HomeMy WebLinkAboutFIRE ALARM SUBMITTAL - 18-00034 - 1160 Bond Ave - Dish One Satellite - New Building Fire : Security : Audio : Video : Camera Systems : Networking : Automation : Access Control : PERS Dish One Satellite Fire Alarm Submittals 1154 Bond Ave Rexburg, ID 83440 Jason Perron ID ELE #25206 NICET III #129957 jasonp@pinn-tech.net Cell – (208) 404-2002 Fire : Security : Audio : Video : Camera Systems : Networking : Automation : Access Control : PERS Building is a fully sprinklered business that will have a basketball court available to its employees. AFC-1000 Fire Alarm Control Panel 8830135 - REV B • 01/18 PAGE 1 OF 4 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description The AFC-1000 is an expandable analog/addressable releasing fire alarm system with a total system capacity of 1270 addresses. Additional capacity on the system is achieved using multi-point SLC modules The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules. The system is expandable with a total of nine additional addressable Signaling Line Circuits (SLC) each with a maximum of 127 devices. Each SLC may be comprised of any combination of smoke sensor, heat detectors or modules and allows for a total of 50 ohms of impedance and may use any wire compliant with the National Electrical Code (NEC). The AFC-1000 has a 10 Amp power supply with six Notification Appliance Circuits (NACs) and four Input/Output (I/O) circuits. The NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Each output is regulated and power limited. In addition, each output is uniquely programmable and may be configured for steady signal, strobe synchronization, constant power, door holder power, or releasing. The strobe synchronization includes Gentex, AMSECO, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. The NACs may be expanded using the PSN-1000 series intelligent power supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional input circuits and the AFC-1000 will support up to 31 power supplies. The system will synchronize the strobes system wide. In addition, the PSN- 1000E has space to allow the installation of up to six PAD100-SLCE SLC loop expansion cards. The cards mount on a stacker bracket that allows access to all SLC circuit connections. Technical Specifications Features • 1,270 addresses available on this analog addressable system • Additional system capacity achieved via multi-point SLC modules • 1500 software zones • NFPA 72 Compliant Smoke Sensitivity Test Built-In • System Operates as Class A or Class B for SLC, P-Link and NACs • 10 Amp Power Supply, Expandable to 315 amps • 6 NACS, Regulated, Rated at 3 Amps each, expandable to 192 • 4 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each, ideal for manual release and abort • Strobe Synchronization and System Wide Sync for Gentex®, AMSECO®, Cooper Wheelock® and System Sensor® strobes • Dedicated Alarm, Supervisory and Trouble Relays • 4,000 Event History Buffer • Optional two line DACT with UD-1000 that can report General, Zone or Point Information • Built in IP communicator • Ethernet Port for Programming and Network Connectivity • E-Mail System Status, Reports and Event Information • Product includes 5 year warranty Dimensions 18 15/16”W x 27 5/16”H x 4 7/16”D AC Mains 5.0 Amps @ 120 VAC 50/60 HZ 3.0 Amps @ 240 VAC 50/60 HZ Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window Battery Standby Current-130 mA Alarm Current-200 mA• 10 Amps power for NACs, I/O, and P-Link• 3 Amps per NAC, regulated• 1 Amp per I/O circuit, regulated• Battery Charger range 8-55 Ah• Battery Charger voltage 27.3 VDC• P-Link maximum current of 1 Amp Temperature and Humidity Range 32° to 120° (0°C to 49°C) with a maximum humidity of 93% non-condensing. S7357165-0328:0509 NYC Fire Dept. Certificate of Approval 6256 8830135 - REV B • 01/18 PAGE 2 OF 4 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com AFC-1000 Fire Alarm Control Panel SLC Loop Accessories SLC Loop Devices Modules The control panel may be connected with up to 1,270 addressable devices or modules in any combination. The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. Device Description PAD100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PAD100-PHD Combination Analog Photo Electric Smoke/Heat Detector – a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135° Fahrenheit heat detector. PAD100-HD Analog Fixed (135d-185dF) or Rate-of-Rise Heat Detector (software selectable) PAD100-DUCTR Addressable Duct Smoke Detector with Form C Relay. Addressable Duct Smoke Detector with Form C relay rated at 10a @ 250/120VAC or 8amps at 30VDC. PAD100-DUCT Addressable Duct Smoke Detector. PAD100-6B 6” round base that is mounted to an electrical box and wired for connection of one of the above sensors. PAD100-4B 4” round base that may be mounted to an electrical box and wired for connection to the above sensors. PAD100-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC. PAD100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call. PAD100-CD Addressable CO gas detector. PAD100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. Device Description PAD100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. PAD100-PSSA Single Action Addressable Pull Station. PAD100-PSDA Dual Action Addressable Pull Station. PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4” square electrical box. PAD100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PAD100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. Also provides two contact inputs. PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PAD100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PAD100-IM Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD100-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. PAD100-LED Module provides a single addressable LED that is controlled by the control panel. PAD100-SM Speaker Module provides switching for two audio channels. PAD100-LEDK Addressable LED and key switch that mounts in a single gang box. PAD100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised. For use with the PAD100-DUCTR only. PAD100-OROI One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. 8830135 - REV B • 01/18 PAGE 3 OF 4 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com AFC-1000 Fire Alarm Control Panel SLC Features Sensor Features User Interface Ethernet/I.P. Connection P-Link The Potter protocol is a digital protocol with a proven design for reliability and noise immunity. The system does not require special cable or conductors for connection of the Signaling Line Circuit as long as the cable is compliant with NFPA 70 and NFPA 72. The system allows for Class A or Class B installations as well as “T-Taps.”Each loop is capable of 127 points, with a max wiring distance of 10,000 ft. The sensors through the fire alarm control panel provide a real time status as to the condition of the system. The smoke detector sensitivity, heat detector temperature level and drift compensation are all programmable options. The system also allows for a day/night mode where the panel automatically adjusts the sensitivity depending on the time of day. To assist in the reduction of false alarms, the smoke detectors also have a maintenance warning that sends a trouble signal when a detector is dirty to the point that it can no longer maintain the programmed sensitivity. The AFC-1000 is shipped standard with an Ethernet connection. This connection is the programming port and may be connected to a building Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the Internet, the panel may be selectively programmed to e-mail alarm conditions, trouble conditions, supervisory conditions, test, Event History and detector status. An e-mail may be sent to the panel and the panel will e-mail the event history, detector status, configuration file or server status to an authorized E-mail account. In addition, reminders may be set to send an e-mail for service, testing or other conditions. In addition, the Ethernet connection is UL listed as an IP communicator. The IP communicator is listed to report to the UL listed Sur-Gard III IP receiver. The IP communicator replaces the traditional less reliable alarm communicator transmitter that utilized telephone lines. The IP communicator is an active method of connection and communication to the monitoring station. The AFC-1000 has a proprietary communication protocol that communicates through a RS-485 connection to field devices. Up to 64 devices may be connected to a single P-Link connection. The P-Link includes the communication terminals and regulated 24 VDC connection for the field devices. The field devices may be any of the following: PAD100-SLCE-Analog/Addressable loop expansion module (maximum of 9 per AFC-1000) SLCE-127 -Nohmi addressable loop expansion module for retrofit applications. The fire alarm control panel has a 4 x 40 LCD display to provide information to the system status. The keypad has navigation keys to allow manipulation of the Menu on board the panel. The panel is shipped standard with the following LEDs: • AC Power - Green • Alarm - Red • Earth Fault - Amber • Supervisory - Amber • Silenced - Amber • Trouble - Amber • Pre-Release - Amber • Release - Red The common buttons include a Silence, Reset, Acknowledge, and Drill. All of the buttons are accessible once the locked door is opened. RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked metal enclosure. RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked metal enclosure. Flush mount version available. LED-16(F) – 16 LED annunciator with common indicators in a locked metal enclosure. Flush mount version available. PSN-1000(E) – 10 amp, remote intelligent power supply with 6 NACs, 2 I/Os and a P-Link repeater. This panel is listed in conjunction with the AFC-1000 as releasing circuits. CA-6500 – Class A convertor that converts the SLC, NACs and P-Link connection UD-1000 – UL listed, Dual line telephone alarm communicator DRV-50 – LED driver expander, used to connect up to 50 LEDs in a graphic display FCB-1000 – Fire communication bridge, provides remote mounting of the Ethernet connection FIB-1000 – Fiber interface module, used to extend P-Link to multi- mode fiber (2 required) RLY-5 – Relay module, provides 5 form C relay contacts rated at 3.0 amps 24VDC/125AC SPG-1000 – Serial parallel gateway, allows for the connection to a serial or parallel printer The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure. MC-1000 Multi-Connect allows up to sixty-three AFC series panels to share a single reporting technology. AE-2 – Two card expansion cabinet AE-8 – Eight card expansion cabinet AE-14 – Fourteen card expansion cabinet 8830135 - REV B • 01/18 PAGE 4 OF 4 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com AFC-1000 Fire Alarm Control Panel 2 7 . 3 2 “ 2 6 . 0 0 “ 4.41” 3.75“ 17.60” 18.91” BOTTOM RIGHT SIDE DEPTH DE P T H TOP LEFT SIDE Dimensions Model Description Stock No. AFC-1000 Fire Alarm Control Panel 3992754 Ordering Information Potter Electric Signal (C)2017 1 of 5 AFC-4000 Battery and Voltage Drop Calculation Project Name: Standby Hours: 24 Alarm Mins: 5 Installed By: Batt Efficiency: 80% Designed By: SLC Type: Class B Date: 7/29/2019 NAC Source Voltage: 20.4 Model #: AFC-1000 Max Panel Current (amps): 10 Panel ID: Location: Qty Part #Description Each Total Each Total 1 AFC-1000 Analog Addressable FACP 0.130 0.130 0.220 0.220 Panel Standby: 0.130 Panel Alarm: 0.220 1 UD-1000 0.016 0.016 0.023 0.023 RA-6075 0.020 0.025 1 RA-6500F 0.020 0.020 0.050 0.050 LED-16F 0.025 0.025 LED-16F LED Annunciator LED Power*0.015 0.210 CA-6500 0.060 0.100 PSN-1000(E)0.015 0.015 NOHMI-SLCE-127*0.060 0.060 PAD100-SLCE-127 SLC Expander (9 Max)0.060 0.060 RLY-5 Relay Expander 0.025 0.035 RLY-5 Relay Expander Power*0.010 0.135 DRV-50 LED Driver Module 0.025 0.025 DRV-50 LED Driver Module LED Power*0.010 0.215 FCB-1000 Fire Communications Bridge 0.025 0.025 FIB-1000 Fiber Interface Board 0.030 0.030 MC-1000 Multi-Connect Expander 0.010 0.010 SPG-1000 Serial Parallel Gateway 0.040 0.040 *REQUIRED IF USING NOHMI PROTOCOL SLC DEVICES (Maximum current draw is 1 Amp per P-Link circuit, with 2 amps total)P-LINK Standby: 0.036 P-LINK Alarm: 0.073 *Only enter quantity if PLINK power is being used to power devices 1 PAD100-PD Analog Photo Smoke 0.000300 0.000300 0.000300 0.000300 PAD100-PHD Analog Photo Smoke/Heat 0.000300 0.000300 PAD100-HD Analog Fixed Temp Heat 0.000300 0.000300 PAD100-CD Analog Carbon Monoxide Detector 0.000300 