Permit Details Permit Number: 13-00046
Madison School District
290 N 1ST E
Commercial Electrical Misc.
Permit Issued Date: 03/29/2013
Permit Inspection Statistics
2Total Inspections Completed:
2Total Inspections Passed:
Inspection Pass Rate: 100.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
02/19/2013PassBret StoddardElectrical Service Inspection
Approved to remain energized for permanent power-need to drive two new
ground rods for main service, need to seperate grounding and grounded
conductors in the now sub-panel, gas line for generator cannot be installed below
the main panel in the dedicated electrical space, need to remove the bonding
wire from the meter to ATS-paralleling the grounded conductor, call for a
re-inspect when ready.
Inspector Comments:
03/04/2013PassBret StoddardElectrical Final Inspection
Approved for a final and to close the permit-new service and generator wired in.Inspector Comments: