Permit Status of (Open) as of Report Date: 11/13/2019 2:38 pm
Permit Details Permit Number: 13-00097
2296 W 960 S - SFR
2296 W 960 S
New Single Family Residence
Permit Issued Date: 04/10/2013
Permit Inspection Statistics
18Total Inspections Completed:
15Total Inspections Passed:
Inspection Pass Rate: 83.33%
Permit Inspection History *Refer to Individual Inspection Report for more Details
04/11/2013PassTed DyeFooting Inspection
bars of the ground
ufer on east wall
all over laps good
OK to pour
Inspector Comments:
04/11/2013PassTed DyeFoundation Inspection
04/11/2013N/ATed DyeRadon-Ground Inspection
04/19/2013PassBret StoddardElectrical Service Inspection
Approved to be energized for permanent power-no receptacles installed.Inspector Comments:
04/22/2013PassDon AllenPlumbing Underground Inspection
under ground is all good to coverInspector Comments:
05/14/2013FailQuinton OwensHVAC Rough-in
1" min clearance around b-vent at roof sheathing. Finish Kitchen exhaust vent.
Need exhaust fan in bath area of mstr bth (No window)
Inspector Comments:
05/16/2013PassDon AllenPlumbing Rough-in
rough in looks all good can cover the wallsInspector Comments:
05/16/2013PassBret StoddardElectrical Rough-in
Approved for cover.Inspector Comments:
05/16/2013PassQuinton OwensHVAC Rough-in
add power to new exhaust fan.Inspector Comments:
06/26/2013PassBret StoddardElectrical Final Inspection
Approved for a final and C.O.-no A/C unit installed(30A OCPD).Inspector Comments:
07/01/2013PassQuinton OwensHVAC Final Inspection
07/01/2013PassQuinton OwensBuilding Final
Page 1 of 2
(Continued)
Permit Details Permit Number: 13-00097
2296 W 960 S - SFR
2296 W 960 S
New Single Family Residence
Permit Status of (Open) as of Report Date: 11/13/2019 2:38 pm
Permit
Inspection
Summary
07/18/2013FailTed DyeFraming/Structure Inspection
Sheeting: Staple patterns look good
braced wall panels done correctly
Framing: J-1 truss hangers are missing diaganol nailing
A-3, A-2, A-5G and A5G are missing bracing
Call when electrition is done
Inspector Comments:
07/18/2013PassTed DyeFraming/Structure Inspection
All corrections madeInspector Comments:
07/18/2013PassTed DyeInsulation Inspection
insulation installation looks good
OK to cover
Inspector Comments:
07/19/2013PassTed DyeSheetrock/Drywall Inspection
5/8" Fire Code in garage both wall and ceiling
5/8" Fire code also on 2nd floor ceiling
Nail patterns look good
OK to TAPE
Inspector Comments:
09/24/2013PassDon AllenPlumbing Final Inspection
10/07/2013PassTed DyeSidewalk Inspection
6 inches +Inspector Comments: