PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: August 26, 2019 APPROVED: August 30, 2019
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Christensen Auto Body
STREET ADDRESS: 900 N 2nd E CITY: Rexburg
AHJ: Madison Fire Department
SUBMITTAL TYPE: New SYSTEM TYPE: NFPA 13
HEAD COUNT: 233 TOTAL SYSTEMS: 1 AREA SQUARE FOOTAGE: 17,995
OCCUPANCY CLASSIFICATION: S-1, B CONSTRUCTION TYPE: 5B
SCOPE OF WORK: new building. Garage with 2 paint booths
SPRINKLER CONTRACTOR: Automatic Fire Sprinkler Services, Inc. (AFSS)
300 S. Catlin Street, Ste 2
Missoula, MT 59801
IDAHO LICENSE: FPSC-136
CONTACT NAME: John Venche
john@afssmt.com
PHONE NO: (208) 695-6553
SYSTEM DESIGNED BY: John Venche
john@afssmt.com
PHONE NO: (208) 695-6553
PLAN REVIEW COMMENTS: Approved with the following comments
1. Working Plans per NFPA 13, 23.1.3
2. Pressure relief valve required. (NFPA 13, 7.1.2.1)
3. Means shall be provided for forward flow test. (NFPA 13, 8.17.4.5.1)
4. General information sign per NFPA 13, 25.6.1.
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho
State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The
State Fire Marshal’s Office and its personnel does not take any responsibility for the back-flow device.