ILI-MB-E3 sub -assembly. The LCD -E3 includes an LCD display for the system status and the following switches and LED indicators: Switches • AC Power • Alarm acknowledge • System reset/lamp test • Trouble • Programming buttons: acknowledge - menu/back (yellow) - back space/edit -OK • Signal silence • 12 button keypad LED Indicators • AC Power (green) • Power Fault (yellow) • Alarm (red) • Ground Fault (yellow) • Supervisory (yellow) • System Silenced (yellow) • System (yellow) Trouble Installation The LCD -E3 is adaptable for installation in any of the following E3 SeriesTM System cabinets: • "A" size cabinet, inner door (E302 -A). • "B" size cabinet, inner door (E31D2-B). a "C" size cabinet, inner door (E311)2 -C). • "D" size cabinet, inner door (E302-13). Ordering Information Model Description LCD -E3 LCD keypad display E3 Series" is a trademark of Fire Control Instruments. LCD -E3 LCD Keypad Displa,, LCD -E3 Features • Provides an 80 -character display of system events together with indicating LEDs and contn switches. • The ILI-MB-E3 can support up to six (6), LCD -E displays, any or all of which may be remote located via the RS -485 serial interface. • Easy to read backlit LED display, low pow( consumption. • Listed under UL Standard 864, 9th Edition. Specifications Operating Voltage: Alarm Current: Operating Current: Operating Temperature: Relative Humidity: 24 VDC FWR (from PM -9 power supply) 0.028 amp. 0.024 amp. 32' to 120° F (0° to 49° C) 0 to 93%, non -condensing E 90° F (32° C) An ISO 9000-2000 Company SIGNALING City of Chicago �L rM MEA 0 Approved City of USTED urxovee Appro�c r Class 1 DENVER 81869 902541E PENDING 71650694 2E8 • Class 2 Approved 71650694 2E9 . High Rise FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090—Tel 781-471-3000—Fax: 781-471-3099 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by fire Control Instruments for their use. 02005 Fire Control Instruments. Airghtsreseved. www.firecontrolinstruments.com 9020-0606 Rev.0 page oft ® FIRE CONTROL INSTRUMENTS by Honeywell Description The ASM -16 Addressable Switch Module is a component of NetSOLOT" and E3 SeriesTM fire alarm and voice evacuation systems. It serves as the point of interface between an operator and the system's audio evacuation, fire fighter intercom, and building control circuits. The ASM -16 is a configurable switch input sub -assembly with sixteen (16), switches and forty-eight (48), status LEDs and may be remotely located via the RS -485 serial interface. Each ASM -16 addressable switch module has sixteen (16), push-button switches that can be programmed to serve any function the application demands. An ASM -16 switch can be programmed as a speaker circuit switch, fire fighter phone switch, an auxiliary control switch using a bank of three (3), switches (one switch each for on -off -auto functions), or switches with custom defined functions (e.g. system reset, system silence, system acknowledge, all -call, phone patch, lamp test, alarm tone on, manual select, etc.). Each ASM -16 switch also has three (3), fully programmable LEDs in red, yellow, and green. These LEDs can be programmed to work in concert with their associated push-button switch or they can be made to work independently as status indicators (e.g. on, off, normal, etc.). An INI-VGC assembly or ILI-MB-E3 can accommodate up to sixteen (16), ASM -16 modules for a total of 256 switches and 768 LEDs. Specifications Operating Voltage: 24 VDC (nominal) (from PM -9 power supply) Operating Current: 0.011 amp (with no LEDs lit) Operating Temperature: 32° to 120' F (0° to 49° C) Relative Humidity: 0 to 93% (non -condensing) at 90° F (32° C) E3 Sede$TM and NetSOLOTM are trademarks of Fire Control Instruments. ASM -16 Addressable Switch Module Front View Rear View Features • Each INI-VGC supports up to sixteen (16), ASM -16 switch modules for a total of 256 switches. • Each ILI-MB-E3 supports up to sixteen (16), ASM -16 switch modules for a total of 256 switches. • Each ASM -16 switch has three (3), fully programmable status, indicating LEDS: red, yellow, and green. • All switch functions are fully software programmable. • Slip -in label inserts allow easily modified switch designations. • Listed under UL Standard 864, 9th Edition. Ordering Information Model Description A M-16 Programme a switch modu De An ISO 9001-2000 Company 310NALmS City of Chicago Approved City of LISTED APPROVES MEA . Class 1 DENVER 3166E 3D17516 217.03E 069110694257• Class 2 Approved • High Rise FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood, MA 02090—Tel: 781-471-3000—Fax: 781-471-3099 Specifications are for information only, are not Intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Fire Control Instruments for their use. •2005 Fire Control instruments. All rights reserved, www.firecontrolinstruments.com 9020-0554 Rev. G page 1 of 1 ^Gamewell ANI FIRE CONTROL FRINSTRUMENTS by Honeywell Description The Gamewell-FCI, Addressable Node Expander (ANX) is a networking interface board that is used to expand the overall E3 Series® capabilities in the system node count, FocalPointO integration and Ethernet connectivity. This powerful interface provides greater data exchange between the following units. • E3 Series FACP • FocalPointGraphicalWorkstation • S3 Series FACP • Installer's PC The ANX allows the E3 Series and S3 Series Networks to expand to two rings. Each ring contains up to 61 nodes, not including the ANX. By bridging the two networks together, each of the E3 and S3 network node counts are increased to 122 nodes. The multi -ring network expansion can activate outputs on any node on the bridged networks including the Control -by -Event functions originating from a connected network (See Figure 1 -Shared Ring Capability). Audio paging and voice messages are also transferred over the two networks through the ANX. The use of the ANX's Ethernet port allows the communica- tion between the E3 Series System, the FocalPoint Gate- ways and Workstations through the TCP/IP. From the FocalPoint Workstation, you can activate "virtual switches" in the ANX for CAM control and status monitoring which might include bypass, control switching, voice evacuation notification or any auxiliary control function. Installers can use the ANX's Ethernet port for high-speed configuration downloading into either of the E3 Series or S3 Series rings, saving time over using the typical RS -232 connections. The ANX can also be used as a downloading gateway for commissioning and is not required to be a part of the system. The ANX expands the operation of the E3 network so that it can support both Mass Notification and Emergency Com- munication System applications used in campuses, large industrial or manufacturing facilities, hospitals, high-rise and multi -building complexes. The following three types of ANX sub -assemblies provide Ethernet connectivity via an Ethernet port. • Addressable Node Expander- Single Ring (ANX-SR). - contains a single E3 Series local network connection. • Addressable Node Expander - Multi -Ring Twisted -Pair (ANX-MR-UTP) contains the following: - a primary and secondary network interface for multi - ring communication. - includes twisted -pair copper (UTP) on the secondary network connection. • Addressable Node Expander- Multi -Ring Fiber Optic (ANX-MR-FO) contains the following: - primary network interface for multi -ring communication. - a fiber-optic (FO) connectivity on the secondary network connection. Addressable Node Expandfi ANX Features Complies with UL® Standard 864 (9th Edition) • Expands the E3 and S3 Networks to two rings, contair Ing 122 nodes allowing a multi -ring network expansion • Provides expanded data exchanges between the E3 network and the FocalPoint Graphic Workstation. • Includes high-speed configuration downloading througl the ANX Ethernet port. • Installed in the standard E3 Series cabinet enclosures • Bridges two of either the E3 Series or S3 Series Net- works to activate outputs on any node on bridged net- works. • Offers shared ring capability. FocalPoint Features • Displays device descriptions for points on events only. • Shows a single icon per SLC device. • Provides up to 512 Virtual Points for programmable control and status monitoring within FocalPoint for: - System control switch (Enable/Disable, Bypass). - Voice evacuation speaker circuit control switch. - Auxiliary control circuit switch. • Provides Ethernet connectivity to allow a high speed supervised connection to the FocalPoint Gateway. • Includes additional point information to the end user. • Allows the user to send the following commands over the E3 Network. - Acknowledge - Reset - Silence - Enable/Disable • Shows the current status on the E3 and S3 networks. • Sends the time to the E3 and S3 networks. sc191rv�11AUNc MEA CA d� FM LISTED a oem 51869 3926416 COA46077 7165170.7:6126 IS09001GAMEWELL-FCI „pTY ..T ... 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to Mange without notice. No responsibility is assumed by Gamewell-KI for their use. ®2013by Honeywell International Im. Allrightsmsened. www.gamewell-fcl.com 9021-60497 Rev. E page 1 of 2 EOornot TCplip Wo,M,Nlbn Is soft, en ^ ��� sway, 62 Node E3 Serbs Network Addreeeeblefil Expender E3 earn. Broadband e\ Network 62 Node E3 Berle, Network Figure 1: Addressable Node Expander Connection in a Multi -Ring Network Expansion Configuration :thernet he Addressable Node Expander uses TCP/IP and incor- orates heavy PPUPSU re -use of the mainstream compo- ents. The three types of ANX sub -assemblies can rovide Ethernet connectivity via an Ethernet port. This :thernet port offers an enhanced network interface etween the E3 Series and S3 Series fire alarm control anal and the FocalPoint Graphic Workstation. This fee - ire improves the communication to monitor the alarm upervisory and trouble conditions of the FocalPoint iraphic Workstation. The E3 Series configuration data an be loaded into the network nodes via the ANX Ether - et port and CAMWorks TN t Download program utility is provided to extract data axcluding the CAMs and voice files on the INI-VG Series) no a job file that allows the ANX to extract all point infor- iation in existing panels. The following list the information iat can be retrieved from the ANX. Custom labels programmed to identify each point. System information that details the configuration of analog addressable monitor and control points Information stored in the CAMWorks job file Compare feature to display configuration differences Converts low level CAMs into corresponding high level CAMs during the download of the CAMWorks configu- ration data for the following node types: - ILI-MB-E3 - ILI-S-E3 - ILI95-MB-E3 - ILI95-S-E3 -NGA -ANX - SLP -E3 3 Series®and FocalPoint®are registered trademarks of Honeywell International Inc. AMWorks- is a trademark of Honeywell International Inc _6 is a registered trademark of underwriters Laboratories Inc. Specifications Operating Voltage: 24 VDC (from the PM-9/PM-9G power supply) Operating/Supervisory Current: 0.066 amp Alarm Current: 0.066 amp Operating Temperature: 32° to 120° F (00 to 490 C) Relative Humidity: 0 to 93%, non -condensing at 90° F (32a C) Supervised Wiring Specifications: (ANX-MR-UTP & ANX-MR-FO only): Copper Wire: 16 to 18 AWG twisted -pair, unshielded. Up to 3,000 feet (914.4 m) between each node. Fiber -Optic Cable Up to 200 microns (optimized (ANX-MR-FO only): for 62.5/125 microns). Up to 8 d6 loss between each node. Ordering Information Part Number Description ANX-SR Addressable Node Expander -Single Ring ANX-MR-UTP Addressable Node Expander -Multi -Ring Twisted -Pair ANX-MR-FO Addressable Node Expander -Multi -Ring Fiber Optic GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60497 Rev. E page 2 of 2 www.gamewell-fci.com ^Gamewell a � FIRE CONTROL INSTRUMENTS by Honeywell Description The ARCNET Repeater Module (RPT -E3) is an optional component of the E3 Series® and S3 Series fire alarm con- trol panels. It allows the following remotable E3 Series and S3 Series sub -assemblies to connect to the Broadband network from the remote locations: • ILI-MB-E3/ILl95-E3 Series • S3 Series, SLP (Smart Loop Panel) • ANX-SR/ANX-MR-UTP/ANX-MR-FO • NGA The RPT -E3 comes standard with network connections using unshielded, twisted -pair, copper wire. The following optional fiber-optic network connections using add-on modules are available. • FML -E3 multi -mode fiber module (optional) • FSL-E3 single -mode fiber module (optional) Installation The RPT -E3 is adaptable for an installation in the standard E3 Series and S3 Series cabinets. Typically, the RPT -E3 module is mounted on standoffs on the top of the right side of the ILI-MB-E3/ILI95-MB-E3/ANX modules and SLP motherboard. For instructions on the installation of the RPT -E3, refer to the following documents: • E3 Series® Expandable Emergency Evacuation Installation/Operation Manual, P/N: 9000-0574 • RPT -E3 -UTP Installation Instructions, P/N: 9000-0580 • S3 Series UL Listing Document, P/N: LS10005-051GF-E Specifications Operating Voltage: 24 VDC FWR Operating Current: 0.016 amp Alarm Current: 0.017 amp Operating Temperature: 320 to 120° F (0° to 49° C) Relative Humidity: 0 to 93%, non -condensing at 90° F (32° C) Wiring Specifications: Copper Wire: 16 to 18 AWG twisted -pair, unshielded Up to 3,000 ft. (914.4 m) between each node. Fiber -Optic Cable: Up to 200 microns (optimized for (FML -E3 only) 62.5/125 microns). Up to 8 dB loss between nodes. Fiber -Optic Cable: Optimized for 9/125 micrometer (FSL-E3 only) cable) @ 1310 nm. Up to 30dB loss between nodes. E3 Seneswis a registered trademark of Honeywell Intemaflonal Inc. UL® is a registered trademark of Underwriters Laboratories Inc. HMO Network RepeatE RPT -E3 -UTP Features Listed under UL® Standard 864, 9th Edition. Provides the capability for networked E3 Series and Series sub -assemblies to connect in Styles 4 or 7 configurations. Standard with unshielded, twisted -pair copper wire network connection. Add-on fiber-optic modules allow the network connel tion through single or multi -mode fiber-optic cables. 625K baud ARCNET Repeater. Ordering Information Part Number Description RPT -E3 -UTP Network Repeater, unshielded, twisted-pai. FML -E3 Multi -mode fiber-optic module for RPT -E3 -UTP (one channel) FSL-E3 Single -mode fiber-optic module for RPT -E3 -UTP (one channel) SIGNALING UL OMEACho, of PM APprwee ChIwIp CltYpf LISTED v.,0 FDNY: 9 Apprmed Denier 51869 3026415 COA #6077 7165-1703:0125 c,—, Approves GAMEWELL-FCI r^t®t.""' 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for Information only, are not intended for installation purposes, and are suKI to change without notice. No responsibility is assumed by Gamewell-FCl for their use. 02013 by Honeywell International Inc. All rights reserved. Www.gameWBll- cLCom 9020-0609 Rev. L page 1 of 1 �Gamemll ®FIRE CONTROL INSTRUMENTS by Honeywell Description The Gamewell-FCI, FML -E3 (Fiber -Optic Multi -Mode) and FSL-E3 (Fiber -Optic Single -Mode) are plug-in fiber loop modules. The two types of fiber option modules are used as one channel to transmit or receive communications with the Gamewell-FCI, RPT -E3 -UTP (Network Repeater), ARCNET communication circuit. The following describe the two types of fiber option modules. • The FML -E3 is a fiber module that allows the multi - mode fiber to network between nodes. It features ST - style connectors with a maximum attenuation of 8db with 62.5/125 micrometer cable. • The FSL-E3 is a fiber module that allows the single - mode fiber to network between nodes. It features LC - style connectors with a maximum attenuation of 30db with 9/125 micrometer cable. Each fiber loop module can Transmit (TX) or Receive (RX) fiber-optic cable connecting to the RPT -E3 -UTP. Up to two fiber loop cards can be added to the RPT -E3 -UTP, and both cards may be combined in the same configuration. Installation The FML-E3/FSL-E3 modules are designed to be plugged - into their designated spots on the RPT -E3 -UTP. Specifications Ordering Information Part Number Description FML -E3 Fiber Loop Module - Multi -mode fiber, single TX or RX channel for RPT -E3 -UTP FSL-E3 Fiber Loop Module - Single -mode fiber, single TX or RX channel for RPT -E3 -UTP RPT -E3 -UTP Network Repeater, unshielded twisted -pair for E3 or S3,optional FML -E3 or FSL-E3 fiber modules UL®is a registered trademark of Underwriter's Laboratories Inc. FML -E3/ FSL-E3 Fiber Loop Modules FML -E3 (Multi -Mode Fiber) FSL-E3 (Single -Mode Fiber) Features • Listed per ANSI/UL® Standard 864 9th edition. • FML -E3 features ST -style connectors with a maximum attenuation of 8 dB with 62.5/125 micrometer cable • FSL-E3 features LC -style connectors with a maximum attenuation of 30db with 9/125 micrometer cable. • Offers the option to combine single and multi -mode modules on the same network card. • Provides a simple, plug-in card installation. SIGNALING U@ LISTED S1869 7165-1703:0176 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 specifications are for intonation only, are not intended for installation puryoses, and are sub act to change without notice. No responsibility is assumed by Gamewel6FC1 for their use. well•I ®2013 by Honeywell International Inc. All rights reserved. www.gamecl.com 9021-60783 Rev. B page 1 of 1 FML -E3 FSL-E3 Connections: ST style LC style Cable type: 62.5/125 9/125 micrometers micrometers Operating Current: 0.053 amp 0.079 amp Alarm Current: 0.053 amp 0.079 amp Operating Temperature: 32° to 120° F (0° t0 49° C) Relative Humidity: 0 to 93%,non-condensing at 90° F (32° C) Ordering Information Part Number Description FML -E3 Fiber Loop Module - Multi -mode fiber, single TX or RX channel for RPT -E3 -UTP FSL-E3 Fiber Loop Module - Single -mode fiber, single TX or RX channel for RPT -E3 -UTP RPT -E3 -UTP Network Repeater, unshielded twisted -pair for E3 or S3,optional FML -E3 or FSL-E3 fiber modules UL®is a registered trademark of Underwriter's Laboratories Inc. FML -E3/ FSL-E3 Fiber Loop Modules FML -E3 (Multi -Mode Fiber) FSL-E3 (Single -Mode Fiber) Features • Listed per ANSI/UL® Standard 864 9th edition. • FML -E3 features ST -style connectors with a maximum attenuation of 8 dB with 62.5/125 micrometer cable • FSL-E3 features LC -style connectors with a maximum attenuation of 30db with 9/125 micrometer cable. • Offers the option to combine single and multi -mode modules on the same network card. • Provides a simple, plug-in card installation. SIGNALING U@ LISTED S1869 7165-1703:0176 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 specifications are for intonation only, are not intended for installation puryoses, and are sub act to change without notice. No responsibility is assumed by Gamewel6FC1 for their use. well•I ®2013 by Honeywell International Inc. All rights reserved. www.gamecl.com 9021-60783 Rev. B page 1 of 1 ^Gamewell FRINSSTCRUMEISM by Honeywell Description The Gamewell-FCI, FocalPoinr Graphic Workstation is a PC-based graphic user interface that connects to the 7200, 7100, E3 Series® or 600 Series of fire alarm control panels via the Gateway interface. It can be connected to a propri- etary or shared TCP/IP network. The FocalPoint Worksta- tion is a high-performance industrial computer that provides text and color graphic display of fire alarm control panel network events and locations. This central command station displays systems' activities in real-time. One work- station has the capacity of simultaneously monitoring multi- ple FocalPoint Gateways that can be connected to the following systems: • Standalone 600 Series • 600 Series Networks • Standalone 7100 • 7100 NetSOLO® Networks • Standalone E3 Series • E3 Series Networks • 7200 Series The FocalPoint Graphic Workstation supports a broad scope of commercial, industrial and institutional applica- tions. The system can be configured to monitor multiple systems installed in remote locations to meet the facility requirements of multi -building complexes. The Workstation is used as a decision support tool by facil- ities management and security personnel. This workstation uses graphic images to display information that allows per- sonnel to quickly evaluate the emergency and make prompt and informed decisions. From a single screen, a workstation operator can: • Magnify the facility map using the "zoom in" and "zoom out' feature to view Floor plans or identify the location and type of multiple events. • Monitor remote site activity and link multimedia (text, audio, video, and bitmaps) to any device. • View the event history log on the same screen as the facility Floor plans to evaluate the sequence of events. • Print reports of system -wide events in real-time. • Display History Manager records for operator, event, and response (with time and date stamp to disk). U Sedes®, FocalPoinfSandNet50100 are registered trademarks of Honeywell International, Inc. Core- Is a trademark of Intele Corporation. Wo is a registered trademark of Underwriters Laboratories. Microsoft® Windows® is a registered trademark of Microsoft® Corporation. Focaftiffi° Graphic Workstatioi PC -Based Graphic User Interfac, FocalPoint Graphic Workstation Features • Listed under UL® Standard 864, 9th Edition • Flexible Remote Control - Using the workstation with the 7200 Series, E3 Series® and 600 Series, the follow ing fire alarm functions can be activated via remote control: - Acknowledge - Reset - Silence • User -Friendly System Setup - Import facility floor plans as Wndows® graphic bitmaps or Windows® graphic meta files • Secure Access - Security profiles provide multiple level of access to different user types • Improved System Maintenance - Reports and logs trouble events • Automatic Screen Navigation -(selectable for each device) that locates and zooms to the device related tc an alarm or event, based on the priority of the event • Backup capability - System backups for screen, user, c history databases. All software is backed up on CD -RU • Information Labels - Identify Hazardous Material (HAZMAT) and handicapped accessible areas using fully linked multimedia An ISO 9000.2000 Company SIGNALING LISTED S5526E0 55526 7300-1703:168 65697 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for Information only,m lot intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. 02010 by Honeywell International, Inc. All dghk •)served. www.gamewell-fci.com 9020-0647 Rev. G page 1 of 4 )escription (Continued) se this graphic workstation to evaluate complex situations id quickly make strategic decisions when monitoring the ,a alarm control system. During an emergency, where formation must be evaluated in seconds, using a small, CD screen to navigate a fire alarm control panel is ardu- us and time-consuming. The Workstation greatly simpli- as the management of medium to large size fire alarm )ntrol systems. Operators can use this workstation to ew the status of multiple fire alarm systems and track ystem events in real-time from a central location. ocalPoint Workstation: Rack -mountable 2.16 GHz Intel® Core TM 2 Duo processor with 2 GBytes of RAM. 19" (48 cm) flat -screen LCD monitor, capable of 1024 x 768 display resolution with sound card and speakers. Operates under Microsoft® Windows® XP Professional SP2. UL 864 9th Edition Listed. iraphics: Graphic editing mode allows on-site programming of floor plan screens, device icons, functional and navigational buttons. Imports the following types of converted vector drawing files from CAD floor plan drawings: -.V\/MF -.JPG -.BMP -.GIF Graphics printing of floor plans and reports. Custom-designed, device icon colors that represent each event type. linimum System Requirements: Intel® Pentium® IV, 2.0 GHz processor. Graphics card capable of supporting 1024 x 768 screen resolution. Auxiliary ports: - One (1), RS -232 port and serial cable for event printer operation. - One (1), parallel printer port for graphics printing. - One (1), USB port for software key. 1 GB RAM. 20 GB. CD -RW drive. Audio with speakers. Microsoft Wndows®XP Service Pack 2. Microsoft serial PS/2—compatible mouse. 101 -key keyboard. letwork: Ethernet network. Fom[Point Gateway FocalPoint Gateway The FocalPoint Gateway is a powerful interface that pro- vides the capacity to monitor multiple networks installed in remote locations. The gateway interfaces with the 7200, 7100, E3 and 600 Series standalone and network product lines via the panel's RS -232 port. In addition, the gateway can be used to connect to the FocalPoint Graphic Worksta- tion via a standard Ethernet TCP/IP networking. Using a wireless connection, the gateway can also transmit to the non -control, FocalPoint Mobile Workstation. Figure 1 illustrates the adaptable, flexibility of the FocalPoint Gateway to connect to any of the following types of network installation options: • Option 1: E3 Series network. • Option 2: 600 Series network. • Option 3: 7100 NetSOLO Broadband network connected to the E3 Series Panel. • Option 4: E3 Series standalone. • Option 5: 600 Series standalone. • Option 6: 7100 Series standalone. • Option 7: 7200 Series standalone. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0647 Rev. G page 2 of 4 www.gamewell-fci.com Control Capabilities Panel Acknowledge Silence Reset Enable/Disable Comments 600 Series Standalone Yes Yes Yes Yes Control Panel 600 Series Network Yes Yes Yes Yes 7200 Yes Yes Yes Yes Direct Connect 7100 Standalone No No No No Monitor only 7100 on E3 Network Yes Yes Yes No Connect through E3,7100 Series Network must have U -MB -E3. E3 Series Standalone Yes Yes Yes Yes Enable/Disable requires ILI/ILI95-E3 Series 1.4 Firmware and FPT3.12 or greater. E3 Series Network Yes Yes Yes Yes Enable/Disable requires ILI/I1-I95-E3 Series 1.4 Firmware and FPT3.12 or greater. 600 Series E3 SeriesW)INeivork E3 Series Ni BroadbandBroadband Network JE3 Series Broadband Network IF610 INX AAio INCC TmW ldff_.