HomeMy WebLinkAboutPLANS STRUCTURAL - 19-00354 - BYUI Hart Building - RemodelSTRUCTURAL GENERAL NOTES BASIS OF DESIGN 1.GOVERNING BUILDING CODE...............................................2015 IBC 2.OCCUPANCY CATEGORY.......................................................III 3.LOAD COMBINATIONS: ASD -GRAVITY AND LATERAL.......................................1605.3.1 4.GRAVITY DESIGN: DEAD LOAD ROOF................................................................................25 PSF ROOF LIVE LOAD (NOT CONCURRENT WITH ROOF SNOW LOAD).........20 PSF ROOF SNOW LOAD GROUND SNOW LOAD...................................................53 PSF FLAT ROOF SNOW LOAD...............................................40 PSF Is........................................................................................1.00 Ce......................................................................................1.00 Ct.......................................................................................1.00 DRIFTING PER ASCE 7 5.LATERAL DESIGN: WIND DESIGN PER ASCE 7-10 ULTIMATE DESIGN WIND SPEED................................120 MPH EXPOSURE.......................................................................B TOPOGRAPHIC FACTOR...............................................1.00 IMPORTANCE FACTOR....................................................1.00 SEISMIC DESIGN SEISMIC DESIGN PROCEDURE.....................................EQUIVALENT Ss CHART VALUE............................................................0.47 g S1 CHART VALUE............................................................0.16 g SITE COEFFICIENT FA....................................................1.00 SITE COEFFICIENT FV....................................................1.00 SDS...................................................................................0.32 g SD1...................................................................................0.11 g SITE CLASS.....................................................................B SEISMIC DESIGN CATEGORY.......................................C IMPORTANCE FACTOR Ie...............................................1.25 REDUNDANCY FACTOR..................................................1.00 PORTION OF SNOW LOAD INCLUDED..........................20% BUILDING PERIOD T........................................................0.03 SEC. LATERAL FORCE RESISTING SYSTEM.........................MASONRY SHEAR WALL AND STEEL NOT SEISMICALLY DETAILED R........................................................................................3 OMEGA.............................................................................3 Cd......................................................................................3 Cs.......................................................................................0.06 g GENERAL 1.THE GENERAL CONTRACTOR SHALL: A.BECOME FAMILIAR WITH ALL PORTIONS OF THE CONTRACT DOCUMENTS AND INSURE THAT ALL SUBCONTRACTORS ARE FAMILIAR WITH THOSE PORTIONS PERTAINING TO THEIR AREA OF WORK. NO DEVIATIONS WILL BE ALLOWED UNLESS AGREED UPON BY ALL PARTIES IN WRITING PRIOR TO CONSTRUCTION FABRICATION. B.VERIFY ALL DIMENSIONS AND ELEVATIONS. COORDINATE ALL DOORS, WINDOWS, NON- BEARING INTERIOR AND EXTERIOR WALLS, ELEVATIONS, SLOPES, STAIRS, CURBS, DRAINS, RECESSES, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES, CHAMFERS, KERFS, ETC. C.FIELD VERIFY ALL SITE CONDITIONS AND IMMEDIATELY NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER REGARDING ACTUAL CONDITIONS AT THE SITE WHICH ARE NOT PER THE DRAWINGS. D.COORDINATE ALL WORK BETWEEN THE VARIOUS TRADES AND SUBCONTRACTORS. REPORT ANY MODIFICATIONS TO THE STRUCTURAL PORTION OF THE BUILDING BY OTHER TRADES TO THE ARCHITECT AND STRUCTURAL ENGINEER. E.BE RESPONSIBLE FOR SAFETY AND PROTECTION IN AND AROUND THE JOB SITE AND/OR ADJACENT PROPERTIES. F.REPORT PROGRESS OF WORK TO ARCHITECT AND STRUCTURAL ENGINEER. G.COORDINATE AND VERIFY LOCATIONS AND WEIGHTS OF MECHANICAL UNITS AND/OR OTHER EQUIPMENT OR DEVICES PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY SUPPORTING STRUCTURE. SUCH LOADS SHALL BE REPORTED TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW. ADDITIONAL FRAMING MAY BE REQUIRED FOR THE PROPER SUPPORT OF SUCH UNITS AND/OR EQUIPMENT. LATERAL SUPPORT FOR THE EQUIPMENT SHALL BE PROVIDED BY EQUIPMENT INSTALLER. H.COORDINATE AND VERIFY ROOF, FLOOR, AND WALL OPENINGS REQUIRED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND/OR OTHER DRAWINGS PRIOR TO CONSTRUCTION. REPORT OPENINGS REQUIRED WHICH ARE NOT SPECIFICALLY SHOWN ON THE STRUCTURAL DRAWINGS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW. I.COORDINATE ANY CONSTRUCTION SITUATION NOT COVERED BY THESE PLANS, GENERAL NOTES, OR SPECIFICATIONS WITH THE ARCHITECT AND STRUCTURAL ENGINEER. 2.CONTRACT DOCUMENTS: A.REFER TO THE SPECIFICATIONS FOR INFORMATION NOT COVERED BY THESE GENERAL NOTES OR THE DRAWINGS. B.DETAILS, SECTIONS AND NOTES SHOWN ON THE STRUCTURAL DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO ALL SIMILAR SITUATIONS ELSEWHERE, UNLESS NOTED OR SHOWN OTHERWISE. C.THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS SPECIFICALLY NOTED OTHERWISE. D.INFORMATION ON DRAWINGS INDICATING EXISTING CONDITIONS IS BASED ON BEST PRESENT KNOWLEDGE, BUT MAY NOT BE ENTIRELY ACCURATE AND MUST BE FIELD VERIFIED. 3.BUILDING CODE COMPLIANCE: A.INSPECTION, TESTING, CONSTRUCTION, WORKMANSHIP AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF THE GOVERNING BUILDING CODE AND STANDARDS. ASTM, IBC, AND OTHER DESIGNATIONS SHALL BE AS AMENDED TO LATEST DATE UNLESS NOTED OTHERWISE. 4.CONSTRUCTION SEQUENCE, SHORING, AND BRACING REQUIREMENTS: A.THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE METHOD, MEANS, AND SEQUENCE OF ALL STRUCTURAL ERECTION EXCEPT WHEN SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING TO PROVIDE ADEQUATE VERTICAL AND LATERAL SUPPORT DURING ERECTION. THIS SHORING AND BRACING SHALL REMAIN IN PLACE UNTIL ALL PERMANENT MEMBERS ARE PLACED AND ALL FINAL CONNECTIONS ARE COMPLETED, INCLUDING ALL ROOF ATTACHMENTS. B.SHORING AND SUPPORTING FORM WORK FOR SUSPENDED CONCRETE OR MASONRY MATERIAL SHALL REMAIN IN PLACE AND SHALL NOT BE REMOVED UNTIL THE STRUCTURAL MEMBERS HAVE ACQUIRED SUFFICIENT STRENGTH TO SAFELY SUPPORT THEIR OWN WEIGHT AND ANY ADDITIONAL CONSTRUCTION, STORAGE, AND/OR OTHER LOADS TO WHICH THE MAY BE SUBJECTED. IN NO CASE SHALL THEY BE REMOVED PRIOR TO 7 DAYS. RE-SHORING SHALL BE IMMEDIATELY INSTALLED UPON REMOVAL OF SUCH FORMS AND SHALL REMAIN IN PLACE UNTIL 28 DAYS AFTER PLACING OF MATERIAL OR UNTIL MATERIAL HAS REACHED ITS 28 DAY DESIGN STRENGTH, WHICHEVER IS LONGER. DO NOT REMOVE LARGE AREAS OF SHORING BEFORE STARTING RE-SHORING PROCEDURES. C.NON-BEARING INTERIOR WALLS SHALL BE ADEQUATELY BRACED TO THE STRUCTURE ABOVE WITH ALLOWANCE FOR DEFLECTION OF THE STRUCTURE ABOVE AND/OR BELOW. 5.OMISSIONS AND/OR CONFLICTS: A.OMISSIONS IN AND/OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER AND SHALL BE RESOLVED BEFORE PROCEEDING WITH ANY WORK INVOLVED. B.IN CASE OF CONFLICTS IN THE STRUCTURAL WORK, THE MOST STRINGENT REQUIREMENTS, AS DIRECTED BY THE ARCHITECT AND STRUCTURAL ENGINEER, SHALL BE IMPLEMENTED AT NO ADDITIONAL COST TO THE OWNER. 6.MISCELLANEOUS: A.DURING AND AFTER CONSTRUCTION, THE CONTRACTOR AND/OR OWNER SHALL KEEP THE LOADS ON THE STRUCTURE WITHIN THE LIMITS OF THE DESIGN. B.OBSERVATION VISITS TO THE SITE BY REPRESENTATIVES OF THE ARCHITECT AND/OR STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS INSPECTION NOR APPROVAL OF CONSTRUCTION. C.STAIRS ARE TO BE AS PER THE ARCHITECTURAL DRAWINGS. D.ALL WORK SHALL BE DONE IN ACCORDANCE WITH OSHA REQUIREMENTS. ANY CONFLICTS BETWEEN THESE DOCUMENTS AND OSHA REQUIREMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER BEFORE PROCEEDING WITH WORK. 7.DEFERRED SUBMITTALS: A.THE FOLLOWING ITEMS REQUIRING DEFERRED SUBMITTALS ARE LISTED BELOW. THESE ITEMS SHALL BE DESIGNED AND FABRICATED BY THE MANUFACTURER ACCORDING TO THE SPECIFICATIONS GIVEN IN THE CONTRACT DOCUMENTS. OPEN WEB STEEL ROOF JOISTS AND GIRDERS LIGHT GAGE METAL FRAMING B.THESE DEFERRED SUBMITTALS SHALL FIRST BE SUBMITTED TO THE PROJECT ARCHITECT AND/OR ENGINEER FOR REVIEW AND COORDINATION. UPON THE COMPLETION OF THE ARCHITECT/ENGINEER REVIEW, THE ARCHITECT/ENGINEER WILL SUBMIT THE DEFERRED SUBMITTALS TO THE BUILDING OFFICIAL FOR REVIEW AND APPROVAL. THE SUBMITTAL TO THE BUILDING OFFICIAL SHALL INCLUDE A LETTER STATING THAT THE ARCHITECT/ENGINEER REVIEW HAS BEEN PERFORMED AND THAT THE PLANS AND THE CALCULATIONS FOR THE DEFERRED SUBMITTAL ITEMS ARE FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN DRAWINGS WITH NO EXCEPTIONS. C.THE FINAL SUBMITTAL SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE IN WHICH CONSTRUCTION WILL OCCUR AND SHALL BE AVAILABLE AT THE JOBSITE THROUGHOUT CONSTRUCTION. D.CONSTRUCTION RELATED TO DEFERRED SUBMITTALS SHALL NOT COMMENCE UNTIL THE BUILDING OFFICIAL HAS APPROVED THE SUBMITTAL. CONCRETE 1.CODES AND STANDARDS: A.CONCRETE CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL COMPLY WITH THE AMERICAN CONCRETE INSTITUTE (ACI) EDITIONS OF: I.ACI 301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS". II.ACI 318, "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", EXCEPT AS MODIFIED BY THE IBC. III.ACI 347, "RECOMMENDED PRACTICE FOR CONCRETE FORM WORK". 2.MATERIALS: A.CEMENT SHALL CONFORM TO ASTM C150, PORTLAND CEMENT. I.USE TYPE I OR II FOR EXPOSURE CLASS S0 II.USE TYPE I OR V FOR EXPOSURE CLASS S1 III.USE TYPE V FOR EXPOSURE CLASS S2 AND S3 B.HARD ROCK AGGREGATES SHALL CONFORM TO ASTM C33. LIGHTWEIGHT AGGREGATES SHALL CONFORM TO ASTM C330. VERIFY NO ALKALI SILICA REACTIVITY (ASR). C.WATER SHALL BE POTABLE. D.AIR ENTRAINMENT SHALL CONFORM TO ASTM C260. I.LIMIT AIR CONTENT TO 3% AT TROWEL FINISHED FLOOR SLABS OR FINISH PER ACI302.1R-96 "GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION" WHERE AIR CONTENT IS >3%. E.FLY ASH, CLASS F POZZOLAN SHALL CONFORM TO ASTM C618. F.CALCIUM CHLORIDE SHALL NOT BE USED. G.DEFORMED BAR ANCHORS (DBA) SHALL CONFORM TO ASTM A496. H.HEADED ANCHOR STUDS (HAS) SHALL CONFORM TO ASTM A108. I.SILICA FUME (2% TO SUSPENDED PARKING SLABS) SHALL CONFORM TO ASTM C1240 3.MIX DESIGNS: A.ONLY ONE TYPE OF CONCRETE SHALL BE PLACED AT THE SITE AT ANY GIVEN TIME. B.LIMIT SLUMP TO 4" MAXIMUM PRIOR TO THE ADDITION OF PLASTICIZERS AND WATER REDUCING ADD MIXTURES. CONCRETE SUPPLIER SHALL INDICATE FINAL SLUMP OF EACH CONCRETE MIX DESIGN. C.CONCRETE MIXES SHALL CONFORM TO THE FOLLOWING: D. LIMIT FLY ASH TO 25% OF THE TOTAL CEMENTITIOUS MATERIAL. E. PEA GRAVEL AGGREGATE AND/OR PLASTICIZER MAY BE USED IN CONGESTED AREAS WHEN REQUIRED TO PROPERLY FILL ALL VOIDS AND/OR FOR WORKABILITY. (CONTRACTORS OPTION). 