HomeMy WebLinkAboutINSPECTION SUMMARY - 13-00123 - 611 Johnson - SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 11/21/2019 2:24 pm
Permit Details Permit Number: 13-00123
611 Johnson - SFR
611 Johnson
New Single Family Residence
Permit Issued Date: 07/02/2013
Permit Inspection Statistics
20Total Inspections Completed:
16Total Inspections Passed:
Inspection Pass Rate: 80.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
07/03/2013PassDon AllenRadon-Ground Inspection
All good to cover the radonInspector Comments:
07/08/2013PassTed DyeFooting Inspection
07/08/2013PassTed DyeFoundation Inspection
07/31/2013PassDon AllenPlumbing Underground Inspection
All good to cover to under groundInspector Comments:
08/07/2013PassBret StoddardElectrical Service Inspection
Approved to be energized for permanent power-inspected the electrical service
on the rough-in inspection.
Inspector Comments:
08/07/2013FailBret StoddardElectrical Rough-in
AFCI protection required for all bedroom outlets, master bedroom outlet cannot
be on laundry circuit, laundry power can't leave the laundry room, floor
receptacle required near stairway, bath receptacles must be on dedicated 20A
circuit, romex connector needed for fan in bath(west), call for a re-inspect when
ready, inspected the electrical service on the rough-in inspection.
Inspector Comments:
08/09/2013PassBret StoddardElectrical Rough-in
Approved for cover-unfinished basement-only the one room to the right of the
stairs is finished(west).
Inspector Comments:
08/09/2013FailTed DyeFraming/Structure Inspection
Joist hangers are required on both sides of truss.
Nail plate missing, in corner, for sink drain
Riser height has a difference of 1" @ top tread; 3/8" allowed
Need truss specs & approved drawing on site
Sheeting missed nailing marked in red crayon
Blocking missed in garage
If a fan is planned on in a room, the end of blade to smoke detector is a min of
36"
Inspector Comments:
08/13/2013PassTed DyeFraming/Structure Inspection
08/15/2013PassDon AllenPlumbing Rough-in
good to cover the rough inInspector Comments:
08/19/2013PassTed DyeInsulation Inspection
Page 1 of 2
(Continued)
Permit Details Permit Number: 13-00123
611 Johnson - SFR
611 Johnson
New Single Family Residence
Permit Status of (Open) as of Report Date: 11/21/2019 2:24 pm
Permit
Inspection
Summary
08/21/2013PassTed DyeSheetrock/Drywall Inspection
09/18/2013PassDon AllenHVAC Rough-in
11/05/2013FailBret StoddardElectrical Final Inspection
Bedrooms must have AFCI protection-GFCI is not required for bedrooms and that
is what is installed, garage door openers must have GFCI protection, floor box in
kitchen area for stair rail not done, unfinished basement entirely except west
bedroom by stairs, no A/C unit is installed (30A OCPD), call for a re-inspect when
done.
Inspector Comments:
11/07/2013PassTed DyeSidewalk Inspection
6" plus of compactable fill
be sure and compact
Inspector Comments:
11/13/2013PassBret StoddardElectrical Final Inspection
Approved for a final and C.O.-unfinished basement entirely except the west
bedroom next to the stairs, no A/C unit installed (30A OCPD).
Inspector Comments:
11/15/2013PassDon AllenPlumbing Final Inspection
All good for the c/oiInspector Comments:
11/26/2013FailTed DyeBuilding Final
-trim on access in garage is not fire rated. you can extend up with rock or with a
1x2
-1 smoke, CO detector combo needed up stairs out side of bedroom and down
stairs in mechanical area
-Handrail needed on back stairs measuring between 1-1/4 to 2-1/4 is code.
-Ladder needed in window well of bedroom. 44" is the max from base to top of
window well.
-need screen of another 45 degree fitting on furnace exhaust
Inspector Comments:
12/05/2013PassTed DyeBuilding Final
12/17/2013PassDon AllenHVAC Final Inspection
Page 2 of 2