0.000300 PAD100-DRTS Duct Remote Test Switch 0.010000 0.015000 PAD100-DUCT Addressable Duct Detector 0.000300 0.000300 2 PAD100-DUCTR*Addressable Duct Detector w/Relay 0.000500 0.001000 0.000500 0.001000 1 PAD100-PSSA/PSDA Addressable Pull Station Single/Dual Action 0.000200 0.000200 0.000200 0.000200 PAD100-MIM Micro Input Module 0.000200 0.000200 PAD100-SIM Single Input Module 0.000240 0.000240 1 PAD100-DIM Dual Input Module 0.000240 0.000240 0.000240 0.000240 PAD100-RM Relay Module 0.000240 0.000240 PAD100-OROI One Relay One Input Module 0.000240 0.000240 PAD100-TRTI Two Relay Two Input Module 0.000240 0.000240 PAD100-ZM*Conventional Zone Module 0.000240 0.000240 PAD100-NAC*Notification Appliance Circuit 0.000200 0.000200 PAD100-SM Speaker Module 0.000200 0.000200 PAD100-IM Isolator Module 0.000150 0.000150 PAD100-LED LED Module 0.000240 0.000240 PAD100-LEDK Addressable LED w/ Key Switch 0.000200 0.000200 PAD100-SB*Addressable Sounder Base 0.000200 0.000200 PAD100-RB Addressable Relay Base 0.000200 0.000200 PAD100-IB Addressable Isolator Base 0.000150 0.000150 PSA Analog Photo Smoke 0.000325 0.000325 PSHA Analog Photo Smoke/Heat 0.000325 0.000325 RHA Analog Rate of Rise Heat 0.000325 0.000325 FHA Analog Fixed Temp Heat 0.000325 0.000325 DDA Addressable Duct Detector 0.000325 0.000325 APS-SA/APS-DA Addressable Pull Station Single/Dual Action 0.000325 0.000325 Standby Alarm Flush Mount LED Annunciator Power Expander SLC Expander (9 Max) SLC Devices Class A Module LCD Annunciator Flush Mount LCD Annunciator Standby (amps) P-LINK (RS-485) (Both P-Link Circuits Combined) Potter AFC-1000 Battery & Voltage Drop Calculations FACP MAIN FACP SPRINKLER RISER ROOM DISH ONE SATELLITE REXBURG, ID 4SIGHT SECURITY JASON PERRON User assumes all responsibility to ensure the quantities and current draw values in this worksheet are accurate prior to submittal. Alarm (amps) Standby Alarm DACT Card Potter Electric Signal (C)2017 2 of 5 AFC-4000 Battery and Voltage Drop Calculation MCM Mini Contact Input Module 0.000325 0.000325 SCM-4 Single Contact Input Module 0.000325 0.001000 DCM-4 Dual Contact Input Module 0.000325 0.001000 TRM-4 Twin Relay Output Module 0.000325 0.001000 CIZM-4 *Conventional Zone Input Mod 0.000325 0.001000 MOM-4 *Monitored Output Module 0.000325 0.001000 ARB *Detector Base w/Relay 0.000325 0.000325 ASB *Detector Base w/Sounder 0.000325 0.000325 SCI **Short Circuit Isolator (Class A)0.000325 0.002340 AIB **Detector Base w/Isolator (Class A)0.000325 0.002340 IM/IB/SCI/AIB Class B ** 1 0.000000 0.000000 0.036000 0.036000 *Requires Aux Power (Configure Below)SLC Standby: 0.001740 SLC Alarm: 0.037740 ** Standby (amps)Alarm (amps) Ckt Use Description Total Total 1 Notification 0.00000 2.03300 2 Notification 0.00000 1.40800 3 Notification 0.00000 1.35500 4 Notification 0.00000 0.19800 5 Aux Power 0.06000 0.12000 6 Unused 0.00000 0.00000 NAC Standby:0.06000 NAC Alarm:5.11400 Standby (amps)Alarm (amps)Ckt Use Description Total Total 1 Aux Power 0.07100 0.20000 2 0.00000 0.00000 3 0.00000 0.00000 4 0.00000 0.00000 I/O Standby:0.07100 I/O Alarm:0.20000 Battery Calculation Summary Standby (amps)Alarm (amps) Panel Current: 0.13000 0.22000 P-Link Current: 0.03600 0.07300 SLC Device Current: 0.00174 0.03774 NAC Circuit Current: 0.06000 5.11400 I/O Circuit Current: 0.07100 0.20000 SLC Loop Type: Class B Total Standby: 0.298740 Total Alarm: 5.64474 Device Addresses Used:5 Standby Hours: 24 Alarm Mins: 5 Device Addresses Available: 127 AH Required:7.17 AH Required:0.48 10 Total Combined Standby & Alarm AmpHours Required: 7.65 Efficiency Factor: 80% Required Battery AmpHours: 9.56 Battery AmpHours Provided: 18 NAC Circuit Configuration & Voltage Drop 7/29/2019 NAC 1 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 275 1.375 2.033 17.60 16 Qty Lookup Type Each Total Each Total 3 Strobes 0.000000 0.000000 0.120000 0.360000 Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to two 55 AH batteries. DISH ONE SATELLITE Circuit Devices Gentex GCS24 Strobe, 15cd NAC Circuits (See NAC Configuration below) GYM & NORTH TENANT SPACE GYM & SOUTH TENANT SPACE I/O Circuits (See I/O Configuration below) CELLULAR RADIO NOT USED NOT USED NOT USED SOUTH TENANT SPACE Description SLC Loop Alarm LED Current See the installation manual for special considerations when installing IM, IB, AIB, SCI devices on Class B loops. Current Draw from Install Manual FIRE SPRINKLER FDC GYM & NORTH TENANT SPACE Standby (amps)Alarm (amps) DUCT SMOKE DETECTORS Notification Potter Electric Signal (C)2017 3 of 5 AFC-4000 Battery and Voltage Drop Calculation 1 HORN/STROBE 0.000000 0.000000 0.275000 0.275000 2 HORN/STROBE 0.000000 0.000000 0.404000 0.808000 2 HORN/STROBE 0.000000 0.000000 0.295000 0.590000 Total Standby:0.00000 Total Alarm: 2.03300 NAC 2 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 175 0.875 1.408 19.17 16 Qty Lookup Type Each Total Each Total 5 Strobes 0.000000 0.000000 0.120000 0.600000 2 HORN/STROBE 0.000000 0.000000 0.404000 0.808000 Total Standby:0.00000 Total Alarm: 1.40800 NAC 3 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 150 0.750 1.355 19.38 16 Qty Lookup Type Each Total Each Total 2 Strobes 0.000000 0.000000 0.120000 0.240000 3 Strobes 0.000000 0.000000 0.120000 0.360000 1 HORN/STROBE 0.365000 0.365000 2 HORN/STROBE 0.195000 0.390000 Total Standby:0.00000 Total Alarm: 1.35500 NAC Circuit Configuration & Voltage Drop (cont'd) NAC 4 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 50 0.250 0.198 20.35 16 Qty Lookup Type Each Total Each Total 1 Horn Strobes 0.000000 0.000000 0.198000 0.198000 Gentex GCC-24, 115cd, Low db Gentex GCC-24, 15cd, Low db GYM & SOUTH TENANT SPACE FIRE SPRINKLER FDC SOUTH TENANT SPACE Standby (amps)Alarm (amps) Notification Circuit Devices Potter HS-24-WP, HSLP-24-WP 75cd, Hi db Description Standby (amps) Notification Gentex GCS24 Strobe, 30cd Gentex GCC-24, 150cd, Hi db Description Description Circuit Devices Gentex GCS24 Strobe, 15cd Standby (amps) Gentex GCS-24, 95cd, Low db Gentex GCS-24, 150cd, High db Alarm (amps) Gentex GCS24 Strobe, 15cd Circuit Devices Notification Gentex GCC-24, 75cd, Low db Alarm (amps) Potter Electric Signal (C)2017 4 of 5 AFC-4000 Battery and Voltage Drop Calculation 0.143000 0.000000 Total Standby:0.00000 Total Alarm: 0.19800 NAC 5 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 175 0.875 0.120 20.30 16 Qty Lookup Type Each Total Each Total 2 SLC Aux Power 0.030000 0.060000 0.060000 0.120000 Total Standby:0.06000 Total Alarm: 0.12000 NAC 6 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 150 0.750 0.000 20.40 16 Qty Lookup Type Each Total Each Total Total Standby:0.00000 Total Alarm: 0.00000 I/O Circuit Configuration & Voltage Drop 7/29/2019 I/O 1 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 5 0.025 0.200 20.40 16 Qty Lookup Type Each Total Each Total 1 COMMUNICATOR 0.071000 0.071000 0.200000 0.200000 Standby (amps)Alarm (amps) DISH ONE SATELLITE CELLULAR RADIO Description Description Potter PAD100-DUCTR Duct Det w/ Relay Aux Power DUCT SMOKE DETECTORS Unused Alarm (amps)Circuit Devices Standby (amps) NAPCO SLE-CDMA-FIRE RADIO Description Standby (amps)Alarm (amps)Circuit Devices Aux Power Circuit Devices Potter Electric Signal (C)2017 5 of 5 AFC-4000 Battery and Voltage Drop Calculation Total Standby:0.07100 Total Alarm: 0.20000 I/O 2 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 0.000 0.000 20.40 16 Qty Lookup Type Each Total Each Total Total Standby:0.00000 Total Alarm: 0.00000 7/29/2019 I/O 3 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 0.000 0.000 20.40 16 Qty Lookup Type Each Total Each Total Total Standby:0.00000 Total Alarm: 0.00000 I/O 4 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4 Usage:Description: Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd #14 Solid 2.5 0.000 0.000 20.40 16 Qty Lookup Type Each Total Each Total Total Standby:0.00000 Total Alarm: 0.00000 Description Standby (amps)Alarm (amps) NOT USED NOT USED Circuit Devices Alarm (amps)Standby (amps) Description Description Circuit Devices Circuit Devices Standby (amps)Alarm (amps) DISH ONE SATELLITE NOT USED MFG. #8830031 - REV 111/11PRINTED IN USA PAGE 1 OF 1 RA-6500 LCD ANNUNCIATOR Potter Electric Signal Company, LLC • St. Louis, MO • 800-325-3936• Canada: 888-882-1833 • www.pottersignal.com Install in accordance with compatible installation manual. Description The RA-6500 is a LCD remote annunciator for the PFC-6000 Series addressable fire control panels. The RA-6500 communicates using a RS-485 connection to the main panel providing common indication of Alarms, Supervisory, Trouble and other system status and control functions. The RA-6500 features a 4x40, 160 character LCD display with LED’s for Power, Alarm, Supervisory, Trouble, and Silenced conditions. It can be mounted on a single gang electrical box or a four square electrical box. The annunciator is enclosed in a sheet metal enclosure and has a Potter lock securing the keypad. Figure 1: Class B Wiring Example Figure 2: Class A Wiring Example Features Operates with all Potter PFC-6000 series• Industry leading 4 line by 40 Character LCD• Common buttons for navigation• Common LEDs for status indication• 31 annunciator per panel• Maximum wire length of 6,500 feet• Size (W x H x D): 9 13/16" x 7 1/6" x 1 11/16" Electrical Specs Standby Current 20 mA• Alarm Current 50 mA• Installation The RA-6500 is connected to the fire alarm control panel using a four wire RS-485 connection. The connection is power limited and supervised. Up to thirty-one (31) RA-6500 LCD annunciators can be connected using Class B or Class A wiring. Product includes a 5 year warranty S2930 7165-0328: 0195 8830048 - REV A • 1/15 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com UD-1000 Digital Alarm Communicator Description The UD-1000 Digital Alarm Communicator Transmitter (DACT) provides for up to two (2) phone lines for communication to a monitoring station. The UD-1000 communicates using the SIA- DCS or Ademco Contact ID protocols. When enabled, the DACT automatically monitors each phone line or voltage and has the ability to seize the line and connect with a remote receiver. Once the communication is complete, the DACT will hang up. The DACT is provided with an RJ-11 jack for each phone line and a RJ-11 to RJ-33 cord. In order for the DACT to work properly, it must be installed on a plain old telephone service (POTS) line or equivalent deemed by the authority having jurisdiction. The DACT must be installed before any other equipment to ensure it can seize the phone line. Phone lines are high voltage and should be run in a separate conduit from other circuits. The wire conductors connecting the DACT to the phone system should be 26 AWG or larger. Technical Specifications Operating Voltage 22.0-24.0V Standby Current 16mA Alarm Current 23mA Max UD-1000s per panel 1 Dimensions 4”W * 6”H * 1-5/8”D Operating Tempuratures 0°C - 49°C (32°F- 120°F) Operating Humidity Range 10% - 93% @ 30°C (86°F) (non-condensing) Mounting Options In FACP Behind keypad Shipping Weight 0.47 lbs Features • Allows for communication to Monitoring Station • Communicates using SIA-DCS or Ademco Contact ID Protocols • For use with 6000 series and P series Addressable Panels • Status LEDs indicate operation of DACT card • Installs with ease behind main panel LCD display via User Interface bracket • Device address is set by dipswitches located on DACT card • Installation materials including 4 pin connector and screw are supplied with DACT card 7165-0328:0195S735 8830048 - REV A • 1/15 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com UD-1000 Digital Alarm Communicator UD-1000 DACT Installation on PFC-6030/6075R UD-1000 DACT Installation on PFC-6800/6200 Installation Slides in guides under main board. Screw DWG #593-32A UD-1000 DACT Slides in guides under main board. Screw DWG #593-32A UD-1000 DACT DETAIL E SCALE 1 : 1 DETAIL D SCALE 1 : 1 P Connector on PFC-6075 main board P Connector on PFC-6800 main board DETAIL B SCALE 1 : 1 Install in accordance with compatible fire alarm control panel installation manual Fig 1 Fig 2 The UD-1000 DACT is connected to the control panel using the provided four-wire cable connection (P/N 5210514) between P4 and UD-1000 P1. The connection is power limited and supervised. 1. Power system down. 2. Slide the UD-1000 into the card guides located under the User Interface bracket. 