4.CONSTRUCTION: A. CONCRETE SHALL BE PROPERLY VIBRATED DURING PLACEMENT. B. PRIOR TO PLACING CONCRETE, CHECK WITH ALL TRADES TO INSURE PROPER PLACEMENT OF OPENINGS, BLOCK OUTS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS, EMBEDS, DOWELS, ETC. ANCHOR BOLTS AND DOWELS SHALL BE PLACED PRIOR TO CASTING CONCRETE. C. CONSTRUCTION JOINTS AND BULKHEADS SHALL BE FORMED WITH A KEY WAY. ALL CONTACT SURFACES, NEW OR EXISTING, AT CONSTRUCTION JOINTS SHALL BE INTENTIONALLY ROUGHENED TO A 1/4" AMPLITUDE PRIOR TO CASTING ADJACENT POUR. D. GROUT SOLID AROUND ALL JOIST AND BEAM ENDS, TYPICAL UNLESS NOTED OTHERWISE. E. OPENINGS IN FLOORS AND/OR WALLS SHALL HAVE ADDITIONAL REINFORCING AROUND ALL SIDES OF THE OPENING EQUIVALENT TO THE BARS CUT BY THE OPENING WITH HALF ON EACH SIDE OF THE OPENING OR 2-#5 BARS, WHICHEVER IS GREATER, UNLESS NOTED OTHERWISE. BARS PARALLEL TO THE PRINCIPAL REINFORCING SHALL RUN FULL LENGTH OF THE SPAN. BARS IN THE OTHER DIRECTION SHALL RUN 24 INCHES BEYOND THE EDGE OF THE OPENING OR END WITH A STANDARD HOOK. ALSO PROVIDE 2-#5 X 4'-0" DIAGONAL BARS AT EACH CORNER OF EACH OPENING. F.NO PENETRATION SHALL BE ALLOWED THROUGH ANY CONCRETE BEAM, JOIST, COLUMN, PIER, OR JAMB WITHOUT THE ARCHITECT?S AND STRUCTURAL ENGINEER'S PRIOR WRITTEN APPROVAL. PENETRATIONS SHALL BE RE-ROUTED AS REQUIRED AT THESE LOCATIONS. G.ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR. FOLLOW MANUFACTURERS RECOMMENDATIONS. 4.FOOTINGS: A.FOOTINGS SHALL BEAR ON PROPERLY PREPARED MATERIAL. SEE THE SITE PREPARATION NOTES. B.FOOTINGS SHALL BE CENTERED BELOW THE WALL AND/OR COLUMN ABOVE, TYPICAL UNLESS NOTED OTHERWISE. C.EXTERIOR FOOTINGS SHALL BEAR BELOW THE EFFECTS OF FROST. D.PROVIDE A 2X4 BEVELED KEY WAY IN ALL CONTINUOUS WALL FOOTINGS. E.STAGGER FOOTING CONSTRUCTION JOINTS FROM WALL CONSTRUCTION JOINTS ABOVE BY AT LEAST 6 FEET. F.REINFORCING IN CONTINUOUS FOOTINGS SHALL BE CONTINUOUS AT CORNERS AND/OR INTERSECTIONS BY PROVIDING PROPER LAP LENGTHS AND/OR CORNER BARS. G.CONTINUOUS FOOTINGS WITHOUT CONCRETE FOUNDATION WALLS ABOVE SHALL BE REINFORCED WITH A MINIMUM OF 2-#6 LONGITUDINAL TOP BARS IN ADDITION TO REINFORCING SPECIFIED IN THE FOOTING SCHEDULE. AT OPENINGS, PROVIDE (1) #6 TOP BAR FOR EACH FOOT OF FOOTING WIDTH OR PORTION THEREOF, EXTEND 24" BEYOND EDGE OF OPENING, EACH SIDE. H.NO PENETRATIONS SHALL BE ALLOWED THROUGH ANY CONCRETE FOOTING. WHEN CONFLICTS ARISE BETWEEN UNDERGROUND PLUMBING, UTILITIES, ETC., THE FOOTING SHALL BE STEPPED DOWN BELOW THE CONFLICT AND A CONCRETE WALL, PIER, COLUMN ETC., SHALL BE EXTENDED TO THE FOOTING AS REQUIRED. I.BEARING SURFACES FOR FOOTINGS WHICH ARE, OR BECOME, UNDERMINED DURING CONSTRUCTION SHALL BE BACKFILLED WITH A LEAN-MIX CONCRETE (2000 PSI MIN.). 5.SLABS ON GRADE: A.INTERIOR SLABS ON GRADE SHALL BE A MINIMUM OF 4 INCHES THICK, SHALL BEAR ON A 4 INCH MINIMUM LAYER OF FREE-DRAINING GRAVEL, AND SHALL BE REINFORCED WITH #4 BARS AT 18" O.C. BOTH WAYS, TYPICAL UNLESS NOTED OTHERWISE. PROVIDE CHAIRS WITH SAND PLATES FOR PROPER PLACEMENT. B.SLABS ON GRADE SHALL BE SUBDIVIDED BY CONSTRUCTION AND/OR CONTRACTION (CONTROL) JOINTS INTO ROUGHLY SQUARES WHOSE SIDES SHALL NOT EXCEED 15 FEET IN EITHER DIRECTION. C.SEE ARCHITECTURAL FOR EXTERIOR SLABS ON GRADE, TYPICAL, UNLESS NOTED OTHERWISE. 6. WALLS: A.CONCRETE WALLS SHALL BE REINFORCED AS FOLLOWS, UNLESS NOTED OTHERWISE: WALL VERTICAL HORIZONTAL THICKNESS REINFORCING REINFORCING 12"#4 @ 12" O.C.,E.F.#4 @ 12" O.C.,E.F. 16"#5 @ 14" O.C.,E.F.#5 @ 14" O.C.,E.F. B.PLACE VERTICAL REINFORCING IN THE CENTER OF THE WALL (EXCEPT FOR BASEMENT WALLS, RETAINING WALLS, OR WHEN EACH FACE IS SPECIFIED). C.VERTICAL REINFORCING SHALL BE DOWELED TO CONCRETE FOOTING OR STRUCTURE BELOW AND TO STRUCTURE ABOVE WITH THE SAME SIZE BAR AND SPACING, TYPICAL, UNLESS NOTED OTHERWISE. D.PROVIDE CORNER BARS AT ALL INTERSECTIONS AND CORNERS. USE SAME SIZE BAR AND SPACING AS THE HORIZONTAL REINFORCING. E.HORIZONTAL REINFORCING SHALL TERMINATE AT THE ENDS OF WALLS AND AT OPENINGS WITH A STANDARD HOOK. F.WHEN TWO CURTAINS OF STEEL ARE REQUIRED, THE SPLICES IN THE HORIZONTAL REINFORCING OF EACH CURTAIN SHALL NOT OCCUR AT THE SAME LOCATION. G.PENETRATIONS THROUGH ANY CONCRETE WALL SHALL BE BUILT INTO THE WALL AS THE WALL IS BEING CONSTRUCTED AND SHALL BE REVIEWED BY THE ARCHITECT AND STRUCTURAL ENGINEER PRIOR TO INSTALLATION. H.PROVIDE DRAINAGE AT THE BASE OF RETAINING WALLS. REINFORCING STEEL 1.CODES AND STANDARDS: A.REINFORCING STEEL SHALL COMPLY WITH: I.CONCRETE REINFORCING STEEL INSTITUTE "MANUAL OF STANDARD PRACTICE". II.AMERICAN CONCRETE INSTITUTE "DETAILING MANUAL", ACI 315 (OR SP-66). 2.MATERIALS: A.REINFORCING STEEL SHALL BE NEW STOCK DEFORMED BARS AND SHALL CONFORM TO ASTM A615, GRADE 60, WITH A DESIGN YIELD STRENGTH OF 60,000 PSI, EXCEPT AS NOTED BELOW. I. DOWELS TO BE BENT IN THE FIELD DURING CONSTRUCTION SHALL BE ASTM A615, GRADE 40 OR ASTM A706, GRADE 60, "LOW-ALLOY STEEL". II. REINFORCING TO BE WELDED SHALL BE ASTM A706, GRADE 60,"LOW-ALLOY STEEL". B.MASONRY JOINT REINFORCING SHALL CONFORM TO ASTM 951 AND SHALL BE MANUFACTURED FROM WIRE WHICH CONFORMS TO ASTM A82. C.MECHANICAL SPLICE COUPLERS SHALL BE CAPABLE OF DEVELOPING 125% OF THE SPECIFIED STRENGTH OF THE BAR. 3.CONSTRUCTION: A.REINFORCING SHALL BE DETAILED, BOLSTERED, AND SUPPORTED PER ACI 315. B.REINFORCING STEEL SHALL BE FREE OF LOOSE FLAKY RUST, SCALE, GREASE, OIL, DIRT, AND OTHER MATERIALS WHICH MIGHT AFFECT OR IMPAIR BOND. C.REINFORCING SHALL BE CONTINUOUS IN WALLS, BEAMS, COLUMNS, SLABS, FOOTINGS, ETC. D.SPLICES IN CONTINUOUS REINFORCING SHALL BE MADE IN AREAS OF COMPRESSION AND/OR AT POINTS OF MINIMUM STRESS, TYPICAL UNLESS NOTED OTHERWISE. LAP SPLICES SHALL BE MINIMUM OF 40 BAR DIAMETERS LONG IN CONCRETE AND 48 BAR DIAMETERS LONG IN MASONRY, TYPICAL UNLESS NOTED OTHERWISE. MINIMUM LAP SHALL BE 24 INCHES LONG. DOWELS SHALL HAVE A MINIMUM OF 30 BAR DIAMETERS EMBEDMENT. TENSION SPICES SHALL BE USED IN CONCRETE WHEN SPECIFICALLY NOTED, USE A CLASS B SPLICE. SPLICES IN TOP BARS IN SUSPENDED SLABS AND BEAMS SHALL BE MADE AT MID SPAN. SPLICES IN BOTTOM BARS IN SUSPENDED SLABS AND BEAMS SHALL BE MADE AT SUPPORTS. E.BENDS SHALL BE MADE COLD. DO NOT USE HEAT. BENDS SHALL BE DONE IN THE FABRICATOR'S SHOP UNLESS SPECIFICALLY NOTED FOR THE FIELD. DO NOT UN-BEND OR RE- BEND A PREVIOUSLY BENT BAR. F.REINFORCING STEEL IN CONCRETE SHALL BE SECURELY ANCHORED AND TIED IN PLACE PRIOR TO PLACING CONCRETE AND SHALL BE POSITIONED WITH THE FOLLOWING MINIMUM CONCRETE COVER: CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH........................................................... 3" CONCRETE EXPOSED TO EARTH OR WEATHER: #6 AND LARGER....................................................................2" #5 AND SMALLER..................................................................1-1/2" CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SLABS AND WALLS, #11 AND SMALLER............................3/4" BEAMS AND COLUMNS, MAIN REINFORCING OR TIES..1-1/2" SLABS ON GRADE................................................................CENTER OF SLAB G.REINFORCING STEEL IN MASONRY SHALL BE PLACED PRIOR TO GROUTING AND SHALL BE PLACED, POSITIONED, AND LOCATED ACCORDING TO THE STRUCTURAL DRAWINGS. IT SHALL BE SECURED AGAINST DISPLACEMENT AT INTERVALS NOT TO EXCEED 200 BAR DIAMETERS OR TEN FEET. H.NO REINFORCING SHALL BE WELDED UNLESS SPECIFICALLY NOTED AS SUCH. USE E90XX ELECTRODES AND ASTM A706 REINFORCING. COMPLY WITH AWS D1.4 REQUIREMENTS. I.EPOXY COATED REINFORCING BARS SHALL BE USED WHEN SPECIFICALLY NOTED. INCREASE LAP SPLICE LENGTHS AS REQUIRED BY THE IBC AND ACI. STRUCTURAL STEEL 1.CODES AND STANDARDS: A.STRUCTURAL STEEL DESIGN, FABRICATION, AND ERECTION SHALL COMPLY WITH: I.THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (AISC 360-10)", WITH "COMMENTARY". II.AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES (AISC 303-10)" EXCLUDING SECTIONS 1.5.1,4.4,7.5.4, AND 7.13.3. III.AMERICAN WELDING SOCIETY (AWS-D1.1) "STRUCTURAL WELDING CODE -STEEL", EXCLUDING ITEMS CONFLICTING WITH AISC REQUIREMENTS. 2.MATERIALS: A.STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992. OTHER STRUCTURAL STEEL SHAPES, PLATES, ANGLES, ETC. SHALL CONFORM TO ASTM A36. RUSSIAN STEEL IS NOT PERMITTED. B.HOLLOW STRUCTURAL SECTIONS SHALL CONFORM TO ASTM A500, GRADE B, WITH A MINIMUM YIELD STRENGTH Fy = 46 KSI. C.STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, WITH A MINIMUM YIELD STRENGTH Fy = 35 KSI. D.HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM A325. ANCHOR RODS SHALL HAVE HEADED STUDS AND SHALL CONFORM TO ASTM F1554. ALL OTHER BOLTS SHALL CONFORM TO ASTM A307 OR BETTER. E.HEADED ANCHOR STUDS AND DEFORMED BAR ANCHORS SHALL CONFORM TO THE MANUFACTURER'S SPECIFICATIONS. F.ALL MEMBERS AND WELDS WHICH HAVE COMPLETE PENETRATION GROOVE WELDS SHALL MEET THE CHARPY V-NOTCH TOUGHNESS IMPACT TEST OF 20 FOOT POUNDS AT 0 DEGREES FAHRENHEIT AND 40 FOOT POUNDS AT 70 DEGREES FAHRENHEIT. 3.CONSTRUCTION: A.FABRICATION SHALL BE DONE IN AN APPROVED FABRICATOR'S SHOP. B.CAMBER IN BEAMS SHALL BE AS INDICATED ON PLANS. C.PROVIDE A SHOP COAT OF PAINT ON ALL STEEL ITEMS, EXCEPT AT AREAS OF WELDING AND/OR BOLTING. D.USE HIGH STRENGTH (8000 PSI MINIMUM AT 28 DAY), NON-SHRINK, LIQUID EPOXY GROUT BENEATH ALL STEEL BASE PLATES AND BEARING PLATES. MIX GROUT WITH SAND OR PEA GRAVEL AS RECOMMENDED BY THE MANUFACTURER. PLACE GROUT AS SOON AS STEEL MEMBER HAS BEEN PROPERLY POSITIONED AND ALIGNED. E.WHERE STRUCTURAL STEEL WIDE FLANGE, PIPE, OR HOLLOW STRUCTURAL SECTIONS ARE EMBEDDED IN CONCRETE OR MASONRY AND REINFORCING BARS BUTT TO IT, DEFORMED BAR ANCHORS OR REINFORCING BARS WITH THE SAME SIZE AND SPACING AS THE ADJACENT REINFORCING BARS, 48 BAR DIAMETERS LONG, SHALL BE WELDED TO THE STRUCTURAL STEEL. THE MANUFACTURER?S WELDING PROCEDURES SHALL BE ADHERED TO. 4.BOLTED CONNECTIONS: A.STEEL TO STEEL BOLTED CONNECTIONS SHALL BE MADE WITH ASTM A325 HIGH STRENGTH BOLTS AND NUTS, UNLESS NOTED OTHERWISE. BOLTS SHALL CARRY THE IDENTIFYING MARK OF THREE (3) RADIAL LINES. B.ALL OTHER BOLTED CONNECTIONS SHALL BE MADE WITH BOLTS AND NUTS CONFORMING TO ASTM A307 UNLESS NOTED OTHERWISE. C.BOLTS SHALL BE 3/4" DIAMETER, TYPICAL, UNLESS NOTED OTHERWISE. STANDARD SPACING SHALL BE 3" O.C. AND STANDARD EDGE DISTANCE SHALL BE 1.1/2", TYPICAL, UNLESS NOTED OTHERWISE. D.BOLT SHALL BE BEARING TYPE CONNECTIONS WITH THREADS EXCLUDED UNLESS NOTED OTHERWISE. E.BOLTED CONNECTIONS SHALL BE TIGHTENED PER SLIP CRITICAL REQUIREMENTS AND SHALL HAVE WASHERS AS REQUIRED BY AISC UNLESS NOTED OTHERWISE. F.ENLARGING OF HOLES SHALL BE ACCOMPLISHED BY MEANS OF REAMING. DO NOT USE A TORCH ON ANY BOLT HOLES. 5.WELDED CONNECTIONS: A.WELDING AND GAS CUTTING SHALL BE DONE PER AWS. B.WELDERS SHALL BE CURRENTLY CERTIFIED ACCORDING TO AWS. ALL WELDING PROCEDURES SHALL BE PRE-QUALIFIED. WELDERS SHALL FOLLOW WELDING PROCEDURES. C.WELDED CONNECTIONS SHALL BE MADE USING LOW HYDROGEN MATCHING FILLER MATERIAL ELECTRODES, UNLESS NOTED OTHERWISE. D.WELDS SHALL HAVE THE SLAG REMOVED. E.FULL PENETRATION WELDS, SHOP OR FIELD, SHALL HAVE BACKER BARS REMOVED, BE BACK GOUGED, AND REWELDED PER AWS TO HAVE FULL PENETRATION WELD. STEEL JOISTS AND JOIST GIRDERS 1.PRODUCT: A.OPEN WEB STEEL JOISTS, JOIST GIRDERS, AND ASSOCIATED HARDWARE SHALL BE DESIGNED, FABRICATED, AND INSTALLED IN CONFORMANCE WITH THE REQUIREMENTS OF THE "STANDARD SPECIFICATIONS OF THE STEEL JOIST INSTITUTE", AISC SPECIFICATIONS, AND SHALL HAVE SPECIFIC PRODUCT APPROVAL OF THE STEEL JOIST INSTITUTE (SJI). 2.DESIGN: A.THE STEEL JOIST/GIRDER MANUFACTURER SHALL BE RESPONSIBLE FOR THE DESIGN AND FABRICATION OF ALL STEEL JOISTS, JOIST GIRDERS, AND THEIR ASSOCIATED HARDWARE. B.ALL STEEL JOISTS AND JOIST GIRDERS SHALL BE DESIGNED AND STAMPED BY A PROFESSIONAL ENGINEER CURRENTLY LICENSED IN THE STATE OF IDAHO. C.JOISTS AND JOIST GIRDERS SHALL BE DESIGNED TO SUPPORT THE FOLLOWING UPLIFT LOADS IN ADDITION TO THE LOADS SHOWN IN THE BASIS OF DESIGN SECTION OF THESE GENERAL NOTES: ROOF NET UPLIFT LOAD TYPICAL INTERIOR BAYS 15 PSF TYPICAL EXTERIOR BAYS 20 PSF TYPICAL CORNER BAYS 25 PSF D.JOISTS AND JOIST GIRDERS SHALL BE DESIGNED TO SUPPORT ALL POINT LOADS SPECIFICALLY SHOWN ON THE DRAWINGS AND ALL MECHANICAL UNITS, SPECIAL EQUIPMENT, AND OTHER SUSPENDED LOADS. CONTRACTOR SHALL COORDINATE. 3.FABRICATION AND ERECTION: A.PROVIDE BRIDGING AS SHOWN ON THE FRAMING PLANS. ALSO, PROVIDE A HORIZONTAL LINE OF BRIDGING AT THE FIRST BOTTOM CHORD PANEL POINT AT EACH END OF THE JOIST. ADDITIONAL BRIDGING REQUIRED BY THE MANUFACTURER SHALL BE PROVIDED AND SHALL BE CLEARLY SHOWN ON THE SHOP DRAWINGS. COORDINATE EXACT LOCATION AS REQUIRED. B.DO NOT CUT, DRILL, MODIFY, OR OMIT ANY PART OF ANY JOIST OR JOIST GIRDER WITHOUT PRIOR WRITTEN CONSENT AND DIRECTION FROM THE MANUFACTURER. C.DO NOT WELD THE BOTTOM CHORD OF THE JOIST GIRDERS TO THE STABILIZER PLATES AT BEARING LOCATIONS UNLESS SPECIFICALLY INSTRUCTED. WHEN WELDING IS SPECIFIED, WELD AFTER ALL DEAD LOAD HAS BEEN APPLIED. D.MECHANICAL EQUIPMENT, PIPES, AND OTHER CONCENTRATED LOADS SHALL NOT BE PLACED ON NOR HUNG FROM STEEL JOISTS OR GIRDERS UNLESS THEY ARE POSITIONED WITHIN 4" OF A PANEL POINT OR A TWO (2) ANGLE (L2X2X1/4) BRACE IS INSTALLED BETWEEN THE LOAD AND THE NEAREST OPPOSITE CHORD PANEL POINT. SOILS 1.SOIL BEARING PRESSURE:2000 PSF (ASSUMED) 2.MINIMUM FROST COVER:36" 3.LATERAL SOIL PRESSURE FLUID EQUIVALENT DENSITY A.ACTIVE 35 PCF B.AT REST 60 PCF C.PASSIVE 250 PCF 4.COEFFICIENT OF FRICTION 0.35 5.A SOILS ENGINEER SHALL REVIEW ALL EXCAVATIONS AND FILL PLACEMENT PRIOR TO PLACING CONCRETE. SITE PREPARATION 1.THE CONTRACTOR SHALL RETAIN A SOILS ENGINEER TO OBSERVE THE EXCAVATIONS AND VERIFY THAT THE ASSUMED SOIL BEARING PRESSURES CAN BE SAFELY OBTAINED. CORRECTIVE MEASURES SHALL BE TAKEN TO OBTAIN THE ASSUMED SOIL BEARING PRESSURES AS REQUIRED. 2.CLEARING: REMOVE THE EXISTING BRIDGE AND THE ENTIRE NEW BUILDING AREA SHALL BE SCRAPED TO REMOVE THE TOPSOIL INCLUDING ALL VEGETATION, DEBRIS, AND DELETERIOUS MATERIAL. 3.PROOF ROLLING: THE NATURAL UNDISTURBED SOIL BELOW ALL FOOTINGS SHALL BE PROOF ROLLED PRIOR TO PLACING CONCRETE. REMOVE ALL SOFT SPOTS AND REPLACE WITH COMPACTED STRUCTURAL FILL. 4.COMPACTED STRUCTURAL FILL: ALL FILL MATERIAL SHALL BE WELL-GRADED AND GRANULAR MATERIAL WITH A MAXIMUM SIZE LESS THAN 4" AND WITH NOT MORE THAN 10% PASSING A #200 SIEVE. IT SHALL BE COMPACTED TO 95% OF THE MAXIMUM LABORATORY DENSITY AS DETERMINED BY ASTM D 1557. ALL FILL SHALL BE TESTED. COMPACTED STRUCTURAL FILL SHALL BE PLACED IN LIFTS NOT EXCEEDING 8" IN UNCOMPACTED THICKNESS. 5.CONSULT THE PROJECT SPECIFICATIONS FOR FURTHER EARTHWORK REQUIREMENTS. A SOILS ENGINEER SHALL REVIEW ALL EXCAVATIONS AND FILL PLACEMENT PRIOR TO PLACING CONCRETE. 7.SUBMITTALS: A.THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION, ERECTION, INSTALLATION, OR OTHERWISE BEING INCORPORATED INTO THE WORK. MATERIALS CERTIFICATION FOR ALL CONCRETE MATERIALS. MIX DESIGNS FOR EACH TYPE OF CONCRETE. MATERIALS CERTIFICATION FOR ALL MASONRY MATERIALS. REINFORCING STEEL SHOP DRAWINGS. STRUCTURAL STEEL SHOP DRAWINGS. WELDING PROCEDURES AND CERTIFICATIONS. LIGHT GAGE METAL SHOP DRAWINGS. STEEL JOIST SHOP DRAWINGS. * STEEL DECK SHOP DRAWINGS. VENEER TIES AND ANCHORS. SPECIAL LOADS ON THE STRUCTURE. OPENINGS THROUGH WALLS AND/OR SLABS. OTHER (AS DIRECTED BY THE ARCHITECT AND STRUCTURAL ENGINEER) * THESE SUBMITTALS SHALL BE STAMPED BY A PROFESSIONAL ENGINEER CURRENTLY LICENSED IN THE STATE OF IDAHO. B.A MINIMUM OF TWO WEEKS SHALL BE ALLOWED FOR THE REVIEW OF ALL SUBMITTALS BY THE ARCHITECT AND STRUCTURAL ENGINEER. C.REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL ENGINEER IN WRITING. REASON(S) FOR THE REQUEST AND COST DIFFERENTIALS SHALL BE INCLUDED IN THE REQUESTS. SUBSTITUTIONS ARE NOT ALLOWED UNLESS APPROVED IN WRITING BY THE ARCHITECT AND STRUCTURAL ENGINEER. QUALITY ASSURANCE PLAN FOR STRUCTURE 1.INSPECTION: A.THE OWNER SHALL PROVIDE SPECIAL INSPECTION BY QUALIFIED INSPECTORS FOR THE FOLLOWING TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1704 AND 1707, THE SPECIFICATIONS, AND THE ATTACHED TABLES INCLUDED IN THESE GENERAL NOTES. SOILS:THE BOTTOM OF EXCAVATIONS AND PLACEMENT OF STRUCTURAL FILL. SEE ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF SOILS. REINFORCED CONCRETE:DURING THE CASTING OF ALL CONCRETE AND TAKING OF ALL TEST SPECIMENS, AND SHALL VERIFY THE PLACEMENT OF ALL REINFORCING. INSPECTOR SHALL BE ACI-II OR ICC CERTIFIED. SEE ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF CONCRETE/STEEL CONSTRUCTION. MASONRY: DURING THE PLACING OF ALL MASONRY UNITS, ALL GROUTING PROCEDURES, AND TAKING OF ALL TEST SPECIMENS, AND SHALL VERIFY THE PLACEMENT OF ALL REINFORCING. INSPECTOR SHALL BE ICC CERTIFIED. SEE ATTACHED TABLE LABELED LEVEL 1/LEVEL 2 SPECIAL INSPECTION OF MASONRY CONSTRUCTION. BOLTING: ALL HIGH STRENGTH BOLTS AND BOLTS EMBEDDED IN CONCRETE AND/OR EPOXY. SEE ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF CONCRETE/STEEL CONSTRUCTION. WELDING: ALL SHOP AND FIELD WELDS. INSPECTOR SHALL BE AWS-QC1 CERTIFIED. SEE ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION. POST-INSTALLED ANCHORS:THE FIRST 25 POST-INSTALLED ANCHORS SHALL BE INSPECTED AND 10 PERCENT OF THE REMAINING ANCHORS SHALL BE INSPECTED. 2.TESTING: A.THE OWNER SHALL PROVIDE TESTING BY QUALIFIED TESTING AGENCIES FOR THE FOLLOWING TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1708 AND THE SPECIFICATIONS. SOILS: COMPACTION OF STRUCTURAL FILL. CONCRETE: STRENGTH, SLUMP, AIR, AND TEMPERATURE. MASONRY: STRENGTH OF MORTAR, GROUT, BLOCK, AND PRISMS. BOLTING: PROPER INSTALLATION AND CORRECT TORQUE AND/OR TENSION. WELDING:TYPE, SIZE, LENGTH, AND QUALITY OF ALL SHOP AND FIELD WELDS BY APPROVED METHODS. ULTRASONICALLY TEST ALL COMPLETE PENETRATION WELDS. 3.STRUCTURAL OBSERVATIONS: A.THE STRUCTURAL ENGINEER SHALL BE NOTIFIED TO PERFORM STRUCTURAL OBSERVATIONS AT SIGNIFICANT THE FOLLOWING STAGES OF CONSTRUCTION.: PRIOR TO PLACEMENT OF CONCRETE FOUNDATIONS PRIOR TO PLACEMENT OF CONCRETE MEMBERS PRIOR TO PLACEMENT OF GROUT IN MASONRY AFTER PLACEMENT OF STEEL MEMBERS AFTER PLACEMENT OF STEEL DECK B.THE STRUCTURAL ENGINEER SHALL PROVIDE A COPY OF THE OBSERVATION REPORT TO THE ARCHITECT FOR FURTHER DISTRIBUTION. 4.THE CONTRACTOR SHALL: A.SUBMIT A STATEMENT OF RESPONSIBILITY TO THE OWNER AND BUILDING OFFICIAL PRIOR TO COMMENCING WORK ON STRUCTURE THAT INCLUDES AWARENESS OF THE QUALITY ASSURANCE PLAN REQUIREMENTS, ACKNOWLEDGMENT THAT CONTROL WILL BE EXERCISED TO OBTAIN CONFORMANCE TO CONSTRUCTION DOCUMENTS, PROCEDURES FOR EXERCISING CONTROL, METHOD AND FREQUENCY OF REPORTING, AND IDENTIFICATION AND QUALIFICATIONS OF PERSONNEL IN CHARGE OF CONTROL. B.CORRECT ALL WORK FOUND TO BE DEFICIENT AT NO ADDITIONAL COST TO THE OWNER. C.COORDINATE ALL THE REQUIRED INSPECTIONS, TESTING, AND/OR STRUCTURAL OBSERVATIONS OF THE QUALITY ASSURANCE PLAN. DO NOT PROCEED WITH SUBSEQUENT WORK UNTIL THE REQUIRED INSPECTIONS, TESTING, AND STRUCTURAL OBSERVATIONS HAVE BEEN PROVIDED. NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER AT LEAST 48 HOURS PRIOR TO ANY REQUIRED OBSERVATIONS. D.PROVIDE COPIES OF THE DAILY INSPECTION REPORTS AND ALL TESTING RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER, OWNER, AND BUILDING OFFICIAL. MASONRY 1.CODES AND STANDARDS: A.MASONRY CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL COMPLY WITH THE AMERICAN CONCRETE INSTITUTE (ACI) 530.1, "SPECIFICATIONS FOR MASONRY STRUCTURES", AND SECTIONS 2103, 2104, AND 2105 OF THE IBC. 2.MATERIALS: A.MASONRY BLOCK SHALL BE LIGHTWEIGHT CONCRETE MASONRY UNITS AND SHALL CONFORM TO ASTM C90, GRADE N, TYPE 1, WITH A MINIMUM COMPRESSIVE STRENGTH OF 2800 PSI AT 28 DAYS FOR NET AREA. B.MORTAR SHALL BE TYPE "S" AS DEFINED BY THE IBC AND SHALL CONFORM TO ASTM C270, WITH A MINIMUM COMPRESSIVE STRENGTH OF 1800 PSI AT 28 DAYS. IT SHALL CONSIST OF 1.0 PART PORTLAND CEMENT, 0.25 TO 0.5 PARTS HYDRATED LIME OR PUTTY LIME, AND 3.5 TO 4.5 PARTS SAND. ALL MEASUREMENTS ARE PARTS BY VOLUME. NO ADDITIVES ARE ALLOWED. C.GROUT SHALL CONFORM TO ASTM C476 WITH A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS. IT SHALL BE OF A FLUID CONSISTENCY AND SHALL CONSIST OF A MINIMUM OF 1.0 PART PORTLAND CEMENT, 2.25 TO 3.0 PARTS SAND, AND MAY CONTAIN AN ADDITIONAL 1 TO 2 PARTS PEA GRAVEL IF GROUT SPACES ARE 4" OR MORE IN EVERY DIRECTION. ALL MEASUREMENTS ARE PARTS BY VOLUME. LIMIT FLY ASH TO 15% OF THE TOTAL CEMENTITIOUS MATERIAL. D.PRISM TESTS SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF F'M = 2000 PSI AT 28 DAYS. E.EPOXY SHALL CONFORM TO ASTM C881, TYPES I, II, IV, AND V, GRADE 3, CLASSES B AND C. 3.CONSTRUCTION: A.ALL MASONRY BLOCK SHALL BE STORED UNDER COVER AT THE JOB SITE. B.FACE SHELLS SHALL BE FULLY BEDDED. C.ALL MORTAR JOINTS SHALL BE TOOLED CONCAVE UNLESS NOTED OTHERWISE. D.DO NOT USE MORTAR FOR GROUT. E.DO NOT USE ANY FROZEN MATERIAL. F.PRIOR TO PLACING MASONRY, CHECK WITH ALL TRADES TO INSURE PROPER PLACEMENT OF OPENINGS, BLOCK OUTS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS, EMBEDS, DOWELS, ETC. G.GROUT SHALL BE POURED IN ACCORDANCE WITH LOW LIFT PROCEDURES PER ACI 530, TYPICAL, UNLESS NOTED OTHERWISE. H.GROUT SHALL BE CONSOLIDATED BY MECHANICAL VIBRATION DURING PLACING AND RECONSOLIDATED AFTER EXCESS MOISTURE HAS BEEN ABSORBED BUT BEFORE WORKABILITY IS LOST. I.ALL CELLS WHICH CONTAIN REINFORCING, BOLTS, ANCHORS, ETC., AND AS OTHERWISE SPECIFIED SHALL BE GROUTED SOLID. ALL CELLS WHICH ARE TO BE GROUTED SHALL BE CLEAN AND FREE FROM DELETERIOUS MATERIALS. J.GROUT SOLID AROUND ALL JOIST AND BEAM ENDS, TYPICAL UNLESS NOTED OTHERWISE. K.HOLES FOR BOLTS IN MASONRY FACE OR END SHELLS SHALL HAVE A DIAMETER TWO INCHES LARGER THAN THE BOLT DIAMETER AND THE HOLE SHALL BE FILLED WITH GROUT. L.NO PENETRATION SHALL BE ALLOWED THROUGH ANY MASONRY BEAM, COLUMN, PIER, OR JAMB WITHOUT THE ARCHITECT'S AND STRUCTURAL ENGINEER'S PRIOR WRITTEN APPROVAL. PENETRATIONS SHALL BE RE-ROUTED AS REQUIRED AT THESE LOCATIONS. M.ALL BOLTS TO BE DRILLED AND EPOXIED SHALL BE INSTALLED IN SOLID MATERIAL. AT CAVITY LOCATIONS GROUT SOLID. ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR. FOLLOW MANUFACTURERS RECOMMENDATIONS. 4.WALLS: A.MASONRY WALLS SHALL BE CONSTRUCTED UTILIZING COMMON RUNNING BOND, TYPICAL, UNLESS NOTED OTHERWISE. B.MASONRY WALLS SHALL BE BUILT AS AN INTEGRAL UNIT AT CORNERS AND INTERSECTIONS. REINFORCING SHALL BE CONTINUOUS AND BACK TO BACK END SHELLS SHALL BE REMOVED IN EACH COURSE. C.MASONRY WALLS SHALL BE REINFORCED AS FOLLOWS, UNLESS NOTED OTHERWISE. WALL VERTICAL HORIZONTAL THICKNESS REINFORCING REINFORCING (WITH JOINT REINFORCING) PROVIDE LADDER-TYPE JOINT REINFORCING CONSISTING OF 2-#9 WIRES (3-#9 WIRES AT VENEER) AT 16" O.C. HORIZONTALLY IN ALL MASONRY WALLS. SEE PLANS, SCHEDULES, AND DETAILS FOR OTHER REINFORCING REQUIREMENTS. 6"1-#5 AT 32" O.C.2-#3 AT 48" O.C. 8"1-#5 AT 24" O.C.2-#4 AT 48" O.C. 12"1-#6 AT 24" O.C.2-#4 AT 48" O.C. SEE PLANS, SCHEDULES, AND DETAILS FOR OTHER REINFORCING REQUIREMENTS. D.PLACE VERTICAL REINFORCING IN THE CENTER OF THE WALL UNLESS EACH FACE IS SPECIFIED OR UNLESS NOTED OTHERWISE. E.VERTICAL REINFORCING SHALL BE DOWELED TO CONCRETE FOOTING OR FOUNDATION WALL BELOW AND TO STRUCTURE ABOVE WITH THE SAME SIZE BAR AND SPACING, TYPICAL, UNLESS NOTED OTHERWISE. F.PROVIDE VERTICAL REINFORCING IN GROUTED CELL AT ALL CORNERS AND INTERSECTIONS. G.PROVIDE CORNER BARS AT ALL INTERSECTIONS AND CORNERS. USE SAME SIZE BAR AND SPACING AS THE HORIZONTAL REINFORCING. H.HORIZONTAL REINFORCING SHALL TERMINATE AT THE ENDS OF WALLS AND AT OPENINGS WITH A STANDARD HOOK. I.HORIZONTAL REINFORCING SHALL OCCUR AT THE TOP AND BOTTOM COURSE OF ALL MASONRY WALLS EXCEPT THE BOTTOM COURSE HORIZONTAL REINFORCING MAY BE OMITTED WHEN THE WALL IS DOWELED TO A CONCRETE FOUNDATION WALL BELOW. J.OPENINGS IN WALLS WHICH EXCEED 24 INCHES IN EITHER DIRECTION SHALL BE REINFORCED WITH A MINIMUM OF 2-#5 BARS IN GROUTED SPACE ON ALL SIDES OF THE OPENING, TYPICAL, UNLESS NOTED OTHERWISE. VERTICAL BARS SHALL EXTEND THE FULL HEIGHT OF THE WALL BETWEEN SUPPORTS. HORIZONTAL BARS SHALL EXTEND A MINIMUM OF 24 INCHES BEYOND THE EDGES OF THE OPENING. K.PENETRATIONS THROUGH ANY MASONRY WALL SHALL BE BUILT INTO THE WALL AS THE WALL IS BEING CONSTRUCTED AND SHALL BE REVIEWED BY THE ARCHITECT AND STRUCTURAL ENGINEER PRIOR TO INSTALLATION. L.CONSTRUCTION JOINTS IN REINFORCED MASONRY WALLS SHALL NOT OCCUR AT THE EDGE OF BEAM SUPPORTS AND SHALL BE PROVIDED PER THE ARCHITECTURAL DRAWINGS. M.WHERE HORIZONTAL REINFORCING BARS JOIN CONCRETE WALLS, COLUMNS, OR PILASTERS, REINFORCING SHALL BE CONTINUOUS. ALSO, A KEY SHALL BE PROVIDED BETWEEN THE MASONRY AND THE CONCRETE. FILL KEY WITH GROUT. 5.BEAMS: A.BEAMS SHALL BE BUILT AS AN INTEGRAL PART WITH THE SUPPORT. NO TOOTHING OR DOWELING ONLY WILL BE PERMITTED. MASONRY UNITS WITH ONE END OPEN-ENDED ("A" BLOCKS) SHALL BE USED IN ALL MASONRY BEAMS. BACK-TO-BACK END SHELLS ARE NOT ALLOWED. GROUT ALL MASONRY BEAMS SOLID FOR FULL DEPTH AND WIDTH SHOWN IN MASONRY BEAM SCHEDULE. B.REINFORCING IN THE MASONRY BEAM SCHEDULE IS IN ADDITION TO STANDARD WALL REINFORCING. C.HORIZONTAL REINFORCING BARS IN THE TOP OF THE MASONRY BEAM SHALL BE PLACED IN THE TOP 4 INCHES OF THE BEAM AND SHALL EXTEND A MINIMUM OF 72 BAR DIAMETERS BEYOND THE EDGE OF THE OPENING OR SHALL BE HOOKED IF REQUIRED. D.HORIZONTAL REINFORCING BARS IN THE BOTTOM OF THE MASONRY BEAM SHALL BE PLACED IN THE BOTTOM 4 INCHES OF THE BEAM AND SHALL EXTEND A MINIMUM OF 24 INCHES BEYOND THE EDGE OF THE OPENING OR SHALL BE HOOKED IF REQUIRED. E.VERTICAL REINFORCING BARS SHALL HOOK AROUND THE BOTTOM HORIZONTAL REINFORCING BARS. THEY SHALL ALSO HOOK AROUND THE TOP HORIZONTAL REINFORCING BARS OR EXTEND INTO THE WALL ABOVE THE MASONRY BEAM A MINIMUM OF 48 BAR DIAMETERS. F.DO NOT SPLICE HORIZONTAL TOP OR BOTTOM BARS, TYPICAL UNLESS NOTED OTHERWISE. G.FOR OPENINGS NOT SHOWN, USE SIMILAR BEAM AS SHOWN IN THAT WALL OR TYPE OF WALL FOR SIMILAR LENGTH OPENINGS. VERIFY WITH THE STRUCTURAL ENGINEER. H.USE THE FOLLOWING MASONRY BEAM SIZES FOR OPENINGS IN NON-BEARING MASONRY WALLS: WIDTH OF OPENING BEAM WIDTH BEAM DEPTH HORIZ. REINF. (FEET)(INCHES)(INCHES) UP TO 4'-0"SAME AS WALL 16 2 # 5 BOTT. UP TO 8'-0"SAME AS WALL 24 2 # 5 TOP & BOTT. UP TO 10'-0”SAME AS WALL 32 2 # 5 TOP & BOTT. FOR WIDER OPENINGS CONTACT THE STRUCTURAL ENGINEER. SEE THE MASONRY BEAM SCHEDULE FOR ADDITIONAL INFORMATION. 6.COLUMNS: A.GROUT JAMBS SOLID FOR FULL HEIGHT OF WALL (FLOOR TO FLOOR AND/OR ROOF) AT SIDES OF OPENINGS; ONE CELL FOR EACH 4'-0" OF SPAN OR PORTION THEREOF. REINFORCE WITH 2- #5 VERTICAL BARS IN EACH GROUTED CELL WITH ONE BAR PLACED AT EACH FACE OF WALL, TYPICAL UNLESS NOTED OTHERWISE. SEE PLANS, SCHEDULES, AND DETAILS FOR OTHER REINFORCING REQUIREMENTS. STEEL DECK 1.PRODUCT: A.STEEL DECK SHALL BE SIZE AND GAUGE AS SPECIFIED ON PLANS. B.STEEL DECK AND ACCESSORIES SHALL BE MANUFACTURED FROM COLD ROLLED STEEL CONFORMING TO ASTM A-653, (GALVANIZED G-60), OR ASTM A-611, GRADE C (PAINTED), AND SHALL CONFORM TO THE STEEL DECK INSTITUTE (SDI) AND AISC STANDARDS 2.ATTACHMENT AND HANDLING: A.WELDING PATTERN SHALL BE AS SPECIFIED ON PLAN. B.WELD METAL DECK TO SUPPORTING FRAMING MEMBERS WITH E60XX OR E70XX ELECTRODES. C.PUDDLE WELDS SHALL HAVE A FUSION AREA OF NOT LESS THAN 3/4" DIAMETER AT THE UPPER SURFACE. WELD METAL SHALL PENETRATE ALL LAYERS OF THE DECK MATERIAL AND SHALL HAVE PROPER FUSION TO THE SUPPORTING MEMBERS. D.CRIMP SIDE SEAMS BEFORE WELDING SIDE LAPS. TOP SEAM WELDS SHALL ENGAGE ALL LAYERS OF THE DECK MATERIAL. E.END LAPS SHALL OVERLAP AT LEAST 2" AND SHALL OCCUR OVER A SINGLE STEEL SUPPORT. PUDDLE WELDS SHALL OCCUR AT LEAST 1" AWAY FROM EITHER END OF DECK. F.PUDDLE WELDS 3/8" X 1.1/2" LONG MAY REPLACE 3/4" DIAMETER PUDDLE WELDS WHEN ACCESS IS LIMITED. G.INSTALL DECK WITH A MINIMUM OF 3 SPANS WHEREVER POSSIBLE. H.PROVIDE ANGLE AND/OR OTHER SUPPORT AROUND THE PERIMETER OF ALL OPENINGS LARGER THAN 10" IN EITHER DIRECTION THROUGH METAL DECK. I.PROVIDE DECK SUPPORT AS REQUIRED AT COLUMNS. J.DO NOT BEND OR MAR DECK. K.STORE DECKING OFF THE GROUND WITH ONE END ELEVATED. COVER DECK WITH WATERPROOF MATERIAL AND VENTILATE TO AVOID CONDENSATION. LIGHT GAGE METAL FRAMING 1.CODES AND STANDARDS: A. LIGHT GAGE METAL DESIGN, FABRICATION, AND ERECTION SHALL COMPLY WITH: I.THE AMERICAN IRON AND STEEL INSTITUTE (AISI) "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS", WITH "COMMENTARY". II.AMERICAN WELDING SOCIETY (AWS-D1.3) "STRUCTURAL WELDING CODE -SHEET STEEL", EXCLUDING ITEMS CONFLICTING WITH AISI REQUIREMENTS. 2.MATERIALS: A.LIGHT GAGE METAL SHALL BE MANUFACTURED BY A CURRENT MEMBER OF THE STEEL STUD MANUFACTURERS ASSOCIATION (SSMA). B.LIGHT GAGE METAL JOISTS, STUDS, TRACKS, STEEL PLATE SHEATHING, AND ACCESSORIES, ETC. SHALL BE GALVANIZED AND SHALL BE GRADE FY=33 KSI UNLESS 50 KSI IS SPECIFICALLY NOTED. 3.CONSTRUCTION: A.PROVIDE ALL ACCESSORIES INCLUDING TRACKS, CLIPS, WEB STIFFENERS, ANCHORS, FASTENING DEVICES, ETC FOR A COMPLETE AND PROPER INSTALLATION. B.INSTALLATION SHALL BE AS RECOMMENDED BY THE MANUFACTURER. C.FASTENERS SHALL BE SELF DRILLING SCREWS OR WELDING. A MINIMUM OF 16 GAGE MATERIAL IS REQUIRED FOR WELDING. TOUCH UP OF WELDS IS REQUIRED. D.LOAD BEARING STUDS SHALL BE PLUMBED, ALIGNED, AND SECURELY ATTACHED TO BOTH FLANGES OF UPPER AND LOWER TRACKS. E.NON-LOAD BEARING WALLS SHALL BE BRACED TO STRUCTURE ABOVE AND SHALL BE INSTALLED SO AS TO ALLOW FOR DEFLECTION OF STRUCTURE. F.SPLICES IN AXIALLY LOADED MEMBERS ARE NOT ALLOWED. G.COMPLETE, UNIFORM, AND LEVEL BEARING SHALL BE PROVIDED FOR ALL BOTTOM TRACKS OF LOAD BEARING WALLS AND FOR ALL LOAD BEARING JOISTS. H.WEB STIFFENERS AND JOIST BRIDGING SHALL BE PROVIDED AS INDICATED ON THE DRAWINGS. END BLOCKING SHALL BE PROVIDED AT JOIST ENDS. I.PROVIDE DOUBLE JOISTS AT THE SIDES OF ALL FLOOR AND/OR ROOF OPENINGS AND AT ALL PARALLEL PARTITION WALLS ABOVE. J.ALL STUDS AND JOISTS SHALL BE SHEATHED ON BOTH FACES OF THE MEMBER. SHEATHING SHALL BE ATTACHED TO EACH MEMBER AT 12" MAXIMUM SPACING. K.HEADERS AND TRIMMERS SHALL BE AS SHOWN ON THE DRAWINGS. L.ALL LATERAL BRACING SHALL CONFORM TO SECTION D3 OF AISI SPECIFICATION. POST-INSTALLED ANCHORS 1.EPOXY ANCHORS: A.THE FOLLOWING EPOXY ADHESIVES SYSTEMS SHALL BE ALLOWED: FOR CONCRETE: SIMPSON SET-XP HILTI HIT-RE 500-V3 HILTI HIT-RE 100 DEWALT PURE 110+ FOR SOLID GROUTED MASONRY: SIMPSON SET HILTI HIT HY 200 DEWALT PURE 110+ FOR UNGROUTED MASONRY: SIMPSON ET HILTI HY 270 B.ANCHOR RODS SHALL BE ASTM A-307, THREADED AND GALVANIZED, AND THE DIAMETER AS INDICATED ON PLAN. C.SCREEN TUBES SHALL BE USED AT UNGROUTED MASONRY UNITS. D.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR. E.INSTALLATION OF ADHESIVE ANCHORS THAT ARE TO BE UNDER SUSTAINED TENSION LOADING IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER (AAI) AS CERTIFIED THROUGH ACI AND IN ACCORDANCE WITH ACI 318-2014 (Section 17.8.2.2). PROOF OF CURENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION. F.PER ACI 318-2014 (Section 17.1.2) ADHESIVE ANCHORS SHALL BE INSTALLLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. FOR INSTALLATIONS SOONER THAN 21 DAYS CONSULT ADHESIVE MANUFACTURER. G.IF TEMPERATURE OF BASE MATERIAL AT TIME OF ADHESIVE INSTALLATION IS AT 45 DEGREES (FAHRENHEIT) OR LESS, AN “ACRYLIC” (COLD WEATHER) ADHESIVE IS REQUIRED –ie DEWALT AC200+, HILTI HY200, SIMPSON AT-XP. 2.MECHANICAL ANCHORS A.THE FOLLOWING MECHANICAL ANCHORS SHALL BE ALLOWED: SIMPSON TITEN HD HILTI KWIK HUS-EZ DEWALT SCREWBOLT+ B.