HomeMy WebLinkAboutFIRE ALARM REPORT - 19-00602 - Madison Middle School - Fire Alarm PanelForm Completion Date: 10-15-19 Supplemental Pages Attached:
1. PROPERTY INFORMATION
Name of property: Madison Middle School
2.
3
9
Address: 575 W 7th S, Rexburg ID 83440
Description of property: Middle School
Name of property representative: Madison School District (Reed Ellis)
Address: 60 W Main St, Rexburg ID 83440
Phone: 208-359-3300 Fax: E-mail:
INSTALLATION, SERVICE, TESTING, AND MONITORING INFORMATION
Installation contractor: Fire Services of Idaho
Address: 610 Mallard St Chubbuck Id, 83202
Phone: 208-232-3640 Fax:
Service organization: Fire Services of Idaho
Address: 610 Mallard St Chubbuck Id, 83202
Phone: 208-232-3640 Fax:
Testing organization: Fire Services of Idaho
Address: 610 Mallard St Chubbuck Id, 83202
Phone: 208-232-3640 Fax:
Effective date for test and inspection contract:
Monitoring organization: Avantguard
Address:
Phone: 877-206-9141 Fax:
Account number: AE01-0257 Phone line 1:
Means of transmission: Alarm Contacts
Entity to which alarms are retransmitted: Avantguard
DOCUMENTATION
On-site location of the required record documents and site-specific FACP
software:
DESCRIPTION OF SYSTEM OR SERVICE
This is a: New System Modification to existing system X Permit number:
NFPA 72 edition: 2016
4.1 Control Unit
Manufacturer: Silent Knight
4.2 Software and Firmware
Firmware revision number: 6.0.20
1
208-232-0449 E-mail:
208-232-0449 E-mail:
208-232-0449 E-mail:
Model number: 6820
E-mail:
P]
P]
4.3 Alarm Verification
Number of devices subject to alarm verification:
5. SYSTEM POWER
5.1 Control Unit
5.1.1 Primary Power
Input voltage of control panel:
Overcurrent protection: Type:
Branch circuit disconnecting means location:
This system does not incorporate alarm verification.
Alarm verification set for sec
24 Control panel amps:
Amps:
Number:
5.1.2 Secondary Power
Type of secondary power: Batteries
Location, if remote from the plant: in FACP
Calculated capacity of secondary power to drive the system:24V
In standby mode (hours): 24 In alarm mode (minutes): 5
5.2 Control Unit
This system does not have power extender panels X
Power extender panels are listed on supplementary sheet A
6. CIRCUITS AND PATHWAYS
Pathway Type
Dual Media Pathway
Separate Pathway
Class
Survivability Level
Signaling Line
21
Addressable
B
Device Power
61
Addressable
alarm
photoelectric
Initiating Device
B
Notification Appliance
Other (specify):
7. REMOTE ANNUNCIATORS
Type Location
None
8. INITIATING DEVICES
Type
Quantity
Addressable or
Conventional
Alarm or Supervisory
Sensing Technology
Manual Pull Stations
21
Addressable
alarm
Smoke Detectors
61
Addressable
alarm
photoelectric
2
Duct Smoke Detectors
0
Description
Audible
Hold -Open Door Releasing Devices
Heat Detectors
3
0
Fire/Smoke Dampers
RO R
Gas Detectors
0
Elevator Recall
0
Elevator Shunt Trip
Waterflow Switches
3
Addressable
alarm
paddle
Tamper Switches
3
Addressable
Supervisory
9. NOTIFICATION APPLIANCES
Type
Quantity
Description
Audible
Hold -Open Door Releasing Devices
0
Visible
0
Fire/Smoke Dampers
Combination Audible and Visible
49
0
10. SYSTEM CONTROL FUNCTIONS
Type
Quantity
Hold -Open Door Releasing Devices
0
HVAC Shutdown
0
Fire/Smoke Dampers
0
Door Unlocking
0
Elevator Recall
0
Elevator Shunt Trip
0
11. INTERCONNECTED SYSTEMS
This system does not have interconnected systems. X
Interconnected systems are listed on supplementary sheet
12. CERTIFICATION AND APPROVALS
12.1 System Installation Contractor
This system as specified herein has been installed according to all NFPA standards cited herein.
Signed: Printed name: Dan Sneigoski
Organization: FSI Title: Alarm Technician
Date:
Phone:
12.2 System Operational Test
This system as specified herein has tested according to all NFPA standards cited herein.
Signed: Printed name: Dan Sneigoski Date:
Organization: FSI Title: Alarm Tech Phone:
12.3 Acceptance Test
3
Date and time of acceptance test:
10-15-19
Installing contractor representative: Dan Sneigoski
Testing contractor representative: Dan Sneigoski
Property representative:
AHJ representative:
Reed Ellis