HomeMy WebLinkAboutPLANS REDLINED REVISIONS - 19-00590 - Fullmer - Medical Office BuildingReview
Report
Current Building Review Status: REVISIONS
Application Number: 19-00590Permit Details
Application Received Date: 09/27/2019
New Commercial Building
Application Approved Date:
Application Approved Status: ACCEPTED
09/27/2019
RPR6N39E246501
Fullmer - RPR6N39E246501 - Medical Office Building
Status of Plan Reviews Completed
10/01/2019Electrical Review COMPLETED
10/02/2019Fire Department Review - Site Plan COMPLETED
10/09/2019Public Works Review - Site Plan COMPLETED
10/11/2019HVAC Review COMPLETED
10/11/2019Plumbing Review COMPLETED
10/11/2019Planning and Zoning Review - Site Plan REVISIONS
10/15/2019Building Review REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Fire Alarm Review
Fire Sprinkler Review
Planning and Zoning Review - Site Plan
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Incidental use meets the requirements of Table
509
REVISIONSAmbulatory care facilities require 1 hour
separation for the following incidental uses:
* Laboratories not classified as group H (N/A -
no labs included in this building)
* Waste and linen rooms with containers having
an aggregate volume of 10 cubic feet or
greater.
* Storage rooms greater than 100 sf.
*Revisions Response :
Fire resistance rating of building elements meet
Sect. 704 & Table 601
REVISIONSAs per V-A construction, structural elements are
to have fire rated protection per Table 601.
* Fire rated protection is not identified on plans
details.
*Revisions Response :
Handrails and Guards meet the requirements of
IBC Sections 1014 and 1015
REVISIONSNo drawings or details included for handrails.
*Revisions Response :
Reviewed By: Quinton Owens
Review Date: 10/15/2019
Plan Review Details
quinton.owens@rexburg.org
Building Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitute approval of variance from code
Building Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Building complies with IECC (IBC 1301)REVISIONS* Plans do not show all R-values for thermal
barrier compliance.
* Is basement and/or crawl space conditioned?
Building section shows floor insulation with no
foundation insulation and no ventilation vents in
foundation, and all ducts in crawl space are
required to be insulated if the space is
unconditioned.
*Revisions Response :
Glass and Glazing meets the requirements of IBC
Chapter 24
REVISIONSWindow type A is not identified as tempered per
2406.4.3. Is there an exception for these
windows or was it just overlooked?
*Revisions Response :
Stairways meet the requirements of IBC Section
1011 & 1019
REVISIONSNo drawings or details included for interior
stairs.
*Revisions Response :
Type of construction is identified.Type VA construction is identified on plans.COMPLETED
Penetrations comply with IBC Section 714 for
rated assemblies
Maintain fire rated protection at all penetrations
in protected assemblies.
COMPLETED
Automatic sprinklers are provided or exempted as
per IBC Section 903.2
Sprinkler system not required, but a fire alarm
system is required per 907.2.2 (see IBC 422.5)
COMPLETED
Occupant load is identified on plans as per IBC
Section 1004
Occupant loads are not identified on plans as
required.
* Default occupant load for entire building will
be 97 based on B occupancy
COMPLETED
Toilets, Bathing Fac., Sinks, Kit. and Drink. Fount.
meet IBC Sec. 1109
Toilet rooms accessed only through a private
office do not require grab bars, but shall have
backing installed for potential installation of
grab bars (A117.1, 604.5)
COMPLETED
Page 2 of 2
Approval of plans does not constitute approval of variance from code