__ Command Center E3 Series Fire Alarm Control Panel over the E3 Series Network tRS232 Wlre FocalPoint Option 4: Option 6: E3 Series 600 Series Standalone Standalone Fire Fire Alarm Alarm Control Panel Control Panel Te9 roeN �a®u�irt�a Nuw.d 600 Series F602 Option 2: 600 Series over the 600 Series NetSOLO NBtSOLO Broadband / Broadband Netw,r Network NotSOLO Broadband R\Netnork Iampw Trder777��� \ I NCC Nx AudConnN,Idntl Center 7100 NetSOLO Broadband Network connected to the E3 leries Panel RS232 Wlre Standard TCP/IP 1 Ethernet Network 1 RS232Wre RS232 Wire _ FaolPpnt R Gaeway3 G FocalPoint Graphic Focall oint Mobile Workstation Workstation option 6: Option 7: 7100 Series 7200 Series Standalone Fire Alarm Fire Alarm Control Panel FocalPoine Network Control Panel Figure 1 FocalPoint Gateway Installation Options GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9020-0647 Rev. G page 3 of 4 ocalPoint Graphic Workstation Screens he FocalPoint Graphic Workstation provides the following (pes of graphic displays. Figures 2 and 3 illustrate the creens. FocalPoint Graphic screen FocalPoint text mode screen Displays system layout from CAD floor plan drawings Figure 2 FocalPoint Graphic Figure 3 FocalPoint Text Mode Specifications CPU 19"Wx7"Hx17.7"D Dimensions: (48.3 x 17.8 x 45 cm) weight: 39 lbs. (17.7 kg) CPU AC Input: Electrical: (frequency 50/60 Hz), 7.0 A @ 115 V (95-132 V), 4.0 @ 230 V (185-264 V) Monitor 19" (48 cm) flat -screen LCD color monitor Dimensions: 16.5" W x 17.2" H x 7.8" D (42 x 44 x 20 cm) weight: 15.6 lbs. (7 kg) Monitor AC Input: Electrical: (frequency 50/60 Hz auto -adjust) 1.8 A @ 120 - 240 VAC. Power consumption: 43 wafts (maximum) Ordering Information Part Number Description FPT-GATE-3 FocalPoint Gateway includes gateway, surge suppressor (PNET -1), cables and cabinet FPT-WKS FocalPoint graphical user interface soft- ware for network annunciation. Worksta- tion UL Listed PC included. (UL Version) FPT FocalPoint graphical user interface soft- ware for network annunciation. Worksta- tion PC not included. (non -UL Version) FPT-MOBILE FocalPoint Mobile Tablet for PC used for non -control network annunciation (Optional) GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 X20-0647 Rev. G page 4 of 4 www.gamewell-fci.com ^Gamewell O INE byby Honeywell Description The Gamewell-FCI Velociti® Series, analog address- able plug-in smoke sensors with integral communica- tion provide features that surpass conventional sensors. Sensitivity can be programmed in the con- trol panel software, and is continuously monitored and reported to the panel. Point ID capability allows each sensor's address to be set, providing exact locations for selective maintenance when the cham- ber contamination reaches an unacceptable level. The ASD-PL2F photoelectric sensor's unique optical sensing chamber is engineered to sense smoke pro- duced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed -tem- perature thermal sensing on the ASD-PTL2F model. The Velociti® Series use a communication protocol that substantially increases the speed of communica- tion between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and concen- trates on the single device. The net effect is a response speed up to five times greater than earlier designs. Ordering Information Model Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing ASD-PL2FR Analog, addressable photoelectronic smoke sensor used with the DNR duct base when the remote test is required. velocitie is a registered trademark of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. Velociti° Serie' ASD-PL2F, ASD-PT1,21 and ASDANI Analog, Addressable Photoelectroni ASD-PL2FIASD-PTL2F Features Smoke Sensc ASD-PL2FR • Sleek, low -profile design • Visual rotary, decimal switch addressing (01-159) • Built-in functional test switch activated by an external magnet • Bicolor LEDs flash green whenever the sensor is addressed, and light steady red on alarm* • Optional relay, isolator, or sounder bases • Low standby current • Analog addressable communication • Stable communication technique with noise immunity • Optional remote, single -gang LED Indicator (RA100Z) • Compatible with Gamewell-FCI analog addressable panels Note: `Only the red LED is operative in panels that do not opera in Velociti® mode. An ISO 9001-2000 Company SIGNALING �y UI. FM8> MEA LISTED S1913 3023594 219.02-EV01.111 7272.1703:0121 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-PCI for their use. 02011 by Honeywell International Inc. All rights reserved. www.gamewell-fel.com 9020-0617 Rev. l page l of nstallation SD-PL2F plug-in sensors use a separate base to implify installation, service, and maintenance. A pecial tool allows maintenance personnel to plug-in nd remove sensors without using a ladder. lount the base on a box which is at least 1.5 (3.8 cm) eep. Suitable mounting base boxes include: 4.0" (10.2 cm) square box 3.5 (8.9 cm) or 4.0" (10.2 cm) octagonal box Single -gang box (except relay or isolator bases) With B200S or B200SR base, mounted on a 4.0" (10.2 cm) octagonal or square box With B224RB or B22481 base, mounted on a 3.5' (8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box TOTE: Because of the inherent supervision provided y the SLC, end -of -line resistors are not required. Viring "T -taps" or branches are permitted for Style 4 :lass "B") wiring. ensor Spacing iamewell-FCI recommends that the spacing sensors e used in compliance with NFPA 72. Specifications ASD-PL2F, ASD-PTL2F, ASD-PL2FR: Dimensions: 2.1" (5.1 cm) height Diameter: 4.1" (10.4 cm) installed in the 8501 base Dimensions: 6.1" (15.5 cm) installed in the B21OLP base Shipping Weight: 5.2 oz. (147 g) Operating ASD-PL2F: Temperature: 32° F to 120° F (0° C to 49° C) Dimensions: ASD-PTL2F: B224RB 32° F to 100° F (0° C to 38° C) UL® -Listed 0-4000 ft./min. (1,219.2 m/min.), Velocity Range: suitable for installation in ducts. Relative 10-93% (non -condensing) Humidity: Up to 14 AWG (2.0 mm2) Thermal Ratings: Fixed -temperature setpoint 135° F (57° C) Electrical Specifications Voltage Range: 15 - 32 volts DC peak Standby Current: (max. avg.):.0003 A @ 24 VDC (one communication every 5 seconds with LED blink enabled) Maximum Alarm - Current: .0065 A @ 24 VDC (LED) lit). Bases and Options 8501 Plug-in sensor base without Flange Dimensions: 4.1" (10.4 cm) diameter B21OLP Flanged mounting base Dimensions: 6.1" (15.5 cm) diameter B21OLPBP Flanged mounting base bulk pack Dimensions: 6.1" (15.5 cm) diameter B224RB Plug-in sensor base with auxiliary Relay Base relay, SPDT, rated 2 amps @ 30 VDC (resistive) Screw terminals: Up to 14 AWG (2.0 mm2) 2 coil latching relay 1 Form C contact UUCSA Rating: 0.9 A @ 125 VAC, inductive 0.9 A @ 110 VDC, inductive 3 A @ 30 VDC, resistive Dimensions: 6.1" (15.5 cm) diameter Maximum: 25 devices between isolator bases. B200S Intelligent sensor sounder base Dimensions: 6.875' (17.5 ren) diameter B200SR Standard sounder base, UL 8649th Edition compliant, ULC Listed Dimensions: 6.875" (17.5 cm) diameter RA10OZ Remote LED Annunciator BCK-200 Black detector covers (box of 10) DNR Duct smoke housing GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0617 Rev. I page 2 of 2 www.gamewell-fel.com REL^aGamewll 10INSTUUMNTS by Honeywell Description The Gamewell-FCI Velociti® Series, addressable plug-in thermal sensors with integral communication provide fea- tures that surpass conventional sensors. Point ID capabil- ity allows each sensor's address to be set, providing exact locations for pinpointing alarm locations and for selective maintenance. ATD thermal sensors use an innovative thermistor sensing circuit to produce 135aF/57aC fixed - temperature (ATD-1-21F). The ATD-RL2F provides a combi- nation 15a/minute rate -of -rise with 135° fixed thermal detection that is included in a low -profile package. The ATD-HL2F provides fixed high-temperature detection at 190aF/880C. These thermal sensors provide cost-effective, addressable property protection in a variety of applica- tions. The Velociti® Series uses a communication protocol that substantially increases the speed of communication between the sensors and Gamewell-FCI analog address- able fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and identifies the single device with the status change. The net effect is response speed up to five times greater than earlier designs. Installation ATD plug-in sensors use a separate base to simplify instal- lation, service, and maintenance. A special tool allows maintenance personnel to plug-in and remove sensors without using a ladder. Mount the base on a box which is at least 1.5" (3.8 cm) deep. Suitable mounting base boxes include: • 4.0" (10.2 cm) square box. • 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box. • Single -gang box (except relay or isolator base). • With B200S or B200SR base, mounted on a 4.0" (10.2 cm) octagonal or square box. • With B224RB or B224BI base, mounted on a 3.5" (8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box. NOTE: Because of the inherent supervision provided by the SLC, end -of -line resistors are not required. Wiring "T - taps" or branches are permitted for Style 4 (Class "B") wiring. Velociti® and E3 Series® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. 1 u r®;• a —;stem frodemar4 of I Inderwdfi.rs I aMratndea Canada Inc. Velociti° Series ATI-L2F, AT8=RL21 Addressable Thermal Senso ATD-L2F Features Sleek, low -profile design Visual rotary switch addressing • Built-in functional test switch activated by an external magnet • Bicolor LEDs flash green whenever the sensor is addressed, and light steadily red on alarm' • Optional relay, isolator, or sounder bases • Low standby current • Addressable communication • Stable communication technique with noise immunity • Optional remote, single -gang LED accessory (RA -100Z) • Suitable for installation in ducts Note: *Only the red LED is operative in panels that do not opera'. in Velociti® mode. An ISO 9001-2000 Company SIGNALING yg &LFM LISTED AeO Approved MEA 52332 3023594 219.02-E VoLVI 72701703:0115 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for infolmaton only, are not Intended for installation purposes, and are subject to change without nolice. No responsibility is assumed by Gamewell-FCI for their use. ®2011 by Honeywell Intemagonal Inc. All rghls reserved. www.gamewell-fcl.com 9020-0620 Rev. E page 1 of 2 Specifications 4TD-L2F/ATD-RL2F Dimensions: 2.1"(5.3cm) Height Options 4.1" (10.4 cm) diameter installed in Plug-in sensor base without flange the B501 base 4.1" (10.4 cm) diameter 6.1" (15.5 cm) diameter installed in Flanged mounting base the B21OLP base Shipping Weight: 4.8 oz. (137 g) Dperating Dimensions: temperature: B224RB ATD-L2F or ATD-RL2F -4° F to 100° F (-20° C to 38°C) ATD-HL2 -4° F to 150°F (-20 C to 66°C) Sensor Spacing: UL® approved for 50 ft. (15.2 m) 0.9 A @ 125 VAC (inductive) center to center 0.9 @ 110 VDC (inductive) FM approved for 25 x 25 ft. 3.A @ 30 VDC (resistive) (7.6 x 7.6 m) spacing Relative Humidity: 10 - 93% (non -condensing) ATD-L2F Fixed -temperature setpoint operation 135-F (57-C) ATD-RL2F Combination 135° F fixed Maximum 25 devices between isolator temperature and 15° F(8.3°c)/per bases minute rate -of -rise° ATD-HL2F Fixed -temperature setpoint 6.875' (17.5 cm) diameter 190-F (88-C) Electrical Specifications Voltage Range: 15 - 32 Volts DC peak Standby Current: 200 mA @ 24 VDC (without communication) (max. avg.) .0003 A @ 24 VDC (one communication every 5 seconds with LED blink enabled) LED Current (max.) .0065 A @ 24 VDC (LED lit) Specifications Bases and Options B501 Plug-in sensor base without flange Dimensions: 4.1" (10.4 cm) diameter B21 OLP Flanged mounting base Dimensions: 6.1" (15.5 cm) diameter B21OLPBP Flanged mounting base bulk pack Dimensions: 6.1" (15.5 cm) diameter B224RB Plug-in sensor base with auxiliary relay, SPDT 2 coil latching relay 1 Form C contact UL/ CSA Rating: 0.9 A @ 125 VAC (inductive) 0.9 @ 110 VDC (inductive) 3.A @ 30 VDC (resistive) Dimensions: 6.1" (15.5 cm) diameter B224BI Plug-in sensor isolator base for Style 7 operation Dimensions: 6.1" (15.5 cm) diameter Maximum 25 devices between isolator bases B200S Intelligent sensor sounder base Dimensions: 6.875' (17.5 cm) diameter B200SR Standard sounder base, UL 864 9th Edition compliant, ULC Listed Dimensions: 6.875' (17.5 cm) diameter RA -1002 Remote LED Annunciator BCK-200 Black detector covers (box of 10) Ordering Information Part Number Description ATD-L2F Addressable thermal sensor, fixed, 135° F ATD-RL2F Addressable thermal sensor, combination fxed,135° F and 15°/minute rate -of -rise. ATD-HL2F Addressable thermal sensor, fixed, 190* F GAMEWELL-FCI Clintonville Road, Northford, CT 06472-1610 USA •Tel: (203) 484-7161 •Fax: (203) 484-7118Ej:7 2 of 2 www Ww.gamewell-fcl.com ^Gamewell 0 .® FIRE CONTROL INSTRUMENTS by Honeywell Description The B200S Velociti® sounder bases sets a new stan- dard for performance, installation, and aesthetics. The B200S is designed for new and existing dwelling unit applications. It offers maximum flexibility in installation, configuration, and operation to meet or exceed the UL® Standard 268 and UL® Standard 464 requirements. One of the unique features of the B200S sounder base offers the functionality "to capture" the commu- nications transmitted between the attached sensor head on the ILI-MB-E3 or the ILI-S-E3 signal line loop of the E3 Series® fire alarm control panel. This new feature allows the E3 Series fire alarm control panel to use the same address as the detector, but use a unique device type on the loop. Using the CAMworksTM Tool, the E3 Series control panel can then use that same address to command and acti- vate an individual sounder or a group of sounders. In CAMWorks, you can program the command set from the E3 Series control panel to a specific event which allows you to select the volume, tone and group. In addition, the E3 Series control panel gen- erates synchronization pulses through the loop and enables selectable tone patterns. With its attractive aesthetics, the B200S is ideal to use for applications where the appearance is critical. For example, to eliminate unsightly surface -mount boxes, the sounder base employs a separate mount- ing plate that can be installed on various junction box sizes. In addition, the mounting plate enables pre - wiring of all connections to simplify the installation. The housing is installed with the mounting plate and is locked in position with two retaining screws. The retaining screws are covered by the installed sensor head for added tamper resistance. E3 Series® and Velocity are registered trademarks and CAMWorks*" is a trademark of Honeywell International Inc. uL® Is a registered mdemark of underwriters Laboratories Inc. Intelligent Sensor Sounder Base B200S Features Built-in supervision (no EOL relays required) Complies with UL® Standard 268 and UL® Standard 464 Offers a programming option to control and acti- vate the sounder base independently Programs the addressability for maximum config-i uration flexibility Broadcasts over two volume levels (75 or 85 dBA) Has multiple event -driven tone outputs and uses custom tone capability with the E3 Series fire alarm control panels Supports Continuous, ANSI Temporal 3, ANSI Temporal 4, and March Time tones - Employs coded patterns that may be optionally syncrhonized over the SLC and promptly changed Synchronized with other System Sensor notifica- tion devices Includes a pre -wire mounting plate that fits various junction box sizes Uses a mechanical locking feature that prevents the removal of the attached sensor head An ISO 9001.2000 Company SIGNALING �9 UL PM °8° LISTED wRRROVFO S1911 3036027 71351653:0213 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to charge without notice' responsibility is assumed by Gamewell-I'D for Meir use. 02011 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60671 Rev. A page 1 of 2 Specifications 3hysical Specifications: Base Diameter: 6.875' (17.46 cm) Base Height: 2.0" (5.08 cm) less sensor Shipping Weight: 0.50 lb. (227 gm) )perating 35 mA maximum (high volume) remperature Range: 32° to 120° F (0° to 49° C) )perating Humidity 10% to 93% relative humidity Range: (non -condensing) Electrical Specifications: External Supply ✓oltage: 16 to 33 VDC (VFWR) External Standby current: 500 pA maximum 41arm Current: 35 mA maximum (high volume) 15 mA maximum (low volume) 5LC Operating Voltage: 15 to 32 VDC 5LC Standby Current: 300 pA maximum Sound Output: Greaterthan85dBAminimum — measured in a UL reverberant room at 10 ft. 24 Volts (in continuous tone) Installation Specifications: Mounting: Mounts directly to 4" (10.16 cm) square, 4" (10.16 cm) octagon, 3 1/2" (8.9 cm) octagon, single - gang or double -gang junction boxes Wire: W re sizes up to 12 AWG Ordering Information Part Number Description B200S Intelligent Sensor Sounder Base Note: The B200S sounder base is compatible with only the E3 Series fire alarm control panel. Use the B200SR with the 7100, 602 Series or Gamewell and FCI (Legacy) panels. For information on the B200SR, refer to the BSOOSR Data Sheet (P/N:9021-60553). GAMEWELL-FCI 12 Clintonville Road, Nodhford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 \ 9021-60671 Rev. A page 2 of 2 www.gamewell-fci.com ^Gamewell a INSSTRUUMEEN S by Honeywell Description The Advanced Multi -Criteria Fire/CO Detector (MCS- COF) is an addressable device that provides both fire and carbon monoxide (CO) detection. For fire detec- tion, the detector combines the following four sepa- rate sensing elements in one unit. • Smoke • Carbon Monoxide (CO) • Light/flame • Heat These elements sense multiple components of a fire. This approach enables an enhanced sensitivity to real fire with a heightened immunity to nuisance par- ticulate. For CO, the detector's electrochemical sens- ing cell creates a separate signal for life safety CO detection. Released through the incomplete burning of various fuels, CO is a colorless, odorless and deadly gas that is virtually impossible to detect with the human senses. Because the potential exists for dangerous levels of CO to accumulate in almost any building, legislation mandates the use of CO detection in com- mercial spaces in the U.S. The MCS-COF is Listed to the ULe 2075 Standard for system -connected life safety carbon monoxide monitoring. It is designed to be used with the Gamewell-FCI, E3 Series or S3 Series fire alarm control panel only. The MCS-COF should be used in conjunction with the B200S intelligent sounder base, which can generate either of the following patterns: • Temp 3 pattern for fire. • Temp 4 pattern for CO alarm indication. The B200S recognizes the System Sensor synchro- nization protocol. This feature enables it to be used as a component of the general evacuation signal, along with other System Sensor horns, horn strobes, and chimes, when the MCS-COF is connected to a power supply or Fire Alarm Control Panel (FACP) output that is capable of generating the System Sen- sor synchronization pulses. With each sounder base carrying a unique address, the FACP can then com- mand an individual sounder, or a group of sounders, to activate. The command set from the panel can be tailored to the specific event, allowing selection of volume, tone, and group For more information on the B200S, refer to Data Sheet P/N: 9021-60671. E3 Seriese is a registered trademark of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. Velociti° Series Advanced Multi-Criteriz Fire/CO Detecto MCS-COF in a B200S Sounder Base Features • Offers the unique function to detect the following four major elements of a fire: - Smoke - Carbon Monoxide (CO) - Light/flame - Heat • Supplies a separate CO detection signal. • Presents the highest nuisance alarm immunity. • Produces an automatic drift compensation of smoke sensor and CO cell. • Uses only one address on the SLC. • Includes the EasyTest CO testing capability. • Complies with ULe Listed Standard 268 and ULe Listed Standard 2075. • Separates the audible signal for fire or CO alarm when used with the B200S Base. • Provides the CO cell end -of -life warning and fault. SIGNALING 0 LISTED $1195 7275-1703:0175 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for infomkaton only, are not intended for installation purposes, and are subject to change without nota. No responsibility is assumed by Gamemil-FCI for their use. 02013 by Honeywell International Inc. All rights nummed. www.gamewell-fcl.com 9021-60708 Rev. C page 1 of 2 Specifications physical Specifications 3ase Diameter: 6.875' (17.46 cm) installed in a B200S Electrical Specifications )perating Voltage Range: 15 to 32 VDC Maximum Standby current: 300 pA at 24 VDC (no communica- tion every 5 seconds with LED blink enabled). Maximum Alarm 'urrent (LED on): 7.2 mA at 24 VDC Sensitivity Settings & Suggested Applications Level 1: 1% per foot (30.48 cm) of smoke base 3ase Height: 3.46"(8.79 cm) installed in B200S base Shipping Weight: 4.6 oz ;olor: Ivory Material: Bayblend FR110 )perating Moderately clean environments: temperature Range:32° F to 100° F (0° C to 38° C) )perating Humidity 3% per foot (30.48 cm) of smoke with different Range: 15 to 90% relative humidity M02-09-01 (non -condensing) kir Velocity: 0 to 4,000 ft/min (0 to 20 m/sec) Electrical Specifications )perating Voltage Range: 15 to 32 VDC Maximum Standby current: 300 pA at 24 VDC (no communica- tion every 5 seconds with LED blink enabled). Maximum Alarm 'urrent (LED on): 7.2 mA at 24 VDC Sensitivity Settings & Suggested Applications Level 1: 1% per foot (30.48 cm) of smoke Warning: After the CO cell has reached the end -of -life, the CO sensor no longer provides life safety protection. How- ever, when the fire detector enters Photo, Thermal, Infra- red (PTIR) mode, the following sensitivities apply: Level 1: 1 % per foot (30.48 cm) of smoke. Very clean environments: Used in Laboratories. Level 2: 2% per foot (30.48 cm) of smoke. Clean environments: Used in offices. Level 5: 3% per foot (30.48 cm) of smoke. Moderately clean environments: Used in hotel rooms, dorm rooms. Level 6: Thermal alarm at 135° F (57° C). Specifications (Continued) CO Monitoring UL Standard Reference - Alarm Thresholds are as follows: Parts per Million 70 ± 5ppm 150±5ppm 400± IOppm Detector Response Time, min. 60-240 10-50 4-15 Note: Per UL Standard 2075, the MCS-COF has been tested to the sensitivity limits defined in UL Standard 2034. Ordering Information Part Number Description MCS-COF Very clean environments: Used in Laboratories. Level 2: 2% per foot (30.48 cm) of smoke. Clean environments: Used in offices. Level 3: 3% per foot (30.48 cm) of smoke. Moderately clean environments: Accessories: Used in hotel rooms, dorm rooms. Level 4: 3% per foot (30.48 cm) of smoke with different M02-04-01 algorithm processing and weighting of sensor M02-09-01 elements. Used in hotel rooms near a shower, boiler rooms. Level S: 4% per foot (30.48cm)ofsmoke. Used in equipment rooms, kitchens, paint shop. Level 6: Thermal alarm at 135° F (57° C). Warning: After the CO cell has reached the end -of -life, the CO sensor no longer provides life safety protection. How- ever, when the fire detector enters Photo, Thermal, Infra- red (PTIR) mode, the following sensitivities apply: Level 1: 1 % per foot (30.48 cm) of smoke. Very clean environments: Used in Laboratories. Level 2: 2% per foot (30.48 cm) of smoke. Clean environments: Used in offices. Level 5: 3% per foot (30.48 cm) of smoke. Moderately clean environments: Used in hotel rooms, dorm rooms. Level 6: Thermal alarm at 135° F (57° C). Specifications (Continued) CO Monitoring UL Standard Reference - Alarm Thresholds are as follows: Parts per Million 70 ± 5ppm 150±5ppm 400± IOppm Detector Response Time, min. 60-240 10-50 4-15 Note: Per UL Standard 2075, the MCS-COF has been tested to the sensitivity limits defined in UL Standard 2034. Ordering Information Part Number Description MCS-COF Advanced Multi -Criteria Fire/CO Detector Note: Due to the unique nature of this detector, please consult your Fire Alarm Control Panel Manufacturer for the specific model and compatibility. Accessories: B200S Addressable Sounder Base M02-04-01 Detector Test Magnet M02-09-01 Telescoping Test Magnet GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60708 Rev page 2 of 2 www.gamewell-fcl.com ^Gamemil FIRE CONTROL INSTRUMENTS by Honeywell Description The InnovairFlex TM Series, DNR intelligent, non -relay pho- toelectric duct smoke detector, and the DNRW watertight, non -relay photoelectric duct smoke detector feature a piv- oting housing that fits both square and rectangular foot- prints. These detectors are capable of mounting to a round or rectangular duct. The DNR/DNRW detectors can be used with the E3 Series®and 7100 Series Systems. Note: The InnovairFlex TM Series, DNR requires the Veloc- iti® Series, ASD-PL2FR Sensor and AOM-2RF, if relays are required for the fan control. The DNRW duct smoke detector, with its NEMA 4 rating, is Listed as a watertight enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water. These features allow operators to use the detector in the most extreme environments. The units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of -4°F to 158°F, and a humidity range of 0 to 95 percent (non -condensing). An improved cover design isolates the sensor head from the low -Flow feature for simple maintenance. A cover tam- per feature was added to indicate a trouble signal for a removed or improperly installed sensor cover. The InnovairFlex housing provides a 3/4 -inch conduit knockout and ample space to facilitate easy wiring and mounting of the relay module. The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories. WARNING:Duct smoke detectors have specific limitations. DUCT SMOKE DETECTORS ARE: NOT a substitute for an open area smoke detector, NOT a substitute for early warning detection, and NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional duct smoke detector 2911 application information. E3 Series®and Velociti®are registered trademarks and InnovairFlex*" is a trademark of Honeywell International, Inc. UL® is a registered trademark of underwriters Laboratories Inc. InnouairFleiff Series DNR/DNRW Duct Smoke Housing Intelligent Non -Relay Photoelectric Duct Smoke Housinc InnovairFlex-DNRIDN RW Features • Photoelectric, integrated low -Flow technology ! • Air velocity rating from 100 Wmin to 4,000ft/min (0.5m/s to 20.32m/sec) • Versatile mounting options: square or rectangular configuration • Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 95% non -condensing) • Patented sampling tube installs from front or back of the detector with no tools required • New Cover tamper signal • Increased wiring space with a newly added 3/4 -inch conduit knockout • Available space within housing to accommodate the mounting of the relay module • Easily accessible code wheels on sensor head (sold separately) • Clear cover for convenient visual inspection • UL®268AListed • Remote testing capability • Requires SLC line power only • NEMA Type 4 UL Listed for non -hazardous indoor and outdoor applications (DNRW only) UV Resistant, UL® Listed housing and cover material (DNRW only) SIGNALING & FM MSFM @LISTED 9 APPROVED 2202 S911 3029700 2207 7272-1703:0121 S911 ISO 9001 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 SpecihcaI oos se for information only, are not intended for installation purposes, and are subject to change without nota. No responsibility is assumed by Gamewell-FCI for their use. 02013by Honeywellintematior,..nc. Alldghtsmsewed. www.gamewell-fci.com 9021-60475 Rev. E page I of krchitectural/Engineering Specifications fhe air duct smoke detector shall be a System Sensor InnovairFleXTm DNR Intelligent Non -Relay Photoelectric Duct Smoke Detector and DNRW Watertight NEMA4 Duct Smoke Detector. The detector housing shall be LIL Listed per LIL >68A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and ectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4,000 ft/min (0.5 m/sec to 20.32 m/ sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly nstalled. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. 