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR. 3.SUBSTITUTES: CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR APPROVAL TO THE ARCHITECT AND STRUCTURAL ENGINEER. MASONRY VENEER 1.PRODUCT: A.LEDGERS AND LINTELS SHALL BE ASTM A36 GALVANIZED MATERIAL. B.MASONRY VENEER ANCHOR TIES SHALL BE ONE OF THE FOLLOWING. I.DOVETAIL ANCHORS. II.DW-10 SEISMIC CLIP INTERLOCK SYSTEM BY HOHMANN & BARNARD. III.ARCHITECT AND STRUCTURAL ENGINEER APPROVED TWO PIECE ADJUSTABLE HOT-DIPPED GALVANIZED TIES. IV.THREE WIRE JOINT REINFORCING. 2.INSTALLATION: A.MASONRY VENEER SHALL BE INDEPENDENTLY SUPPORTED AT EACH STORY IN SEISMIC DESIGN CATEGORY D, E, OR F. B.MAXIMUM SPACING OF ANCHOR TIES SHALL BE 16" O.C. HORIZONTAL AND VERTICAL. C.PROVIDE CONTINUOUS HORIZONTAL GALVANIZED #9 WIRE IN CENTER THIRD OF MORTAR JOINTS AT 16" O.C.. ENGAGE #9 WIRE WITH ALL ANCHOR TIES. D.MAXIMUM SPACING OF STUD BACKING SHALL BE 16" O.C. STUDS SHALL BE COVERED WITH 1/2" SHEATHING AND APPROVED PAPER. E.CONSTRUCTION JOINTS IN MASONRY VENEER WALLS SHALL BE PROVIDED AS PER THE ARCHITECTURAL DRAWINGS, AND SHALL BE SPACED AT A MAXIMUM OF 30'-0" O.C. FOR BRICK VENEER AND A MAXIMUM OF 15'-0" O.C. FOR MASONRY BLOCK VENEER. PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 8/ 1 2 / 2 0 1 9 3 : 1 8 : 3 3 P M C : \ U s e r s \ D o n \ D o c u m e n t s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R 1 8 _ D B a r f u s s @ T B S E . u s . r v t GE N E R A L N O T E S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-001 Checker Project Number Author SLAB ON GRADE 4000 0.45 145 3/4 - 564 F0,S0,P0,C0 WALLS 4000 0.45 145 3/4 - 564 F0,S0,P0,C0 FOOTINGS 4000 0.45 145 1 - 564 F0,S0,P0,C0 INTERIOR MEMBERS SLAB ON GRADE 4500 0.42 145 3/4 6±1.5 611 F2,S0,P0,C1 OTHER SITE CONCRETE 4500 0.42 145 3/4 6±1.5 611 F2,S0,P0,C1 WALLS, PIERS, BEAMS 4500 0.42 145 3/4 6±1.5 611 F2,S0,P0,C1 FOOTINGS 4000 0.45 145 1 6±1.5 564 F0,S0,P0,C0 EXTERIOR MEMBERS TYPE OF MEMBER MIN. STRENGTH @ 28 DAYS (PSI) MAX. W/C (RATIO) DRY WEIGHT (PCF) MAX AGGREGTE SIZE (INCHES) AIR ENTRAIN- MENT (%) MIN. CEMENT PER YARD (LBS) EXPOSURE CLASS CONCRETE MIX DESIGN TABLE NO. DESCRIPTION DATE 08/12/2019 NOTES: 1.ALL FOOTINGS SHALL BEAR ON PROPERLY PREPARED MATERIAL. SEE THE SITE PREPARATION NOTES. 2.ALL FOOTINGS SHALL BE CENTERED BELOW THE WALL AND/OR COLUMN ABOVE, TYP., U.N.O. 3.ALL EXTERIOR FOOTINGS SHALL BEAR BELOW THE EFFECTS OF THE FROST. 4.PROVIDE A 2X4 BEVELED KEY WAY IN ALL CONTINUOUS WALL FOOTINGS. 5.PROVIDE DOWELS WITH STANDARD HOOKS FROM FOOTINGS TO ANY REINFORCED ELEMENT ABOVE WITH SIZE AND SPACING TO MATCH VERTICAL REINFORCING IN ELEMENT ABOVE. 6.PROVIDE MINIMUM COVER FOR ALL REINFORCING PER GENERAL NOTES. 7.ANY INCREASE IN THE SIZE OF FOOTINGS SHOWN TO ACCOMODATE CONSTRUCTION PRACTICES MAY REQUIRE ADDITIONAL REINFORCING, COORDINATE WITH THE ARCHITECT AND STRUCTURAL ENGINEER. 8.PENETRATIONS THROUGH FOOTINGS ARE NOT ALLOWED, UNLESS APPROVED BY THE ARCHITECT AND/OR STRUCTURAL ENGINEER IN WRITING PRIOR TO CASTING FOOTING. 9.SEE GENERAL NOTES FOR ADDITIONAL INFORMATION. TYPICAL BOTTOM FOOTING REINFORCING.3" M I N . 3" MIN.EQ.EQ.EQ.3" MIN. TYPICAL TOP REINFORCING.TYPE 1 #2 TIES @ 8" O.C. EXISTING WALL 5/8"X11" HEADED BOLT W/ 5½" EMBED IN EPOXY AT 16" O.C. (USE SCREEN IF REQUIRED) TYPE 2 ALT. TYPE 1 ALT. TYPE 2 EXISTING COLUMN 5/8"XREQUIRED HEADED STUD AT 16" O.C. WELD TO COLUMN EXISTING COLUMN 5/8"X5" HEADED STUD AT 16" O.C., WELD TO COLUMN TYPE 3 (2) #3 TIES AT 24" O.C. IN BOND BEAM (2) #5 EACH VERTICAL CELL NOTES: 1. GROUT ALL CELLS SOLID, TYP. 2. USE OPEN ENDED 'A' BLOCK UNITS THROUGHOUT MASONRY BEAM. BACK-TO-BACK END SHELLS ARE NOT ALLOWED. 3. PROVIDE SPLICES IN HORIZONTAL TOP REINFORCING AT MID SPAN ONLY, TYP., U.N.O. 4. PROVIDE SPLICES IN HORIZONTAL BOTTOM REINFORCING AT SUPPORTS ONLY, TYP., U.N.O. 5. EXTEND TOP BARS A MINIMUM OF 72 BAR DIAMETERS BEYOND THE FACE OF THE OPENING OR TERMINATE WITH A STANDARD HOOK, TYP., U.N.O. 6. EXTEND BOTTOM BARS A MINIMUM OF 24" BEYOND THE FACE OF THE OPENING OR TERMINATE WITH A STANDARD HOOK, TYP., U.N.O. 7. HOOK VERTICAL REINFORCING AROUND HORIZONTAL BOTTOM REINFORCING. HOOK VERTICAL REINFORCING AROUND HORIZONTAL TOP 8. STANDARD VERTICAL WALL REINFORCING DOES NOT NEED TO HOOK AROUND HORIZONTAL REINFORCING. 9. THE FIRST VERTICAL REINFORCING ADJACENT TO THE SUPPORT SHALL BE PLACED WITHIN A DISTANCE NOT GREATER THAN ONE HALF THE TYPICAL SPACING OF THE ADJACENT VERTICAL REINFORCING FROM THE FACE OF THE SUPPORT. 10. PROVIDE VERTICAL JAMB REINFORCING EACH SIDE OF OPENING PER THE GENERAL NOTES, U.N.O. EXTEND FULL HEIGHT OF WALL BETWEEN LEVELS. 11. PROVIDE VERTICAL CONTROL JOINTS AT MID SPAN ONLY, TYP., U.N.O. DO NOT PLACE CONTROL JOINTS AT OR NEAR FACE OF SUPPORTS. 12. PENETRATIONS THROUGH MASONRY BEAMS ARE NOT ALLOWED, UNLESS APPROVED BY THE ARCHITECT AND/OR STRUCTURAL ENGINEER IN WRITING PRIOR TO CONSTRUCTING BEAM. 13. SEE GENERAL NOTES FOR ADDITIONAL INFORMATION. 'PLAN' HORIZ. STEEL. 'A' BLOCK WITH OPEN ENDED UNITS TYP. THROUGHOUT ENTIRE BEAM. 'A' BLOCK BOTTOM STEEL TOP STEEL FU L L H E I G H T 36" JA M B S T E E L "ELEVATION" FU L L H E I G H T 36" JA M B S T E E L LESS THAN 1/2" TIE SPACING, TYP. 24"24" NOTES: 1.PROVIDE 1" OF BEARING FOR EACH FOOT OF OPENING, 6" MINIMUM, EACH SIDE. 2.CONTRACT STRUCTURAL ENGINEER FOR ALL LINTELS WITH SPANS GREATER THAN 12 FEET. 3.ALL LINTEL ANGLES SHALL BE GALVANIZED. PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 2 7 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t SC H E D U L E S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-002 Checker Project Number Author C.W. = CROSSWISE E.W. = EACH WAY L.W. = LENGTHWISE F-4 4'-0" 4'-0" 14" (6) - #5 - (6) - #5 - - F-5C 5'-0" CONT. 15" #5 @ 14" O.C. # 5 @ 14" O.C. (4) - #5 (4) - #5 - F-2.5C 2'-6" CONT. 12" #4 @ 12" O.C. - (3) - #5 - - F-2C 2'-0" CONT. 12" #4 @ 18" O.C. - (2) - #5 - BOTTOM TOP BOTTOM TOP - MARK WIDTH LENGTH THICK. CROSSWISE REINFORCING LENGTHWISE REINFORCING NOTES CONCRETE FOOTING SCHEDULE 2000 PSF SOIL PRESSURE ASSUMED ML-2 WALL THICKNESS 24" (2) #5 TOP AND BOTTOM ML-1 WALL THICKNESS 16" (2) #5 TOP AND BOTTOM - MARK WIDTH DEPTH REINFORCING NOTES MASONRY LINTEL SCHEDULE MP-3 8" 2'-8" (2) #5 EACH END (2) #3 @ 24" O.C. TYPE 3 MP-2 8" 8" (2) #5 NONE TYPE 2 MP-1 8" 16" (2) #5 EACH CELL #2 @ 8" O.C. TYPE 1 VERTICAL TIES SETS MARK WIDTH (IN) LENGTH (IN) REINFORCING NOTES MASONRY PIER SCHEDULE 10'-0" TO 12'-0"6"X4"X3/8" 9'-0" TO 10'-0"5"X3-1/2"X5/16" 7'-0" TO 9'-0"4"X3-1/2"X5/16" 5'-0" TO 7'-0"3-1/2"X3-1/2"X5/16" UP TO 5'-0"3-1/2"X3-1/2"X1/4" CLEAR OPENING ANGLE SIZE STEEL ANGLE LINTEL SCHEDULE NO. DESCRIPTION DATE 08/03/2019 DN E F G H H1 J J1 K 2221 181716151211141310 14 SE-501 15 SE-501 16 SE-501 FILL THIS OPENING WITH CMU 1 SE-502 5 2 SE-501 20 SE-501 20 16 SE-511 15 SE-501 4 3 NEW MASONRY WALL 2 1 5 19 SE-501 1 66 SE-511 21 SIM. 6 21 SE-501 7 7 ML-1 MP-2 MP-2 7 3 6 SE-511 21 SIM. NEW STUD WALL 8 5 M P -2 M P -1 ML - 1MP-1 ML - 1 9 6SIM. 8 TYP. SE-501 22 SIM. SE-501 22 SIM. NEW MASONRY WALL LEGEND INDICATES FLOOR SLAB ELEVATION INDICATES DETAIL SECTION VIEW? S??-?? F.S.E. = ??' -??" INDICATES MASONRY WALL, SEE SCHEDULES MW-?? INDICATES NOTES ARE KEYED ON PLAN. 1.SEE ARCH. FOR EXTENT OF DEMOLITION. 2.AFTER REMOVAL OF WALLS, STAIRS, FLOOR TILE, ECT. FLOORS SHALL BE REPAIRED AS REQUIRED. 3.REINFORCE NEW MASONRY WALLS W/ #5 @ 32" O.C. VERTICAL IN GROUTED CELLS IN CENTER OF WALLS AND (2) #4 @ 48"O.C. HORIZONTAL IN GROUTED BOND BEAM. 4.BRACE TOP OF NEW MASONRY WALLLS TO STRUCTURE ABOVE PER DETAIL 19/SE501. 5.BRACE TOP OF STUD WALLS TO STRUCTURE ABOVE PER STUD WALL MANUFACTURING REQUIREMENTS. ATTACH TO FLOOR SLABS PER DETAIL 18/SE-501. 6.BRACE TOP OF NEW MASONRY WALL TO STRUCTURE PER DETAIL 23/SE-511 OR 24/SE-511. EXTEND WALL ABOVE CEILING AS REQUIRED. 7.SEE DETAIL 3/SE-502 FOR MASONRY WALL CONNECTION TO SLAB ON GRADE. 8.SEE DETAIL 18/SE-501 FOR STUD WALL CONNECTION TO FLOOR SLAB. 9.FILL SPACE FROM MP-1 TO COLUMN W/ GROUTED MASONRY AS REQUIRED. SEE MASONRY PIER SCHEDULE TYPE 1 ALT. 10.PROVIDE ADEQUATE SHORING FOR EXISTING MASONRY ABOVE NEW OPENINGS. SHEET NOTES PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 2 7 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t LE V E L 1 F L O O R PL A N JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-101 Checker Project Number Author 1/8" = 1'-0"1 Level 1 NO. DESCRIPTION DATE 08/03/2019 F.E.C. INDICATES NOTES ARE KEYED ON PLAN. 1.REMOVE EXISTING CONCRETE STAIRS AND SLAB ON GRADE AT EAST ENTRY TO BUILDING AS REQUIRED TO INSTALL NEW ENTRY STAIRS, AND RAMP SLABS. 2 4" CONCRETE SLAB ON 4" FREE DRAINING GRAVEL. REINFORCE WITH #4 AT 24"O.C. EACH WAY, CENTER OF SLAB 3.5" MINIMUM THICKNESS CONCTRETE STAIR SLAB ON 4" FREE DRAINING GRAVEL, SEE ARCH. REINFORCE W/ #4 @ 16" O.C. BOTH WAYS IN CENTER OF SLAB. ADD #3 NOSE BARS. 4.REMOVE ALL MASONRY WALLS EXCEPT AS NOTED THIS AREA. USE CAUTION TO NOT DAMAGE STEEL COLUMNS EMBEDED IN WALLS. SHEET NOTES 5.NEW MASONRY PIERS, DOWEL TO FOUNDATION WALL 8" EMBED IN EMPOXY. 6.SEE DETAIL 18/SE-501 FOR TYPICAL STUD WALL TO FLOOR SLAB CONNECTION. 7.SEE DETAIL 9/SE-501 FOR NON-TYPICAL STUD WALL CONNECTION TO FLOOR SLAB. (EXAMPLE -ALL STUD WALLS IN RESTROOMS) 8.BRACE STUD WALLS AS REQUIRED BY STUD WALL INSTALLER. 9.BRACE MASONRY WALLS TO STRUCTURE ABOVE, SEE DETAIL 16,17, OR 18/ SE-511. 10.PROVIDE ADEQUATE SHORING FOR EXISTING MASONRY ABOVE NEW OPENINGS. 11.FOOTING STEPS SHALL BE LOCATED TO MAINTAIN FROST COVER OF 3'-6" MINIMUM. ADD ALTERNATE #1 B C D E F G H H1 J J1 K L 121110987654321 S S T.F. = 86' - 0" T.F. = 86' - 0" F-5C F-5C F- 2 C F-5C F-5C T.F. = 91' - 0" CW-16 CW-16 CW - 1 2 CW-16 CW-16 86 ' - 0" F -2C 86 ' - 0" F -2C 1 SE-501 3 SE-501 1 1 SE-501 1 SE-501 SE-501 7 SE-501 6 1 SE-501 4 SE-501 SE-501 5 SE-501 5 OPP. EX I S T I N G EXISTING FOOTING EXISTING FOOTING EX I S T I N G DN DN2 DN3 2 SE-501 11 SE-501 10 SE-501 9 SE-501 9 SE-501 13 SE-501 13 SE-501 MP-1 MP-1 MP-1 MP-1MP-1 MP-1 MP-1 3 SE-502 SIM. 1 SE-502 SE-502 2 7 SE-502 SIM. 3 SE-502 SE-502 6 SE-502 6 OPP. 4 SE-502 3 SE-502 3 SE-502 4 SE-502 4 SE-502 3 SE-502 3 SE-502 5 SE-502 4 4 3 SE-502 DOOR SHALL BE IN CENTER OF PRE-CAST PANEL 6 SE-512 1 SE-502 F- 2 . 5 C SE-502 8 SE-502 9 SIM. SE-502 9 11 SE-502 10 SE-502 17 SE-511 MP-2 6 2 SE-512 4 SE-512 MP-1 MP-1MP-2MP-1 76 EXISTING WALL TO REMAIN 15 SE-511 H SS4X4X5/16 H SS4X4X5/16 MP-2 6 8 6 8 7 6 6 8 6 8 STEEL COLUMNS, SEE DETAIL 14/SE-512 MP-1 MP-3 MP-3 MP-1 9 SE-502 12 13 SE-502 SE-502 14 NEW MASONRY INFILL 6 1 SE-503 17' - 11 5/8" 6 6 F-4 9 9 SE-501 22 SIM. MP-2 MP-2 EXISTING WALL EXISTING WALL - --- _______ 3 SE-503 S S 20'-0" ±8'-0" ± S S S S T.F. = 87' - 0" T.F. = 91' - 0" T.F. = 87' - 0" T.F. = 91' - 0" 11 F.S.E. = 96'-4"H SS 4 X4X1/4 H SS 5 X5X1/4 7 SE-502 SIM. 5 SE-502 SIM. PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 3 1 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t LE V E L 2 RE V I S I O N S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-102 Checker Project Number Author 1/8" = 1'-0"1 FOUNDATION PLAN NO. DESCRIPTION DATE 08/03/2019 F.E.C. INDICATES NOTES ARE KEYED ON PLAN. 1.SEE ARCHITECTURAL DRAWINGS FOR DEMOLITION AND ROOF SLOPE. 