Loading...
HomeMy WebLinkAboutINSPECTION SUMMARY - 13-00046 - 290 N 1st E - Madison School DistrictPermit Inspection Summary Permit Status of (Expired) as of Report Date: 11/18/2019 12:46 pm Permit Details Permit Number: 13-00046 Madison School District 290 N 1ST E Commercial Electrical Misc. Permit Issued Date: 03/29/2013 Permit Inspection Statistics 2Total Inspections Completed: 2Total Inspections Passed: Inspection Pass Rate: 100.00% Permit Inspection History *Refer to Individual Inspection Report for more Details 02/19/2013PassBret StoddardElectrical Service Inspection Approved to remain energized for permanent power-need to drive two new ground rods for main service, need to seperate grounding and grounded conductors in the now sub-panel, gas line for generator cannot be installed below the main panel in the dedicated electrical space, need to remove the bonding wire from the meter to ATS-paralleling the grounded conductor, call for a re-inspect when ready. Inspector Comments: 03/04/2013PassBret StoddardElectrical Final Inspection Approved for a final and to close the permit-new service and generator wired in.Inspector Comments: