HomeMy WebLinkAboutFIRE SPRINKLER PLAN REVIEW - South Fork Villa 6-Plex South Fork Villa 6-Plex – Sugar City 1 of 1
STATE FIRE MARSHAL STATE OF IDAHO
IDAHO DEPARTMENT OF INSURANCE Brad Little
700 W. State Street, 3rd Floor
P.O. Box 83720
Boise, ID 83720-0043
(208) 334-4370 | www.doi.idaho.gov/sfm
PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: March 20, 2019 APPROVED: April 3, 2019
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: South Fork Villa 6-Plex
STREET ADDRESS: 425 S. 3rd W. CITY: Sugar City
AHJ: Madison Fire Department
SUBMITTAL TYPE: New SYSTEM TYPE: NFPA 13R/Wet
HEAD COUNT: TOTAL SYSTEMS: AREA SQUARE FOOTAGE: 97,621
OCCUPANCY CLASSIFICATION: A3 - B CONSTRUCTION TYPE: Tyle II - B
SCOPE OF WORK: New two story 6-plex to be fully sprinkled.
SPRINKLER CONTRACTOR: Phoenix Fire Protection
4130 Airport Road
Nampa, ID 83687
IDAHO LICENSE: FPSC-108
CONTACT NAME: Teri Cruikshank
teri@phoenixfp.com
PHONE NO: (208) 468-9115
SYSTEM DESIGNED BY: Brook Stewart
brook@phoenixfp.com
PHONE NO: (208) 468-9115
PLAN REVIEW COMMENTS:
Approved with the following comments
1. Working Plans per NFPA 13R, 8.1.7
2. Piping hanging and bracing shall comply with NFPA 13. (NFPA 13R 6.13)
3. Means shall be provided for forward flow test. (NFPA 13R, 6.8.8)
4. At least six spare sprinklers shall be provided. (NFPA 13R 11.1.1)
Approval of shop drawings is not intended to imply waiver or modification of any
requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA
Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local
water purveyer. The State Fire Marshal’s Office and its personnel does not take any
responsibility for the back flow device.