HomeMy WebLinkAboutFIRE SPRINKLER PLAN REVIEW - South Fork Villa 6-Plex South Fork Villa 6-Plex – Sugar City 1 of 1 STATE FIRE MARSHAL STATE OF IDAHO IDAHO DEPARTMENT OF INSURANCE Brad Little 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: March 20, 2019 APPROVED: April 3, 2019 REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer PROJECT: South Fork Villa 6-Plex STREET ADDRESS: 425 S. 3rd W. CITY: Sugar City AHJ: Madison Fire Department SUBMITTAL TYPE: New SYSTEM TYPE: NFPA 13R/Wet HEAD COUNT: TOTAL SYSTEMS: AREA SQUARE FOOTAGE: 97,621 OCCUPANCY CLASSIFICATION: A3 - B CONSTRUCTION TYPE: Tyle II - B SCOPE OF WORK: New two story 6-plex to be fully sprinkled. SPRINKLER CONTRACTOR: Phoenix Fire Protection 4130 Airport Road Nampa, ID 83687 IDAHO LICENSE: FPSC-108 CONTACT NAME: Teri Cruikshank teri@phoenixfp.com PHONE NO: (208) 468-9115 SYSTEM DESIGNED BY: Brook Stewart brook@phoenixfp.com PHONE NO: (208) 468-9115 PLAN REVIEW COMMENTS: Approved with the following comments 1. Working Plans per NFPA 13R, 8.1.7 2. Piping hanging and bracing shall comply with NFPA 13. (NFPA 13R 6.13) 3. Means shall be provided for forward flow test. (NFPA 13R, 6.8.8) 4. At least six spare sprinklers shall be provided. (NFPA 13R 11.1.1) Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyer. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.