2hysical Specifications Size: Rectangular Dimensions: 14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.6 cm) Depth Square Dimensions: 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Neight: 1.6 Ib (0.73 kg) Environmental Rating: NEMA4 (DNRW only) )perating Temperature Range: —40 to 158°F (-200 to 70°C) Storage Temperature Range: —220 to 158°F (-300 to 70°C) Operating Humidity Range: 0% to 95% relative humidity non -condensing kir Duct Velocity: 100 to 4000 ft/min (0.5 to 20.32 m/sec) )COIL - (if included) 17.5 - 26.4 VDC .95mA max. Electrical Ratings For information on the electrical specifications, refer to the InnovairFlex DNR Duct Smoke Detector Installation Instructions, P/N 156-3051-001 R. Accessory Current Loads at 24 VDC Device Standby Trouble RA100Z 0 mA 12 mA Max. RTS151/RTS151 KEY 0 mA 12 mA Max. Installing the InnovairFlex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab. (Figure 3 illustrates the front locking tab). Figure 1 Figure 2 Figure 3 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60475 Rev. E page 2 of 4 www.gamewell-fel.com Wiring for Intelligent Non -Relay Duct Smoke Detector UUFM LISTED IST 2ND CONTROL DETECTOR DETECTOR PANEL IN LOOP IN LOOP Figure 4 System Wiring Diagram for DNR + RA W - RA 0 RA10OZ REMOTE ALARM LED OPTION 1 PER UNIT Figure 5 DNR to RA10OZ DNR TO RTS451/RTS451 KEY/RTS151/ RTS151 KEY WITH"R"REMOTE TEST I I CAPABLE DETECTOR HEAD OPTION: I COMM. I I I LINE (+) COMM. I I I LINE I I COMM+ ® I I I I + I I COMM. LINE (-) I I �� I I I I ��,� COMM_ ® UUFM LISTED IST 2ND CONTROL DETECTOR DETECTOR PANEL IN LOOP IN LOOP Figure 4 System Wiring Diagram for DNR + RA W - RA 0 RA10OZ REMOTE ALARM LED OPTION 1 PER UNIT Figure 5 DNR to RA10OZ DNR TO RTS451/RTS451 KEY/RTS151/ RTS151 KEY WITH"R"REMOTE TEST CAPABLE DETECTOR HEAD OPTION: TEST COIL + TEST COIL+® TEST COIL-RTS451/RTS451KEY ® TEST COIL ® " x,14 RTS151/RTS151 KEY - COMM+ ® CONM+® OUT (CONN ONLY) + OUT (CONN ONLY) + ��,� COMM_ ® RT151/RTS151KEY COMM- ® REMOTETESTSTATION �••• RAIRTS - RA/RTS -PUMPER RA+® �D0Fnm PER UNIT RA+ ® 4 RTS+ ®..--..! TESIC RON RTS + +PER UNIuNlr 595m4CURREAT waw Figure 6 DNR to RTS1611RTS151 Key Important Notes: • The use of either RTS151 or RTS151 KEY requires the installation of an accessory coil, DCOIL, sold separately. For additional information, refer to the DNR or DNRW Duct Smoke Detector Installation Instructions, P/N 156-3051-001R and the Duct Application Smoke Detectors Application Guide. • The RTS 151/RTS151KEY test coil circuit requires an external 24 VDC power supply which must be UL Listed. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60475 Rev. E page 3 of 4 4ccessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different neans of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accesso- ies are UL Listed. Ordering Information Part Number Description DNR Intelligent non -relay photoelectric low -flow duct smoke detector DNRW Watertight intelligent non -relay photoelectric low -flow duct smoke detector ASD-PL2FR Intelligent photoelectric smoke sensorwith remote test capability in duct applications Accessories Part Number Description DCOIL Remove test coil required with RTS1 51/RTS1 51151 KEY DST1 Metal sampling tube duct width up to 1 ft (0.3m) DST1.5 Metal sampling tube duct widths 1 ft to 2 it (0.3 to 0.6 m) DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) DST3 Metal sampling tube duct widths 2 it to 4 ft (0.6 to 1.2 m) DST5 Metal sampling tube duct widths 4 ft to 8 it (1.2 to 2.4 m) Figure 7 RTS151 UL S2522 Figure 8 RTS151 KEY UL S2522 Figure 10 ASD-PL2FR Figure 9 RA10OZ UL S2522 Ordering Information Part Number Description DNR Intelligent non -relay photoelectric low -flow duct smoke detector DNRW Watertight intelligent non -relay photoelectric low -flow duct smoke detector ASD-PL2FR Intelligent photoelectric smoke sensorwith remote test capability in duct applications Accessories Part Number Description DCOIL Remove test coil required with RTS1 51/RTS1 51151 KEY DST1 Metal sampling tube duct width up to 1 ft (0.3m) DST1.5 Metal sampling tube duct widths 1 ft to 2 it (0.3 to 0.6 m) DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) DST3 Metal sampling tube duct widths 2 it to 4 ft (0.6 to 1.2 m) DST5 Metal sampling tube duct widths 4 ft to 8 it (1.2 to 2.4 m) DST10 Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) DH4000E-1 Weatherproof enclosure ETX Metal exhaust tube duct width 1 f (0.3m) M02-04-00 Test magnet P48-21-00 End cap for metal sampling tubes RA100Z/RA100ZA Remote annunciator alarm LED RTS151 Remote test station RTS151 KEY Remote test station with key lock GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60475 Rev. E page 4 of 4 www.gamewell-fci.com ^Gamewell Q FIRECONTROL INSTRUMEISM by Honeywell Description The Gamewell-FCI, MS -7 Series manual fire alarm sta- tions are available in a wide variety of configurations. The Stations comply with the Americans with Disabilities Act (ADA) 5 -Ib. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle. All stations have a key lockireset which is keyed alike with Gamewell-FCI fire alarm control panels and other manual fire alarm stations. MS-7AF Velociti Addressable Station The MS-7AF Velociti® Series addressable station is a dou- ble action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which Flashes green in normal condition and lights steady red when the station has been activated.` The sta- tion features screw terminals. MS-7ASF Velociti Addressable Station The MS-7ASF Velociti® Series addressable station is a single action station designed for installation in the signal- ing line circuit of Ganr ll-FCI analog addressable con- trol panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which Flashes green in normal condition and lights steady red when the station has been activated.` The sta- tion features screw terminals. The Velociti® Series stations use a communication proto- col that substantially increases the speed of communica- tion between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and focuses on the single device. The net effect is response speed up to five times greater than earlier designs. MS -7 Double Action Station The MS -7 double action station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. Velociti® is a registered trademark of Honeywell International Inc. UL® is a registered trademark of Underwriter's Laboratories Inc. LEXANO is a registered trademark of GE Plastics, a subsidiary of General Electric Company. S=7 Series Non -Coded, Manui Fire Alarm Station: NIS -7 Features • Addressable stations compatible with all Gamewell-F( analog addressable fire alarm controls • Conventional stations suitable for use with any UL® Listed control panel • Both single and double action stations available • Tumbler lock for test and reset keyed alike with Gamewell-FCI controls • Surface or semi -Flush mounting • Shock and vibration resistant • Stations (MS-7LOB) Listed for outdoor applications • Complies with ADA pull force requirements 'Only the red LED is operative in panels that do not ape, ate in Velociti mode. i An ISO 9001.2000 Company LISTED — A 2" .t sm.ew.w Ohwa®axn GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are sulbect to change without notice. No responsibility is assumed by Gamewel4FCl for Nair use. 02010 by Honeywell International Inc. All nghts reserved. www.gamewell-fcl.com 9020-0616 Rev. D page 1 of 2 11S -7S Single Action Station 'he MS -7S single action station is used with conventional re alarm control panels. It features a set of single pole ontacts and wire leads for connection to an initiating circuit. 11S-7SP Double Action Station he MS-7SP is a double action station similar to the MS -7 tation, with the additional feature of both English and ipanish instructions molded into the unit. AS-7LR Dual -action Agent Release Station 'he MS-7LR is designed for use with the Gamewell-FCI ire alarm control panels with releasing capabilities and lex Series releasing systems. It features a set of single pole contacts and screw terminals for connection to an ini- iating circuit. AS-7LRA Agent Release Station with Abort 'he MS-7LRA is designed for use with the Gamewell-FCI ire alarm control panels with releasing capabilities and :lex Series releasing systems where system abort capabil- Jes are required. It consists of an MS-7LR mounted on a date with an abort switch and LED indicators for system rormal, and system activated status. AS-7LOB Double Action Station Listed for Outdoor Applications) fhe MS-71LOB station must be mounted on a Model SB -1/0 rackbox. In retrofit applications, the station is UL Listed for ise with the WP -10 backbox. It is intended for use with *nventional control panels and has a set of single pole *ntacts and screw terminals. Mounting -he MS -7 interior stations may be surface mounted or semi -Flush mounted on a standard double -gang, or 4 -inch 10.2 cm) square electrical box. An optional trim ring BG12TR) may also be used for semi -flush mounting. OYC-Plate fhe NYC -Plate provides the backplate for the manual pull station. (See Figure 1). Figure 1 NYC -Plate Specifications Material: Lexan® Contact Ratings: 0.25 amps. @ 30 VACNDC MS-7AF** (resistive) Dimensions: 5 5/8" H x 4 1/4" W x 1 1/4" D MS-7ASF** (14 x 10.1 x 3.2 cm) Operating Temperature Single action station, wire leads (MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C) (MS-7LOB): -30° to 150° F (-350 to 66° C) Relative Humidity Agent release station, dual -action (MS-7AF, MS-7ASF): 10 to 93% (non -condensing) (MS -71_06): 85% t 5% @ 86° t 3.61 MS -71_013 (30° t 2- C) Alarm Current: .0030 amp. 0.007 for LED Supervisory Current backbox) (MS-7AF, MS-7ASF): .00030 amps. Ordering Information Part Number Description MS -7 Double action station MS-7AF** Velociti addressable double action station MS-7ASF** Velociti addressable single action station MS -7S Single action station, wire leads MS-7SP Double action station, English and Spanish instructions MS-7LR Agent release station, dual -action MS-7LRA Agent release station with abort switch, LED indicators, dual- action MS -71_013 Double action station, outdoor use (Includes SB -1/0 - Indoor/outdoor use backbox) SB -1/0 Indoor/outdoor use backbackbox SB -10 Surface backbox BG12TR Trim ring for semi -flush mount, plastic NY -PLATE NYC backplate for manual pull station **For use with the Gamewell-FCI analog addressable control panels only. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0616 Rev. D page 2 of 2 www.gamewell-fci.com ^Gamewell a "INSSTRRUUMEENT'S by Honeywell Description The Gamewell-FCI Velociti® Series, addressable monitor module (AMM -41F) features a single Style D, Class A initiat- ing device circuit. It may also be configured as a Style B. Class B initiating circuit with end -of -line resistor. This mod- ule provides an address for any device or group of devices connected to this circuit. Any alarm initiating devices with normally open (N.O.) dry contacts, such as heat detectors, linear heat detection devices, 4 -wire projected beam smoke detectors, 4 -wire smoke detectors, water Flow switches, tamper switches, manual stations, etc. may be installed in this circuit. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FC] analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The AMM -41F module is designed for installation in the sig- naling line circuit of any Gamewell-FCI analog addressable control panel. The initiating circuit of the AMM -4F has a maximum line resistance of 40 ohms, allowing the module to accommodate a number of initiating devices at a dis- tance from the module. The AMM -4F is designed to mount in a 4" square junction box 2 1/8" deep. The initiating device circuit of the AMM -4F can support a maximum line resistance of up to 40 ohms allowing the use of linear heat detection devices. Ordering Information Model Description AMM-4FAddressable monitor module, single circuit, Style D, Class A or Style BC/A and B Velocitia and E3 Sedesw are registered trademarks of Honeywell International Inc. Velocitl® Series AMM -41 Addressable Monitor Moduli AW4F Features Compact size allows easy installation • Class A, Style D, or Class B, Style B initiating circuit • Visual rotary, decimal switch addressing (01-159) • 40 ohm line resistance for each initiating device circuit Accommodates any N/0 dry contact device Bicolor LEDs flash green whenever the module is addressed, and light steady red on alarm* *Note: Only the red LED is operative in panels that do nc operate in Velocitie mode. Specifications Supervisory current: Alarm current: Operating temperature: Relative humidity: End -of -line resistor: Dimensions: .000375 amps. (LED flashing) .005 amps. (LED lit) 320 to 120° F (0° to 49° C) 10 to 93% (non -condensing) 47K ohms 4 1/2" H x 4" W x 1 1/4" D (11.4x10.2x3.2cm) An ISO 9001.2000 Company SIGNALING &S>MEA L%STED .11.O ED Anprov� 899 3823584 387.aPEVOIV 073808894778 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for info8na8on only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. 02008 Honeywell International Inc. All fights reserved. www.gamewell-fci.com 9020-0624 Rev. D1 page 1 of 1 ^Gamewell Q FIRE CONTROL INSTRUMENTS by Honeywell Description The Gamewell-FCI Velociti® Series, addressable output relay control module (AOM-2RF) allows an Gamewell-FCI analog addressable fire alarm control to switch discrete relay contacts by code command. The relay provides two (2), isolated sets of Form -C contacts which transfer simul- taneously. Circuit connections to the relay contacts are not supervised by the module. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The AOM-2RF Module is designed for installation in the signaling line circuit of any Gamewell-FCI analog address- able fire control panel. The module contains a panel con- trolled LED. The AOM-2RF is designed to mount in a 4" square junction box 2 1/8" deep. Relay Contact Ratings Current Rating Maximum Voltage Load Description Application 3A 30 VDC Resistive Non -Coded 2A 30 VDC Resistive Coded 0.9A 110 VDC Resistive Non -Coded 0.5A 125 VAC Resistive Non -Coded 0.5A 30 VDC Inductive (UR=5ms) Coded to 30 VDC Inductive (UR=2ms) Coded 0.5A 125 VAC Inductive (PF=.35) Non -Coded 0.7A 75 VAC Inductive Non -Coded Velociti® Series is a registered trademark of Honeywell International Inc. Veieciti® Series AOM-2RF Addressable Output Relay Control Module L AOM-2RF Features • Two (2) sets of Form "C" contacts • Visual rotary, decimal switch addressing (01-159) • Bicolor LEDs flash green whenever the sensor is addressed, and light steady red on alarm` • Compact size allows easy installation Note: Only the red LED is operative in panels that do not operate in Velociti® mode. Specifications Supervisory current: Alarm current: Operating temperature: Relative humidity: Dimensions .000375 amps. .0065 amps. 32° to 120° F (0° to 490 C) 10 to 93% relative humidity (non -condensing) 41/2"Hx4"Wx11/4° (11.4 x 10.2 x 3.2 cm) Ordering Information Model Description AOM-2RF Addressable output relay control module An ISO 9001.2000 Company staw.uaa �L< FM >MEA ON LISTED APPaov6o Approved 67949 3013594 22703{ VoLIV 07300-0694178 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for Meir use. ®2009 Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0625 Rev. D1 page 1 of 1 ^Gamewell a FIRE CONTROL ® INSTRUMENTS by Honeywell Description The Gamewell-FCI Velociti'"m Series addressable output supervised control module (AOM-2SF) allows an Gamewell-FCI analog addressable fire alarm control to switch an external power supply, such as a DC supply or audio amplifier (up to 80 VRMS) to notification appliances. The AOM-2SF notification appliance circuit can be wired either Class A (Style Z) or Class B (Style Y). It also super- vises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN or SHORT CIR- CUIT. The module contains a panel controlled LED. The VelocitiTM Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The module is UL Listed as suitable for releasing device service and FM Approved for deluge and preaction ser- vice. Refer to the Gamewell-FCI Compatibility Addendum, P/N 9000-0427, for a list of approved, compatible sole- noids. The AOM-2SF module is designed for installation in the signaling line circuit of any Gamewell-FCI analog addressable control panel. The signaling line circuits of Gamewell-FCI analog addressable control panels are designed to accommodate up to 159 modules per circuit. The AOM-2SF is designed to mount in a 4" (10.16 cm) square junction box 2 1/8" (5.5 cm) deep. Relay Contact Ratings Current Maximum Load Applicatior Rating Voltage Description Temperature: 3A 30 VDC Resistive Non -Coded 2A 30 VDC Resistive Coded 0.9A 110 VDC Resistive Non -Coded 0.5A 125 VAC Resistive Non -Coded 0.5A 30 VDC Inductive (UR=5ms) Coded 1A 30 VDC Inductive (UR=2ms) Coded 0.5A 125 VAC Inductive (PF=.35) Non -Coded 0.7A 75 VAC Inductive Non -Coded Ve10c11ITM Series AOM-2SI Addressable Output Rela Supervised Control Modul AOM -28F Features • Compact Size allows easy installation. • Class A, Style Z, or Class B, Style Y notification i appliance circuit. • Will accommodate audio amplifiers up to 80 VRMS. • Listed as suitable for releasing device service. • Bicolor LEDs flash green whenever the module is addressed, and lights steady red on alarm." 'Note: Only the red LED is operative in panels that do not operate' Velocitimm mode. Specifications Supervisory Current: .00030 amp. Alarm Current: .00030 amp. Operating Temperature: 320 to 1200 F (00 to 490 C) Relative Humidity: 10 to 93% relative humidity (non -condensing) Dimensions: 4 1/2" H x 4" W x 1 1/4" D (11.4 H x 10.2 IN x 3.2 D cm) Ordering Information Model Description AOM-2SF Addressable output supervised control module An ISO 9001-2000 Company ncwuxc S � MEA u1E0 .. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsit1lity is assumed by Gamewell-FCI for their use. =7 Honeywell International Inc. All rights reserved. www.gamewell4ci.com 9020-0627 Rev. C1 page 1 of 1 �� SYSTEM 14 SENSOff Multi -Voltage Conventional Relays System Sensor's multi -voltage conventional relays are used for high -current switching applications such as fan and damper assembly control, door control, air handling unit controls, and other types of system interfacing. Features The R -10T, R -20T, R -14T, and the R -24T models are multi - Multi -voltage operation Activation LEDs • Easy and flexible installation • Reliable and robust design • Multipurpose field installations • Multi -voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-1 OT/20T and R-1 4T/24T • Removable front cover on steel enclosure for R-10E/R-20E and R - 14/R -24E, which mount inside the enclosure • LED viewing hole on top of the steel enclosures cover • Extra pair of wires for redundant power input on PR -3 •Terminal strip field wiring connections, mounting track, and hardware Agency aMEA LISTED voltage relays with terminal strip field wiring connections, mounting track, and hardware.The R -10T is a single FORM -C (SPDT) relay with a red activation LED, and the R-1 4T is a four -gang 1 FORM -C (SPDT) relay with four red activation LEDs. The R -20T is a single 2 FORM -C (DPDT) relay with a red activation LED, and the R -24T is a four -gang 2 FORM -C (DPDT) relay with four red activation LEDs. The R-10E/R-20E and R-14E/R-24E are similar to the -F -series track mount relays, but they are mounted into a steel enclosure.The enclosure has a removable front cover that provides easy access and an LED viewing hole on the top of the cover. PR-1/PR-2/PR-3 are epoxy encapsulated multi -voltage relays.They are single -pole double -throw relays that use a red LED as a visible indication of relay coil energization. PR -3 is identical to PR -2, except it has an extra pair of wires for redundant power input. Model EOLR-1 is an epoxy encapsulated, single -pole single -throw, normally open relay that can be used as an end of line device in fire alarm systems, e.g. to supervise power supplies. Multi -Voltage Conventional Relay Specifications r r 10to40VDC Operating Current Operating Voltage 18-35VDC, 18-35VAC, 115VAC, 230VAC Operating Voltage 18-35VDC, 18-35VAC, 120VAC Operating Current 20 mA DC max.@ 24 VDC, 24VAC, 115 VAC, Operating Current 15 mA DC max.@ 24VDC, 24 VAC, 120 VAC 230VAC (13 -10T/11 -14T) Operating Temperature -407 to 1587(-40°C to 70°q 40 mA DC max.@ 24 VDC, 24 VAC, 115 VAC, Humidity Range 10-93%RH 2 30 VAC (R-20T/R-24T) Operating Temperature -407 to 158T( -40'C to 70°Q Wire Length Dimensions Humidity Range 10% - 93% non -condensing Contact Ratings Dimensions R-10T/R-20T:251x3.35Wxl2li R-14T/R-24T: 101 x 3.35-W x 1.211 Contact Ratings 24 VDC:7 Awith UR=5 mS 120 VAC: 10 A 120VAC: 1/6 HP 230VAC: 7 A Operating Voltage 18-35VDC, 18- 35 VAC, 11 SVAC, 230VAC Operating Current 20 mA DC max.@ 24 VDC, 24 VAC, 115 VAC, 230VAC (R-l0E/R-14E) 40 mA DC max. @ 24 VDC, 24 VAC, 115 VAC, 1587 8"minimum 0.8TH x 2.01 W x l A2"D 24 VDC:7 A with UR = 5 mS 120 VAC: 7 A max. (0.35 PF) 250 VAC: 10 A resistive 30 VDC: 10 A resistive Operating Voltage 10to40VDC Operating Current 30 mA DC max. Operating Temperature -40°F to 158°F(-4WC to 7CrQ Humidity Range 10-93%RH Wire Length 8'minimum Dimensions 0.91'H x 1.65W x 1.22"D Contact Ratings 120 VAC: 10 A max. (resistive load) 120VAC: 7 A max. (0.35 PF) 250 VAC 10 A max. (resistive load) Dimensions R-l0UR-2095.11 x 3.75W x 2.5"H R-14E/R-24E:111 x 5.3 W x 2.5'H Contact Ratings 24 VDC:7 Awith UR=5 mS Operating Voltage 9 t 40 VDC 120 VAC: 10 A Operating Current 20 mA DC max. 120VAC: 1/6 HP Operating Temperature -22'F to 140°F( -30'C to 60°Q 230VAC 7A Humidity Range 10-93%RH Wire Length 8'minimum Contact Ratings 120VAC: 0.5 A max. (resistive load) 30VDC:3 A max. (resistive load) T� 1 PR I EOLIP I FR -3 PR -2 R -10T R -14T R-1 OE & R -20E Enclosure 8-1 4E & R -24E Enclosure .SYSTEM 3825 Ohio Avenue -St. Charles, IL 60174 SENSOR" Phone:800-SENSOR2 • Fax: 630-377-6495 5-""""'""°'"`tla"sbet 4S93I3 W5�73W)-el>0] SYSTEM 30 SENSOR Selectable Output Horns, Strobes, and Horn/Strobes SpectrAlert* Advance selectable-outputhorns, strobes, and horn/strobes are rich with features guaranteed to cut installation times and maximize profits. Features The SpectrAlert Advance series of notification appliances is Electrically compatible with existing SpectrAlert products Automatic selection of 12- or 24 -volt operation at 15 and 15/75 candela Plug-in design designed to simplify installations, with features such as plug in designs, instant feedback messages to ensure correct installation of individual devices, and 11 field -selectable candela settings for wall and ceiling strobes and horn/strobes. Field selectable candela settings on wall and ceiling units: 15, 15/75, When installing Advance products, first attach a universal mounting 30, 75, 95, 110, 115, 135, 150, 177, 185 plate to a four -inch square, four -inch octagon or double -gang Same mounting plate for wall -and ceiling -mount units junction box.The two -wire mounting plate attaches to a single -gang junction box, • Shorting spring on mounting plate for continuity check before installation •Tamper resistant construction • Outdoor wall and ceiling products rated from -40"F to 151'F • Design allows minimal intrusion into the back box • Horn rated at 88+dbA at 16 volts • Rotary switch for horn tone and three volume selections • Outdoor products UL listed to UL 1638 (strobe) and UL 464 (horn) outdoor requirements • Outdoor products NEMA 4X rated • Compatible with MDL sync module Agency Listings SIGNALING UL F M n,u6: 887MEA l �I633,19 �hoIN3VCrl3. approved m'mer,°� LISTED APPROVED ]t33-,63 89lho— 7 ) Next, connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate. Finally, attach the horn, strobe or horn/strobe to the mounting plate by inserting the product's tabs in the mounting plate's grooves.The device will rotate into position, locking the product's pins into the mounting plate's terminals.The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. The SpectrAlert Advance series includes outdoor notification appliances. Outdoor strobes and horn/strobes (two wire and four wire) are available for wall or ceiling. Outdoor horns are available for wall only. All System Sensor outdoor products are rated between minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or dry applications. Alert Advance General SpectrAlert Advance horns, strobes and horn/strobes shall mount to a standard 4 x 4 x 1'/cinch back box, 4 -inch octagon back box or double -gang back box. Two -wire products shall also mount to a single -gang 2 x 4x 17/s -inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync -Circuit" Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync -Circuit Module, 12 -volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts; 24 -volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full -wave rectified, unfiltered power supply. Strobes and horn/strobes shall have field -selectable candela settings including 15,15/75, 30 75, 95,110,115,135,150,177,185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, Flashing at 1 Hz over the strobes entire operating voltage range. The strobe light shall consist of a xenon Flash tube and associated lens/reflector system. Horn/Strobe Combination The horn/strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn/strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, Flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon Flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three -pattern and a non -temporal (continuous) pattern.These options are set by multiple position switch. On four -wire products, the strobe shall be powered independently of the sounder -The horn on horn/strobe models shall operate on a coded or non -coded power supply. Outdoor Products SpectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151 degrees Fahrenheit.The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three-fourths inch conduit entries. Synchronization Module The module shall be a System Sensor Sync -Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn/strobe models over a single pair of wires.The module shall mount to a 411/lo x 411/i,,x 2'/e -inch back box. The module shall also control two Stylet/ (class B) circuits crone Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they controfThe module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (TC to 49°Q K Series Operating Temperature -407 to 1517 (-40°C to 66°C) Humidity Range 10 to 93% non -condensing (indoor products) Strobe Flash Rate 1 Flash per second Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWR' Operating Voltage Range' 8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal) Input terminal wire gauge 12 to 18 AWG Ceiling mount dimensions (including lens) 6.8"diameter x 2.5"high (173 mm diameter x 64 mm high) Wall mount dimensions (Including lens) 5.67 x 4.7V x 2.5"D 042 mm L x 119 mm W x 64 mm D) Horn dimensions 5.61 x 4.7W x 1.3"D (142 mm L x 119 mm W x 33 mm D) Wall -mount back box skirt dimensions (BBS -2, BBSW-2) 5.91x5.0W x 2.2D 051 mm L x 128 mm W x 56 mm D) Ceiling -mount back box skirt dimensions(BBSC-2, BBSCW-2) 7.1 -diameter x 2.25'high IT 80 mm diameter x 57 mm high) Wall -mount weatherproof back box dimensions(SA-WBB) 5.71x5.1W x 2.0'D(145 mm L x 130 mm W x 51 mm D) Ceiling -mount weatherproof back box dimensions(SA-WBBC) 7.1"diameterx2.0"high(180 mm diameter x 51 mm high) Wall -mount trim ring dimensions (TR -HS, TRW -HS) 5.71x4,812W x 0.35D(146 mm L x 122 W mm x 9 D mm) Ceiling -mount trim ring dimensions (TRC -HS, TRCW-HS) 6.9- diameter x 0.35 high (176 mm diameter x 9 mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time varying power source that is used on some power supply and panel outputs 2. P, 5, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. Irl 0191.5 UL Current Draw Data 177 NA NA 281 251 185 NA NA 286 258 DClnput 8-17.5 Volts 15 15/75 16-33 Volts 15 15/75 30 75 95 110 115 Temporal High 137 147 79 8-17.5Volts 107 16-33Volts 194 212 8-17.5 Volts 16-33 Volts 69 Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15* 123 128 66 71 Temporal High 57 55 69 75 Candela Range 15/75* 142 148 77 81 Temporal Medium 44 49 58 69 216 30* NA NA 94 96 Temporal Low 38 44 44 48 75* NA NA 158 153 Non -temporal High 57 56 69 75 214 95* NA NA 181 176 Non -temporal Medium 42 50 60 69 110 NA NA 202 195 Non -temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela Range 150 NA NA 246 220 Coded Low 40 46 52 50 177 NA NA 281 251 185 NA NA 286 258 DClnput 8-17.5 Volts 15 15/75 16-33 Volts 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non -temporal High 141 152 91 100 116 176 201 221 229 Non -temporal Medium 133 145 75 85 102 163 187 207 216 Non -temporal Low 131 144 68 79 96 156 182 201 210 FWRlnput 135 150 177 185 FWR Input 135 150 Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non -temporal High 142 161 103 112 126 181 203 221 229 Non temporal Medium 134 155 85 95 110 166 189 208 216 Non -temporal Low UL Max. Current Draw 132 16-33 Volts 154 80 90 105 161 184 16-33 Volts 202 211 DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non -temporal High 255 270 303 309 Non -temporal High 233 248 275 281 Non -temporal Medium 242 259 293 299 Non -temporal Medium 219 232 262 267 Non -temporal Low 238 254 291 295 Non -temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures, listed candela Horn and Horn/Strobe Output (dBA) ratings must be reduced in accordance with this table. 8-17.5 16-33 24 Volt Nominal Switch Volts Volts Reverberant Anechoic Listed Candela Candela rating at -40°F Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 15 1 Temporal High 78 78 84 84 88 88 99 98 15/75 Do not use below 32'F 2 Temporal Medium 74 74 80 80 B6 86 96 96 30 3 Temporal Low 71 73 76 76 83 80 94 89 75 44 4 Non -temporal High 82 82 88 88 93 92 100 100 95 70 5 Non -temporal Medium 78 78 85 85 90 90 98 98 110 110 6 Non -temporal Low 75 75 81 81 88 84 96 92 115 115 7t Coded High 82 82 88 88 93 92 101 101 135 135 8` Coded Medium 78 78 85 85 90 90 97 98 150 150 9` Coded Low 75 75 81 81 88 85 96 92 177 177 'Settings 7, 8, and 9 are not available on 2 -wire horn/strobe. 185 185 A�30395W5 SpectrAlert Advance Dimensions Ceiling -mount horn/strobes 7V 2.25'112.p- � 5.05"___1 i.2.231 Dia. DO 06 a ® o 0 5.98" ® 6.2" O a Q UM o a O i 5.1"-./ Wall weatherproof back box Ceiling weatherproof back box Wall back box skirt Ceiling back box skirt SpectrAlert Advance Ordering Information r Wall Horn/Strobes P2R*' 2 -wire Horn/Strobe, Standard cd', Red P2RH* 2 -wire Horn/Strobe, Hioh cd, Red P2RK" 2 -wire Horn/Strobe, Standard cd, Red, Outdoor Ceiling Horn/Strobes (contd.) PC4W 4 -wire Horn/Strobe, Standard cd,White PC4WH 4 -wire Horn/Strobe, High cd, White Ceiling Strobes P2RHK' 2 -wire Horn/Strobe, High cd, Red, Outdoor SCR* Strobe, Standard cd, Red P2W* 2 -wire Horn/Strobe, Standard cd, White SCRH* Strobe, High cd, Red P2WH* 2 -wire Horn/Strobe, High cd, White SCRK' Strobe, Standard cd, Red, Outdoor P4R* 4 -wire Horn/Strobe, Standard cd, Red P4RH* 4 -wire Horn/Strobe, High cd, Red P4RK° 4 -wire Horn/Strobe, Standard cd, Red, Outdoor P4RHK^ 4 -wire Horn/Strobe, High cd, Red, Outdoor P4W' 4 -wire Horn/Strobe. Standard cd. White SCRHK' Strobe, High cd, Red, Outdoor SCW*t Strobe, Standard cd, White SCWH*t Strobe, High cd, White Horns Strobe, High cd, Red P4WH* 4 -wire Horn/Strobe, High cd, White Wall Strobes Back Box Skirt, Wall, White SR*t Strobe, Standard cd, Red SRH*t Strobe, High cd, Red SRK° Strobe, Standard cd, Red, Outdoor SRHK Strobe, High cd, Red, Outdoor SW* Strobe, Standard cd, White SWM* Strobe, High cd,White Ceiling Horn/Strobes PC2R* 2 -wire Horn/Strobe, Standard cd, Red PC2RH* 2 -wire Horn/Strobe, High cd, Red PC2RK' 2 -wire Horn/Strobe, Standard cd, Red, Outdoor PC2RHK' 2 -wire Horn/Strobe, High cd, Red, Outdoor PC2W*'2-wire Horn/Strobe, Standard cd, White PC2WH*' 2 -wire Horn/Strobe, High cd, White PC4R 4 -wire Horn/Strobe, Standard cd, Red PC4RH 4 -wire Horn/Strobe, High cd, Red PC4RK 4 -wire Horn/Strobe, Standard cd, Red, Outdoor PMHl ° 4 -wire Horn/Strobe, High cd, Red, Outdoor HR Horn,Red HRK' Horn, Red, Outdoor HW Horn,White Accessories BBS -2 Back Box Skirt, Wall, Red BBSW-2 _HSC Back Box Skirt, Wall, White -2 Back Box Skirt, Ceiling, Red BBSCW-2 Back Box Skirt, Ceiling, White TR -HS Trim Ring, Wall, Red TRW -HS Trim Ring, Wall White TRC -HS Trim Ring, Ceiling, Red TRCW-HS Trim Ring, Ceiling,White Notes: * Add"-P"to model number for plain housing (no"FIRE°marking on cover), e.g., P2R-P. t Add'-SP"to model number for"FUEGO"marking on cover, e.g., P2R-SP. 3"Standard cd, refers to strobes that include 15,15/75, 30,75,95, 110, and 115 candela settings."High cd, refers to strobes that include 135, 15Q 177, and 185 candela settings. All outdoor units ending in"K"include a weatherproof back box. a Add"-R"to model number for weatherproof replacement device (no back box included). SYSTEM SENSOR* hone: BioAvenue•St.ax:630, 77-649 Aa oa, ,va .ugm,om u� we*u,u„ em <�,a Phone: 800.5ENSOR2•Fax:630-377-6495 nos039sms. aoa..zoi 8 ^Gamewell ©FIRE CONTROL INSTRUMENTS by Honeywell Description The Gamewell-FC], HPFF8 is a Notification Appliance Cir- cuit (NAC) expansion panel designed to extend the power capabilities of existing NACs and provide power for auxil- iary devices. The HPFF8 connects to any 12 or 24V Fire Alarm Control Panel (FACP) or stand alone. Available in 8.0 amps, they provide regulated and filtered 24VDC power to each of the four NACs and an auxiliary output. The NAC outputs are rated at 3.0 amps each (the total output cannot exceed 8.0 amps). The auxiliary output is rated at 2.0 amps. This output is continuously supplied, even in alarm, and therefore must be taken into account for power supply loading and battery size calculations. The NAC outputs may be configured as any of the follow- ing: • Four Class B (Style Y) • Two Class A (Style Z) • Two Class B and one Class A • Four Class A with the optional HPP31076 Class A adapter installed These power supplies contain an internal Battery charger capable of charging up to 26.0 amp -hour (AH) batteries. The HPFF8 is mounted in lockable wall cabinet units that can accommodate up to two 18AH batteries. A multipack option allows for up to four chassis mount units installed in a single lockable SBB-D4 enclosure. These chassis mount units have a "CM" suffix, HPFF8CM and can accommo- date two 12AH batteries. Power supplies are available in either 120VAC/60 Hz or 240VAC/50 Hz. One of the most challenging aspects of a retrofit applica- tion is locating the existing End -of -Line (EOL) resistor. In these applications that have EOL values, other than the 3.9k normally used with the HPFF8, a single resistor matching the existing EOL can be used as a reference for all the outputs. This feature speeds the installation and the system checkout, because the actual EOL does not need to be located and changed in the circuit. The reference resistor must be within the range of 1.9k to 25k. HPFF8 NAC Expander/Power Supply HPFF8 Features • Four (4) supervised notification application circuits (NACs) capable of supplying +24VDC at 3.0 amp maximum each • NAC output circuits may be configured as any of the following: - Four Class B (Style Y) - Two Class B & one Class A - Two Class A (Style Z) - Four Class A with the optional HPP31076 Class A adapter installed • Four field -programmable operational modes • 2.0 amp auxiliary continuously supplied output • Two fully supervised inputtoutput control circuits • Temporal coding and sync protocols compatible with the following notification appliance brands: - System Sensor - Faraday - Gamewell - Amseco - Cooper -Wheelock - Gentex • Supervised AC input, battery voltage, auxiliary output, charger, and earth ground faults • Trouble indication for supervision of the following: - NAC circuits - Auxiliary output - AC input - Charger - Battery voltage - Open contacts in the initiat- - Earth ground faults by ing device signal inputs (for individual status LED's FACP trouble notification) • Separate Trouble and AC Fail Form -C relay Contacts wak• '111 111 9 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change Without notice. No responsibility is assumed by Gamewell-FCI for their use. 02009 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60521 Rev. B page 1 of Features (Continued) • The Trouble Form -C relay contacts selectable for imme- diate or a 2 hour delay with AC failure • 26 AH battery charger capability; the wall cabinet supports two 12V 18AH batteries, while the multi -pack equipment cabinets supports two 12V 12AH batteries. • NAC Overload protection and indication • Up to four chassis mount units (HPFF8CM) can be installed in the SBB-D4 backbox • Wall mount units can be configured to internally house the following: - one AOM-2SF single control module - one AOM -2R single relay module Specifications Primary Input Power: Secondary Power: Battery Charging Capacity Battery Space: HPFF8 Cabinet: SBB-D4 Cabinet: Total Output Power: Standby Current: Auxiliary Power Output: 120VAC/60Hz, 3.OA or 220VAC/50Hz, 1.5A 24 volt operation: two (2), 7-24 AH batteries Up to 26 AH batteries mounted Up to two 18AH batteries Up to two 12AH batteries per supply B.OA max 0.030 A 0.15A under all conditions 2.OA if load is removed dur- ing operation (external relay or AC Fail Relay is required) Specifications (Continued) NAC Output Ratings: 24VDC fully regulated, 3.OA End -of -Line Resistor Range: Common Trouble Relay/AC Fail Relay: Input Control Circuit: Temperature Rating: Relative Humidity: Cabinet Dimensions: max per circuit (B.OA total) 2K to 25k ohm, Yz watt 2.OA at 28VDC or 120VAC 16-30VDC @ 5mA min. 32°F to 120°F (0°C to 49°C 10% to 93% non -condensing HPFF8 Cabinet: 16.65' W x 19.0" H x 5.2" D (42.29 W x 48.26 H 13.23 D cm) SBB-D4 Cabinet: 24" W x 45.9" H x 5.15" D (60.96 W x 116,52 H x 13.1 D cm) Ordering Information Part Number Description HPFF8 8A fire rated power supply operating at 120VAC/60 Hz. Unit includes red enclosure with HPP lock and key HPFF8CM 8A fire rated power supply - chassis mounted operating at 120VAC/60 Hz. Unit includes mounting hardware for installation in the SBB-D4 enclosure HPFFBE 8A fire rated power supply operating at 240VAC/50 Hz HPFFBCME 8A fire rated power supply chassis mounted operating at 240VAC/50 Hz HPP31076 Class A (Style Z) NAC module FCI-VDR-D4 Vented door, PK -625 lock and key for SBB-D4 backbox, black SBB-D4 Backbox, accepts up to 4 chassis, black GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60521 Rev. 6 page 2 of 2 www.gamewell-fci.com Nelson I d I L1 I Systems FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 www.nelsonf"ire.com BYU-Idaho Student Housing Building A Fire Alarm System Submittal Battery Calculations & Voltage Drop ia. �. 9 . .. � . k .l System Current Draw ®a E3 Series Control Panel with Broadband Total Standby 0.689 A Total Alarm 4.218 A Device Qty Draw I Standby Cit Draw Alarm 1. System Device Intel_ Loop Interface, Main Board ILI-MB-E3 1 x 0.08100 0.08100 1 x 0.15000 0.15000 Intel. Loop Interface Supplement BoardILI-S-E3 3 x 0.08100 0.24300 3 x 0.15000 0.45000 Intel. Lao Interface Main Board - Apollo ILI95-MB-E3 0 x 0.05000 0 x 0.08100 Intel. Loop Interface Supplement Board - A ollo I1 -I95 -S -E3 0 x 1 0.05000 0 x 0.09100 7100 Panel, 1 SLC 0 z 1 0.05600 0 x 0.070 7100 Panel, 1 SLC with DACT 0 x 0.07500 0 x 0.0950060 7100 Panel, 2 SLC 0 x 0.06500 0 z 0.08500 7100 Panel, 2 SLC with DACT 0 x 0.08500 0 x 0.10500 2. E3 Optional Modules 120V Power Supply Sub-AssemblyPM-9) 1 x 0.05000 0.05000 1 x 0.05000 0.05000 240V Power Su Sub-AssemblyPM-9G 0 x 0.02700 0 x 0.05000 LCD Display 8 Switch Control LCD -E3 2 x 0.02400 0.04800 2 x 0.02800 0.05600 ARCNET Re eater RPT -E3 2 x 0.01300 0.02600 2 x 0.01300 0.02600 Di ital CMUDACT-E3 0 x 0.01800 0 x 0.01800 Optional Remote Serial Annunicator LCD -7100 0 x 0.05000 0 x 0.07500 Network LCD Annunicator NGA 0 x 0.20000 0 x 0.20000 Auxilia Switch Sub-AssemblyASM-16 2 x 0.01100 0.02200 2 x 0.01100 0.02200 Remote LED Driver Module ANU-48 0 x 0.01100 0 x 0.01100 Addressable Node Expander(ANA) 1 x 0.06500 0.06500 1 x 0.06500 1 0.06500 3.7100 Optional Modules Intelligent Network Interface Module INI-7100 0x 0.04000 0 x 0.04000 Printer Transient Module PTRM 0 x 0.02000 0 x 0.02000 Remote LED Driver Module LDM-7100 Class A Otion Module (;AOM 0 o x z 0.03500 0.00100 0 0 x x 1 0.20000 0.00100 unici a ncmt Option Module x I o.uuiuu I U x Command enter Intel. Network Command Center INI-VGC 0 x 0.15000 0 x 0.15000 Addressable Switch Sub-assemblyASM-18 0 x 0.01100 0 x 0.01100 Voice Pam Micro hone Micro hon 1 0 1 x I 0.00100 I 0 I x I 0.00100 Firefighter's Telephone Handset 0 1 x 1 0.02000 1 1 0 1 x 1 0.02000 IN6VGX Voice Gatewa Intel. Network Voice Gateway INI-VGX In 0I x 1 0.15000 0 x 0.15000 120V Power Su I Sub-Assembl PM -9 0 x 0.05000 0 x 0.05000 240V Power Su Sub-Assembl PM -8G) 0 x 0.02700 0 x 0.05000 Amplifier Sub -assembly, 50 watt 25V AM -50 0 x 0.08600 0 x 2.20600 Amplifier Sub -assembly, 50 watt 70V AM -50-70 0 x 0.04900 0 x 2.30000 Addressable Output Module -Signal AOM -28F 0 x 0.00200 0 x 0.00650 Addressable 29! 12 Module -Tele hone AOM -TEL 0 x 0.00200 0 x 0.00650 Addressable Out ut Module -Audio (AOM -MUX 0 x 0.00200 0 x 0.00650 6. INI-VGE Command Center Voice Gateway Intel. Network Command Voice Gateway (INI-VGE 0 x 0.15000 0 1 x 1 0.15000 Addressable Switch Sub -assembly ASM -16 0 x 0.01100 0 x 0.01100 Voice Paging Microphone (Microphone) 0 x 0.00100 0 x 0.00100 Firefi hter's Tele hone Handsel 0 x 0.02000 0 x 0.02000 Addressable Output Module -Signal AOM -28F 0 x 0.00200 0 x 0.00650 Addressable L'9!,12t Module -Tele hone AOM -TEL 0 x 0.00200 0 x 0.00650 Adtlressable Ouul Module -Audio (AOM -MUX) 0 x 0.00200 0 x 0.00650 7. Smoke Detectors/Modules ASD-PL2F/ASD-IL2F 292 1 x 1 0.00030 0.08760 292 z 0.00650 1.89800 ATD-RL2F/ATD-HL2F 2 x 0.00030 0.00060 2 x 0.00650 0.01300 DNR 87 x 0.00030 0.02610 87 x 0.00650 0.56550 AMM4F 4 x 0.00038 0.00150 4 x 0.00500 0.02000 AOM-2RF 5 x 0.00038 0.00188 5 x 0.00650 0.03250 MS-7AF 2 x 0.00030 0.00060 2 x 0.00300 0.00600 MCS-COF 120 x 0.00030 0.03600 120 x 0.00720 0.86400 8. Notification Appliances 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 000000 0 x 0.00000 Total Standby Load: 0.689 A Total Alarm Load: 4.218 A a GOMM System Power Requirements E3 Fire Alarm Control Panel with Broadband Protected Premises: Building A -- BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared E Nelson Fire Systems Phone: 801-468-8300 Address: 1481 S Major Street Email: offceCc nelsonfire corn City: Salt Lake City State: Utah Zip: 84115 Secondary Load Requirements 20.28 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby LoadRe 0.689 A x uired Standb Time 24 hours 16.54 Secondary Alarm LoadRe 4.218 A x uired Alarm Time hours) 0.084 hours 0.35 Total Secondary Load 16.90 Derating factorl x 1.20 Secondary Load Requirements 1 20.28 AH Battery Selection 26.00 Amp Hours Select batteries from the list 26 AH Battery 12 volt Battery Distribution Chart Shows amp -hour distribution of your selections. SecondaryAlarm Load 2% Secondary Standby Load 76% !Spare Battery Capacity 5.72 Am Hours ISecondary Standby Load 19.85 Amp Hours ISecondary Alarm Load 0.43 Amp Hours eSpare BaVery Capacity Mecondary Standby Load MSecondaryNan Load Honeywell System Current Draw - HPFF8 #1 Standb 0.075A Alarm 2.634A Device SecondaELNonAlar7, e Dr- , x . 1. system Modules HPFF8 Main Circuit Board 1 1 x I 0.07500 0.07500 1 x 0.20600 0.20600 2. HS -1 P2W15 2 x 0.00000 0.00000 2 1 z 0.09100 0.18200 p2W75 6 x 0.00000 0.00000 6 x 0.17600 1.05600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 o z 0.00000 0 x 0.00000 0 x 0.00000 o x 2.00000 0 x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Am s): 0.00000 1.23800 3.. 0 x 0.00000 0 1 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 NAC #2 Totals (Max 3 Amps): 0.00000 1 0.00000 4.. o z 0.00000 o z 0.00000 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 N0 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Am s): 0.00000 0.00000 5.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 1 0.00000 0.00000 6. Auxiliary Power B200S 34 x 0.00000 0.00000 34 x 0.03500 1.19000 Auxiliary Device0 z 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device0 x 0.00000 0 x 0.00000 Auxillary Device 0 z 0.00000 0 x 0.00000 TB4 Totals Max 2 Anus): 0.00000 1.19000 7. Com a0ble Devices not listed Other compatible devices0 x 0.00000 0 x 0.00000 m Other coatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 I x 1 0.00000 0 1 x 1 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 2.634 Honeyv; `' �=�1 Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building A - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: office-@neisonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements F 2.43 Amp Hours Total Secondary Load from the calculation table below. Current Draw Time (hours) Total (AH) Secondary Standby LoadRequired Standby Time 0.075 A x 24 hours 1.80 Secondary Alarm Load Required Alarm Time (hours) 2.634 A x 0.084 hours 0.22 Total Secondary Load 2.02 Derating factor x 1.2 Secondary Load Requirements 2.43 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 3% ■ Spare Battery Capacity ■ Secondary Standby Load ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - IiPFF8 #2 -Ji IStandby 10.075A Alarm 12.789A r • r • r . 1. System Modules HPFFB Mein Circuit Board I 7 I x 1 0.07500 0.07500 7 1 x 0.20600 0.20600 2. HS-4 P2W75 3 x 0.00000 0.00000 3 z 0.09100 0.27300 P2W75 1 x 0.00000 0.00000 1 x 0.17600 0.17600 P2WH777 3 0.00000 0.00000 3 x 0.30300 0.90900 0 0.00000 0 x 0.00000 0 0.000Do 0 x 0.00000 0 0.00000 Ix 0 x 0.00000 0 0.00000 0 x 0.00000 0 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 1.35800 3.. 0 x 0.00000 0 x 0oOOODo D x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC#2 Totals Max 3 Amps): 0.00000 0.00000 4.. 0 x 0.00000 0 x 0.00000 0 x O.D0000 0 x O.000DO 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.00000 5.. 0 x 0.00000 0 x 0.00000 o 1 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 x O.0000D 0 x 0.00000 0 x 0.000Do 0 x 0.00000 0 x o.0OODo 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x o.DOOOO 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.00000 6. Auxiliary Power B2009 35 x 1 0.00000 0.00000 35 x 0.03500 1.22500 AuxiliaryDevice 0 x0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps) 0.00000 1.22500 7. Compatible Devices not listed Other oom atibie devices0 x 0.00000 0 x 0.0000000 Other compatible devices 0 x 0.00000 0 z 0.000 Other oom alible devices 0 x 0.00000 0 z I 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Load: 2.789 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building A - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: Office0ne sonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements F-24-4-1 Amp Hours Total Secondary Load from the calculation table below. Current Draw Total Secondary Standby Load Required Standby Time 0.075 A x 24 hours 1.80 Secondary Alarm Load Required Alarm Time (hours) 2.789 A x 0.084 hours0.23 Total Secondary Load 2.03 Derating factorl x 1.2 Secondary Load Requirements 2.44 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 4% ■ Spare Battery Capacity • Secondary Standby Load •SecondaryAlarm Load Comments 1. Batteries will ft in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). !Spare Battery Capacity 5.58!Battery Selection AH - Secondary Load Requirements AH Secondary Standby Load 1 2.16 ISeconclary Standby Load (AH)' Derating Factor Secondary Alarm Load 1 0.28 Secondary Alarm Load (AH)' Derating Factor Page 3 of 129 Honeywell System Current Draw - HPFF8 #3 stanab 0.075A Alarm 2.824A �. 1. System Modules . .IMMI MIUM.1,42.. HPFF8 Main Circuit Board 1 z 1 0.07500 1 0.07500 1 i 1 x 1 0.20600 1 0.20800 2. HS-5 P2W15 3 z 1 0.00000 0.00000 3 x 0.09100 0.27300 P2W75 1 x 0.00000 0.00000 1 x 0.17600 0.17600 P2WH177 3 x 0.00000 0.00000 3 x 0.30300 0.90900 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #7 Totals (Max 3 Amps): 1 0.00000 1.35800 3.. 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 0000 0 x 0.00000 o 0 x 0.00000 o 0 x 0.00000 0 tXO.OEOOGO 0 x 0.00000 0 o x 0.00000 0 NAC #2 Totals (Max 3 Am s : 0.00000 0.00000 4.. 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0x o.a0000 0 x 0.00000 a x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps) 0.00000 0.00000 5.. x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 li0 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.00000 6. Auxiliary Power B2008 36 x 0.00000 0.00000 36 0.03500 1.28000 Auzilia Device 0 x 0.00000 0 0.00000 AuxiliaryDevice 0 x 0.00000 0 Ix 0.00000 AuxiliaryDevice 0 x 0.00000 0 0.00000 Auxiliary Devlce 0 x 0.00000 0 0.00000 T64 Totals Max 2 Amps): 0.00000 1.26000 7. Com alible Devices not listed Other compatible devices0 x 0.00000 0 x 0.00000 Other wni alible devices 0 x 0.00000 0 x 1 0.00000 Other cem atible devices 0 1 z 1 0.00000 0 x 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Load: 2.824 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building A - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: orrceraneisonrre.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.44 Amp Hours Total Secondary Load from the calculation table below. Current Draw Time (hours) Total [AH) Secondary Standby Load Required StandbyTime 0.075 A x 24 hours 1.80 Secondary Alarm Load Required Alarm Time (hours) 2.824 A x 0.084 hours 0.24 Total Secondary Load 2.04 Derating factor x 1.2 Secondary Load Requirements 2.44 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 4% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will ft in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 19001iny elp :system Cuireltt Maw- I IPI-1-8 N Standby 10.075A °. Alarm 12.430 A 1. System Modules HPFFB Main Circuit Board 1 1 x 1 0.07500 1 0.07500 1 1 x 0.20600 0.20600 2. HS-3 P2W15 2 1 z 1 0.00000 1 0.00000 2 z 1 0.09100 0.18200 P2W75 1 x 0.00000 0.00000 1 z 0.17600 0.17600 P2WH177 2 0.00000 2 x 0.30300 0.60600 0 0 x 0.00000 0 0 x 0.00000 0 EX0.0000(00P0010 0 x 0.00000 o 0 x 0.00000 o o x 1 0.00000 NAC #1 Totals (Max 3 Am s): 0.00000 0.96400 3.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 1 o x 0.00000 o x 0.00000 1 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 a x 0.00000 NAC #2 Totals (Max 3 Amps) 0.00000 0.00000 C. 0 z 0.00000 0 % 1 0.00000 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0 OOOOO 0 x 0.00000 1o0 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.00000 5.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00OOO 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.00000 6. Auxiliary Power B2008 36 x 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x O.o0000 Auxiliary Device 0 x 0.00000 0x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals Max 2 Am s): 0.00000 1.26000 7. Compatible Devices not listed Other wmipatible devices0 x 0.00000 0 x 0.00000 Other cem atibie devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 x 1 0.00000 0 x 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Load 2.430 Honeywell Secondary Power Requirements Page 2 of 129 HPFF8 Power Supply Protected Premises: Building A - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: Offce(aMelsonfire.corn City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.40 Amp Hours Total Secondary Load from the calculation table below. Current Draw Time (hours) Total (AH) Secondary Standby Load Required StandFyTime 0.075 A x 24 hours 1.80 Secondary Alarm Load Required Alarm Time (hours) 2.430 A x 0.084 hours 0.20 Total Secondary Loadl 2.00 Derating factor x 1.2 Secondary Load Requirements 2.40 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp-hour distribution of your selections. Secondary Alarm Load 3% Secondary Standby Load ■Spare Battery capacity 27% ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). !Spare Battery Capacity 5.60 atte Selection AH - SecondaryLoad Requirements AH SecondaryStandbyLoad 2.16 cStandby Load AH * Derating Factor ISewndary, Alarm Load 0.24 ISecondary Alarm Load AH . Derating Factor Page 3 of 129 Honeywell System Current Draw - HPFF8 #5 Standby 0.075A Alarm 4.077 A 1. .S stem Modules HPFFe Main Circuit Board 1 I x 1 0.07500 1 0.07500 1 1 1 x 1 0.20600 1 0.20600 2. HS-2 0.00000 0.00000 5 x 0.09100 0.45500 0.00000 0.00000 1 x 0.11600 0.11600 0.00000 0.00000 1 x 0.17600 0.17600 20.60000 0 x 0.00000 !MM 0.00000 0 x 0.00000 0.00000 0 x 0.00000 0.00000 0 x 0.00000 20.00000 0 x 0.00000 Max 3 Am s): 0.00000 0.74700 3. HS-6 P2W15 7 z 1 0.00000 0.00000 7 1 x 0.09100 0.63700 0 x 1 0.00000 0 z 0.00000 0 x 0.00000 0 x 20.00000 0 x 0.00000 0 x 0.00a00 0 x 0.00000 0 x 20.200000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #2 Totals Max 3 Amps): 0.00000 0.63700 4. HS-7 P2W15 3 z 0.00000 0.00000 1 3 x 0.09100 0.27300 p2W30 t x 0.00000 0.00000 1 x 0.11600 0.11600 p2W75 1 x 0.00000 0.00000 1 0.17600 0 z 0000000 0000 x 0000000 0000 x 0000000 tXO.17600 0000 x000000o 0000 x 20.000020 0 000 NAC #3 Totals (Max 3 Amps): 0.00000 0.56500 5. HS-6 P2W15 6 z 0.00000 0.00000 6 x 0.09100 0.54600 p2W30 1 x 0.00000 0.00000 1 x 0.11600 0.11600 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps :1 0.00000 0.66200 6.AuxiliaryPomr 8200S 36 1 x 0.00000 1 0.00000 38 1 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000000 0 x 0.00000 Auxiliary Device 0 x 0.00 0 x 0.00000 TB4 Totals (Max 2 Amps):j 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices 0 z0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other com alible devices 0 1 x 0.00000 1 10 x 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Load: 4.077 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building A - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: of go pneisonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements F-2.57-1 Amp Hours Total Secondary Load from the calculation table below. r . Secondary Standby Load ed Standby Time 0.075 A x24 hoursSecondary 70.084 Alarm Load Alarm Time (hours 4.077 A x hours 0.34 Total Secondary Load 2.14 Derating factor x 1.2 Secondary Load Requirements 2.57 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt G Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa( 27% SecondaryAlarm Load 5% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 46 Stantlb 0.075A --Alarm 3.295A .- . . . .. 1. System Modules HPFFB Main Circuit Board 1 1 x 1 0.07500 1 0.07500 1 z 0.20600 1 0.20600 2. HS -9 P2W15 z 0.00000 0.00000 3 x 0.09100 0.27300 P2W30 z 0.00000 0.00000 1 x 0.11600 0.11600 x 0.00000 0 x 0.00000 x 0.00000 0 x 0.00000 EO x O.00GOO 0 x 0.00000 x 0.00000 0 x 0.00000 x 0.00000 0 x 0.00000 x 0.00000 0 x O.D000O NAC p1 Totals Max 3 Amps): 0.00000 0.38900 3. HS -10 P2Wl5 4 x 0.00000 1 0.00000 4 x 0.09100 0.36400 P2W30 1 x 0.00000 1 0.00000 1 x 0.11600 0.11600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x o.00000 0 x 0.00000 NAC p2 Totals (Max 3 Amps): 0.00000 0.48000 4. HS -11 P2W15 3 x 0.00000 0.00000 3 x 0.09100 0.27300 P2W30 1 x 0.00000 0.00000 1 x 0.11600 0.11600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x D.00DOO 0 x 0.00000 o x 0.00000 0 x 0.00000 0 z 0.00000 0 x O.DO000 0 x 0.00000 0 x 0.00000 NAC O Totals (Max 3Amps):j 0.00000 0.38900 5. HS -12 P2W15 5 x 0.00000 0.00000 5 x 0.09100 0.45500 P2W30 1 x 0.00000 0.00000 1 x 0.11600 0.11600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x O.00000 0 x 0.00000 0 x 0.00000 NAC 44 Totals (Max 3 Amps)] 0.00000 0.57100 6. Auxiliary Power 82005 36 1 x 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps): 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices0 z 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 3.295 1 0"eywell Secondary Power Requirements HPFF8 Power Supply dam Page 2 of 129 Protected Premises: Building A - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: office0nelsonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements r 2.49 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Load Required Standby Time x 0.075 A 24 hours 1 1.80 Secondary Alarm Load Required Alarm Time (hours 0.084 hours 0.28 3.295 A x Total Secondary Loadl 2.08 Derating factorl x 1.2 Secondary Load Requirements 2.49 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% SecondaryAlarm Load 4% ■ Spare Battery Capacity ■ Sewndary Standby Load •Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Hon"ell System oniont 1how - HPFF8 #7 Standby 0.075A Alarm 1.616A 1. S stem Modules HPFF8 Main Circuit Board 1 x 0.07500 0.07500 7I x 1 0.20600 1 0.20600 2. Rete #1 PR -3 2 x 0.00000 0.00000 2 x 0.03000 0.06000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 o x 0.00000 o x ;.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps): 1 0.00000 1 0.06000 3. Rola #1 PR -3 1 x 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x O.00n. NAC #2 Totals (Max 3 AMPS): 0.00000 0.03000 1 x 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 M 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x o.00DDo o x 0.00000 o x 0.00000 NAC #3 Totals (Max 3 AMPS): 0.00000 0.03000 S. Rate #d ---FX-F- PR -3 1 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.a0000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.03000 6. Auxilia Power B200S 36 x 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 002 0.00000 AuxiliaryDevice 0 z 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals Max 2 Amps)] 0.00000 1.26000 7. Com alible Devices not listed Other compatible devices 0 z 0.00000 0 x 0.00000 Other cem alible devices 1 0 1 x 1 0.00000 0 x 0.00000 Other com atible devices 0 x 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 1.615 Honeyweii Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building A - BYU-ID Student Housing Address: BYU-Idaho Date: 2/24/2014 City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: ofece0neisonflre.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.32 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A x I Time (hours) Total (AH) ---Required Standby Time 24 hours 1.80 Secondary Alarm Loadx 1.616 A Required Alarm Time (hours) 0.084 hours 0.14 Total Secondary Load 1.94 Derating factor x 1.2 Secondary Load Requirements 2.32 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Lo; 27% SecondaryAlarm Load 2% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #8 Standb 0.075 A Alarm 1.646 A Modules HPFFB Main Girmll Board 1 1 x 1 0.07500 1 0,07600 1 1 1 x 1 0.20600 0.20600 PR -3 1 x 0.00000 0.00000 1 x 0.03000 0,03000 0 x 0.00000 0 x 0.00000 2-x 201201 0 x 0.00000 0 x 0!000;0 0 x 0.00000 0 x a mom 0 x 0.00000 0 x 0.00000 0 x 0,00000 --Q-Lx I om000 0 x 0,00000 - 0 1 x 0.00000 0 x 0,00000 NAC #1 Totals (Max 3 Amps) 0.00000 0.03000 3. Relay #6 PR -3 I x 0.00000 0.00000 1 z 0.03000 0.03000 0 x 0.00000 0 x 0,00000 0 x 0.00000 0 x 0.00000 0 x -0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 - 0 x 0.00000 ETotals W3Amps) 0 x 0.00000 NEC (Max 10.00000 0.03000 4. Relay #7 PR -3 2 1 X 1 0.00000 1 0.00000 2 z 0.03000 0.06000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 000000 0 x 0,00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0,00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.06000 5. Relay #8 PR -3 2 1 x 1 0.00000 0,00000 2 X 0.03000 0.06000 0 x 0,00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.06000 6. Auxiliary Power B200S 36 x 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 2 2.00000 Auxiliary Device 0 x 0.002000 ro : x 0.00000 Auxiliary D"ce x 0.000 5 0 x 0.00000 TB4 Totals (Max 2 Amps): 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices 1 000000 0 x 0.00000 Other compatible devices 0 0.00000 0 x 0,00000 Other compatible devices 1 0 1 x 11 0.00000 0 x om000 Total Non -Alarm Load: 0.075 Total Alarm Load: 1.646 Secondary Power Requirements Protected Premises: Building A - BYU-ID Student Housing Address: BYU-Idaho Date: 2/24/2014 City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: Officeftelsonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements F 2.33 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A Time (hours) x Required Standb Time 24 hours Total (AH) 1.80 Secondary Alarm Load 1.646 A x Required Alarm Time (hours) 0.084 hours 0.14 Total Seconda Load 1.94 Derating factorl x 1.2 Secondary Load Requirements 1 2.33 Battery Selection Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) ® Amp Hours C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Lo 27% Comments Secondary Alarm Load 2% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 SYSTEM SENSOR° N=Ded kieasodvanoed sdulions: tb Name: Student Housing Building A BYU-Idaho Rexburg, ID Circuit Information Panel Name: HPPF8-1 Circuit Name: HS -1 Starting Voltage: Starting Voltage = 20.4 Prepared By: Nelson Fire Systems 1481 S. Major Street Salt Lake City, 84115 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (it) ern/Strobe 75 0.156 Non -temporal, Low 20 20 18.691 17.687 16.080 W m/Strobe 75 0.156 Non -temporal, Low 3050 18.709 17.717 16.127 W im/Strobe 75 0.156 Non -temporal, Low 40 90 18.760 17.797 16.254 W )m/Strobe 15 0.068 Non -temporal, Low 50 140 18.854 17.946 16.492 W xn/Strobe 75 0.156 Non -temporal, Low 25 165 18.908 18.031 16.628 iW xn/Strobe 75 0.156 Non -temporal, Low 55 220 19.061 18.274 17.015 lW orn/Strobe 15 0.068 Non -temporal, Low 30 250 19.163 18.436 17.273 IW orn/Strobe 75 0.156 Non -temporal, Low 20 270 19.236 18.553 17.459 2W Total current/amps 1.072 Total DIst:270 voltage drop 1.709 2.713 F 4.320 /27/2014 Circuit Information Panel Name: HPFF8-2 Circuit Name: HS -4 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 18 (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 40 40 19.213 18.517 17.401 P2W Horn/Strobe 177 0.291 Non -temporal, Low 25 65 19.220 18.528 17.418 P2WH Horn/Strobe 177 0.291 Non -temporal, Low 20 85 19.249 18.574 17.491 P2WH Horn/Strobe 15 0.068 Non -temporal, Low 20 105 19.301 18.657 17.624 ! P2W Horn/Strobe 177 0.291 Non -temporal, Low 20 125 19.359 18.748 17.769 16.216 P2WH Horn/Strobe 75 0.156 Non -temporal, Low 20 145 19.440 18.877 17.974 16.542 P2W 15 0.068 Non -temporal, Low 25 170 19.557 19.063 18.270 17.013 Eor,/'trorb amps 1.233 Total Dist: 170 voltage drop 1.187 1.883 2.999 2/27/2014 2 SYSTEM SENSOR' civariced idea& advanced solutions: Circuit Information Panel Name: HPFF8-3 Circuit Name: HS -5 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16r (Amps) last device source (ft) Drn/Strobe 75 0.156 Non -temporal, Low 60 60 19.171 18.450 17.294 2W orn/Strobe 177 0.291 Non -temporal, Low 20 80 19.184 18.470 17.326 2WH orn/Strobe 15 0.068 Non -temporal, Low 20 100 19.220 18.527 17.417 1 1 2W orn/Strobe 177 0.291 Non -temporal, Low 20 120 19.261 18.593 17.522 2WH torn/Strobe 177 0.291 Non -temporal, Low 20 140 19.326 18.695 17.685 16.082 2WH I oco/Strobe 15 0.068 Non -temporal, Low 20 160 19.414 18.835 17.908 16.437 2W lorn/Strobe 15 0.068 Non -temporal, Low 20 180 19.508 18.984 18.145 16.813 2W Total current/amps 1.233 Total Dist: 180 voltage drop 1.229 1.950 1 3.106 2/27/2014 3 Circuit Information Panel Name: HPFF8-4 Circuit Name: HS -3 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 la (Amps) last device soume(ft) Horn/Strobe 35 0.068 Non -temporal, Low 30 30 19.887 19.586 19.104 18.338 P2W Horn/Strobe 177 0.291 Non -temporal, Low 20 50 19.893 19.595 19.118 18.360 P2WH Horn/Strobe 15 0.068 Non -temporal, Low 20 70 19.921 19.641 19.191 18.476 P2W Horn/Strobe 177 0.291 Non -temporal, Low 20 90 19.956 19.695 19.277 18.614 P2WH Horn/Strobe 75 0.156 Non -temporal, Low 20 110 20.014 19.787 19.423 18.846 P2W Total current(amps 0.874 Total Dist: 110 voltage drop 0.513 0.814 1.296 2.062 2/27/2014 4 •� SYSTEM . SENSOR` fy« idecn o sdutions :ircuit Information Panel Name: HPFF8-5 Circuit Name: HS -2 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 16 (Amps) last device saume (n) rn/Strobe 15 0.068 Non -temporal, Low 110 110 19.588 19.112 18.348 17.137 N rn/Strobe 15 0.068 Non -temporal, Low 45 155 19.601 19.131 18.380 17.186 W rn/Strobe 30 0.096 Non -temporal, Low 20 175 19.612 19.149 18.407 17.230 W ern/Strobe 15 0.068 Non -temporal, Low 20 195 19.630 19.178 18.454 17.305 W vn/Strobe Non-temporal, Low 25 220 19.660 19.226 18.531 17.427 W rn #150.068 Non -temporal, Low 30 250 19.715 19.313 18.670 17.648 W/Strobe W Irn/Strobe Non -temporal, Low 20 270 19.757 19.380 18.776 17.817 �yy Total current/amps 0.592 Total DIst:270 voltage drop 0.812 1.288 2.052 3.263 :/27/2014 5 Circuit Information Candela Panel Name: HPFF8-5 Circuit Name: HS -6 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 SS (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 55 55 19.506 18.981 18.141 16.807 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 75 19.512 18.990 18.155 16.829 P2W Horn/Strobe 15 0.068 Non -temporal, Low 35 110 19.531 19.020 18.203 16.906 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 130 19.547 19.046 18.244 16.971 P2W Horn/Strobe 15 0.068 Non -temporal, Low 90 220 19.646 19.203 18.493 17.367 P2W Horn/Strobe 15 0.068 Non -temporal, Low 80 300 19.755 19.376 18.770 17.807 P2W 15 0.068 Non -temporal, Low 20 320 19.788 19.428 18.852 17.939 FornIStrorbe amps 0.476 Total Dist:320 voltage drop 0.894 1.419 2.259 3.593 2/27/2014 6 ,•`� SYSTEM SENSOR° wed klem odvonced solutions Circuit Information Panel Name: HPFF8-5 Circuit Name: HS -7 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela CurrentLNon-temporal, Dist from Dist from 12 14 16 18 (Amps)last device source (R) m/Strobe 15 0.068 125 125 19.891 19.593 19.114 18.355 W m/Strobe 15 0.068 55 180 19.906 19.617 19.152 18.416 :W ern/Strobe 30 0.096 Non -temporal, Low 20 200 19.917 19.634 19.180 18.460 W. )m/Strobe 15 0.068 Non -temporal, Low 20 220 19.936 19.663 19.227 18.534 !Wr xn/Strobe 75 0.156 Non -temporal, Low 20 240 19.960 19.702 19.286 18.631 ryy rotal currenVamps 0.456 Total Dist: 240 voltage drop 0.509 0.807 1.286 2.045 ?/27/2014 7 Circuit Information Panel Name: HPFF8-5 Circuit Name: HS -8 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 1214 16 18 (props) last device source (R) Horn/Strobe 15 0.068 Non -temporal, Low 50 50 19.467 18.920 18.043 16.651 P2W Horn/Strobe 15 0.068 Non -temporal, Lowd40 70 19.473 18.929 18.057 16.673 P2W Horn/Strobe 15 0.068 Non -temporal, Low 110 19.495 18.963 18.112 16.761P2WHorn/Strobe 15 0.068 Non -temporal, Low 130 19.511 18.989 18.153 16.827P2WHorn/Strobe 15 0.068 Non -temporal, Low 220 19.610 19.145 18.402 17.222 P2W Horn/Strobe 15 0.068 Non -temporal, Low 80 300 19.719 19.319 18.678 17.662 P2W 30 0.096 Non -temporal, Low 20 320 19.752 19.371 18.761 17.794 E amps 0.504 Total Dist: 320 voltage drop 0.933 1.480 2.357 3.749 2/27/2014 8 ?1 SYSTEM _40SENSOR" vanced ideas advanced sohrtion :ircuit Information Panel Name: HPFF8-6 Circuit Name: HS -9 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - Volt Supply rpe and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 16 (Amps) last device source (ft) n/Strobe 15 0.068 Non -temporal, Low 60 60 20.065 19.868 19.552 19.052 V n/Strobe 15 0.068 Non -temporal, Low 20 80 20.070 19.876 19.566 19.074 N n/Strobe 30 0.096 Non -temporal, Low 60 140 20.103 19.928 19.649 19.205 N m/Strobe 15 0.068 Non -temporal, Low 60 200 20.159 20.017 19.790 19.430 N rtal current/amps 0.300 Total DIst:200 voltage drop 0.335 0.532 0.848 1.348 '27/2014 9 Circuit Information Candela Panel Name: HPFF8-6 Circuit Name: HS -10 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 18 (Amps) lest device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 65 65 19.851 19.529 19.013 18.193 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 85 19.856 19.537 19.026 18.215 P2W Horn/Strobe 15 0.068 Non -temporal, Low 90 175 19.906 19.616 19.151 18.413 P2W Horn/Strobe 15 0.068 Non -temporal, Low 80 255 19.971 19.720 19.317 18.677 P2W Horn/Strobe 30 0.096 Non -temporal, Low 20 275 19.993 19.754 19.372 18.765 P2W Total current/amps 0.368 Total Dist:275 voltage drop 0.549 0.871 1.387 2.207 2/27/2014 10 SYSTEM . SENSOR` vaned idem advanced solutiorw, :ircuit Information Panel Name: HPFF8-6 Circuit Name: HS -11 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply rpe and Model Candela Current Tone and Volume Dist from Dist froF2O 14 16L19O'0'3 (Amps) last device cource(nn/Strobe 15 0.068 Non -temporal, Low 70 7 19.849 19.522 V 'n/Strobe 15 0.066 Non -temporal, Low 20 90 20.058 19.857 19.536 19.025 N -n/Strobe 30 0.096 Non -temporal, Low 60 150 20.091 19.909 19.618 19.157 N rn/Strobe 15 0.068 Non -temporal, Low 60 210 20.147 19.998 19.760 19.382 N otal current/amps 0.300 Total DIst:210 voltage drop 0.347 0.551 0.878 1.397 /27/2014 I1 Circuit Information Panel Name: HPFF8-6 (1.5) amp circuit Circuit Name: HS -12 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 18 (Amps) last device source (R) Horn/Strobe IS 0.068 Non -temporal, Low 75 75 19.694 19.279 18.615 17.561 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 95 19.699 19.288 18.629 17.563 P2W Horn/Strobe 15 0.068 Non -temporal, Low 90 185 19.748 19.366 18.753 17.780 P2W Horn/Strobe 15 0.068 Non -temporal, Low 80 265 19.814 19.470 18.919 18.044 P2W Horn/Strobe 30 0.096 Non -temporal, Low 20 285 19.836 19.505 18.974 18.132 P2W Horn/Strobe IS 0.068 Non -temporal, Low 20 305 19.865 19.552 19.049 18.251 P2W Total current/amps 0.436 Total Dist:305 voltage drop 0.706 1.121 1.785 2.839 2/27/2014 12 Nelson I d I L1 I Systems FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 www.nelsonfirexom BYU-Idaho Student Housing Building B Fire Alarm System Submittal Battery Calculations & Voltage Drop ftdrnewell System Current Draw QJ xM E3 Series Control Panel with Broadband Device Total Standby 1 QtDraw 1 0.586 A Standby Qty Total Alarm Draw 3.304 A Alarm 1. System Device Intel. Loop Interface, Main Board ILI-MB-E3 1 x I 0.08100 0.08100 1 x 0.15000 0.15000 Intel. Loop Interface Supplement Board ILI-6-E3 3 x 0.08100 0.24300 3 x 0.15000 0.45000 Intel. Loop Interface Main Board - Apollo ILI95-MB-E3 0 x 0.05000 0 x 0.09100 Intel. Loop Interface Supplement Board - Apollo ILI95-S-E3 0 x 0.05000 0 x 0.09100 7100 Panel, 1 SLC 0 x 0.05600 0 x 0.07600 7100 Panel, 1 SLC with DACT 0 x 0.07500 0 x 0.09500 7100 Panel, _2SLC 0 x 0.06500 0 x 0.08500 7100 Panel, 2 SLC with DACT 0 x 0.08500 0 x 0.10500 2. E3 Optional Modules 120V Power Supply Sub -Assembly PM -9 1 x 1 0.05000 0.05000 1 x 0.05000 0.05000 240V Power Supply Sub -Assembly PM -9G 0 x 1 0.02700 0 x 0.05000 LCD Display & Switch Control LCD -E3 2 x 0.02400 0.04800 2 x 0.02800 0.05600 ARCNET Repeater RPT -E3 2 x 0.01300 0.02600 2 x 0.01300 0.02600 Digital Communicator DACT-E3 0 x 0.01800 0 x 0.01800 Optional Remote Serial Annumcator LCD -7100 0 x 0.05000 0 x 0.07500 Network LCD Annunicalor (NGA) 0 x 0.20000 0 x 0.20000 Auxiliary Switch Sub -Assembly ASM -i6 2 x 0.01100 0.02200 2 x 0.01100 0.02200 Remote LED Driver Module ANU-48 0 x 0.01100 0 x 0.01100 Addressable Node Expander ANX 0 x 0.06500 0 x 1 0.06500 3.7100 Optional Modules Intelligent Network Interface Module INI-7100 0 x 0.04000 0 x 1 0.04000 Printer Transient Module PTRM 0 x 0.02000 0 x 0.02000 Remote LED Driver Module LDM-7100 0 x 0.03500 0 x 0.20000 Class A O lion Module CAOM 0 x 0.00100 0 x 0.00100 unici a ncm hon o u e x 0.00 o x ommana Center Intel. Network Command Center INI-VGC 0 x 1 0.15000 1 0 x 0.15000 Addressable Switch Sub -assembly ASM -16 0 x 1 0.01100 1 0 I x 1 0.01100 Voice Paging -Microphone (Microphone) 0 1 x I 0.00100 I 0 I x I 0.00100 Firefighter's Telephone Handset 0 1 x 1 0.02000 1 1 0 1 x 1 0.02000 x S. INI-VGX Voice Gatewa Intel. Network Voice Gateway INI-VGX 0 x 1 0.15000 0 x 0.15000 Power Su I Sub-Assembl PM -8 0 0 x 0.05000 MM120V Power Su I Sub-Assembl (PM -9G 0 0 x 0.05000 Am lifer Sub-assembl 50 watt 25V AM -50 0 0 x 2.20600 Am lifer Sub-assembl 50 watt 70V AM -50-70 0 EO.O2700 0 x 2.30000 Addressable Out ut Module -Si nal AOM-2SF 0 o x 0.00650 Addressable Out ul Module -Tele hone AOM -TEL 0 0 x 0.00650 Addressable Oul ut Module -Audio AOM -MUX 0 0 x 0.00650 6. INI-VGE Command Center Voice Gateway Intel. Network Command Voice Gateway INI-VGE 0 x 1 0.15000 0 x 0.15000 Addressable Switch Sub -assembly ASM -16 0 x 0.01100 0 x 0.01100 Voice Paging Microphone (Microphone) 0 z 0.00100 0 x 0.00100 Firefighter's Telephone Handset 0 x 0.02000 0 x 0.02000 Addressable Output Module -Signal AOM-2SF 0 x0.00200 0 x 0.00650 Addressable Output Module -Telephone AOM -TEL 0 x 0.00200 0 x 0.00650 Addressable Output Module -Audio AOM -MUX 0 x 0.00200 0 x 0.00650 7. Smoke Detectors/Modules ASD-PL2F/ASD-IL2F 217 x 0.00030 0.06510 217 x 0.00650 1.41050 ATD-RL2F/ATD-HL2F 2 x 0.00030 0.00060 2 x 0.00650 0.01300 DNR 68 x 0.00030 0.02040 68 x 0.00650 0.44200 AMM -0F 3 z 0.00038038 0.00113 3 x 0.00500 0.01500 AOM-2RF 5 x 0.00 0.00188 5 x 1 0.00650 0.03250 MS-7AF 1 x 0.00030 1 0.00030 1 x 0.00300 0.00300 MCS-COF 88 x 1 0.00030 1 0.02840 88 x 1 0.00720 0.63360 8. Notification Appliances 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 000000 0 x 1 0.00000 Total Standby Load: 0.586A Total Alarm Load: 3.304A �tgyi System Power Requirements ® E3 Fire Alarm Control Panel with Broadband Protected Premises: Building B -- BYU-ID Student Housing Address: BYU-Idaho Date: 2/24/2014 City: Rexburg State: ID Zip: Prepared t Nelson Fire Systems Phone: 801-468-8300 Address: 1481 S Major Street Email: oKce o nelsonfire com City: Salt Lake City State: Utah Zip: 84115 Secondary Load Requirements 17.20 Amp Hours Total Secondary Load from the calculation table below. Current Draw Time (hours) Total (AH) Secondary Standby Load Required Standby Time 0.586 A x 24 hours 14.06 Secondary Alarm LoadRe uired AlaTime hours rm0.084 3.304 A x hours 0.28 Total Secondary Load 14.34 Derating factor x 1.20 Secondary Load Requirements 1 17.20 AH Battery Selection 26.00 Amp Hours Select batteries from the list 26 AH Battery (12 volt) Battery Distribution Chart Shows amp -hour distribution of your selections. SecondaryAlarm Load 1% CSpara Badery Capacay nSacontlary Standby Loetl .Secondaryaarm Load Secondary Standby Load 1 65% !SDare Battery Capacity 8.80 Am Hours ISecondary Standby Load 1 16.87 Amp Hours ISecondary Alarm Load 1 0.33 Amp Hours ,110wde"Y x;111 Currcllt f lr�wv 5ysicnllWEIMMMM I II'1 1 £� ill Standby 0.075A Alarm 3.047 A a. 1. S stem Motlules r r • a HPFFe Main Circuit Board 1 z 1 0.07500 1 0.07500 1 1 x 1 0.20600 1 0.20600 2. HS -1 3 x 0.00000 0.00000 3 z 0.09100 0.27300 2 x 0.00000 0.00000 2 x 0.17600 0.35200 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 z 0.00000 0 x 0.00000 F3.HS-2 a x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 NAG #1 Totals Max 3Am s): 0.00000 0.62500 P2W15 3 x 0.00000 0.00000 1 3 1 z 0.09100 0.27300 P2W75 2 z 0.00000 0.00000 2 1 x 0.17600 0.35200 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 NAC #2 Totals Max 3 Amps : 0.00000 0.62500 4. HS -3 P2W15 6 x 1 0.00000 0.00000 6 z 0.09100 0.54600 P2W30 1 x 1 0.00000 0.00000 1 x 0.11600 0.11600 P2W75 1 z 0.00000 0.000DO 1 x 0.17600 0.17600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o z 0.00000 NAC #3 Totals (Max 3 Amps):i 0.00000 O.B3800 S. HS -4 P2W15 7 x 0.00000 0.00000 7 x 0.09100 1 0.63700 P2W30 1 x 1 0.00000 0.00000 1 x 0.11600 0.11600 0 00000 0 x 0.00000 0 000000x 0.00000 0 000000 x 0.00000 0 000000 txO z 0.00000 0 000000 x 0.00000 0 00000 0 x 0.00000 NAC #4 T :1 0.00000 0.75300 6. Auxiliary Power Auxiliary Device D I z 1 0.00000 0 1 x 1 0.00000 Auxiliary Device 0 x 0.000000 x 0.00000 Auxilia Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 z 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals Max 2 Am s): 0.00000 0.00000 7. Compatible Devices not listed Other compatible devices 0 z0.00000 0 x 0.00000 Other compatible devices 0 x 0.000000 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 3.047 Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building B - BYU-ID Student Housing Address: BYU-Idaho City: Rexburg State: ID Prepared By: Nelson Fire Systems Address: 1481 S Major Street Email: City: Salt Lake City State: UT Secondary Load Requirements FTUTAmp Hours Total Secondary Load from the calculation table below. Date: 2/24/2014 Zip: Phone: 801.468.8300 Calnelsonfre.com Zip: 84115 Current Draw Secondary Standby Load 0.075 A x Time (hours) Total (AH) Re uired Standby Time 24 hours 1.80 Secondary Alarm Load 3.047 A x Required Alarm Time hours) 0.084 hours 0.26 Total Secondary Load 2.06 Derating factor x 1.2 Secondary Load Requirements 2.47 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loan 27% SecondaryAlarm Load 4% ■ Spare Battery Capacity • Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Drow 1 1111:1 H 112 mmffmrmffrm Slandb 0.075A Alarm r 1.377 A D Secondary Non-Alam � . Current i � M. . . 1.5 stem Modules HPFFB Main Circuit Board 1 1 x 1 0.07500 0.07500 1 1 x 0.20600 0.20600 2. HS-5 P2W15 00 0.00000 6 x 0.09100 0.54600 P2W75 00 0.00000 1 x 0.17600 0.17600 00 0 x 0.00000 00 0 x 0.00000 00 N##1 UAmps) 0 x 0.00000 000 0 x 0.00000 oo0 0 x 0.00000 000 o x 0.00000 Am s : 0.00000 0.72200 3. HS-5 P2W15 3 x 0.00000 1 0.00000 3 x 0.09100 0.27300 P2W75 1 x 0.00000 1 0.00000 1 x 0.17600 0.17600 0 0.00000 0 x 0.00000 0 0 x 0.00000 0 0 x 0.00000 0 Ix E0.00000 0 x 0.00000 0 0 x 0.00000 o 0 x 0.00000 NAC #2 Totals (Max 3 Amps) 0.00000 0.44900 4.. o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.00000 5.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 z 0.00000 o x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps) 0.00000 0.00000 6. Auxiliary Power Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Maz 2 Am s : 0.00000 0.00000 7. Compatible Devices not listed Other compatible devices 0x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 1 x 0.00000 Other compatible devices 1 0 x 0.00000 0 1 x 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Laad: 1.377 oneyrell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building B - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: offce@nelsonfire.corn City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.30 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Loadx 0.075 A Time (hours) Re uired StandbyTime Total (AH) 24 hours 1.80 Secondary Alarm Load 1.377 A x Required Alarm Time (hours) 0.084 hours 0.12 Total Secondary Load 1.52 Derating factor I x 1.2 Secondary Load Requirements 1 2.30 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp-hour distribution of your selections. Secondary Alarm Load 2% Secondary Standby Load 27% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will ft in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). !Spare Battery Capacity 5.70!Battery Selection AH - Secondary Load Requirements AH ISeconclary Standby Load 2.16 ISeconclary Standby Load AH . Derating Factor ISecondary Alarm Load 1 0.14 1 Secondary Alarm Load AH ' Derating Factor Page 3 of 129 Honeywell System Current Draw - Hf'Ff=8 ##3 Standb 0.075A Alarm 1. B stem Modules HPFFB Main Circuit Board i I z 1 0.07500 1 0.07500 1 1 1 x 1 0.20600 1 0.20600 2. Relay #1 PR -3 2 x 0.00000 1 0.00000 2 x 0.03000 0.06000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 NAC #1 Totals Max 3 Amps) 0.00000 10.08000 3. Relay #2 PR -3 1 x 1 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 X0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #2 Totals Max 3 Amps): 1 0.00000 0.03000 4. Relay #3 PR -3 1 z 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 z 1 0.00000 o x 0.00000 0 x 0.00000 0 x 20.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0O 0 x 0.00000 0 x 0.00000 0 x 0.00000 ACO Totals Max 3 Am s : 0.00000 0.03000 5. Relay #4 PR -3 1 x 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x o.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.03000 S. Auxiliary Power 0 x 0.00000 0 z 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary DeWce 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals Max 2 Am s : 0.00000 0.00000 7. Compatible Devices not listed Other compatible devices 0 x0.0 0 x 0.00000 Other compatible devices 0 x 0.000000000 0 1 x 0.00000 Other compatible devices 0 x 0.00000 1 1 0 1 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 0.358 Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building B - BYU-ID Student Housing Date: Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.4E Address: 1481 S Major Street Email: ofBceOnelsonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.20 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby LoadRequired A FT—F-32 Time (hours) Total (AH) StandbyTime 24 hours 1.80 Secondary Alarm Load 0.356 A x Required Alarm Time (hours 0.084 hours 0.03 Total Secondary Load 1.83 Derating factor x 1.2 Secondary Load Requirements 2.20 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Lc 27% SecondaryAlarm Load 0% ■ Spare Battery capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #A Standby 0.075 A Alarm 10.356 A •- • r MM 1. System Modules HPFF8 Main Circuit Board 1 x 0.07500 0.07500 1 1 x 1 0.20600 0.20600 2. Relay #5 PR -3 i x 0.00000 0.00000 1 X 0.03000 0.03000 0 x 0.00000 o x 0.00000 0 X 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #1 Totals Max 3 Amps):1 0.00000 1 0.03000 3. Relay #6 PR -3 1 I x I 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o X 0.00000 0 x 0.00000 NAC #2 Totals (Max 3 Amps) 11 0.00000 1 0.03000 4. Relay #7 PR -3 1 x 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 X 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals Max3Am s): 0.00000 0.03000 S. Relay #8 PR -3 2 z 1 0.00000 0.00000 2 X 0.03000 0.06000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o X o.00aoo o x 0.00000 o X 0.00000 o x 0.00000 NAC #4 Totals (Max 3 Amps)'. 0.00000 0.06000 6. Auxiliary Power 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 T84 Totals Max 2 Amps) 0.00000 0.00000 7. Compatible Devices not listed Other compatible devices 0 x 0.00000000 0 x 1 0.00000 Other compatible devices 0 x 0.00 0 x 0.00000 Other compatible devices 0 1 x 1 0.00000 1 1 0 1 x 1 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 0.358 Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building B - BYU-ID Student Housing Date: Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: offceonelsonfre.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.20 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A x Time (hours) Total (AH) Required Standby Time 24 hours 1.80 Secondary Alarm Load 0.356 A x Required Alarm Time (hours) 0.084 hours 0.03 Total Secondary Load 1.83 Derating factorl x 1.2 Secondary Load Requirements 1 2.20 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Lc 27% Secondary Alarm Load 0% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #5 Standby0.076A Alarm 11.851 A r. i. S stem Modules • r e r . HPFFB Main Circuit Board 1 1 z I 0.07500 1 0.07500 1 1 1 x 1 0.20600 1 0.20600 2.. 0 x 0.00000 0 z0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 00.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #1 Totals Maz 3 Am s :1 0.00000 0.00000 3.. 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAG 02 Totals Max3Amps): 0.00000 0.00000 4.. 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 o x 0.00000 Po 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 x 0.00000 0 x 0.00000 NAC #3 Totals Max 3 Amps): 0.00000 0.00000 5.. 0 z 0.00000 0 1 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 z 0.00000 o x 0.00000 o x 0.00000 a x 0.00000 o x 0.00000 NAC #4 Totals (Max 3 Am s): 0.00000 0.00000 6. Auxiliary Power 47 x 0.00000 0.00000 47 x 0.03500 1.64500 Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Device 0 x 0.00000 0 x 0.00000 Device0 LOtherwmvatibledevi�s z 0.00000 0 x0.00000 T64 Totals Max 2 Am s): 0.00000 1.64500 lible Devices not listed atlble devices 0 x 0.00000 0 X 0.00000 alible tlevices 0 z 0.00000 0 x 0.00000 Other com alible tlevices 0 x 0.00000 0 z 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 1.851 Secondary Power Requirements Protected Premises: Building B - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.4@ Address: 1481 S Major Street Email: o�re.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements F-2-35--1 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby LoadRequired 0.075 A x I Time (hours) Total (AH) 75My Time 24 hours 1.80 Secondary Alarm Load 1.851 A x Required Alarm Time (hours) 0.084 hours 0.16 Total Secondary Loadl 1.96 Derating factorl x 1.2 Secondary Load Requirements 1 2.35 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loi 27% SecondaryAlarm Load 2% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #6 Standb 0.075A Alarm 1.781 A Device 1. System Modules . QtY I I r • Current • . . HPFF8 Main Circuit Board1 x 0.07500 0.07500 1 x 0.20800 0.20600 2.. o 1 z 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 o 1 x 0.00000 0x 0.00000 o x 2.00000 o x 0.00000 0 x 0.;0000 o x 0.00000 ox 2.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC M7 Totals Maz3Am s: 0.00000 0.00000 3.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00 000 0 x 0.00000 0.00000 0 x 0.00000 Ax0.00000 0.00000 0 x 0.00000 0.00000 0 x 0.00000 NAC #2 Totals Max 3 Amps) 0.00000 0.00000 4.. 0 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00022 o x 0.00000 o 0.00020 0 x 0.00000 0 -X-L x F 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 NAC 43 Totals (Max 3 Amps): 0.00000 0.00000 5.. 0 1 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 X-1 0.00000 0 x 0.00000 0 x 0.00000 o z I 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Am s): 0.00000 0.00000 6. Auxiliary Power B200S 45 x 0.00000 0.00000 45 1 x 0.03500 1.57500 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 z 0.00000 0 x 0.00000 TB4 Totals (Maz 2 Am s : 0.00000 1.57500 7. Compatible Devices not listed Other compatible devices 0 x 2.00000 0 x 0.00000 Other com atible devices 20! 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Loetl: 1.781 HOIIenyell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building B - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: Office0nelsonflre.corn City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.34 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A r x Required -,-.,-DV Time 24 hours 1.80 Secondary Alarm LoadRequired 1.781 A x Alarm Time (hours) 0.084 hours 0.15 Total SecondaryLoad 1.155 Derating factorl x 1.2 Secondary Load Requirements 1 2.34 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loi 27% SecondaryAlarm Load 2% ■ Spare Battery Capacity ■ Secondary Standby load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell Standb 10.075A. Alarm 12.096 A System Current Draw - HPFF8 #7 1" 11 r , WIN r. 7. S stem Modules HPFF8 Main Circuit Board 1 x 1 0.07500 1 0.07500 1 1 I x 1 0.20600 1 0.20800 2.. 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 lox U0.00D00 0 x 0.00000 0 x 9.00000 0 x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Am s : 0.00000 0.00000 3.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 o0 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 9.99990 x 0.00000 o x 9.99999 o x 0.00000 NAC #2 Totals (Max 3 Amps): 0.00000 0.00000 0 x 9.0000=101.00000 .000000 x 0.0000.000000 x 0.0000.000000 x 0.00000.000000 W x 0.00000.000000 x 0.00000.000000 x 0.00000.000000 x 0.00000.00000AC #3 Totals Max 3 Am0.00000 5. . 0 x 0.000000 x 0.00000 0 x 0.00000F0.00000 0 x 0.00000 0 x 0.000000 x 0.00000 0 x 0.000000 x 0.00000 0 x 0.000000 x 0.00000 o x 0.000000 x 9.99999 0 x 0.000000 x 20.00000 o x 0.00000o x 9.99999 NAC #4 Totals (Max 3 Amps): ------- S. Auxiflary Power B200S 54 x 0.00000 0.00000 54 z 0.03500 1.89000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Maz 2 Am s : 0.000001 1.89000 7. Compatible Devices not listed Other compatible devi0as0 z 0.00000 0 x 0.00000 Other cum alible devices 0 z 0.00000 0 1 z I 0.00000 Olhercom atible devices 0 x 0.00000 0 z 1 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Load: 2.096 noneywen Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building B - BYU-ID Student Housing Address: BYU-Idaho Date: 2/24/2014 City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: office(a)nelsonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.37 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A x1 I Time (hours) Total (AH) Required StandbV Time 24 hours 1.80 Secondary Alarm LoadRequired 2.096 A x Alarm Time (hours) 0.084 hours 0.18 Total Secondary Load 1.98 Derating factor x 1.2 Secondary Load Requirements 1 2.37 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 3% ■ Spare Battery Capacity ■Secondary Standby load ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell Standb 0.075 A Alarm 2.168 A Dr 1. S stem Modules System Current Draw - HPFF8 #8 Secondarr Non -Alarm rmnLs000ndary Alarm Current a . . HPFF8 Main Clrcuit Board 1 x 0.07500 0.07500 7 1 z 1 0.20600 1 0.20600 2.. 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o 0.00000 0 x 0.00000 0 0 x 0.00000 o ISJ�0 o x 0.00000 0 0 x 0.00000 NAC 41 Totals Max 3 Amps) .00000 0.00000 3.. 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 `-x 0.00000 o x 0.00000 0 z 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x o.00000 o x 0.00000 NAC #2 Totals Max 3 Amps): 0.00000 1 0.00000 4.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o z 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.00000 5. . 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x o.a0000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.000OO 8. Auxilia Power B200S 0.00000 0.00000 56 x 0.03500 1.96000 AuxiliaryDevice 0.00000 0 x 0.00000 Auxiliary Device 0.00000 0 x 000000 Auxilia Device 0.00000 101 0 x 000000 Auxiliary Device 0.00000 0 x 0.00000 TB4 Totals Max 2 Amps) 0.00000 1.96000 7. Compatible Devices not listed Other com alible devices0 x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0 . 00 000 Other compatible devices 0 1 z 1 0.00000 0 z 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 2.786 Honeywell Secondary Power Requirements HPFF8 Power Supply --i Protected Premises: Building B - BYU-ID Student Housing Address: BYU-Idaho City: Rexburg State: ID Prepared By: Nelson Fire Systems Address: 1481 S Major Street Email: City: Salt Lake City State: UT Secondary Load Requirements 2.38 Amp Hours Total Secondary Load from the calculation table below. Dale: 2/24/21 Zip: Phone: 801.4E @nelsonfire.com Zip: 84115 Current Draw Secondary Standby Load 0.075 A Time (hours) x Required StandbyTime 24 hours Total (AH) 1.80 Secondary Alarm Load 2.166 A x Required Alarm Time (hours) 0.084 hours 0.18 Total Secondary Load 1.98 Derating factorl x 1.2 Secondary Load Requirements 1 2.38 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) G Four (two 12VDC sets in parallel) -age 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% SecondaryAlarrn Load 3% ■ Spare Battery Capacity ■ Secondary Standby Wad ■SecondaryAlarm Wad Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 SYSTEM SENSOR' uncecl idem advanced solulloris' P Name: Student Housing Building B IYU-Idaho texburg, ID ircuit Information Candela Panel Name: HPFF8-1 Circuit Name: HS -1 Starting Voltage: Starting Voltage = 20.4 Prepared By: Nelson Fire Systems 1481 S. Major Street Salt Lake City, 84115 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply pe and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 16 (Amps) last device source (ft) i/Strobe 1 15 0.068 Non -temporal, Low 115 115 19.927 19.649 19.204 18.497 n/Strobe I 15 0.068 Non -temporal, Low 20 135 19.932 19.657 19.218 18.519 n/Strobe 75 0.156 Non -temporal, Low 20 155 19.943 19.675 19.245 18.563 n/Strobe 15 0.068 Non -temporal, Low 20 175 19.967 19.712 19.305 18.658 V n/Strobe 75 0.156 Non -temporal, Low 20 195 19.996 19.758 19.378 18.774 V ital current/amps 0.516 Total Dist: 195 voltage drop 0.473 0.751 1.196 1.903 27/2014 1 Circuit Information Panel Name: HPFF8-1 Circuit Name: HS -2 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 is (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 55 55 19.884 19.581 19.096 18.325 P2W Horn/Strobe 75 0.156 Non -temporal, Low 20 75 19.889 19.590 19.109 18.347 P2W Horn/Strobe 75 0.156 Non -temporal, Low 30 105 19.916 19.632 19.178 18.456 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 125 19.947 19.681 19.255 18.579 P2W Horn/Strobe 15 0.068 Non -temporal, Low 50 175 20.037 19.824 19.483 18.941 P2W Total current/amps 0.516 Total Dist: 175 voltage drop 0.516 0.819 1.304 2.075 2/27/2014 2 SYSTEM SENSOR' onced kL-m ottvonced solullom, rcuit Information Panel Name: HPFF8-1 (1.5) amp circuit Circuit Name: HS -3 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply is and Model Candela Current (Amps) Tone and Volume Dist from last device Dist from scums(it) 12 14 16 18 /Strobe 15 0.066 Non -temporal, Low 110 110 18.870 17.973 16.534 i/Strobe 15 0.068 Non -temporal, Low 75 185 18.891 18.005 16.586 i/Strobe 30 0.096 Non -temporal, Low 60 245 18.924 18.057 16.669 1 1 i/Strobe 15 0.068 Non -temporal, Low 20 265 18.942 18.087 16.716 i/Strobe I 75 0.156 Non -temporal, Low 20 285 18.967 18.125 16.777 n/Strobe I 15 0.068 Non -temporal, Low 20 305 19.003 18.183 16.870 n/Strobe I 15 0.066 Non -temporal, Low 60 365 19.130 18.384 17.189 n/Strobe V 15 0.068 Non -temporal, Low 60 425 19.272 18.610 17.550 ital current/amps 0.660 Total Dist:425 voltage drop 1.530 2.427 3.866 27/2014 Circuit Information Panel Name: HPFF8-1 Circuit Name: HS -4 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 18 (Amps) last device soume(R) Horn/Strobe 15 0.068 Non -temporal, Low 120 120 19.002 18.182 16.867 P2W Horn/Strobe 15 0.068 Non -temporal, Low 65 185 19.020 18.210 16.912 * P2W Horn/Strobe 30 0.096 Non -temporal, Low 65 250 19.055 18.266 17.002 P2W Horn/Strobe 15 0.068 Non -temporal, Low 25 275 19.079 18.303 17.061 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 295 19.103 18.341 17.122 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 315 19.132 18.388 17.197 P2W Horn/Strobe 15 0.068 Non -temporal, Low 70 385 19.255 18.583 17.507 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 445 19.377 18.776 17.814 16.267 P2W Total current/amps 0.572 Total Dlst:445 voltage drop 1.396 2.218 3.533 2/27/2014 SYSTEM SENSOR` orioDcl lcleni advanced 5dutio 15'- rcult Information Panel Name: HPFF8-2 (1.5) amp circuit Circuit Name: HS -5 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply 1e and Model Candela Current (Amps) Tone and Volume Dist from last device Dist from soume(it) 12 14 16 16 /Strobe 15 0.068 Non -temporal, Low 130 130 19.151 18.418 17.244 /Strobe 15 0.068 Non -temporal, Low 20 150 19.157 18.427 17.258 /Strobe 15 0.068 Non -temporal, Low 75 225 19.198 18.492 17.361 1/Strobe 75 0.156 Non -temporal, Low 20 245 19.214 18.518 17.403 i/Strobe 15 0.068 Non -temporal, Low 20 265 19.243 18.564 17.476 VStrobe 1 15 0.068 Non -temporal, Low 70 335 19.363 18.755 17.780 16.233 n/Strobe I 15 0.068 Non -temporal, Low 65 400 19.493 18.961 18.108 16.754 tal current/amps 0.564 Total Dist:400 voltage drop 1.249 1.982 3.156 27/2014 Circuit Information Panel Name: HPFF8-2 Circuit Name: HS -6 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 18 (Amps) lost device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 95 95 19.853 19.531 19.017 18.200 P2W Horn/Strobe 75 0.156 Non -temporal, Low 20 115 19.858 19.540 19.031 18.222 P2W Horn/Strobe 15 0.068 Non -temporal, Low 65 180 19.917 19.633 19.179 18.457 P2W Horn/Strobe 15 0.068 Non -temporal, Low 85 265 20.016 19.791 19.431 18.856 P2W Total current/amps 0.360 Total Dist: 265 voltage drop 0.547 0.869 1.383 2.200 2/27/2014 Nelson I d I L, I Systems FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 www.uelsonfire.com BYU-Idaho Student Housing Building C Fire Alarm System Submittal Battery Calculations & Voltage Drop a ;<� � ' .,� . ,, a �W65"ll System Current Draw ® E3 Series Control Panel with Broadband Total Standby 0.616 A Total Alarm 3.962 A Q Draw Standb Ql Draw Alarm em Device o Interface, Main Board ILI-MB-E3 1 x 0.08100 0.08100 1 x 0.15000 0.15000 oo Interface Su Iement Board III -S-FM 3 x 0.08100 0.24300 3 x 0.15000 0.45000 oo Interface Main Board - A ollo ILI95-MB-E3 0 VIntel, x 0.05000 0 x 0.09100 oo Interface Su IementBoard-A ollo ILI95-S-E3 0 x 0.05000 0 x 0.09100 anel, 1 SLC 0 x 0.05600 0 x 0.07600 anel, 1 SLC with DACT 0 x 0.07500 0 x 0.09500 anel, 2 SLC 0 x 0.06500 0 x 0.08500 7100 Panel, 2 SLC with DACT 0 x 0.08500 0 x 0.10500 2. E3 Optional Modules 120V Power Supply Sub -Assembly PM -9) 1 x 0.05000 0.05000 1 x 0.05000 0.05000 240V Power Supply Sub -Assembly PM -9G 0 x 0.02700 0 x 0.05000 LCD Dis la 8 Switch Control LCD -E3 2 x 0.02400 0.04800 2 x 0.02800 0.05600 ARCNET Re eater RPT -E3 2 x 0.01300 0.02600 2 x 0.01300 0.02600 Digital Communicator UACT-E3 C x 0.01800 0 x=0.20000 0 tional Remote Serial Annunicator LCD -7100 0 x 0.05000 0 x Network LCD Annunicator NGA 0 x 0.20000 0 zAuxilia Switch Sub-Assembl ASM -16 2 x 0.01100 0.02200 2 xRemote LED Driver Module ANU-48 0 x 0.01100 0 xAddressable Node Ex ander ANX 0 x 0.06500 0 x 3.7100 Optional Modules Intelligent Network Interface Module INI-7100 0 x 0.04000 0 x 0.04000 Printer Transient Module PTRM 0 x 0.02000 0 x 0.02000 Remote LED Driver Module LDM-7100 Class A UPRModule CAOM Municipal ircuit Option Module OVIFUUM 0 0 x x 0.03500 0.00100 1 0 1 0 I u x 1 x 1 I x I 0.20000 0.00100 U.Uuluu 4, INI-VGC Command enter Intel. Network Command Center INI-VGC 20 .15000 0 x 0.15000 Addressable Switch Sub-assemblyASM-16 0 x 0.01100 0 x 0.01100 Voice Pacing Microphone (Microphone) 0 x 0.00100 0 x 0.00100 Firefighters Telephone Handset 0 x 0.02000 1 1 0 1 x 0.02000 00 1 1 0 x 000550 5. INI-VGX Voice Gatewa Intel. Network Voice Gateway INI-VGX 0 x 1 0.15000 0 1 x 0.15000 120V Power Su I Sub-Assembl PM -9 0 x 0.05000 0 x 0.05000 240V Power Su I Sub-Assembl PM -9G 0 x 0.02700 0 x 0.05000 Amplifier Sub-assembly,50 watt 25V AM -50 0 x 0.08600 0 x 2.20600 Amplifier Sub-assembly,50 watt 70V AM -50-70 0 x 0.04900 0 x 2.30000 Addressable Output Module -Si nal AOM-2SF 0 x 0.00200 0 x 0.00650 Addressable Oul ut Module -Tele hone AOM -TEL 0 x 0.00200 0 x 0.00650 Addressable Out ut Module -Audio (AOM -MUX) 0 x 0.00200 0 x 0.00650 6. INI-VGE Command Center Voice Gateway Intel. Network Command Voice Gateway (INI-VGE 0 x 0.15000go Addressable Switch Sub-assembl ASM -16 0 x 0.01100x 0.01100 Voice Pa in Micro hone Micro hone 0 x 0.00100x 0.00100 Firef hter's Tele hone Handset 0 x 0.02000x 0.02000 Addressable Out ul Module -Si nal AOM-2SF 0 x 0.00200x 0.00650 Addressable Out ut Module -Tele hone AOM -TEL 0 x 0.00200x 0.00650Addressable Out ut Mdule-Audio (AOM -MUX 0 x 0.00200x 0.00650 7. Smoke Detectors/Modules ASD-PL2F/ASD-IL2F 272 x 0.00030 0.08160 272 x 0.00650 1.76800 ATD-RL2F/ATD-HL2F 1 x 0.00030 0.00030 1 x 0.00650 0.00650 DNR 82 1 x 1 0.00030 0.02460 82 x I 0.00650 0.53300 AMM -41' 6 x 0.00038 0.00225 6 x 0.00500 0.03000 AOM-2RF 5 x 0.00038 0.00188 5 x 0.00650 0.03250 MS-7AF i x 0.00030 0.00030 1 x 0.00300 0.00300 MCS-COF 116 x 0.00030 0.03480 116 x 0.00720 0.83520 8. Notification Appliances 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 20 0.00000 0 x 0.00000 0 x o.00aoo o x 0.00000 Total Standby Load: 0.616 A Total Alarm Load: 3.962 A a mi System Power Requirements ®mum E3 Fire Alarm Control Panel with Broadband Protected Premises: Building C -- Address: BYU-Idaho BYU-ID Student Housing Date: 2/24/2014 City: Rexburg State: ID Zip: 0.084 hours 0.33 Prepared I Nelson Fire Systems Derating factor x 1.20 Phone: 801-468-E Address: 1481 S Major Street City: Salt Lake City State: Utah Email: otrcerartklsonrre com Zip: 84115 Secondary Load Requirements 18.13 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.616 A x71 Time (hours) Total (AH) Required Standby Time 24 hours 14.78 Secondary Alarm Load 3.962 A x Required Alarm Time hours 0.084 hours 0.33 Total Secondary Load 15.11 Derating factor x 1.20 Secondary Load Requirements 1 18.13 AH Battery Selection 26.00 Amp Hours Select batteries from the list 26 AH Battery (12 volt) Battery Distribution Chart Shows amp -hour distribution of your selections. SecondaryAlarm Load 2% nSpare Ballery Oapaclly CSecondary Slandby Load MSecondary M.M Load Secondary Standby Load 68% Spare Battery Capacity 7.87 Amp Hours ISecondary Standby Load I 17.73 Amp Hours ISecondary Alarm Load 1 0.40 Amp Hours kii'doncyruclu Systom C uuront [.)raw - 111111-8 It Standby 0.075 A Alarm 12.529 A 5 stem Modules ' M1. HPFFB Main Circuit Board 1 x 0.07500 0.07500 1 1 x 1 0.20600 1 0.20800 2. HS-6 P2Wl5 4 x 0.00000 0.00000 4 z 1 0.09100 0.36400 P2WH177 3 x 0.00000 0.00000 3 x 0.30300 0.90900 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 6.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 NAC#1 Totals (Max3Am s): 0.00000 1 1 1.27300 3.. 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o .00000 0 x 0.00000 o o x 0.00000 0 tFL0002000 0 x 0.00000 0 0 x 6.00000 0 NAC #2 Totals Max 3 AMPS): 0.00000 4.. 0 1 z 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 z 6.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 oz 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals Max 3 Amps): 0.00000 0.00000 5.. 0 x 0.00000 0 1 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 NAC#4 Totals (Max 3 AMPS) 0.00000 0.00000 6. Auxiliary Power B200S 30 1 x 1 0.00000 1 0.00000 30 x 0.03500 1.05000 Auxiliary Device 0 z 0.00000 0 z 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 AMPS) : 0.00000 1.05000 7. Compatible Devices not listed Other compatible devices 0 z 0.00000 0 z 0.00000 Other compatible devices 0 z 0.00000 0 z 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total NonmAlarm Load: 0.076 Total Alarm Load: 2.529 `i'� ^��1 Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Address: BYU-Idaho Date: 2/24/2014 City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email; orrceraneisonfre.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.41 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby LoadRequired 0.075 A x I Time (hours) Total (AH) Standby Time 24 hours 1.80 Secondary Alarm Load 2.529 A x Required Alarm Time (hours) 0.084 hours 0.21 Total Secondary Load 2.01 Derating factor x 1.2 Secondary Load Requirements 2.41 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 3% ■ Spare Battery Capacity ■ Secondary Standby Load ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (BAH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - H£'1IT8 112 Standb 0.O75A Alarm 12.494 A 1. System Modules HPFFB Main Circuit Board 1 x 1 0.07500 1 0.07500 1 1 1 x 1 0.20600 1 0.20600 2. HS -5 P2W15 4 x 0.00000 0.00000 4 x 1 0.09100 0.36400 P2WH177 3 x 0.00000 0.00000 3 x 0.30300 0.90900 0 x0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 1.27300 3. 0 X 0.00000 0 x 0.00000 0 X 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #2 Totals (Max 3 Amps): 0.00000 0.00000 4.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.00000 5.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 2.00000 0 x 0.00000 0 x 2.20000 0 x 0.00000 2 x 0.00000 0 x 0.00000 2 x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Am s): 0.00000 0.00000 S. Auxiliary Power 62005 29 x 0.00000 1 0.00000 29 x 0.03500 1.01500 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 X0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 TB4 Totals (Max 2 Amps): 0.00000 1.01500 7. Compatible Devices not listed Other cem alible devices 0 x 0.00000 0 z 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices0 x 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 2.494 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: oftce@nelsonfre.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.41 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A Time (hours) I Required Standby Time Total (AH) x 24 hours 1.80 Secondary Alarm Load 2.494 A Required Alarm Time( ours x 0.084 hours 0.21 Total Secondary Load 2.01 Derating factorl x 1.2 Secondary Load Requirements 1 2.41 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp-hour distribution of your selections. SecondaryAlarm Load 3% Secondary Standby Load ■Spare Battery Capacity 27% ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). S are Batte Ca acil 5.59 Batte Selection AH - SecondaryLoad Requirements AH Seconda StandbyLoad 2.16 SecondaryStandbyLoad AH `Deratin Factor Seconda Alarm Load 1 0.25 1 Secondary Alarm Load AH . Derating Factor Page 3 of 129 Honeywell System Current Draw - HPFF8 #3 Ix'�Standb ...rrz5�v...i '�cSk ' F 0076A Alarm 2.275 A -AA= r.Secondary 1. S Stem Modules Non -Ala UPI I I Draw • EW r . HPFF8 Main Circuit Board 1 x 0.07500 0.07500 1 x 0.20600 0.20600 2. HS -4 P2W15 3 x 0.00000 0.00000 3 x 0.09100 0.27300 PM11177 2 x 0.00000 0.00000 2 x 0.30300 0.60600 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 0 x a O0000 o x 0.00000 NAC #1 Totals (Max 3 Am s): 0.00000 0.87900 3.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x O.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 NAC M2 Totals (Max 3 Am s): 0.00000 0.00000 4.. 0 X 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 NAC M3 Totals (Max 3Am s): 0.00000 0.00000 0 z 0.00000 0 x 000000 0x.000000 z 0.000000 z 0.00000 0 x 0.00000o x 2.00000 o x 0.00000 RMNAG#4TOt�aIs(Maxo3AGMps)] 0 x 000000ox 0.00000ox a.00000 o x 0.00000 0 X 0.00000 o x 0.000000 0000o x 0.00000 0.00000 0.00000 6. AUXIllary Power 82005 34 x 0.00000 0.00000 34 x 0.03500 1.19000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxilia Device 0 x 0.00000 0 x 0.00000 AuxiliaryDeNce 0 z 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals Max 2 Am s :1 0.00000 1.19000 7. Compatible Devices not lisletl Other com alible devices 0x 0.00000 0 x 0.00000 Other conralible devices 0 x 0.00000 0 x 0.00000 Other com atible devices 0 1 x 0.00000 0 1 z 1 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 2.275 Secondary Power Requirements Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: office(&nelsonfire com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.39 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby LoadRequired 0.075 A x Time (hours) Total (AH) Standby Time 24 hours 1.80 Secondary Alarm Load 2.275 A x Required Alarm Time (hours 0.084 hours 0.19 Total Secondary Load 1.99 Derating factor x 1.2 Secondary Load Requirements 2.39 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 3% ■ Spare Battery Capacity ■ Secondary Standby Load ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #4 Standby 10.07777771 .. Alarm 2.573 A r 1. System Modules HPFF8 Main Circuit Board 1 1 x 0.07500 1 0.07500 1 1 1 x 1 0.20600 1 0.20600 2. HS -1 P2Wi5 2 x 0.00000 0.00000 2 z 0.09100 0.18200 P2W75 1 x 0.00000 0.00000 1 x 0.17600 0.17600 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 2.00000 o x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 NAC#1 Totals Max 3Amps) : 0.00000 0.35800 3. HS -2 P2W15 5 x 0.00000 0.00000 5 x 0.09100 0.45500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 NAC #2 Totals Max 3 Amps): 0.00000 0.45500 4. HS -3 P2W15 4 1 x 0.00000 0.00000 4 x 0.09100 0.36400 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.36400 5.. 