3. Secure the UD-1000 to the User Interface bracket using the provided #6-32x3/8” screw 4. Install the provided four-wire conductor jumper between UD-1000 P1 and P4. PAD100-DIM Dual Input Module 8830082 - REV C • 3/18 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description The PAD100-DIM uses one (1) SLC loop address when monitoring two (2) Class B circuits or one (1) Class A circuit. The module mounts on either a 4” square or double gang box. The module is capable of monitoring two (2) separate class B circuits making it ideal for monitoring sprinkler waterflow and valve tamper switches when they are located in the same proximity. The PAD100-DIM includes one red LED to indicate the module’s status. In normal condition, the LED flashes when the device is being polled by the control panel. When an input is activated, the LED will flash at a fast rate. Application The PAD100-DIM is compatible with Potter’s IPA and AFC/ARC series addressable fire alarm control panels. The PAD100-DIM is an interface module used to monitor dry contact devices such as sprinkler waterflow, valve tamper switches, or conventional pull stations. The module is capable of monitoring two separate Class B or one Class A circuits. Setting the Address Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the PAD100-DIM. When the PAD100- DIM is used to monitor two individual Class B circuits a single device address is assigned, each input is then identified as a sub-point of the module address. For example, if the address number is assigned as “8”, the first input will be “8.1” and the second input will be “8.2”. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device: 1. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Technical Specifications Operating Voltage 24.0V Max SLC Standby Current 240μA Max SLC Alarm Current 240μA Max Wiring Resistance of IDC 100 Ω Max Wiring Capacitance of IDC 1μF EOL Resistor 5.1K Ω Operating Temperature Range 32 to 120ºF (0 to 49ºC) Operating Humidity Range 0 to 93% (non-condensing) Max no. of Module Per Loop 127 units Dimensions 4.17” (106mm)L × 4.17” (106mm)W × 1.14” (29mm)D Mounting Options Standard 4” Square or Double Gang Box Shipping Weight 0.6 lbs Features • Single module with dual contact monitoring inputs • Two (2) Class B or one (1) Class A monitoring inputs • SLC Class A, Class X & Class B • Mounts in a standard 4” or double gang box • Wiring terminals accessible when mounted in box • All wiring terminals accept 22 to 12 AWG • Product includes a 5 year warranty NOTE: This addressable module does not support 2-wire smoke detectors. 8830082 - REV C • 3/18 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PAD100-DIM Dual Input Module FROM FACP OR PREVIOUS MODULE TO NEXT MODULE NOTE:END-OF-LINE RESISTORIS NOT REQUIRED MOVE THE “CL-A” DIP SWITCHTO “UP” POSITIONFOR CLASS A WIRING Installation Using Compatible Electrical Box Wiring Diagrams PAD100-DIM With One Class A Circuit PAD100-DIM With Two Class B Circuits Fig 2 Fig 3 Fig 1 Model Description Stock No. PAD100-DIM Dual Input Module 3992703 Ordering Information MOVE THE “CL-A” DIP SWITCHTO “DOWN” POSITIONFOR CLASS B WIRING FROM FACP OR PREVIOUS MODULE TO NEXT MODULE END-OF-LINE RESISTOR5.1K OHM 12W END-OF-LINE RESISTOR5.1K OHM 12W Part #3005013 Part #3005013 PAD100-PSSA/PSDA Addressable Pull StationSingle/Dual Action 8830097 - REV C • 3/18 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description The PAD100-PSSA (Single Action) is activated by simply pulling the white “T” bar handle down. The PAD100-PSDA (Dual Action) is activated by lifting the front cover and then pulling the white “T” bar handle down. Once activated, the “T” bar cannot be reset without opening the front cover. Opening the front cover will also activate the pull station. To reset the PAD100-PS Series, use the Potter WS-93 key to unlock and open the front cover. Once the cover is open, push the “T” bar back into the normal position and re-secure the front cover. Application The PAD100-PSSA/PSDA is compatible with Potter’s IPA and AFC/ ARC series addressable fire alarm control panels. It is a non-coded addressable pull station available in either a single or dual action model and installs on a single gang box or surface mounts using the P32-BB or P32-DBB (deep) back