Building Review on 10/28/2019:
Permit Number: 19-00599Permit Details
Commercial - Remodel
Permit Issued Date:
Final Inspections Required
Plumbing Final Inspection Commercial Electrical Final Inspection
HVAC Final Inspection Commercial Building Final
72 S 1st E
72 S 1st E - Grand Peaks Medical - Remodel
Inspection Details
quinton.owens@rexburg.org
Inspected By: Quinton Owens
Building Review on 10/28/2019:
D ESCRIPTIO N CO M M EN TS STATUS
Checked for linked cases Found electrical, plumbing, and mechanical
permits for existing Grand Peaks building, but
no building permit was pulled as required by
code.
YES
Occupant load is identified on plans as per IBC
Section 1004
Identify Occupant load REVISIONS
Special Inspection Contractor is identified (IBC
1704.2.1)
Who will be performing the required special
inspections?
REVISIONS
504 - Allowable height (Feet/Stories)
506 - Allowable area
* Identify allowed area increases beyond the
allowed 9,000 sf. (V-B construction, B
occupancy, non-sprinklered)
* Identify Fire walls and rating if applicable.
REVISIONS
Exterior wall openings meet the requirements of
IBC Section 705.8
* No openings are allowed with less than 3 feet
from property line - West wall cannot have any
openings as shown.
* A restrictive lot agreement tying the three lots
together has been submitted to Tawnya Grover.
This will allow the vestibule and windows on the
south adjacent to parking and connection
between the two buildings.
REVISIONS
Parapets meet the requirements of IBC Section
705.11
Pending revisions regarding any fire walls
(check requirements of this section where it
applies)
REVISIONS
Fire walls meet the requirements of IBC Section
706
Pending revisions identifying allowed building
area and separation to adjacent building as
required
REVISIONS
Penetrations comply with IBC Section 714 for
rated assemblies
Fire rating shall be maintained at all
penetrations in fire rated walls.
APPROVED
Concealed spaces are fireblocked/draftstopped
per Section 718
Fire blocking per IBC 718 will be approved
based on inspection.
APPROVED
Use classification is identified as per IBC Section
302
B occupancy APPROVED
Toilets, Bathing Facilities, Sinks, Kitchens and
Drinking Fountains meet the requirements of IBC
Section 1109
Be sure the drinking fountain closer to the
Waiting area is the accessible fountain.
APPROVED
Page 1 of 2
(Continued)
Permit Number: 19-00599
D ESCRIPTIO N CO MMEN TS STATUS
Service Facilities comply with IBC 1109.12 For accessible requirements, a portion of
service counter shall be provided not more than
36" above floor (36" minimum in length for
parallel wheelchair approach)
* Portion of service desk in corridor may be
used to meet this requirement.
APPROVED
Page 2 of 2