00000 0 x 0.00000 00000 0 x 0.00000 00000 0 x 0.00000 00000 0 x 0.00000 00000 H(Ma. 0 x 0.00000 00000 0 x 0.00000 00000 0 x 0.00000 00000o x 0.00000N 3 Amps): 0.00000 0.00000 6. Auxiliary Power B2005 34 z 0.00000 0.00000 34 x 0.03500 1.19000 AuxiliaryDevice 0 z 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 z 0.00000 0 x 0.00000 TB4 Totals (Max 2 Am s): 0.00000 1.19000 7. Compatible Devices not listed Other compatible devices 0x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total All Load: 2.573 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Address: BYU-Idaho City: Rexburg Prepared By: Nelson Fire Systems Address: 1481 S Major Street City: Salt Lake City State: ID Email: Date: 2/24/2014 Zip: Phone: 801.468.8300 State: UT Zip: Secondary Load Requirements F2.42 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A x Required tandb Time 2-4'h ours 1.80 Secondary Alarm Load 2.573 A x Required Alarm Time (hours) 0.084 hours 0.22 Total Secondary Load 2.02 Derating factorl x 1.2 Secondary Load Requirements 1 2.42 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp-hour distribution of your selections. Secondary Alarm Load 3% ■ Spare Battery Capacity Secondary Standby Load ■ secondary standby Load 27% ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). !Spare Battery Capacity 5.58 !Battery Selection AH - Secondary Load Requirements AH Secondary Standby Load 1 2.16 ISecondary Standby Load AH ' Derating Factor ISecondary Alarm Load 1 0.26 ISecondary Alarm Load AH ' Derating Factor Page 3 of 129 Honeywell Slandb O.O75A Alarm 3.754A 1. System Modules System Current Draw - HPFF8 #5 - - - HPFF8 Main Circuit Board 1 x 1 0.07500 0.07500 1 x 1 0.20600 0.20600 2. HS -7 P2W15 5 x 0.00000 0.00000 5 z0.09100 0.45500 o x 0.00000 o x a.00000 o x o.a0000 a x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #1 Totals Max 3Arnps):j 0.00000 0.45500 3. HS41 P2W15 5 x 0.00000 0.00000 5 x 1 0.09100 0.45500 P2W30 x 0.00000 0.00000 1 z 0.11600 0.11600 P2W75 x 0.00000 0.00000 1 x 0.17600 0.17600 x 0.00000 0 x -.00000 NO) x 0.00000 0 x 0.00000 x 0.00000 o x 0.00000 x 0.00000 a x 0.00000 x 0.00000 o x 0.00000 NAC #2 Totals Max 3 Amos): 0.00000 0.74700 4. HS -9 P2W15 5 x 0.00000 0.00000 5 x 0.09100 0.45500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals Max 3 Amps)' 0.00000 0.45500 S. HS -10 P2W15 5 x 0.00000 0.00000 5 x 0.09100 0.45500 P2W75 1 x 0.00000 0.00000 1 x 0.17600 0.17600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 ox 0.00000 o x 0.00000 0 x 0.00000 0 x 1 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.63100 6. Auxiliary Power B200S 36 x 0.00000 0.00000 36 x 1 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 z 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps) 0.00000 1.26000 7. Compatible Devices not listed Other cum alible devices 0 1 x 1 0.00000 0 x0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other ooatible devices m 0 x 0.00000 0 1 x 0.00000 Total Non -Alarm Load: D.075 Total Alarm Load; 3.754 Honeywell Secondary Power Requirements HPFF8 Power Protected Premises: Building C - BYU-ID Student Housing Address: BYU-Idaho City: Rexburg State: ID Prepared By: Nelson Fire Systems Address: 1481 S Major Street Email: City: Salt Lake City State: UT Secondary Load Requirements F 2.54 1 Amp Hours Total Secondary Load from the calculation table below. Date: 2/24/2014 Zip: Phone: 801.468.8300 Zip: 84115 Current Draw Secondary Standby Load 0.075 A Time (hours) Required Standb Time x 24 hours 1 1.80 Secondary Alarm Load 3.754 A Required Alarm Time (hours) x 0.084 hours 0.32 Total Secondary Load 2.12 Derating factor x 1.2 Secondary Load Requirements 2.54 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt C Four (two 12V DC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% SecondaryAlarm Load 5% ■ Spare Battery capacity ■ Secondary Standby Load ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). S are Batte Ca acit 5.46 Batte Selection AH - Seconda Load Requirements AH Seconda Standb Load 2.16 Seconds Standbyload AH `Dentin Factor Secondary Alarm Load 1 0.38 l3econdaa Alarm Load AH * Derating Factor Page 3 of 129 Honeywell System Current Draw .. I IPFF8 #6 Istandby 0.075A Alarm 12.194A Secondary Non-Alame Curren Cty Serdary Alarm Current 1. System Modules HPFFB Main Circuit Board 1 x 0.07500 1 0.07500 1 1 1 x 1 0.20600 0.20600 2. HS-11 P2W15 5 x 0.00000 1 0.00000 5 x 0.09100 0.45500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 0.45500 3. HS42 P2W15 3 x 0.00000 0.00000 3 x 0.09100 0.27300 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x o 00000 0 x 0.00000 o x 0.00000 o x 0.00000 NAC #2 Totals (Max 3 Amps):j 0.00000 0.27300 4.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC 03 Totals (Max 3 Ams): 0.00000 0.00000 5.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.00000 6. Auxiliary Power B200S 36 x 1 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 x 0.00000 AuxiliaryDevice 0 x 0.00000 WxI x 0.00000 AuxiliaryDevice 0 x 0.00000 0.00000 Auxiliary Device 0 x 0.00000 x 0.00000 TB4 Totals (Max 2 Amps): 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices 0 x 0.00000 0 x 0.00000 Other com alible devices 0 x 0.00000 0 x 0.00000 Other com alible devices 0 x 0.00000 0 1 x 1 0.00000 Total Non-Alarm Load; 0.075 Total Alarm Load: 2.194 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: ofBcer)a nelsonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.38 Amp Hours Total Secondary Load from the calculation table below. Current Draw Secondary Standby Load 0.075 A Time (hours) Re uired Standby Time x 24 hours 1.80 Secondary Alarm LoadRe 2.194 A x uired Alarm Time (hours) 0.084 hours 0.18 Total Secondary Load 1.98 Derating factorl x 1.2 Secondary Load Requirements 1 2.38 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp-hour distribution of your selections. Secondary Alarm Load 3% Secondary Standby Load ■Spare Batter,Capacity 27% ■Secondary Standby Load ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). !Spare Battery Capacity 5.62!Battery Selection AH - Secondary Load Requirements AH lSewndary Standby Load 2.16 ISecondary Standby Load AH * Derating Factor iSewndaryAlarm Load 1 0.22 ISecondary Alarm Load AH . Derating Factor Page 3 of 129 Honeywell System Current Draw - HPFF8 til MEMMERM IStandby 10.075A Alarm 11.616 A e 1.stem Modula r • . •ly r WNrHMain Circuit Board 7 1 x 1 0.07500 1 0.07500 1 1 1 x 1 0.20600 1 0.20600 2. Relay #1 PR-3MNAC#1 1 x 0.00000 0.00000 i x 0.03000 1 0.03000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 Totals Maz3Am s: 0.00000 0.03000 3. Relay #2 PR -3 1 x 0.00000 0.00000 7 z 0.03000 0.03000 0 x 0.00000 0 x 0.00000 00.00000 0 x o.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #2 Totals (Max 3 Am s :1 0.00000 0.03000 4. Relay #3 PR -3 1 x 1 0.00000 0.00000 1 x 0.03000 0.03000 0 x 1 0.00000 0 z 0.00000 00.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x o.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 T :1 0.00000 0.03000 5. Relay #4 PR -3 2 x 0.00000 0.00000 2 x 0.03000 0.06000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 z 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.06000 6. Auxiliary Power 82005 36 x 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxilia Device 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals Max 2 Amps): 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 z 0.00000 0 z I 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 1.616 'il" I 1 I ; ;: '+ °( =I it Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Address: BYU-Idaho City: Rexburg State: ID Prepared By: Nelson Fire Systems Address: 1481 S Major Street Email: City: Salt Lake City State: UT Secondary Load Requirements 2.32 Amp Hours Total Secondary Load from the calculation table below. Date: 2/24/2014 Zip: Phone: 801.468.8, @nelsonflre.com Zip: 84115 .11 Secondary Standby Load 0.075 A x . HI -1111A Mr-IFIMWM Re uired Standby Time 24 hours1 1.80 Secondary Alarm Load 1.616 A x Required Alarm Time (hours) 0.084 hours 1 0.14 Total Secondary Loadl 1.94 Derating factorl x 1.2 Secondary Load Requirements 1 2.32 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Lo; 27% SecondaryAlarm Load 2% ■ Spare Battery Capacity ■Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will ft in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #8 IStandby 10.075A Alarm 11.646 A 1. System Modules HPFF8 Main Circuit Board 1 x 0.07500 1 0.07500 1 1 1 x 1 0.20600 0.20600 2. Relay #5 PR -3 7 x 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 o z 0.00000 NAG #1 Totals Max 3 Amps):1 0.00000 0.03000 3. Relay #6 PR -3 1 I % 1 0.00000 0.00000 1 x 0.03000 0.03000 0 1 % 1 0.00000 0 z 0.00000 o 1 x 1 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o 1 x 0.00000 o x 0.00000 NAC #2 Totals Max 3 Amps : 0.00000 0.03000 4. Relay #7 PR -3 2 x 1 0.00000 0.00000 2 x 0.03000 0.06000 0 x 1 0.00000 0 x 0.00000 0 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals Max 3 Amps): 0.00000 0.06000 5. Relay #8 PR -3 2 x 1 0.00000 0.00000 2 x 0.03000 0.06000 0 x 1 0.00000 0 x 0.00000 0 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x O.00DDO 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 1 0.00000 0 x o.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.06000 6. Auxiliary Power B200S 36 x 0.00000 0.00000 36 x 0.03500 1.26000 AuxiliaryDevice 0 x 0.00000 0 z 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 T84 Totals Max 2 Amps) 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices 0x 0.00000 0 z 0.00000 Other compatible devices 0 x 0.00000 o z 0.00000 Other compatible devices 0 x 1 0.00000 1 1 0 1 z 1 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 1.646 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Address: BYU-Idaho City: Rexburg State: ID Prepared By: Address: City: Nelson Fire Systems 1481 S Major Street Salt Lake City State: UT Email: Secondary Load Requirements F 2.33 Amp Hours Total Secondary Load from the calculation table below. Date: 2/24/2014 Zip: Phone: 801.468.8300 a7nelsonfre.corn Zip: 84115 Current Draw Secondary Standby Load 0.075 A x Re wired Standby Time 24 hours 1 1.80 Secondary Alarm Load 1.646 A x Required Alarm Time (hours) 0.084 hours 1 0.14 Total Secondary Loadl 1.94 Derating factorl x 1.2 Secondary Load Requirements 1 2.33 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Alarm Load 2% Secondary Standby Load 27% ■ Spare Battery Capacity ■ Secondary Standby Load ■Secondary Alarm Load 0 Comments 1. Batteries will ft in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). IS pare Battery Capacity 5.67 Mattery Selection AH - Secondary Load Requirements AH Secondary Standby Load 1 2.16 ISeconclary, Standby Load AH * Derating Factor Secondary, Alarm Load 1 0.17 ISeconclary Alarm Load AH * Derating Factor Page 3 of 129 fb Name: Student Housing Building C BYU-Idaho Rexburg, ID Circuit Information Candela Panel Name: HPFF8-1 Circuit Name: HS -6 Starting Voltage: Starting Voltage = 20.4 Prepared By: Nelson Fire Systems 1481 S. Major Street Salt Lake City, 84115 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (ft) rn/Strobe 15 0.068 Non -temporal, Low 130 130 18.919 18.050 16.658 W rn/Strobe 177 0.291 Non -temporal, Low 20 150 18.925 18.059 16.672 WH ern/Strobe 177 0.291 Non -temporal, Low 20 170 18.954 18.105 16.745 WH ern/Strobe 177 0.291 Non -temporal, Low 20 190 19.006 18.187 16.877 WH ,m/Strobe 15 0.068 Non -temporal, Low 20 210 19.082 18.308 17.068 W )m/Strobe 15 0.068 Non -temporal, Low 20 230 19.163 18.436 17.273 W xn/Strobe 15 0.068 Non -temporal, Low 20 250 19.249 18.574 17.492 'W total current/amps 1.145 Total Dist:250 voltage drop 1.481 2.350 3.742 /27/2014 1 r Circuit Information Panel Name: HPFF8-2 Circuit Name: HS -5 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (n) Horn/Strobe 15 0.068 Non -temporal, Low 125 125 19.050 18.257 16.988 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 145 19.055 18.266 17.002 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 165 19.066 18.283 17.029 P2W Horn/Strobe 177 0.291 Non -temporal, Low 20 185 19.083 18.309 17.071 P2WH Horn/Strobe 177 0.291 Non -temporal, Low 20 205 19.123 18.373 17.171 P2WH Horn/Strobe 177 0.291 Non -temporal, Low 20 225 19.186 18.473 17.331 P2WH Horn/Strobe 15 0.068 Non -temporal, Low 20 245 19.272 18.610 17.550 P2W Total current/amps 1.145 Total Dist: 245 voltage drop 1.350 2.143 3.412 2/27/2014 :ircuit Information Panel Name: HPFF8-3 Circuit Name: HS -4 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (ft) rn/Strobe 15 0.068 Non -temporal, Low 180 180 19.470 18.924 18.050 16.662 N rn/Strobe 15 0.068 Non -temporal, Low 20 200 19.475 18.933 18.063 16.684 W rn/Strobe 177 0.291 Non -temporal, Low 20 220 19.486 18.950 18.091 16.727 WH rn/Strobe 177 0.291 Non -temporal, Low 20 240 19.521 19.005 18.178 16.865 WH m/Strobe 15 0.068 Non -temporal, Low 20 260 19.578 19.096 18.324 17.098 W otal current/amps 0.786 Total Dist:260 voltage drop 0.930 1.476 2.350 3.738 127/2014 3 Circuit Information Panel Name: HPFF8-4 (1.5) amp circuit Circuit Name: HS -1 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 18 (Amps) last device source (ft) Horn/Strobe 35 0.068 Non -temporal, Low 220 220 20.078 19.890 19.587 19.107 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 240 20.084 19.898 19.601 19.129 P2W Horn/Strobe 75 0.156 Non -temporal, Low 20 260 20.095 19.916 19.629 19.173 P2W Total current/amps 0.292 Total Dist:260 voltage drop 0.322 0.510 0.813 1.293 2/27/2014 :ircuit Information Panel Name: HPFF8-4 (1.5) amp circuit Circuit Name: HS -2 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply (pe and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (n) -n/Strobe 15 0.068 Non -temporal, Low 215 215 19.667 19.237 18.548 17.455 N rn/Strobe 15 0.068 Non -temporal, Low 75 290 19.688 19.270 18.600 17.537 N rn/Strobe 15 0.068 Non -temporal, Low 75 365 19.729 19.335 18.704 17.702 N rn/Strobe 15 0.068 Non -temporal, Low 45 410 19.766 19.393 18.797 17.851 N rn/Strobe 15 0.068 Non -temporal, Low 30 440 19.799 19.446 18.880 17.982 W otal current/amps 0.340 Total Dist:440 voltage drop 0.733 1.163 1.852 2.945 '27/2014 5 Circuit Information Panel Name: HPFF8-4 Circuit Name: HS -3 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and volume Dist from Dist from 12 14 16 is (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 25 25 20.168 20.031 19.813 19.466 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 45 20.173 20.040 19.827 19.488 P2W Horn/Strobe 15 0.068 Non -temporal, Low 50 95 20.200 20.083 19.896 19.598 P2W Horn/Strobe 15 0.068 Non -temporal, Low 50 145 20.241 20.148 19.999 19.763 P2W Total current/amps 0.272 Total Dist: 145 voltage drop 0.232 0.369 0.587 0.934 2/27/2014 :ircult Information Panel Name: HPFF8-5 Circuit Name: HS -7 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ape and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 is (Amps) last device source (n) n/Strobe 15 0.068 Non -temporal, Low 220 220 19.661 19.226 18.531 17.428 V n/Strobe 15 0.068 Non -temporal, Low 75 295 19.681 19.259 18.583 17.510 V 'n/Strobe 15 0.068 Non -temporal, Low 75 370 19.722 19.324 18.687 17.675 V 'n/Strobe 15 0.068 Non -temporal, Low 45 415 19.759 19.383 18.780 17.823 N ,n/Strobe 15 0.068 Non -temporal, Low 30 445 19.792 19.435 18.863 17.955 N )Lal current/amps 0.340 Total Dist:445 voltage drop 0.739 1.174 1.869 2.972 27/2014 Circuit Information Panel Name: HPFF8-5 Circuit Name: HS -8 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (R) Horn/Strobe 15 0.068 Non -temporal, Low 35 35 19.549 19.049 18.248 16.978 P2W Horn/Strobe IS 0.068 Non -temporal, Low 60 95 19.565 19.075 18.290 17.044 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 155 19.598 19.127 18.373 17.175 P2W Horn/Strobe 15 0.066 Non -temporal, Low 25 180 19.618 19.159 18.424 17.258 P2W Horn/Strobe 30 0.096 Non -temporal, Low 20 200 19.640 19.194 18.480 17.346 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 220 19.670 19.241 18.555 17.465 P2W 75 0.156 Non -temporal, Low 50 270 19.757 19.380 18.776 17.817 E,r./Str.rbe amps 0.592 Total Dist:270 voltage drop 0.851 1.351 2.152 3.422 2/27/2014 :ircuit Information Panel Name: HPFF8-5 (1.5) amp circuit Circuit Name: HS -9 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply ,pe and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 i8 (Amps) last device source (ft) n/Strobe is 0.068 Non -temporal, Low 230 230 19.647 19.205 18.497 17.373 V n/Strobe 15 0.068 Non -temporal, Low 75 305 19.667 19.237 18.548 17.455 V 'n/Strobe 15 0.068 Non -temporal, Low 75 380 19.708 19.302 18.652 17.620 V 'n/Strobe 15 0.068 Non -temporal, Low 45 425 19.745 19.361 18.745 17.768 V ,n/Strobe 15 0.068 Non -temporal, Low 30 455 19.778 19.413 18.828 17.900 v rtal current/amps 0.340 Total Dist:455 voltage drop 0.753 1.195 1.903 3.027 27/2014 SOR Circuit Information Panel Name: HPFF8-5 Circuit Name: HS -10 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 45 45 19.837 19.506 18.976 18.135 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 105 19.853 19.532 19.017 18.201 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 165 19.886 19.584 19.100 18.333 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 185 19.902 19.610 19.142 18.399 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 205 19.924 19.645 19.197 18.487 P2W Horn/Strobe 75 0.156 Non -temporal, Low 20 225 19.951 19.688 19.266 18.597 P2W Total c,rrent/amps 0.496 Total Dist:225 voltage drop 0.563 0.894 1.424 2.265 2/27/2014 10 Arcuit Information Panel Name: HPFF8-6 Circuit Name: HS -11 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply fps and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (ft) 'n/Strobe 15 0.068 Non -temporal, Low 240 240 19.633 19.183 18.462 17.318 N m/Strobe 15 0.068 Non -temporal, Low 75 315 19.654 19.216 18.514 17.400 N rn/Strobe 15 0.068 Non -temporal, Low 75 390 19.695 19.281 18.618 17.565 rn/Strobe 15 0.068 Non -temporal, Low 45 435 19.732 19.339 18.711 17.713 N rn/Strobe EN 15 0.068 Non -temporal, Low 30 465 19.764 19.391 18.794 17.845 N otal current/amps 0.340 Total Dist:465 voltage drop 0.767 1.217 1.938 3.082 27/2014 11 Circuit Information Panel Name: HPFF8-6 Circuit Name: HS -12 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (R) Horn/Strobe 15 0.068 Non -temporal, Low 55 55 20.207 20.094 19.913 19.625 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 115 20.224 20.120 19.954 19.691 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 175 20.256 20.172 20.037 19.823 P2W Total current/amps 0.204 Total Dist: 175 voltage drop 0.193 0.306 0.487 0.775 2/27/2014 12 Nelson I d I L1 I Systems FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 www.nelsoufire.com BYU-Idaho Student Mousing Building C Fire Alarm System Submittal Battery Calculations & Voltage Drop 13-00342 BYUI Student Apts, Bldg C; 56 Units Fire Alarm Revisions 02/24/2014 Jobsite Copy JOB SITE COPY "These plans are to remain on the job and be available upon request during inspections. pGa iWMI System Current Draw E3 Series Control Panel with Broadband Total Standby 0.616 A Total Alarm 3.962 A Device i Q Draw Standby Ot Draw I Alarm 1. System Device Intel. Loop Interface, Main Board ILI-MB-E3 1 x 0.08100 0.08100 1 x 0.15000 0.15000 Intel. Loop Interface Supplement Board UkS-E3 3 x 0.08100 0.24300 3 x 0.15000 0.45000 Intel. Loop Interface Main Board - Apollo IL195-MB-E3) 0 x 0.05000 0 x 0.09100 Intel. Loop Interface Supplement Board - Apollo ILI95-S-E3 0 z 0.05000 0 x 0.09100 7100 Panel, 1 SLC 0 x 0.05600 0 x 0.07600 7100 Panel, 1 SLC with DACT 0 x 0.07500 0 x 0.09500 7100 Panel, 2 SLC 0 x 0.06500 0 x 0.08500 7100 Panel, 2 SLC with DACT 0 x 0.08500 0 x 0.10500 2. E3 Optional Modules 120V Power Supply Sub -Assembly PM -9 .05000 0.05000 1 x 0.05000 0.05000 240V Power Su Sub-AssemblyPM-9G .02700 0 x 0.05000 LCD Display & Switch Control LCD -E3 .02400 0.04800 2 x 0.02800 0.05600 ARCNET Repeater RPT -E3 .01300 0.02600 2 x 0.01300 0.02600 Digital Communicator DACT-E3 iffo. .01800 0 x 0.01800 Optional Remote Serial Annunicalor LCD -7100 .05000 0 x 0.07500 Network LCD Annunicalor NGA .20000 0 z 0.20000 Auxilia Switch Sub-AssemblyASM-16 .01100 0.02200 2 x 0.01100 0.02200 Remote LED Driver Module ANU-48 .01100 0 x 0.01100 Addressable Node Expander ANA 06500 0 x 0.06500 3.7100 Optional Modules Intelligent Network Interface Module (INI-7100) 0 1 x 1 0.04000 1 0 x 1 0.04000 Printer Transient Module (FIRM)0 x 0.02000 0 x 0.02000 Remote LED Driver Module LDM-7100 0 1 x 1 0.03500 1 0 1 x 1 0.20000 Class A O tion Module CAOM 0 x 0.00100 0 x 0.00100 unl" a ircuit bon o u e 0 x x I u.uuluu 4. INI-VU(; E;ommand Center Intel. Network Command Center INI-VGC 0 x 0.15000 10 x 0.15000 Addressable Switch Sub-assemblyASM-16 0 x 0.01100 0 x 0.01 100 Voice Pa in Micro hone (Microphone) 0 x I 0.00100 I I 0 I x 0.00100 Firefighters Telephone Handset 0 z 1 0.02000 1 1 0 1 z 1 0.02000 0 5. INI-VGX Voice Gateway Intel. Network Voice Gateway (IN[-VGX 0 x 0.15000 0 x 0.15000 120V Power SuDolv Sub-Assembl PM -9 0 x 0.05000 0 x 0.05000 240V Power Su Sub-Assembl PM -9G 0 x 0.02700 0 z 0.05000 Amplifier Sub -assembly, 50 watt 25V AM -50 0 x 0.08600 0 x 2.20600 Amplifier Sub -assembly, 50 waft 70V AM -50-70 0 x 0.04900 0 x 2.30000 Addressable Output Module -Signal AOM-2SF 0 x 0.00200 0 x 0.00650 Addressable Output Module -Telephone AOM -TEL 0 x 0.00200 0 x 0.00650 Addressable Output Module -Audio AOM -MUX 0 x 0.00200 0 x 0.00650 6. IN] -VGE Command Center Voice Gateway Intel. Network Command Voice Gateway (INI-VGE 0 I x 1 0.15000 0 x 0.15000 Addressable Switch Sub -assembly ASM -16 0 x 0.01100 0 x 0.01100 Voice Paging Microphone (Microphone) 0 x 0.00100 0 x 0.00100 Firefighter's Telephone Handset 0 x 0.02000 0 z 0.02000 Addressable Output Module -Signal AOM-2SF 0 z 0.00200 0 x 0.00650 Addressable Output Module -Telephone AOM -TEL 0 x 0.00200 0 x 0.00650 Addressable Output Module -Audio AOM -MUX 0 x 0.00200 0 x 0.00650 7. Smoke Detectors/Modules ASD-PL2F/ASD-IL2F 272 z 0.00030 0.08160 272 x 0.00650 1.76800 ATO-RL2F/ATD-HL2F 1 x 0.00030 0.00030 1 x 0.00650 0.00650 DNR 82 x 0.00030 0.02460 82 x 0.00650 0.53300 AMM -41' 6 x 0.00038 0.00225 6 x 0.00500 0.03000 AOM-2RF 5 z 0.00038 0.00188 5 z 0.00650 0.03250 MS-7AF 1 x 0.00030 0.00030 1 x 0.00300 0.00300 MCS-COF 116 x 1 0.00030 1 0.03480 116 x 0.00720 0.83520 8. Notification Appliances 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 Total Standby Load: 0.616 A Total Alarm Load: 3,962 A System Dower Requirements E3 Fire Alarm Control Panel with Broadband Protected Premises;.. Building C -- BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared I Nelson Fire Systems Phone: 801-468-8300 Address: 1481 S Major Street Email: orrcen. nelsonfire.com City: Salt Lake City State: Utah Zip: 84115 Secondary Load Requirements 18.13 Amp Hours Total Secondary Load from the calculation table below. Current Draw I Time (hours) Total (AH) Secondary Standby Load uired StandbyTime 0.616A_.___.. xRe 24 hours .__ ___ 14.78 Secondary Alarm LoadRe rm uired AlaTime hours 3.962 A x 0.084 hours 0.33 Total Secondary Load 15.11 Derating factor x 1.20 Secondary Load Requirements 18.13 AH Battery Selection 26.00 Amp Hours Select batteries from the list 26 AH Battery (12 volt Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Alarm Load 2% OSpereeabry Capadly .Secondary Standby Load MSewndary Alarm Load Secondary Standby Load 68% !Spare Battery Capacity 7.87 Am Hours ISecondary Standby Load 17.73 Amp Hours Seconds Alarm Load 1 0.40 Amp Hours Honeywell System Current Draw - HPFF8 #1 Standby 0.076A Alarm 2.629 A 1. System Modules _ HPFFB Main Cmit Board 1 I x 1 0.07500 0.07500 1 1 x 1 0.20600 1 0.20800 2. HS -6 P2W15 4 x 0.00000 0.00000 4 x 0.09100 0.36400 P2WHI77 3 z 0.00000 0.00000 3 x 0.30300 0.90900 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x o 00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 1.27300 3.. 0 x 0.00000 0 x 0.00000 0 x I 0.00000 0 x 0.00000 0 0 x 0.00000 0 0 x 0.00000 o 0 x 0.00000 MOOOOOO o 0 x 0.00000 0 0 x O.0o0o0 0 0 x 0.00000 NAC #2 Totals (Max 3 Amps):1 0.00000 0.00000 4.. 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.00000 5.. 0 x 1 0.00000 0 x 0.00000 0 xPOOOOOO 0 x 0.00000 0 x 0 x 0.00000 0 x 0 x 0.00000 0 x 0 x 0.00000 0 x o z 0.00000 0 x 0 x 0.00000 0 x 0 x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.00000 6. Auxiliary Pourer B200S 30 x 0.00000 0.00000 30 z 0.03500 1.05000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps): 0.00000 1.05000 T. Compatible Devices not listed Other com alible devices 0 x 0.00000 0 z 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other oom atible devices 0 x 1 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 2.529 Honeywell Secondary Power Requirements _.............. HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: Ofrioeagnelsonrire.com City: Salt Lake City - State: UT - Zip: Secondary Load Load Requirements 2.41 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Load Required Standb Time 0.075 A x 24 hours 1.80 Secondary Alarm LoadRequired Alarm Time (hours) 2.529 A x 0.084 hours 0.21 Total Secondary Load 2.01 Derating factor x 1.2 Secondary Load Requirements 2.41 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) G Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 3% ■ Spare Battery Capacity ■Secondary Standby load ■Secondary Alarm Load Comments 1. Batteries will ft in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Spare Battery Capacity 5.59 Battery Selection (AH) - Secondary Load Requirements (AH) (Secondary Rad 1 2.16 ISeconclary Standby Load (AH)' Derating Factor �econdary Alarm Load 1 0.25 ISeconcl Alarm Load (AH)' Derating Factor Page 3 of 129 Honeywell System Current Draw - HPFF8 #2 vi 10 1 -Standb O.075A Alarm 12.494 A Device 1.5 stem Modules-____. Secondary No I • Draw ._.. _ �, HPFF8 Main Circuit Board 1 1 1 x 1 0.07500 0.07500 1 x 0.20600 0.20600 2. HS-5 P2W15 4 x 0.00000 0.00000 4 x 0.09100 0.36400 P2WHi77 3 x 1 0.00000 0.00000 3 x 0.30300 0.90900 0 x 0.00000 0 x 0.00000 x _ _0.00000__ 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 1.27300 0.. 0 x 0.00000 0 x I 0.00000 0 x 0.00000 0 x 0.00900 0 x 0.00000 0 x 0.00000 0 x 0 x 000000 0 x 0 x 0.00000 0 x no 0 x 0.00000 o x 0 x 0.00000 0 x 0.00000 NAC #2 Totals Max 3 Amps) 0.00000 0.00000 4.. 0 x 0.000000 x 020000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 020000 020000 5.. 0 x 0.00000 0 000 0 z 0.00000 0 000 0 x 0.00000 0 000 0 x 0.00000 0 000 0 x 0.00000 0 000 EX0 0 x 0.00000 0 000 0 x 0.00000 0 000 o x 0.00000 o 000 NAC #4 Totals (Max 3 Amps) 0.00000 0.00000 6. Auxiliary Power 8200S 29 x 0.00000 0.00000 29 x 0.03500 1.01500 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps) 0.00000 1.01500 7. Compatible Devices not listed Other compatible devices 0 z 0.00000 0 x 0.00000 Other mr, atible devices 0 x 020000 0 x 020000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Load: 2.494 inoneywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: OffceOnelsonfre com City: Salt Lake City Slate: UT Zip: 84115 Secondary Load Requirements 2.41 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Loadx 0.075 A Required Standby Time 24 hours 1.80 Secondary Alarm Loadx 2.434 A Required Alarm Time (hours) 0.084 hours 0.21 Total Secondary Loadl 2.01 Derating factorl x 1.2 Secondary Load Requirements 1 2.41 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt) G Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load ■ Spare Battery capacity ■ Secondary Standby Load •Secondary Alarm Load 4 Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #3 Standb 0.075A Alarm 12.275 A 1. System Modules HPFF8 Main Circuit Board 1 x 0.07500 0.07500 1 z 0.20600 0.20800 2. HSd P2W15 3 x 0.00000 0.00000 3 x 0.09100 0.27300 P2WH177 2 z 0.00000 0.00000 2 x 0.30300 0.60600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x o.a0000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 0.87900 3.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 NAC 02 Totals (Max 3 Amps) 0.00000 0.00000 4.. o x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x o.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.00000 5.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #4 Totals (Max 3 Am s): 0.00000 0.00000 5. Auxiliary Power B200S 34 x 0.00000 0.00000 34 x 0.03500 1.19000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 z 0.00000 0 X 0.00000 Auxilia Device 0 z 0.00000 0 -L x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps) 0.00000 1.19000 7. Com Devices not Ilatetl Other compatible alible devices 0x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 z 0.00000 Other compatible devices 0 x 0.00000 0 z 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 2.276 l Honeywell Secondary Power Requirements Page 2 of 129 HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: Officgpnelsonfre.corn City: Salt Lake City State: UT- — — Zip: 84115- — Secondary Load Requirements 2.39 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Load 0.075 A x Required Standby Time 24 hours 1.80 Secondary Alarm Load 2.275 A x Required Alarm Time (hours) 0.084 hours 0.19 Total Secondary Load 1.99 Derating factor x 1.2 Secondary Load Requirements 2.39 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery 12 volt G Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% SecondaryAlarm Load 3% ■ Spare Battery Capacity •Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw - HPFF8 #4 *Alarm"573A.. r. stem Modules 5F8 aminim, , • r . Main Circuit Board I x 1 0.07500 1 0.07500 1 1 1 x 1 0.20600 1 0.20600 2. HS-7 P2W15 2 x 0.00000 0.00000 2 z 0.09100 0.18200 p2W75 1 x 0.00000 0.00000 1 x 0.17600 0.17600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 ---T0 x 0.00000 0 x 0.00000 0 x 0.00000 0 - x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Am s): 0.00000 0.35800 3. HS-2 P2W15 5 x 0.00000 0.00000 5 x 0.09100 0.45500 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.000DO NAC #2 Totals (Max 3 Amps): O.000DO 0.45500 4. HS-3 P2W15 4 x 0.00000 0.00000 4 0 0.36400 0 z 0.00000 0 0 0 x 0.00000 0 0 0 x 0.00000 o 0 UO.00OOG 0 x 0.00000 0 0 o x 0.00000 0 0 0 x 0.00000 0 0 0 x 0.00000 0 0 NAC #3 Totals (Max 3 Amps): 0.00000 1 0.36400 5.. I x 0.00000 o x 0.00000 o x 0.00000 o x o.00ao0 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 o x O.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.00000 B. Auxiliary Pourer B200S 34 x 0.00000 O.o00o0 34 x 0.03500 1.19000 Auxiliary Device 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 z 0.00000 0 x 0.00000 Auxiliary Device0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps): 0.00000 1.19000 T. Compatible Devices not listed Other compatible devices0 z 0.00000 0 x 0.00000 Other cum alible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 1 0 1 x 1 0.00000 0 x 0.00000 Total Non-Alarm Load: 0.075 Total Alarm Load: 2.573 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: offce0nelsonfire.com City: Salt Lake City Slate: UT Zip: 84115 Secondary Load Requirements 2.42 Amp Hours Total Secondary Load from the calculation table below. Cu LrLnLDrawTime (hours) -Total (AH) Secondary Standby Load ired Standby Time Requ 0.075 A 24 hours 1.80 EE Secondary Alarm Load Required Alarm Time (hours) 2.573 A x 0.084 hours 0.22 Total Secondary Load 2.02 Derating factor x 1.2 Secondary Load Requirements 2.42 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VOC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% Secondary Alarm Load 3% ■ Spare Battery Capacity - •Secondary Standby Wad ■SecondaryAlarm Wad Comments 1. Batteries will ft in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw e HPFF8 #5 Standby 0.075A Alarm 13.754 A r 1.5 stem Modules • r • r . HPFF8 Main Circuit Board 1 x 0.07500 1 0.07500 1 1 1 x 1 0.20600 0.20600 2. HS -7 P2W155 x 0.00000 0.00000 5 x 0.09100 0.45500 - 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 _ 0 x 0.00000 NAC 01 Totals (Max 3 Amps): 0.00000 0.45500 3. HS -8 P2W75 5 x 1 0.00000 0.00000 5 x 0.09100 0.45500 P2W30 1 x 1 0.00000 0.00000 1 x 0.11600 0.11600 P2W75 1 x 0.00000 0.00000 1 x 0.17600 0.17600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #2 Totals (Max 3 Amps): 0.00000 0.74700 4. HS -9 P2W15 5 x 1 0.00000 0.00000 5 x 0.09100 0.45500 0 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.45500 5. HS -10 P2W15 5 x 0.00000 0.00000 5 x 0.09100 0.45500 P2W75 1 x 0.00000 0.00000 1 x 0.17600 0.17600 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x o.00000 0 x 0.00000 0 x o.00000 0 x 0.00000 NAC #4 Totals (Max -3Amps) 0.00000 0.63100 6. Auxiliary Power B200S 36 x 0.00000 0.00000 36 z 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps):j 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices 0x 0.00000 0 x 0.00000 Other compatible devices 0 z 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 3.764 Honeywell Secondary Power Requirements Page 2 of 129 HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: pffice@nelsonfire.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.54 Amp Hours Total Secondary Load from the calculation table below. MMUMMMMM Secondary Standby Load 0.075 A x Required Standby Time 24 hours 1.80 Secondary Alarm Load 3.754 A Required Alarm Time (hours x 0.084 hours 0.32 Total Secondary Loaal 2.12 Derating factorl x 1.2 Secondary Load Requirements 1 2.54 Battery Selection E-8 -1Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loai 27% Secondary Alarm Load 5% ■ Spare Battery capacity ■ Serondary Standby Load ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). S areBatte Ca acit 5.46 Battery Selection (AH) - Secondary. Load Requirements (AH) Secondary Standby Load 2.16 ISeconclary Standby Load (AH)' Derating Factor Secondary Alarm Load 1 0.38 Secondary Alarm Load (AH) • Derating Factor Page 3 of 129 Honeywell System Current Draw - HPFF8 #6 Standb 0.075 A Alarm 12.194 A Me •. 1. S stem Modules HPFF8 Main Cirwil Board 6tysic2i Draw Mozam• 1 z 0.07500 0.07500 1 x MW r . 0.20800 0.20800 2. HS -11 PPYJ15 5 z 0.00000 0.00000 5 x 0.09100 0.45500 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x -.00000 0 x 0.00000 o x 0.00000 o x o.00000 o x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 0.45500 3. HS -12 P2W15 3 z 0.00000 0.00000 3 x 0.09100 0.27300 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 NAC #2 Totals (Max 3 Amps): 0.000000.27300 4.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #3 Totals (Max 3 Am s): 0.00000 1 0.00000 5.. 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 0 x 0.00000 0 x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 o x 0.00000 o x o.00000 NAC #4 Totals (Max 3 Am s): 0.00000 0.00000 6. Auxilia Power BP00S 38 1 x0.00000 0.00000 36 x 0.03500 1.28000 Auxilia Device 0 x 0.00000 0 x 0.00000 Aa%lila Device 0 z 0.00000 I 1 0 x 0.00000 Auxilia Device 0 x 0.00000 0 x 0.00000 Auxiliary Device o x 0.00000 0 x 0.00000 T64 Totals (Max 2 Amos): 0.00000 1 128000 7. Compatible Devices not listed Other compatible devices 0 x 0.00000 0 z 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 z 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.075 Total At Load- 2194 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: otrceanneisonere.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.38 Amp Hours Total Secondary Load from the calculation table below. -Curren awffm6 (hours) .1 Total- (AH) Load Required btandb�ired Standb Time 0.075 A x 24 hours 1.80 Secondary Alarm Load Required Alarm Time (hours) 2.194 A x 0.084 hours 0.18 TotalSeconda Load 1.98 Derating factorl x 1.2 Secondary Load Requirements 1 2.38 Battery Selection F-8 —1 Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt G Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Loa 27% SecondaryAlarm Load 3% ■ Spare Battery Capacity ■ Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Page 3 of 129 Honeywell System Current Draw- HPFF8 #7 IStandby 10.076A Alarm 11.616 A 1. System Modules HPFF8 Main Circuit Board 1 x 0.07500 0.07500 1 z 0.20800 0.20800 2. Relay #1 PR -3 1 x 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 I 0 x 0.00000 0 0.00000 0 x 0.00000 0 0.00000 0 x 0.00000 0 0.00000 0 x 0.00000 0 0.00000 Ix 0 x o.00000 0 0.00000 0 x 0.00000 o 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps): 0.00000 0.03000 3. Relay #2 PR -3 1 z 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x=Amps)�o 0 x 0.00000 0 x0 x 0.00000 0 z0 x 0.00000 0 x0 x 0.00000 0 x0 x 0.00000 NAC #2 Totals oo 0.03000 4. Relay #3 PR -3 1 x 1 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 20.00000 o x 20.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x OA0000 0 x 0.00000 NAC #3 Totals (Max 3 Amps): 0.00000 0.03000 5. Relay #4 PR -3 x 0.00000 0.00000 2 x 0.03000 0.06000 x 0.00000 0 z 0.00000 x a.o0o000 x 0.00000 x 0.00000 0 x 0.00000 M12 x 0.00000 o x 0.00000 x 0.00000 0 x 0.00000 x 0.00000 0 x 0.00000 x 0.00000 o x 20.00000 NAC #4 Totals (Max 3 Amps): 0.00000 0.06000 6. Auxiliary Power B2005 36 x 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 z 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 TB4 Totals (Max 2 Amps): 0.00000 1.26000 7. Compatible Devices not listed Other ocm atible devices 0 x 0.00000 0 x 0.00000 Other cam atible devices 0 x 0.00000 0 1 x 0.00000 Other compatible devices 0 x Omixi0 0 1 x 0.00000 Total Non -Alarm Load: 0.075 Total Alarm Load: 1.616 Honeywell Secondary Power Requirements F77— HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: Otscer�neisonrre.com City: Salt Lake City Stale: UT Zip: 84115 Secondary Load Requirements 2.32 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Load Required Standby Time 0.075 A 24 hours 1.80 Secondary Alarm Load 1.616 A 7Required Alarm Time hours 0.084 hours 0.14 Total Secondary Loadl 1.94 Derating factor x 1.2 Secondary Load Requirements 2.32 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Batte 12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp-hour distribution of your selections. SecondaryAlarm Load 2% Secondary Standby Load 27% ■ Spare Battery capacity • Secondary Standby Load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). S are 5.68 !BatterySelection AH - SecondaryLoad Requirements AH Seondb Load 1 2.16 ISeconclary Standby Load AH • Derating Factor Secondary Alarm Load 1 0.16 ISecondary Alarm Load (AH)' Derating Factor Page 3 of 129 Honeywell system Current Draw - HPFF$ #8 Standb 0.075 A Alarm 11.646 A 1. System Modules HPFFB Main Circuit Board 1 x 0.07500 1 0.07500 1 1 x 1 0.20600 1 0.20600 2. Relay #5 PR -3 1 x 0.00000 0.00000 1 x 0.03000 0.03000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 z 0.00000 0 z 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 z 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC #1 Totals (Max 3 Amps):1 0.00000 1 0.03000 3. Relay #6 PR -3 1 z 1 0.00000 0.00000 1 x 0.03000 0.03000 0 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 0.00000 0 x 0.00000 0 0.00000 0 x 0.00000 0 0.00000 0 x 0.00000 0 tx 0.00000 0 x 0.00000 0 0.00000 o x 00.0000000000 o 00.00000 NAC 92 T :1 0.00000 0.03000 4. Relay #7 PR -3 2 z 1 0.00000 0.00000 2 x 0.03000 0.06000 0 x 1 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 o 00.00000 0 x 0.00000 00.000000 x 0.00000 000.000000000 tXXX 0 x 0.00000 0o.000ao0 x 0.00000 000.000000000 0 x 0.00000 NAC #3 Totals Max 3 Amps): 0.00000 1 0.06000 5. Way #8 PR -3 2 x 0.00000 0.00000 2 x 0.03000 0.06000 0 x 0.00000 0 x 0.00000 0 x 00.00000 0 x 0.00000 o x 0.00000 o x 0.00000 0 x 00.00000 0 x 0.00000 o x 00.000000000 0 x 0.00000 0 x 00.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 NAC 04 Totals (Max 3 Amp$):l 0.000001 0.06000 6. Auxiliary Power 82006 36 z 0.00000 0.00000 36 x 0.03500 1.26000 Auxiliary Device 0 x 0.00000 0 x 0.00000 AuxiliaryDevice 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 x 0.00000 0 x 0.00000 Auxiliary Device 0 z 0.00000 0 x 0.00000 T64 Totals Max 2 Amps): 0.00000 1.26000 7. Compatible Devices not listed Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Other compatible devices 0 x 0.00000 0 x 0.00000 Total Non -Alarm Load: 0.0751 Total Alarm Load: 1 1.846 Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C - BYU-ID Student Housing Dale: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: ofrce@neisonflre.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.33 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Load Required Standby Time 0.075 A x 24 hours 1.80 Secondary Alarm Load Required Alarm Time (hours) 1.646 A x 0.084 hours 0.14 Total Secondary Load 1.94 Derating factor x 1.2 Secondary Load Requirements 2.33 Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) C Four (two 12VDC sets in parallel) Page 2 of 129 Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Standby Lo; 27% SecondaryAlarm Load 2% ■ Spare Battery Capacity • Secondary Standby load ■SecondaryAlarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). Spare Battery Capacity 5.67 18attery Selection (AH) - Secondary Load Requirements (AH) Secondary Standby Load 2.16 Secondary Standby Load (AH) a Derating Factor Secondary Alarm Load i 017 ISewnclary Alarm Load (AH)' Derating Factor Page 3 of 129 Honeywell System Current Draw - HPFF8 #9 ra.. CJ.. 0'; 5 A . A,.— _F2 —52-9AJ 5-.eo.e:.. .Q.. D..w •,N C.... Ir. Af.: m'I '.'S Q"I .:A,-C.nw.. . I D...., "',A.— oe ., .. ..., oe ..... ee,..,,. wee ....., MEN MEN oe....., woe ,..,,, MEN ENEME NEEME ....., wee ....., MEN MEN oe..,.,. wee ..,... MEN EINEEM ..,,,. woe ...... INNEE INNEENIN ..,.,. woe ...... MEN e ....�oe......� e..,.,. wee ....,, MEN ee,...,. woe ,.,.,, MEN ee...... wee ,,,,,, MEN oe,.... wee ,,,,,, MEN NEENNEEN NNEN wee...... MEE wee ...... INEEN � e MEN MEN ....,, EME oe ...,,. woe ....,, MEN oe,...,. wee ..,.,, MEN IMENEEN oe,...., wee ,,..., MEN ee....., wee .,.,.. MEN oe....., woe ...... MEN IMMEMENIMENIN .. , moo■ ...... MEN oe®woe ...... MEN NOMMIN ME MEN oe .., .. woe MEN MEN MEN oe®woe ...... oe ...... woe ..,.,. MEN ee ...... woe ,.,,,, MEN Honeywell Secondary Power Requirements HPFF8 Power Supply Protected Premises: Building C- BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: ggiicejMnelsonfire.corn City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements F 2.41 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Load Required Standby Time 0.075 A x 24 hours 1.80 Secondary Alarm Load 2.529 A x Required Alarm Time (hours) 0.084 hours 0.21 Total Secondary Load 2.01 Derating factor x 1.2 Secondary Load Requirements 2.41 AH Bathry Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) Battery Distribution Chart Shows amp-hour distribution of your selections. Secondary Alarm Load 3% ■ Spare Battery Capacity Secondary Standby Load ■SecondaryStandby Load 27% ■Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). S are Battery Capacity 5.59 Battery Selection(AH)-Secondary Load Requirements (AH) Secondary Standby Load 1 2.16 Secondary Standby Load (AH)"Derating Factor Secondary Alan Load 1 0.25 ISecondary Alarm Load (AH)' Derating Factor Honeywell System Current Draw - HPFF8 #10 ,T.I..7 ..n� SI.n� 100 Al.,. 12.529 A ., ,..' ..�.. S....a:.r D.. N.- Ai. — D,.„.. C.,.,.,,. No. A..,- I So..Id—Al.—G.—.. D.... X.— Ems....., .••.., oe ..• ., .... ©e .,..., .,••,. ©e . , •. .•,••. ee oe.•..., wee ...•., � oe .,.•.. wee ...,•. e� ee•.,,,, epee ,,..., � oe,...., woe ..•.., � ee. •..., wee ..,•., e� ee• � wee • •,.•. � ee •,,,,. woe ....,• � oe....•, woe ..••.• oe.,,••• woe .•..•. � ee,...., wee ..••., � ee,.•.., wee ••,•., � ee. ••... wee • •,... � ee....•. epee ,.,,,. � ee.,,,,, woe ,,...• migini oe , •..., woe ..,,., � oe.•...• wee •.,,•. � oe.••••. wee ,•.... e� oe.,,•,• wee ,,..,• 0■ •.,,,, wee ..•.,. ee•.,.,. woe ..,.., e� ee,..., wee •.,... � ;. me .,•••• ....., me ., .. .... ee•.,,,, epIRI 110 ..••., ee,...., epee ..••., � ee,...., epee ••,,.. e� oe •.•., woe • •.,•. � oe • ..,,, woe • ., � Honeywell Secondary Power Requirements HE8 Power Supply Protected Premises: Building C-BYU-ID Student Housing Date: 2/24/2014 Address: BYU-Idaho City: Rexburg State: ID Zip: Prepared By: Nelson Fire Systems Phone: 801.468.8300 Address: 1481 S Major Street Email: of iicepnelsonflre.com City: Salt Lake City State: UT Zip: 84115 Secondary Load Requirements 2.41 Amp Hours Total Secondary Load from the calculation table below. Secondary Standby Load Required Standby Time 0.075 A x 24 hours 1.80 Secondary Alarm Load 2.529 A x Required Alarm Time (hours) 0.084 hours 0.21 Total Secondary Load 2.01 Derating factor x 1.2 Secondary Load Requirements 2.41 j AH Battery Selection ® Amp Hours Select batteries from the list below. 8.0 AH BAT -1270 Battery (12 volt) Babb Distribution Chart Shows amp -hour distribution of your selections. Secondary Alarm Load 3% -- - - • Spare Battery capacity- - - — - Secondary Standby Load 27% • Secondary Standby Load •Secondary Alarm Load Comments 1. Batteries will fit in the FACP cabinet. 2. Selected battery size meets secondary load requirements. 3. The selected batteries (8AH) are within the charger range of this power supply (7-26AH). ISpare Battery Capacity 5.59!Battery Selection AH) -Secondary Load Requirements (AH) ISeconclary Standby Load 2.18 l8econclary Standby Load (AH)` Derating Factor SecondaryAlarm Load 1 0.25 ISecondary Alan Load (AH"Dentin Factor Page 3 of 131 14� SYSTEM SENSOR' xdvonced iclem advanced solutbris lob Name: Student Housing Building C BYU-Idaho Rexburg, ID Circuit Information Candela Panel Name: HPFF8-1 Circuit Name: HS -6 Starting Voltage: Starting Voltage = 20.4 Prepared By: Nelson Fire Systems 1481 S. Major Street Salt Lake City, 84115 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (ft) torn/Strobe 15 0.068 Non -temporal, Low 130 130 18.919 18.050 16.658 '2W lorn/Strobe 177 0.291 Non -temporal, Low 20 150 18.925 18.059 16.672 '2WH torn/Strobe 177 0.291 Non -temporal, Low 20 170 18.954 18.105 16.745 '2WH corn/Strobe 177 0.291 Non -temporal, Low 20 190 19.006 18.187 16.877 '2WH corn/Strobe 15 0.068 Non -temporal, Low 20 210 19.082 18.308 17.068 '2W corn/Strobe 15 0.068 Non -temporal, Low 20 230 19.163 18.436 17.273 12W corn/Strobe 15 0.068 Non -temporal, Low 20 250 19.249 18.574 17.492 '2W Total current/amps 1.145 Total DIst:250 voltage drop 1.481 2.350 3.742 2/27/2014 1 SYSTEM SENSOR' c"Tinced ideasodvonced sdutbn& Circuit Information Candela Panel Name: HPFF8-2 Circuit Name: HS -5 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 1s (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 125 125 19.050 18.257 16.988 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 145 19.055 18.266 17.002 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 165 19.066 18.283 17.029 P2W Horn/Strobe 177 0.291 Non -temporal, Low 20 185 19.083 18.309 17.071 P2WH Horn/Strobe 177 0.291 Non -temporal, Low 20 205 19.123 18.373 17.171 P2WH Horn/Strobe 177 0.291 Non -temporal, Low 20 225 19.186 18.473 17.331 P2WH Horn/Strobe 15 0.068 Non -temporal, Low 20 245 19.272 18.610 17.550 " Pew Total current/amps 1.145 Total Dist:245 voltage drop 1.350 2.143 3.412 2/27/2014 2 t� SYSTEM L4 SENSOR' fArv:ed iciest. cxiva)ced sdutkxw Circuit Information Panel Name: HPFF8-3 Circuit Name: HS -4 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply rype and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 -18 (Amps) last device source (ft) xn/Strobe 15 0.068 Non -temporal, Low 180 180 19.470 18.924 18.050 16.662 W )rn/Strobe 15 0.068 Non -temporal, Low 20 200 19.475 18.933 18.063 16.684 PW xn/Strobe 177 0.291 Non -temporal, Low 20 220 19.486 18.950 18.091 16.727 WH )m/Strobe 177 0.291 Non -temporal, Low 20 240 19.521 19.005 18.178 16.865 ?WH 3rn/Strobe 15 0.068 Non -temporal, Low 20 260 19.578 19.096 18.324 17.098 )W total current/amps 0.786 Total Dist: 260 voltage drop -0.930 1.476 2.350 3.738 './27/2014 �4 e advanced ideas. advanced solutions, Circuit Information �- -- - - Panel Name: HPFF8-4 (1.5) amp circuit Circuit Name: HS -1 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20A------- - - - DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device 220 source (it) Horn/Strobe 15 0.068 Non -temporal, Low 220 20.078 19.890 19.587 19.107 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 240 20.084 19.898 19.601 19.129 P2W Horn/Strobe 75 0.156 Non -temporal, Low 20 260 20.095 19.916 19.629 19.173 P2W Total current/amps 0.292 Total Dist:260 voltage drop 0.322 0.510 0.813 1.293 2/27/2014 4 Circuit Information Candela Panel Name: HPFF8-4 Circuit Name: HS -2 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela CurrentTone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (ft) m/Strobe 15 0.068 Non -temporal, Low 215 215 19.667 19.237 18.548 17.455 W Irn/Strobe 15 0.068 Non -temporal, Low 75 290 19.688 19.270 18.600 17.537 IW IW/Strobe 15 0.068 Non -temporal, Low 75 365 19.729 19.335 18.704 17.702 W xn/Strobe 15 0.068 Non -temporal, Low 45 410 19.766 19.393 18.797 17.851 .W xn/Strobe 15 0.068 Non -temporal, Low 30 440 19.799 19.446 18.880 17.982 WW Total current/amps 0.340 Total DIst:440 voltage drop 0.733 1.163 1.852 2.945 /27/2014 5 SYSTEM SENSOR' advar ced idem Ddw,ced solution Circuit Information Candela Panel Name: HPFF8-4 Circuit Name: HS -3 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and model Candela Current Tone and Volume Dist from Dist from 12 14 1618 (Amps) -- - - last device -- source (ft) - - Horn/Strobe 15 0.068 Non -temporal, Low 25 25 20.168 20.031 19.813 19.466 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 45 20.173 20.040 19.827 19.488 P2W Horn/Strobe 15 0.068 Non -temporal, Low 50 95 20.200 20.083 19.896 19.598 P2W Horn/Strobe 15 0.068 Non -temporal, Low 50 145 20.241 20.148 19.999 19.763 P2W Total current/amps 0.272 Total Dist: 145 voltage drop 0.232 0.369 0.587 0.934 2/27/2014 6 Circuit Information Panel Name: HPFF8-5 Circuit Name: HS -7 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (R) rn/Strobe 15 0.068 Non -temporal, Low 220 220 19.661 19.226 18.531 17.428 W ern/Strobe 15 0.068 Non -temporal, Low 75 295 19.681 19.259 18.583 17.510 W ern/Strobe 15 0.068 Non -temporal, Low 75 370 19.722 19.324 18.687 17.675 W irn/Strobe 15 0.068 Non -temporal, Low 45 415 19.759 19.383 18.780 17.823 W irn/Strobe 15 0.068 Non -temporal, Low 30 445 19.792 19.435 18.863 17.955 W "otal current/amps 0.340 Total Dist:445 voltage drop 0.739 1.174 1.869 2.972 127/2014 �� SYSTEM D4O SENSOR` (YM orxed idecutxlvanced solutis Circuit Information Candela Panel Name: HPFF8-5 Circuit Name: HS -8 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 1416 18 (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 35 35 19.549 19.049 18.248 16.978 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 95 19.565 19.075 18.290 17.044 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 155 19.598 19.127 18.373 17.175 P2W Horn/Strobe 15 0.068 Non -temporal, Low 25 180 19.618 19.159 18.424 17.258 P2W Horn/Strobe 30 0.096 Non -temporal, Low 20 200 19.640 19.194 18.480 17.346 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 220 19.670 19.241 18.555 17.465 P2W 75 0.156 Non -temporal, Low 50 270 19.757 19.380 18776 17817 E amps 0.592 Total Dist:270 voltage drop 0.851 1.351 2.152 3.422 2/27/2014 8 :ircuit Information Panel Name: HPFF8-5 (1.5) amp circuit Circuit Name: HS -9 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply rpe and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device soume(R) rn/Strobe 15 0.068 Non -temporal, Low 230 230 19.647 19.205 18.497 17.373 N rn/Strobe 15 0.068 Non -temporal, Low 75 305 19.667 19.237 18.548 17.455 N m/Strobe 15 0.068 Non -temporal, Low 75 380 19.708 19.302 18.652 17.620 W rn/Strobe 15 0.068 Non -temporal, Low 45 425 19.745 19.361 18.745 17.768 W rn/Strobe 15 0.068 Non -temporal, Low 30 455 19.778 19.413 18.828 17.900 W otal current/amps 0.340 Total Dist:455 voltage drop 0.753 1.195 1.903 3.027 27/2014 SYSTEM SENSOR' cslvcry..ed ki'°.ra. rxivnr>ced sdurarur. Circuit Information ----------- Panel Name: HPFF8-5 Circuit Name: HS -10 Starting Voltage: Startinq Voltaqe = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current -Tone and volume -Dist from _...Dist from 12 - - 14 - 16 is (Amps) last device source (ft) Horn/Strobe 15 0.068 Non -temporal, Low 45 45 19.837 19.506 18.976 18.135 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 105 19.853 19.532 19.017 18.201 P2W Horn/Strobe 15 0.066 Non -temporal, Low 60 165 19.886 19.584 19.100 18.333 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 185 19.902 19.610 19.142 18.399 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 205 19.924 19.645 19.197 18.487 P2W Horn/Strobe 75 0.156 Non -temporal, Low 20 225 19.951 19.688 19.266 18.597 P2W Total current/amps 0.496 Total Dist:225 voltage drop 0.563 0.894 1.424 2.265 2/27/2014 10 SYSTEM SENSOR° fvanoed Ideas advanced sa'u bm Circuit Information Candela Panel Name: HPFF8-6 Circuit Name: HS -11 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Vpe and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 1s_ (Amps) last device source (A) rn/Strobe 15 0.068 Non -temporal, Low 240 240 19.633 19.183 18.462 17.318 W m/Strobe 15 0.068 Non -temporal, Low 75 315 19.654 19.216 18.514 17.400 W on/Strobe 15 0.068 Non -temporal, Low 75 390 19.695 19.281 18.618 17.565 W rn/Strobe 15 0.068 Non -temporal, Low 45 435 19.732 19.339 18.711 17.713 W rn/Strobe 15 0.068 Non -temporal, Low 30 465 19.764 19.391 18.794 17.845 W dotal current/amps 0.340 Total DIst:465 voltage drop 0.767 1.217 1.938 3.082 27/2014 11 'Z45 SYSTEM �4 SENSOR' advonced idem cidvanced solulions:. Circuit Information Candela Panel Name: HPFF8-6 Circuit Name: HS -12 Starting Voltage: Starting Voltage = 20.4 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (ft) Horn/Strobe _ _. _.. .. 15. 0.068. Non -temporal. Low _ 55 55 20.207 20.094 19.913 19.625 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 115 20.224 20.120 19.954 19.691 P2W Horn/Strobe 15 0.068 Non -temporal, Low 60 175 20.256 20.172 20.037 19.823 P2W - Total current/amps 0.204 Total Dist: 175 voltage drop 0.193 0.306 0.487 0.775 2/27/2014 12 SYSTEM �� SENSOR` dvonced ideas advanced solutions, Db Name: Student Housing Building C BYU-Idaho Rexburg, ID Circuit Information Candela Panel Name: HPFF8-9 Circuit Name: HS -13 Starting Voltage: Starting Voltage = 20.4 Prepared By: Nelson Fire Systems 1481 S Major Street Salt Lake City, 84115 (1.5) amp circuit Class A @ 14 AWG DC 24 - volt Supply ype and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 18 (Amps) last device source (R) ern/Strobe 15 0.068 Non -temporal, Low 100 100 19.057 18.269 17.007 R rn/Strobe 177 0.291 Non -temporal, Low 20 120 19.063 18.278 17.021 2H rn/Strobe 177 0.291 Non -temporal, Low 20 140 19.092 18.324 17.094 2H �rn/Strobe 177 0.291 Non -temporal, Low 20 160 19.144 18.407 17.226 RH m/Strobe 15 0.068 Non -temporal, Low 20 180 19.220 18.527 17.417 R irn/Strobe 15 0.068 Non -temporal, Low 20 200 19.301 18.655 17.622 R irn/Strobe 15 0.068 Non -temporal, Low 20 220 19.387 18.793 17.841 16.329 R 'otal current/amps 1.145 Total Dist:220 I voltage drop 1.343 2.131 3.393 21/2014 1 Job Name: Student Housing Building C__.� Prepared By: BYU-Idaho Nelson Fire Systems - - - - - ` 1481- S -Major Street - Rexburg, ID - -. Salt Lake -City, -84135 Circuit Information Panel Name: HPFF8-30 (1.5) amp circuit Circuit Name: HS -14 Class A @ 14 AWG Starting Voltage: Starting Voltage = 20.4 DC 24 - volt Supply Type and Model Candela Current Tone and Volume Dist from Dist from 12 14 16 3S (Amps) last device source (n) Horn/Strobe 15 0.068 Non -temporal, Low 150 150 18.935 18.075 16.697 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 170 18.940 18.083 16.711 P2W Horn/Strobe 15 0.068 Non -temporal, Low 20 190 18.951 18.101 16.738 P2W Horn/Strobe 177 0.291 Non -temporal, Low 20 210 18.968 18.127 16.780 P2WH Horn/Strobe 177 0.291 Non -temporal, Low 20 230 19.007 18.190 16.880 P2WH Horn/Strobe 177 0.291 Non -temporal, Low 20 250 19.071 18.290 17.040 P2WH Horn/Strobe 15 0.066 Non -temporal, Low, 20 270 19.157 18.428 17.259 P2W Total current/amps 1.145 Total Dist:270 voltage drop 1.465 2.325 3.703 4/21/2014 1