2.ROOF DECK SHALL BE 1 1/2" X 20 GAUGE TYPE "B" GALVANIZED ROOF DECK WITH INTERLOCKING SIDE LAPS. THREE SPAN MINIMUM. ATTACH TO PERPENDICULAR SUPPORTS WITH (7) 3/4" DIAMETER PUDDLE WELDS PER 36" WIDE SHEET. ATTACH TO PARALLEL SUPPORTS WITH 3/4"Ø DIAMETER PUDDLE WELDS AT 12"O.C. ATTACH SIDE LAPS WITH 1 1/2" LONG TOP SEAM WELDS AT 12"O.C. MINIMUM SHEAR STRENGTH REQUIRED = 840 PLF. VERCO PUNCHLOK DECKING (PLB) DECK WITH VERCO SIDE LAP CONNECTIONS (VSC2) IS ALSO ACCEPTABLE PROVIDED THE SHEAR STRENGTH IS EQUAL TO OR GREATER THAN SPECIFIED ABOVE. SHEET NOTES 3.DEMOLITION TO BE PER ARCH. DRAWINGS. BRACE TOP OF EXISTING MASONRY WALLS AT SIDES OF NEW OPENINGS. SEE DETAIL 18/SE-511. SEE SHEET SE-102 FOR DEMO AT POOL AREA. 4.BRACE TOP OF EXISTING WALLS WHERE OPENINGS HAVE BEEN INFILLED W/ MASONRY. SEE DETAIL 18/SE-511. 5.BRACE TOP OF NEW MASONRY WALLS, SEE DETAILS 16/SE-511 OR 17/SE-511. 6.NEW STUD WALLS SHALL BE BRACED TO THE STRUCTURE ABOVE BY THE INSTALLER AS REQUIRED. 7.NEW WINDOW. PROVIDE EXTRA METAL STUDS AND LIGHT GAUGE HEADER AS REQUIRED FOR MOUNTING DOOR. BRACE TOP OF STUDS TO STRUCTURE ABOVE AS REQUIRED. 8.REMOVE EXISTING MASORY WALL TO TOP OF WALL. REPAIR CEILING PER ARCH. 9.NEW MASONRY WALLS, PIERS, AND BEAMS, BRACE TO STRUCTURE, SEE NOTE 5. 10.(2) 4X3 1/2X5/16 ANGLES (LONG LEGS BACK TO BACK. WELD TO COLUMN AT CENTER AND 6" BEARING AT EACH END. 11.SEE DETAIL 11/SE-512 FOR ROOF OPENINGS IN EXISTING ROOF. 12.SEE DETAIL 12/SE-512 FOR FLOOR DECK OPENINGS IN EXISTING FLOOR. 13.SEE DETAIL 13/SE-512 FOR CONCENTRATED LOADS ON BOTTOM CHORD OF JOISTS. 14.PROVIDE ADEQUATE SHORING FOR EXISTING MASONRY ABOVE NEW OPENINGS. ADD ALTERNATE #1 B C D E F G H H1 J J1 K L 1211 10987654321 SE-103 2 1 SE-502 18 SE-511 3 17 SE-501 4 6 1 SE-503 4 17 SE-501 3 4 9 9 7 5 17 SE-511 ML-1 6 5 SE-512 7 ML-2 ML-2 ML-2 ML-2 ML - 1 ML - 1 REMOVE MASONRY BELOW WINDOW AND REPLACE WINDOW W/ NEW DOOR ML-1 8 MP-1MP-1 9 5 MP-1 MP-1 MP-1 MP-1MP-1 MP-2 MP-2 ML - 2 M L - 2 ML-1ML-1 INFILL DOOR SHALL BE IN CENTER OF PRE-CAST PANEL 2 SE-512 ML - 1 17 SE-501 SIM. 10 HSS6X4X1/4HSS6X4X1/4HSS6X4X1/4 8 SE-502 12 9 9 6 SE-512 11 SE-502 SE-502 9 SE-502 9 SIM. 10 SE-512 11 SE-512 11 TYP. SE-512 11 TYP. 6 6 MP-1 6 MP-2 6 SE-512 17 SE-511 6 STEEL COLUMNS BELOW, SEE DETAIL 14/SE-512 MP-1 MP-3 MP-3 MP-1 ML - 2 MP-1 13 SE-502 SIM. INFILL BOTH SIDES OF NEW DOOR MP-1 MP-2 MP-1 SE-511 21 SIM. 22 SE-511 3 SE-512 SE-512 12 ML-2ML-2 SE-512 14 SE-501 22 SIM.20 SE-511 ML-1 MP-2 MP-2EXISTING WALL EXISTING WALL 9 8 3 SE-503 1 F G F G 1W6X20 W 6 X 2 0 W 6 X 2 0 W6X20 OPP. 2 " EXP A NS I ON J OI N T SIM. 2" E X P A N S I O N J O I N T 16K3 @ 6'-0" O.C. HS S 3 X 3 X 1 / 4 @ 6 ' -0" O . C . SE-511 7 5 SE-511 3 SE-511 6 SE-511 5 SE-511 SE-511 7 2 SE-511 6 SE-511 2 SE-511 5 SE-511 SE-501 8 1 SE-511 SE-501 8 5 SE-511 3 SE-511 W1 0 X 3 0 W1 0 X 3 0 W18X35 W18X35 4 SE-503 4 SE-503 6 SE-503 5 SE-503 5 SE-503 PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 3 2 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t LO W E R R O O F FR A M I N G AD D I T I O N JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-103 Checker Project Number Author 1/8" = 1'-0"1 LOWER ROOF FRAMING ADDITION 3/16" = 1'-0"2 Level 2 - Callout 1 NO. DESCRIPTION DATE 08/03/2019 INDICATES NOTES ARE KEYED ON PLAN. 1.REMOVE EXISTING CURTAIN AND CURTAIN SUPPORT AT CENTER OF GYM. 2.INSTALL STUD WALL IN TRUSS SPACE PRIOR TO INSTALLING WALL BELOW TRUSSES. 3.PROVIDE ADEQUATE SHORING FOR EXISTING MASONRY ABOVE NEW OPENINGS. 4.FOR LOCATION OF POSSIBLE SPLICE AND DETAIL, SEE DETAIL 1/SE-104. SHEET NOTES 2 43 5 6 7 B C D E F G H J K L B C D E F G H J K L 765432 9 SE-511 SIM. 9 SE-511 10 SE-511 SIM. 11 SE-511 13 SE-511 14 SE-511 BOTTOM CHORD OF TRUSS 8 SE-511 9 SE-511 10 SE-511 12 SE-511 8 SE-511 W24X76 CAMBER 1"2' - 8" T-5 T-5 T-5 T-5 T-5 T-5 T-5 T-5 3'-0"X3'-0" MECHANICAL DUCT THRU WALL 2 SE-503 (2 ) H S S 6 X 6 X 1 / 4 (2 ) H S S 6 X 6 X 1 / 4 (2 ) H S S 6 X 6 X 1 / 4 (2 ) H S S 6 X 6 X 1 / 4 (2 ) H S S 6 X 6 X 1 / 4 2 SE-104 LEGEND INDICATES FINISHED FLOOR SLAB ELEVATION INDICATES TOP OF WALL ELEVATION INDICATES TOP OF PIER ELEVATION T.W. = ??' -??" T.P. = ??' -??" INDICATES TOP OF STEEL ELEVATIONT.S. = ??' -??" INDICATES DETAIL SECTION VIEW? SE?-?? INDICATES DETAIL VIEW OR ENLARGED PLAN CALLOUT ? SE?-?? F.S.E. = ??' -??" INDICATES CONCRETE PIER (CP) OR MASONRY PIER (MP), SEE SCHEDULESCP-? 0' - 1 1/2" 0' - 1 1/2" 1' - 8 1 / 2 " PROVIDE BACK-UP BARS. REMOVE, BACK GOUGE, RE-WELD, TYP. 3/8" PLATE EACH SIDE OF WEB W/ (6) ROWS OF BOLTS CJP CJP PROVIDE BACK-UP BARS. REMOVE, BACK GOUGE, RE-WELD, TYP. THIS DETAIL (IF REQUIRED) SHALL BE WITHIN THE CENTER 2'-0" OF THE BEAM. W24X76 BEAM PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 3 2 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t HI G H R O O F FR A M I N G P L A N RE V I S I O N S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-104 Checker Project Number Author 1/8" = 1'-0"1 HIGH ROOF FRAMING PLAN NO SCALESE-104 2 NO. DESCRIPTION DATE 08/03/2019 EXISTING CONCRETE FOOTING EXISTING CONCRETE FOUNDATION WALL #4 @ 24" O.C. EACH WAY CENTER OF SLAB CONCRETE SLAB ON GRADE, SEE PLAN NEW RAMP SLAB ON GRADE, SEE ARCH FOR SLOPE. 90'-2" SEE ARCH. (2) #6, DOWEL TO EXISTING WALLS EACH END. EMBED DOWELS 10" IN EXISTING WALLS. SAW CUT TOP OF WALL TO BE BELOW NEW RAMP SLAB. 0' - 8" 4" CONCRETE SLAB. ELEVATION VARIES, SEE PLAN #5 @ 14" O.C. DOWELS (CLASS B LAP SPLICE) #4 @ 24" O.C. CENTER OF SLAB #5 @ 14" O.C. EACH FACE BRICK VENEER, SEE ARCH. 3" COVER 1' - 4" #5 @ 14" O.C. 42 " M I N . F R O S T C O V E R SEE ARCH. 95'-0" (4) #5 CONT. #5 @ 14" O.C. 4" INSULATION SPACE, SEE ARCH.(2) #6 TOP AND BOTTOM 8" M I N . 8" MIN. (2) #4 X CONT. #4 @ 24" O.C. CENTER OF SLAB 12" HOOK, TOP AND BOTTOM #4 @ 12" O.C. (2) #4 X CONT.#4 @ 24" O.C. CENTER OF SLAB 4" SLAB ON GRADE #4 @ 12" O.C. 4" SLAB ON GRADE SEE ARCH FOR HANDRAIL VARIES 95'-0" REMOVE FLOOR SLAB AND WOOD FLOOR AS REQUIRED. REPLACE AS REQUIRED. HSS5X5X1/4 3/4"X12"X12" BASE PLATE W/ (4) 3/4" A307 BOLTS W/ 8" MIN. EMBED. USE DOUBLE LOCKING NUTS 4'-0"X4'-0" FOOTING W/ (6) #5 BARS EACH WAY BOTTOM OF FOOTING 1/4 3" COVER #4 BARS AT 12" O.C. ALL 4 SIDES, EMBED 4" IN EPOXY SHEATHING PER ARCHITECT 600S137-33 STUDS @ 16" O.C. 16 GAUGE TRACK (E) 4" FLOOR SLAB ON GRADE 3/16" TITEN CONCRETE SCREWS @ 24" O.C. BY SIMPSON OR EQUAL. 1½" EMBED IN CONCRETE FLOOR SLAB. USE 2" SQUARE WASHERS REMOVE AND REPLACE WOOD FLOOR AS REQUIRED SEE ARCH. EXISTING 12" MASONRY WALL HSS4X4X1/4 COLUMN 3/4"X5"X12" PLATE W/ (4) 3/4"Ø A325 BOLTS EXISTING (3) #8 (GB-2, SEE EXISTING PLANS) EXISTING (2) #4 TOP OF PIERS AT EXISTING STEEL COLUMNS, 90'-0" 91'-0" 1/4 EXISTING #4 @ 18" O.C. HORIZONTAL BETWEEN EXISTING (3) #8 TOP AND BOTTOM 12 SE-501 3/4"X6"X27" PLATE 5/8"X15½"X27" PLATE (2) 5/8"XREQUIREDX14" STIFFENER PLATES (6) 3/4" TITEN HD BOLTS BY SIMPSON OR EQUAL, 12" SPACING BOTH VERTICAL AND HORIZONTAL 1/4 1' - 4 " EXISTING CONCRETE FLOOR SLAB PROVIDE CONCRETE PROTECTION AROUND COLUMN BRACKET AND COLUMN. (6" MIN.) REMOVE EXISTING CONCRETE FLOOR SLAB AND REPLACE AS REQUIRED EXISTING #4 @ 18" O.C. VERTICAL EACH FACE 0' - 1 1/2"1' - 0"1' - 0" 0' - 1 1/2" SEE PLAN FOR COLUMN 3/4"X5"X10" PLATE W/ (2) 3/4"Ø A325 BOLTS (6) 3/4" SIMPSON TITEN HD ANCHORS OR EQUAL 5/8" PLATE 3/4" PLATE 1' - 0" 0' - 1 1/2" 0' - 2" 16" CONCRETE FOUNDATION WALL. SEE GENERAL NOTES FOR REINFORCING 3/4"X7"X10" PLATE W/ (4) 3/4" ANCHOR BOLTS (12" EMBED). PROVIDE 1" NON-SHRINK GROUT SPACE T.F.W = SEE ARCH. 12" FOUNDATION WALL. SEE GENERAL NOTES FOR REINFORCING 5/16 T.F.W =95'-0" 2'-0" 3'-0"CONCRETE SLAB ON GRADE, SEE PLAN. FOOTING, SEE PLAN 12" FOUNDATION WALL, SEE PLAN #4 @ 16" O.C. (2) #5 X CONT. EXTERIOR SLAB, SEE ARCH. ENTRY WALL, SEE ARCH EXISTING 12" CONCRETE WALL 2" EXPANSION JOINT ABOVE IN MASONRY WALL, SEE ARCH 3/4"X7"X10" BASE PLATE 16" CONCRETE FOUNDATION WALL W/ (2) #6 TOP AND BOTTOM CONT. SEE GENERAL NOTES FOR WALL REINFORCING. DOWEL HORIZONTAL REINFORCING TO EXISTING W/ 6" EMBED IN EPOXY.SEE DETAIL 8/SE-501 FOR COLUMN IN CMU WALL. EXISTING CONCRETE WALL 3/4"X7"X10" PLATE W/ (4) 3/4" ANCHOR BOLTS (12" EMBED) 16" CONCRETE FOUNDATION WALL W/ (2) #6 TOP AND BOTTOM CONT. SEE GENERAL NOTES FOR WALL REINFORCING. DOWEL HORIZONTAL REINFORCING TO EXISTING W/ 6" EMBED IN EPOXY. SEE DETAIL 8/SE-501 FOR COLUMN IN CMU WALL.BRICK VENEER, SEE ARCH. FACE OF EXISTING BUILDING 2" EXPANSION JOINT STANDARD HOOK WELD DOWELS FOR HORZIONTAL REINFORCING. USE A706 DOWELS, SEE GENERAL NOTES CMU WALL GROUT SOLID AT STEEL COLUMN CMU WALL INSULATION, SEE ARCH. EXISTING MASONRY OR CONCRETE WALL (8" OR 12", SEE PLAN) EXISTING CONCRETE SLAB EXISTING FOOTING NEW FLAT SLAB ON GRADE OR SLOPED SLAB ON GRADE, SEE PLAN REMOVE EXISTING FLOOR OR STAIR SLAB ON GRADE. COMPACT EXISTING GRADE AND ADD NEW WELL GRADED GRANULAR FILL AS REQUIRED. 91'-0" 90'-2" VARIES 79'-0" 76'-0" FIELD VERIFY ELEVATIONS AND SEE ARCH. FOR HANDRAIL. #3 NOSE BARS TYP. (7) #4 TOTAL #4 @ 16" O.C. NEW CONCRETE STAIR SLAB EXISTING FLOOR SLAB ON GRADE EXISTING GRADE BEAM EXISTING FLOOR SLAB EMBED 5" IN EPOXY EMBED 3" IN EPOXY 0' - 8" VARIES, SEE PLAN EXISTING SLAB ON GRADE 79'-0" FIELD VERIFY EMBED 4" IN EPOXY EXISTING GRADE BEAM (12"X40" TOTAL HEIGHT) #4 @ 16" O.C. EXISTING 4" SLAB ON GRADE EMBED 3" IN EPOXYGEOFOAM SEE ARCH. FOR HANDRAIL #3 NOSE BARS TYP. #4 @ 16" O.C. EXISTING SLAB ON GRADE EXISTING GRADE BEAM GEOFOAM EMBED 3" IN EPOXY 4" SLAB ON GEOFOAM #4 @ 16" O.C. EXISTING 4" SLAB ON GRADE SEE ARCH FOR STUD WALLS, WIDTH AND GAUGE STUDS 18 GAUGE TRACKS EXISTING CONCRETE SLAB SIMPSON PDPA-100 POWDER ACTUATED FASTENERS @ 16" O.C. OR EQUAL EXISTING STEEL COLUMN 3X3X1/4X8" ANGLES @ EACH BOND BEAM W/ (2) 5/8"X4" HEADED STUDS #5 @ 32" O.C. VERTICAL(2) #4 @ 48" O.C. HORIZONTAL NEW MASONRY WALL, SEE ARCH. TYP. 3/16 NOTE:CONTRACTOR SHALL REVIEW CONCRETE SLAB ON GRADE FOR DEFECTS. REPORT TO ARCHITECT/STRUCTURAL ENGINEER AFTER REVIEW.EXISTING SLAB ON GRADE #5 @ 24" O.C. MASONRY WALL, SEE ARCH. EXISTING CONCRETE SLAB ON METAL DECK 1/2"X6"X10" PLATE @ 48" O.C. W/ (2) 5/8"X8" HEADED ANCHOR STUDS EXISTING STEEL BEAM 1/4 2@4 (2) #4 TOP OF WALL (2) #4 @ 48" O.C. EMBED 3" IN EPOXY 0' - 8" VARIES, SEE PLAN EXISTING SLAB ON GRADE 79'-0" FIELD VERIFY DOWEL 4" IN EXISTING BEAM EXISTING GRADE BEAM (12"X4" TOTAL HEIGHT) #4 @ 16" O.C. DOWEL 3" IN EXISTING IN EPOXY GEOFOAM #4 @ 16" O.C. VARIES, SEE PLAN #4 @ 16" O.C. EXISTING 4" SLAB ON GRADE #4 @ 12" O.C. INFILL W/ 8" CMU W/ #5 @ 24' O.C. VERTICAL AND (2) #4 @ 32" O.C. HORIZONTAL (REMOVE MASONRY ABOVE DOOR AND ESTEND NEW ALL ABOVE CEILING AND BRACE TO STRUCTURE) EXISTING MASONRY WALL 40 BAR DIAMETER LAPS, TYP. EMBED 6" IN EPOXY TYPICAL. TOP AND SIDES EMBED DOWELS IN EPOXY 3" IN EXISTING 4" SLAB, 8" IN EXISTING FOUNDATION WALLS OR GRADE BEAMS EXISTING FLOOR SLAB, GRADE BEAM, OR FOUNDATION WALL NOTE: WHERE 4" CERAMIC TILE IS ADDED TO 8" CMU, ATTACH AS VENEER, W/ (3) WIRE JOINT REINFORCING. 16 SE-511 18 SE-511 ALT. BRACE TO STRUCTURE TOP OF WALL EXISTING MASONRY WALL (1) #4X40" DOWEL TO EXISTING MASONRY WALL. EMBED 5" IN EPOXY, USE WIRE SCREEN AS REQUIRED. NEW MASONRY WALL (CERAMIC-TILE COATED, WHERE REQUIRED). #5 @ 24" O.C. VERTICAL. (2) #4 @ 48" O.C. HORIZONTAL PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 3 3 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t DE T A I L S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-501 Checker Project Number Author NO SCALESE-501 3 NO SCALESE-501 1 NO SCALESE-501 2 NO SCALESE-501 10 NO SCALESE-501 9 NO SCALESE-501 11 NO SCALESE-501 12 NO SCALESE-501 5 NO SCALESE-501 4 NO SCALESE-501 7 NO SCALESE-501 6 NO SCALESE-501 8 NO SCALESE-501 13 NO SCALESE-501 14 NO SCALESE-501 15 NO SCALESE-501 16 NO SCALESE-501 18 TYPICAL STUD WALL CONNECTION TO EXISTING CONCRETE SLAB NO SCALESE-501 20 NO SCALESE-501 19 NO SCALESE-501 21 NO SCALESE-501 17 EXISTING DOOR INFILL IN MASONRY WALLS NO SCALESE-501 22 NO. DESCRIPTION DATE 08/03/2019 INFILL W/ 8" CMU W/ #5 @ 24' O.C. VERTICAL AND (2) #4 @ 48" O.C. HORIZONTAL EXISTING MASONRY WALL 40 BAR DIAMETER LAPS, TYP. EMBED 6" IN EPOXY TYPICAL. TOP AND SIDES EMBED DOWELS IN EPOXY 3" IN EXISTING 4" SLAB, 8" IN EXISTING FOUNDATION WALLS OR GRADE BEAMS EXISTING FLOOR SLAB, GRADE BEAM, OR FOUNDATION WALL NOTE: WHERE WALL IS 8" BLOCK AND 4" CERAMIC TILE, DETAIL SHOWS 8" BLOCK CONSTRUCTION -CERAMIC TILE SHALL BE INSTALLED AS VENEER W/ (3) WIRE LADDER TYPE JOINT REINFORCING. EXISTING MASONRY WALL AND CERAMIC TILE EXISTING MASONRY WALL 8" MASONRY WALL CAULK JOINT EXISTING MASONRY AND STEEL COLUMN 9 SE-501 STUD WALL #5X36" AT BOND BEAMS, EMBED 6" IN EPOXY STUD WALL #5X36" AT BOND BEAMS, EMBED 6" IN EPOXY #5 @ 24" O.C. #5 DOWEL @ 24" O.C. EMBED 3" IN EPOXY (2) #4 @ 48" O.C. EXISTING SLAB ON GRADE #5 @ 24" O.C. #5 DOWEL @ 24" O.C. EMBED 3" IN EPOXY (2) #4 @ 48" O.C. EXISTING SLAB ON GRADE EXISTING THICKENED SLAB #5 @ 24" O.C. #5 DOWELS @ 24" O.C. EMBED 8" IN FOUNDATION WALL 8" MASONRY WALL (2) #4 @ 48" O.C. EXISTING FLOOR SLAB ON GRADE EXISTING FOUNDATION WALL EXISTING SUSPENDED SLAB OVER POOL SERVICE AREA 4" CERAMIC TILE BLOCK EXISTING 6" CMU WALL EXISTING 4" CMU EXISTING 4" GLAZED CERAMIC TILE #5 EACH END OF NEW WALL (2) #4 @ 48" O.C. (1) WITH HOOK AS SHOWN. EMBED 8" IN EXISTING WALL 8" CMU WALL (2) 5/8"X9" HEADED BOLTS @ 48" O.C. EMBED 4" IN EPOXY. 8" MASONRY WALL (COURSE OUT W/ CORRIDOR WALL). #5 @ 24" O.C. VERTICAL ENDS AND CORNERS, EMBED 3" IN EXISTING SLAB. SLAB IS 4½" W/ 1½" DECK. DRILL 3" OR UNTIL STEEL DECK IS HIT W/ DRILL BIT. REPAIR EXISTING WOOD FLOOR AS REQUIRED INSTALL DOWEL PRIOR TO INFILL W/ CONCRETE (2) #4 @ 48" O.C. INFILL W/ CONCRETE AFTER REMOVAL OF WOOD FLOOR EXISTING CONCRETE SLAB ON METAL DECK EXISTING STEEL COLUMN #4X24" REBAR (A706) WELD TO COLUMN AT 48" O.C. 8" MASONRY WALLS W/ #5 VERTICAL @ 24" O.C. AT ENDS AND AT INTERSECTION. (2) #4 @ 48" O.C. IN BOND BEAM 1/4 (2) #4 DOWELS (A706) WELDED TO COLUMN AT 48" O.C. EXISTING STEEL COLUMN (2) #4 HORIZONTAL AT 48" O.C. IN BOND BEAMS. (BOND BEAMS AT TOP, BOTTOM, AND 48" O.C.) NEW MASONRY WALL TYP. 1/4 #5 @ 24" O.C. VERTICAL #4 DOWELS @ 24" O.C. EMBED 4" IN EPOXY (2) #4 CONTINUOUS. 1ST COURSE AND 48" O.C. EXISTING SLAB ON GRADE SEE PLAN FOR FOOTING SIZE AND REINFORCING 18" LAP. UNDERCUT SOIL BY 2"± SAWCUT CONCRETE SLAB. DO NOT CUT STEEL COLUMN 5/8" X 6" WELDED ANCHOR STUDS @ 16" O.C. SE-512 9 SE-512 9 SIM. OPP. EXISTING PIER NEW F-2.5C FOOTING EXISTING PIER EXISTING WALL NEW F-2.5C FOOTING EXISTING FRAMING EXISTING FRAMINGEXISTING FRAMING EXISTING FRAMINGEXISTING FRAMING NEW MASONRY WALL, REINFORCE W/ #5 AT 24" O.C. VERTICAL AND (2) #4 AT BOTTOM, TOP AND 48" O.C. HORIZONTAL. WELD HORIZONTAL BARS TO COLUMNS. SEE GENERAL NOTES. H S S 4 X 4 X 5 /1 6 9 SE-502 7 SE-503 EXISTING GLAZED TILE NEW GLAZED TILE. MATCH EXISTING, SEE VENEER NOTE #5 VERTICAL AT CORNER NEW 8" CMU WALL W/ #5 AT 24" O.C. VERTICAL, (2) #4 AT 48" O.C. HORIZONTAL #5 NEAR END OF WALL #5 AT 48" O.C. EMBED 6" IN EPOXY AS REQUIRED 16" EXISTING 8" CMU MP-2 EXISTIND DOUBLE DOOR EXISTING CERAMIC TILE EXISTING 6" BLOCK HSS4X4X5/16 TUBE FROM FLOOR TO STRUCTURE ABOVE. BRACE TO STEEL STRUCTURE ABOVE WITH 3X3X1/4 ANGLE 5/8"XREQUIRED THREADED ROD, EMBED 4 1/2" IN 6" BLOCK AT 16" O.C. USE SCREEN IF REQUIRED FOR EPOXY 1/4"X4"X4" SQUARE WASHER PLAN VIEW PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 8/ 1 2 / 2 0 1 9 3 : 1 8 : 3 4 P M C : \ U s e r s \ D o n \ D o c u m e n t s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R 1 8 _ D B a r f u s s @ T B S E . u s . r v t DE T A I L S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-502 Checker Project Number Author NO SCALESE-502 1 EXISTING DOOR INFILL IN MASONRY WALLS NO SCALESE-502 2 NO SCALESE-502 3 NO SCALESE-502 4 NO SCALESE-502 5 NO SCALESE-502 6 NO SCALESE-502 7 NO SCALESE-502 8 NO SCALESE-502 9 NO SCALESE-502 10 NO SCALESE-502 11 NO SCALESE-502 12 NO SCALESE-502 13 NO SCALESE-502 14 NO. DESCRIPTION DATE 08/12/2019 0' - 6"0' - 6" EXISTING W10X33 COLUMN 1/2" RODS AT 24" O.C. AND AT EACH END WELD AND GRIND SMOOTH (2) 6X4X1/4 ANGLES 3/4"X4"XREQUIRED PLATE 1/2" STIFFENER AT CENTER MASONRY INFILL, REINFORCE WITH (2) #4 VERITCAL AND (2) #4 HORIZONTAL AT 32" O.C. 1/4 4" 1/4 1/4 0' - 4" TOP OF EXISTING FOUNDATION NEW MASONRY WALL EMBED DOWELS IN EPOXY 3" IN EXISTING 4" SLAB, 8" IN EXISTING FOUNDATION WALLS OR GRADE BEAMS MP-2, SEE SCHEDULE EXISTING MASONRY ABOVE, BRACE TO STRUCTURE EXISTING MASONRY A706 REINFORCING 3/16 2 MP-1 3' - 0 " 3' - 0" 1/2" THRU RODS, WELD TO EACH ANGLE AND GRIND SMOOTH ((8) TOTAL) EXISTING MASONRY BOTH SIDES AND TOP AND BOTTOM 6"X4"X5/16" ANGLES BOTH SIDES OF WALL (4 SIDES OF OPENING) PROVIDE BOND BEAM AT TOP OF WALL, EXTEND 6" IN EPOXY TO EXISTING MASONRY. EXTEND TO TOP OF WALL (2) #5 AT 32" O.C., EXTEND TO TOP OF WALL NEW MASONRY ABOVE TO EQUAL EXISTING MASONRY HEIGHT. BRACE TO STRUCTURE ABOVE EMED 6" IN EPOXY, USE SCREENS AS REQUIRED EXISTING MASONRY 5/8" HEADED BOLTS AT 24" O.C., EMBED 6" IN EPOXY. USE SCREENS AS REQUIRED. EMBED VERTICAL REINFORCING 6" IN EPOXY ML-1 MP-2 EXISTING MASONRY 4" FACE BRICK 2" AIR GAP 8" CMU 2" RIGID INSULATION 16" DEEP TRUSS (2) 7/8"x#12 SELF TAPPING SCREWS EACH STUD METAL STUD WALL 3/16"X3" TITEN HD SCREWS AT 16" O.C. (ALIGN WITH STUDS) 7/8"X#12 SELF TAPPING SCREWS AT EACH STUD 1/8" BENT PLATE AS REQUIRED, CONTINUOUS 5/16"XREQUIREDX5" BENT PLATE CONTINUOUS BETWEEN JOISTS, W/ 3/4"X8" HEADED ANCHOR STUDS AT 16" O.C. METAL ROOF DECK 3/4 6" O.C. EXTEND END 16" DEEP JOIST METAL STUD WALL WINDOW AS PER SPEC. STUD WALL BRACE (16 GAUGE) W18X35 BEAM 2½"X2½X1/4" ANGLE. BRACE AT EACH JOIST (TO WEB OF BEAM) HSS2½X2½X1/4 CONTINUOUS TUBE BETWEEN JOISTS 3/16 2 3/16 3/16 2@12 METAL ROOF DECK 2½"X2½"X1/4" ANGLE BRACE AT 8'-0" O.C. METAL STUD WALL, SEE ARCH. WINDOW WALL, SEE ARCH. W10X30 BEAM C8X11.5 SEE ARCH. TYP.3/16 3/16 DECK WELD 3/4 6" O.C. HSS3X3X3/16 AT 8'-0" O.C. 1/4"X4"XCONT. PLATE 3/16 2@12 3" ±3" ± EXISTING STEEL BEAM (W10X21) 5/8"X8" WELDED ANCHOR STUDS (2) #4 CONTINOUS, TYP. VERTICAL REINFORCING IN CENTER OF WALL, EXTEND TO TOP OF WALL (24" O.C.) FORMED CONCRETE BOND BEAM AT TOP OF WALL. CAST TOP COURSE OF BLOCK AND CONCRETE BOND BEAM TOGETHER PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 3 5 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t DE T A I L S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-503 Checker Project Number Author NO SCALESE-503 1 NO SCALESE-503 2 NO SCALESE-503 3 NO SCALESE-503 4 NO SCALESE-503 5 NO SCALESE-503 6 NO SCALESE-503 7 NO. DESCRIPTION DATE 08/03/2019 ROOF DECK, SEE PLAN L3½"X3"X1/4" CONTINUOUS STEEL BEAM, SEE PLAN L2½"X2½"X1/4 AT EACH HSS3 TUBE SECTION 4" TOTAL, MIN.1/4 1/4 TYP. EACH END 1/4 4" MIN. ROOF BEAM, SEE PLAN ROOF JOIST, SEE PLAN ROOF DECK, SEE PLANCONT. L-2½"X2"X1/4" 3/16 3/16 2½ @ 16 3/16 3 @ 18 STEEL BEAM, SEE PLAN 1/2" PLATE W/ (2) 3/4"Ø A325 BOLTS STEEL COLUMN, SEE PLAN 5/8" CONTINUITY PLATE TOP AND BOTTOM CJP CJP TYP.1/4 SINGLE PLATE TO COLUMN 1/4 TYP.1/4 NOT USED BRICK VENEER, SEE ARCH.MASONRY WALL, SEE PLAN ROOF DECK, SEE PLAN 3/4"X7"X12" PLATE W/ (2) 3/4"X8" HEADED ANCHOR STUDS @ 16" O.C. 1/4 GROUT SOLID SEE DETAIL 22 FOR ROOF DECK CONNECTION BETWEEN JOISTS 3/16"X3" TITEN HD SCREWS AT 16" O.C. (ALIGN WITH STUDS) 7/8"X#12 SELF TAPPING SCREWS AT EACH STUD 1/8" BENT PLATE AS REQUIRED, CONTINUOUS FOR CONTINUATION OF FASCIA, SEE ARCHITECTURAL DRAWINGS AND DETAIL 4/SE-503. 3/8" STIFFENER EACH SIDE 3/4"X7"X11" PLATE W/ (2) 3/4" ANCHOR BOLTS, 12" MIN. EMBED (2) #4 X 3'-0" DOWELS. LAP W/ (2) #4 IN WALL CMU WALL STEEL BEAM, SEE PLAN 1/4 (2) 3X3X1/4 ANGLE 1/2" END PLATE W/ (4) 3/4" A325 BOLTS 3X3X1/4 ANGLE BRACE 1/2" END PLATE 1/4"X2¾"X6" PLATE WELD TO 3X3X1/4 ANGLE PRIOR TO ERECTION W/ 3/16" FILLET WELD FULL LENGTH 3X3X1/4 ANGLE BRACE TYP.3/16 3" MIN. 3/16 TYP.3/16 3" MIN. TYP.3/16 5" MIN. EXISTING STEEL COLUMN EXISTING STEEL COLUMN (2) HSS6X6X1/4 TUBES 1/4 2@12 EXISTING ROOF DECK 1/2" PLATE (2) 3/4"Ø A325 BOLT (1) 3/4"Ø A325 BOLT (2) 2½"X2½"X1/4" ANGLES (2) 3X3X1/4 ANGLES 1/2" END PLATE W/ (4) 3/4"Ø A325 BOLTS (2) HSS6X6X1/4 TUBES EXISTING MASONRY WALL EXISTING ROOF BEAM EXISTING ROOF JOIST 3/16 3@9" 3/16 14 SE-511 3X3X1/4 ANGLE, SEE 14/SE-501 EACH ANGLE3/16 3" MIN. 1/2" STIFFENER PLATE EACH SIDE W24X76 STEEL BEAM, SEE PLAN HSS5X5X1/4 TUBE, SEE PLAN 3/4" CAP PLATE W/ (4) 3/4"Ø A325 BOLTS FUTURE CONNECTION, PROVIDE (6) HOLES FOR 3/4"Ø A325 BOLTS FUTURE BEAM 1/4 1/4 AS REQ'D AS REQ'D AS REQ'D 14 GAUGE X REQUIRED CONT. PLATE BETWEEN JOISTS EXISTING 1½" ROOF DECK SPECIAL 14 GAUGE TRACK SPECIAL 16 GAUGE TRACK TO ALLOW 2" INSERT INTO 14 GAUGE TRACK PLUS 2½" FROM BOTTOM OF 14 GAUGE TRACK TO CENTERLINE OF SCREW. PROVIDE 2" CLEAR ALL AROUND K-BRACE. STUDS ARE TO BE SPACED TO MISS K-BRACE (2) 6" STUD WALLS (600S137-33 STUDS AT 16" O.C. EACH WALL) SOUND BATS AND SHEATHING PER ARCH. W24X76, SEE PLAN (2) 1/2" HANGER RODS @ 24" O.C. MAX. SPACING C10X15.3 CONT. FOR SKY FOLD DOOR PROVIDE FOR 2" VERTICAL MOVEMENT, TOP AND BOTTOM INFILL W/ STUDS AND GYB BOARD EACH SIDE. WELD STUDS TO BEAM 3X3X1/4" ANGLE BRACE. (1) 3/4" A325 BOLT EACH END. USE LOCK NUTS FINGER TIGHT HSS5X3X1/4 @ EACH K-BRACE LOCATION (4) 7/8" LONG #12-24 SELF TAPPING SCREWS AT 6" O.C. 0' - 5" 1/2"X4"X4" PLATE 1/4 TYP.1/4 4" EXISTING TOP CHORD TRUSS EXISTING TRUSS BOTTOM CHORD 0' - 3" 1/8"XREQ'D BENT PLATE 1/8 2@12 7/8"X#12 SELF TAPPING SCREWS AT 8" O.C. EACH SIDE 2" W/O SNOW ON ROOF 2" W/O SNOW ON ROOF 0' - 2 1/4" STUD WALL SCREWS BY STUD WALL INSTALLER EXISTING TRUSS BOTTOM CHORD 1/2" PLATES 3"X3"X1/4" ANGLE W/ 3/4"Ø BOLTS EACH END. USE LOCK NUTS, FINGER TIGHT W24X76 1/2" STIFFENER PLATE HSS5X5X1/4 COLUMN 3/4" CAP PLATE 1/4 1/4 1/4 TYP. 1/4 TYP. 1/4 2" EXISTING BOTTOM CHORD OF TRUSS (2) HSS6X6X1/4 TUBES 3/8"X7"X12" PLATE EACH SIDE OF (2) HSS6X6 TUBES W/ (2) 3/4" A307 BOLTS TO EACH TUBE. PROVIDE LOCK NUTS, SNUG TIGHT. DO NOT OVERTIGHTEN. STUD WALLS NOT SHOWN FOR CLARITY EACH END 2" W/O SNOW ON ROOF 2" W/O SNOW ON ROOF 0' - 4" . (2) 7/8" LONG #12-24 SELF TAPPING METAL SCREW @ 6" O.C. 16 GAUGE TRACKS, TYP. 7/8" #12-24 SELF TAPPING METAL SCREWS @ 12" O.C. STUDS-600S137-33 MIN. @ 16" O.C. 16 GAUGE TRACK (2) HSS6X6X1/4" BEAMS. PROVIDE 1/2" CAMBER 1/8" PLATE AS REQ'D AS REQ'D AS REQ'D SPECIAL 16 GAUGE TRACK ALLOW FOR 2½" TO CENTER OF SCREW 600S137-33 STEEL STUDS @ 16" O.C. 1/8 2@12 EXISTING METAL ROOF DECK SEE ARCH. 1/8 2@12 WELD HORIZONTAL DOWELS TO COLUMN, USE A706 . SEE GENERAL NOTES GROUT SOLID SEE DETAIL 5/SE-511 BRICK VENEER, SEE ARCH CJP TOP & BOTTOM FLANGE INSULATION, SEE ARCH 8" CMU SEE PLAN FOR COLUMN AND BEAM SIZE 3/8"X5"X12" PLATE W/ (2) 5/8" TITEN HD ANCHORS (4" EMBED) @ 24" O.C. 3/8"X1 1/2" SHIMS @ 36" O.C. 1/2"X5"X10" PLATE @ 48" O.C. W/ (2) 5/8"X7" HEADED STUD ANCHORS (2) 2½X2X1/4 ANGLES TO 12'-0" LONG. (2) 3X2½X1/4 ANGLES TO 15'-0" LONG. (ALL ANGLES LONG LEG BACK TO BACK) 1/4 3/16 3" MIN. EACH ANGLE TYP. EACH END (4) 1/2" RODS, WELD ENDS AND GRIND SMOOTH (2) 4"X4"X5/16 AT 8" WALLS (2) 6"X4"X5/16 AT 12" WALLS HSS8X2X3/16 AT 8" WALLS HSS12X2X1/4 AT 12" WALLS 1/2" THREADED RODS, WELD AND GRIND SMOOTH. EMBED 6" IN EPOXY. PROVIDE LEVELING GROUT 0' - 3" 0' - 2" NOTE: DO NOT OVERCUT AT CORNERS ANGLES AT BOTTOM WHERE OPENING DOES NOT EXTEND TO FLOOR AND SLABS ABOVE 3/8"X1 1/2" SHIMS @ 48" O.C. 1/2"X5"X10" PLATE @ 48" O.C. W/ (2) 5/8"X7" HEADED STUD ANCHORS (2) 2½X2X1/4 ANGLES TO 12'-0" LONG. (2) 3X2½X1/4 ANGLES TO 15'-0" LONG. (ALL ANGLES LONG LEG BACK TO BACK) 1/4 3/16 3" MIN. EACH ANGLE TYP. EACH END TOP CHORD OF JOIST ABOVE 3/8"X1 1/2" SHIMS @ 48" O.C. 1/2"X5"X10" PLATE @ 48" O.C. W/ (2) 5/8"X7" TITEN HD BOLTS BY SIMPSON OR EQUAL (2) 2½X2X1/4 ANGLES TO 12'-0" LONG. (2) 3X2½X1/4 ANGLES TO 15'-0" LONG. (ALL ANGLES LONG LEG BACK TO BACK) 1/4 3/16 3" MIN. EACH ANGLE TYP. EACH END TOP CHORD OF JOIST OR TOP FLANGE OF BEAM ABOVE EXISTING MASONRY WALL (GROUT TOP 8" IF NOT GROUTED) 8" WALLS USE (2) 3½X3½X1/4 ANGLES (LONG LEGS BACK TO BACK) DOORS UP TO 48" WIDE AND (2) 4X3½X5/16 ANGLES LONG LEG BACK TO BACK FOR DOORS UP TO 72" WIDE. 12" WALLS NEW 12" MASONRY WALLS, USE (2) 5X5X5/16 ANGLES (VERTICAL LEGS BACK TO BACK) FOR OPENINGS 72" WIDE. NEW MASONRY WALL, #5 @ 24" O.C. VERTICAL, (2) # 4 HORIZONTAL @ 48" O.C. EXISTING CONCRETE SLAB ON METAL DECK EMBED VERTICAL 2½" IN EPOXY EXISTING MASONRY WALL REMOVE EXISTING MASONRY AS REQUIRED. INSTALL ANGLES AND GROUT SOLID AROUND END EXTEND REINFORCING TO TOP OF WALL PROVIDE HOLE FOR #5 REBAR. EXISTING 8" MASONRY WALL. SEE DETAIL 19/SE-501 FOR ADDED INFORMATION HOOK AT ENDS (2) #4 IN TOP AND BOTTOM OF 16" DEEP BOND BEAM SAW CUT 7" WIDE X LINTEL DEPTH OPENING AND GROUT W/ MASONRY LINTEL EXISTING MASONRY WALL (MAY BE CONCRETE AT SIMILAR CONDITION) (1) #4X40" DOWEL TO EXISTING MASONRY WALL. EMBED 6" IN EPOXY, USE WIRE SCREEN AS REQUIRED. NEW MASONRY WALL (CERAMIC-TILE COATED, WHERE REQUIRED). #5 @ 24" O.C. VERTICAL. (2) #4 @ 48" O.C. HORIZONTAL GLAZED TILE SEE ANGLE LINTEL SCHEDULE SEE MASONRY LINTEL SCHEDULE 1/2"X5"X10" PLATE @ 48" O.C. W/ (2) 5/8" BOLTS IN EPOXY. (USE SCREEN IF REQUIRED) TOP CHORD OF JOIST OR TOP FLANGE OF BEAM ABOVE EXISTING BEAM EXISITNG MASONRY WALL 1/2"X5"X10" PLATE @ 48" O.C. W/ (2) 5/8" BENT ANCHOR BOLTS EXISTING BEAM NEW MASONRY INFILL WALL TOP CHORD OF JOIST OR TOP FLANGE OF BEAM ABOVE PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 8/ 1 2 / 2 0 1 9 3 : 1 8 : 3 8 P M C : \ U s e r s \ D o n \ D o c u m e n t s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R 1 8 _ D B a r f u s s @ T B S E . u s . r v t DE T A I L S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-511 Checker Project Number Author NO SCALESE-511 1 NO SCALESE-511 3 NO SCALESE-511 5 NO SCALESE-511 4 NO SCALESE-511 6 NO SCALESE-511 2 NO SCALESE-511 14 NO SCALESE-511 13 NO SCALESE-511 12 NO SCALESE-511 11 NO SCALESE-511 10 NO SCALESE-511 9 NO SCALESE-511 8 NO SCALESE-511 7 NO SCALESE-511 16 NO SCALESE-511 15 FOR OPENINGS UP TO 72" WIDE NO SCALESE-511 17 NO SCALESE-511 18 NO SCALESE-511 19 NO SCALESE-511 20 NO SCALESE-511 21 NO SCALESE-511 22 NO SCALESE-511 23 NO SCALESE-511 24 NO. DESCRIPTION DATE 08/12/2019 EXISTING 12" MASONRY WALL, SEE PLAN 1/2" ROD AT 24" O.C. WELD ENDS AND GRIND SMOOTH (2) 6X4X5/16 ANGLE LINTEL. PROVIDE 6" BEARING EACH END. DO NOT OVERCUT OPENINGS AT CORNERS SAW CUT NEW OPENING. DO NOT OVERCOVER AT CORNERS EXISTING 12" MASONRY WALL 1/2" ROD AT 24" O.C. WELD ENDS AND GRIND SMOOTH. REMOVE BRICK VENEER AS REQUIRED AND REPLACE AFTER INSTALLING ANGLES. 6X6X5/16 ANGLES 3½X3X1/4 ANGLE LINTEL EXISTING BRICK VENEER 3/16 2 @ 24" PROVIDE 6" BEARING FOR ANGLE LINTELS EACH END. DO NOT OVERCUT OPENING AT CORNERS EXISTING MASONRY WALL #6 @ 24" O.C. (2) 6X4X5/16" ANGLES 1/2" RODS @ 24" O.C. WELD ENDS AND GRIND SMOOTH EXISTING MASONRY ABOVE EXISTING DOOR EMBED 6" IN EPOXY NEW MASONRY INFILL WALL EMBED 6" IN EPOXY (2) #4 @ 48" O.C. 0' - 4" 6" MIN. TYP. 1/2" RODS @ 24" O.C. WELD AND GRIND SMOOTH (2) 4X4X1/4 ANGLES BRACE TOP OF WALL AT BOTH SIDES OF OPENING. SEE DETAIL 16,17,18/SE-511 SIM. PROVIDE ADEQUATE SHORING SAWCUT OPENING. DO NOT OVERCUT AT CORNERS FOR OPENINGS TO 48" WIDE, SEE DETAIL 15/SE-511 FOR OPENINGS TO 6'-0" WIDE IN 8" WALLS. 6" BEARING 6" BEARING EXISTING MASONRY WALL 1/2" ROD AT 24" O.C. WELD ENDS AND GRIND SMOOTH (2) 6X6X5/16 ANGLE LINTEL. PROVIDE 6" BEARING EACH END SAW CUT NEW OPENING. DO NOT OVERCOVER AT CORNERS EXISTING 8" CMU EXISTING 4" CERAMIC TILE NEW OPENING EXISTING MASONRY (8" CMU, 4" CERAMIC TILE) EXISTING FOUNDATION WALL BRACE WALL ABOVE CEILING FAR SIDE TO STRUCTURE ABOVE. EACH SIDE OF EXISTING DOOR TO BE GROUTED AND AT SOUTH EDGE OF NEW DOOR, ATTACH NEW CERAMIC TILE TO BLOCK WALL W/ (3) WIRE LADDER TYPE JOINT REINFORCING. 5 SE-512 17 SE-511 8" MASONRY WALL TO BE REINFORCED W/ #5 VERTICAL @ 24" O.C. AND (2) #4 HORIZONTAL @ 48" O.C. EMBED 8" IN EPOXY TO EXISTING FOUNDATION WALL AND 6" IN EPOXY AT EXISTING MASONRY. EXISTING MASONRY WALL AND CERAMIC TILE EXISTING MASONRY WALL 8" MASONRY WALL CAULK JOINT EXISTING MASONRY AND STEEL COLUMN STUD WALLS 8" WALL ABOVE LINTEL ANGLES (2) 4X3 1/2X5/16 ANGLES. 6" BEARING ON MASONRY, WELD TO COLUMN 8" MASONRY WALL 6" MASONRY 6" SPACE EXISTING 4" CMU EXISTING 4" GLAZED TILE EXISTING W10X21 BEAM EXISTING 6X15.5 COLUMN NEW MASONRY WALL BELOW EXISTING BEAM, SEE PLAN 1/4 4 PLACES 20" TOTAL1/4 51/2" PLATE EXISTING 4½" CONCRETE SLAB EXISTING 14X22 BEAM EXISTING 6X15 COLUMN EXISTING 10X21 BEAM EXISTING 14X22 BEAM EXISTING 6X15 COLUMN EXISTING 10X21 BEAM HSS4X4X1/4 HSS6X4X1/4 TYP.1/4 0' - 6" TYP. 1/4 4" 5/8" PLATE TYPICALTYP. 1/4 4" TYP.1/4 4" HSS4X4X1/4 1/4 2 ROOF JOIST L2X2X1/4 ANGLE BRACE FROM ANGLE BEARING TO BOTTOM CHORD PANEL POINT (NOT REQ'D IF ANGLE BEARS AT TOP CHORD PANEL POINT) DECK OPENING L6X4X5/16 ANGLE (LLV) TO 10'-0" SPAN L6X4X5/16 FROM 1'-0" TO 3'-0" SPAN L3X3X1/4 FROM 1'-0" LLV (TYP.) EXISTING STEEL ROOF JOIST, TYP. EXISTING STEEL ROOF JOIST, TYP. B A A B NOTE: USE THIS DETAIL AT OPENINGS 10" OR GREATER. OPENINGS LESS THAN 12" SHALL BE REINFORCED WITH 16 GAUGE PLATE, 10" LARGER THAN OPENING IN ALL DIRECTIONS & FASTENED TO DECK @ 6" O.C. AROUND THE OPENING AND THE PLATE PERIMETER. NOTE: IF LOW POINT OF DECK OCCURS OVER ANGLE, WELD W/ 3/4"Ø PUDDLE WELDS AT 12" O.C. SE E P L A N 3/4 6" BRACE3/16 2 3/16 FLOOR BEAM FLOOR BEAM CHANNEL CHANNEL CHANNEL 9'-0" TO 12'-0"C8X11.5 LENGTH 1'-0" TO 6'-0" 6'-0" TO 9'-0" CHANNEL C6X8.2 C7X9.8 A B B A EXISTING CONC. SLAB ON METAL DECK, SEE PLAN 1/4" BENT PLATE ALL AROUND OPENING WITH 1/2" TITEN HD BOLTS BY SIMPSON OR EQUAL W/ 3½" MIN. EMBED AT 16" O.C. CHANNEL EXISTING CONCRETE SLAB ON METAL DECK. FLOOR BEAM CHANNEL 1/4" BENT PLATE ALL AROUND OPENING WITH 1/2" TITEN HD BOLTS BY SIMPSON OR EQUAL W/ 3½" MIN. EMBED AT 16" O.C. 1/4 1/4 1/4 2@12 1/4 2@12 1/4 NOTE: USE THIS DETAIL AT OPENINGS 8" OR GREATER. OPENINGS LESS THAN 8" SHALL BE CORE DRILLED AND LOCATED TO MISS STRUCTURE. WHEN SAWCUTTING OPENINGS IN CONCRETE ON METAL DECK, DO NOT OVERCUT AT CORNERS. 36" MAX. IF MORE THAN 36", CONTACT STRUCTURAL ENGINEER 36" MAX. IF MORE THAN 36", CONTACT STRUCTURAL ENGINEER 1/4" GAP BOTTOM CHORD LOADS TOP CHORD LOAD DOUBLE ANGLE STRUT (1) EACH SIDE PANEL POINT 0' - 6"0' - 6" 3/16 CONCENTRATED LOADS ON BOTTOM CHORD OF JOISTS NOTES: 1.PROVIDE DOUBLE ANGLE STRUTS BETWEEN CONCENTRATED LOAD AND PANEL POINT ON OPPOSITE CHORD WHERE CONCENTRATED LOADS EXCEED 150#. ANGLE STRUTS SHALL BE AS FOLLOWS: 2.WHERE CONCENTRATED LOADS OCCUR WITHIN 6" OF PANEL POINT, NO STRUT IS REQUIRED. ± 6" MAX.2 2 1 1 15 SE-512 #4 AT 12" O.C. NEW CONCRETE STEPS #5 AT 12" O.C. EMBED 3½ IN EPOXY. DO NOT BREAK OUT BOTTOM SLAB. VERIFY LOCATION OF EXISTING REINFORCING. LOCATE #5 TO MISS EXISTING REINFORCING. (3) #5 CONT. 10" 4" EXISTING STRUCTURE PROJECT NAME: SHEET NAME: OF SHEET NUMBER: DRAWN BY: CHECKED BY: PROJECT NO: DOCUMENT STATUS STATUS DATE REVISIONS CONSTRUCTION SET 06/28/2019 6/ 2 6 / 2 0 1 9 2 : 4 6 : 4 0 P M C : \ U s e r s \ L U K E \ D o c u m e n t s \ L o c a l R e vi t F i l e s \ B Y U I H A R T B U I L D I N G R E M O D E L - S t r u c t u r a l - R1 8 _ j s t a p l e s @ t b s e . u s . r v t DE T A I L S JO H N W . H A R T B U I L D I N G - AU X I L I A R Y G Y M RE M O D E L SE-512 Checker Project Number Author NO SCALESE-512 1 NO SCALESE-512 2 NO SCALESE-512 3 NO SCALESE-512 4 NO SCALESE-512 5 NO SCALESE-512 6 NO SCALESE-512 7 NO SCALESE-512 8 NO SCALESE-512 9 NO SCALESE-512 10 NO SCALESE-512 11 OPENING IN EXISTING ROOF DECK NO SCALESE-512 12 30" TO 48" (2) L2X2X1/4 UP TO 30" (2) L1 1/2 X 1 1/2 X 1/4 DEPTH OF JOIST ANGLE SIZE NO SCALESE-512 13 NO SCALESE-512 14 NO SCALESE-512 15 NO. DESCRIPTION DATE 08/03/2019