box. Technical Specifications Operating Voltage 24.0 VDC Max SLC Standby Current 200uA Max SLC Alarm Current 200uA Environmental Limitations 32°F - 120°F (0° - 49°C) Indoor Only Dimensions 4.75” H x 3.25” W x 1.75” D Relative Humidity Range 0 - 93% (non-condensing) Mounting Options Single gang box or Potter P32-BB/DBB Shipping Weight APS-SA - 1.22 lbs. APS-DA - 1.46 lbs. Features • Single or Dual Action versions • Durable die-cast construction • Reset key matches the fire alarm control panels • Compatible with IPA Series panels • SLC Class A, Class X & Class B • Product includes a 5 year warranty 8830097 - REV C • 3/18 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PAD100-PSSA/PSDA Addressable Pull StationSingle/Dual Action The PAD100-PS Series uses one SLC address assigned to the device. The address is set using the DIP switch located on the back of the PAD100-PS device. Setting the Address Fig 1 Fig 2 Model Description Stock No. PAD100-PSSA Addressable Pull Station, Single Action 3992721 PAD100-PSDA Addressable Pull Station, Dual Action 3992720 Ordering Information P POTTER P POTTER Pull Station Front View Pull Station Back View and Wiring PAD100-PSDA PAD100-PSSA FACTORY WIRED CONTACTS FROM FACP OR PREVIOUS DEVICETO NEXT DEVICE PAD100-PD Photoelectric Smoke Sensor 8830108 - REV C • 3/18 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description The Photoelectric Smoke Sensor is a listed Analog Addressable smoke sensor compatible with fire alarm control panels that utilize the Potter Addressable Device (PAD) protocol. The PAD100-PD is a low profile smoke sensor with a wide sensitivity range. The sensor and base (not included) are made of a durable plastic in an off-white color to blend in with the ceiling. The PAD100-PD has a sensitivity range of 1.0 to 3.7 % per foot and is UL. The PAD100-PD features drift compensation and has built in dirty detector warning as well as. The PAD100-PD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements. The sensor is compatible with any of the PAD series sensor bases and simply twists on. The PAD100-PD is addressed using DIP switches in the rear of the sensor and can be easily programmed in the field without special tools. Setting the Address Each addressable device on the SLC loop must have a unique address from 1 to 127 to function properly. The address is set using DIP switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following: 1. Power to the device is removed 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Technical Specifications Operating Voltage 24 VDC Detector Current Draw 300 µA Alarm indicator 1 LED Alarm set-point range 1.0 to 3.7 %/ft 3.6-12 %/m Installation temperature range 32 to 120 ° F / 0 to 49 ° C Operating relative humidity range 0% to 93% (Non-condensing) Start-up time Max. 1 sec. Maximum number of addresses per loop 127 Maximum number of lighted indicators in alarm per loop.30 Color Eggshell White Weight (without base)101g (3.56oz) Dimensions (without base) Height: 1.35 in (34mm) Diameter: 3.93 in (100 mm) Features • Low profile, less than 2 inches with the base • Wide selectable sensitivity range of 1.0 to 3.7%/foot • Sensor communicates sensitivity to control panel • UL listed smoke calibration and sensitivity • Optional locking tab to prevent unwanted removal • Simple DIP switch address setting, no programming tool required • LED alarm indicator • Product includes a 5 year warranty 8830108 - REV C • 3/18 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PAD100-PD Photoelectric Smoke Sensor Air Velocity Ratings Operation Sensor Sensitivity Spacing Compatible Bases Model Description Stock No. PAD100-PD Photoelectric Smoke Sensor 3992733 Ordering Information The PAD100-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD100-PD will operate even though the LED may not illuminate. The PAD100-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is in an active status. The polling LED can be turned off if desired for less conspicuous operation. The PAD100-PD with the PAD100-4DB or PAD100-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector. The PAD100-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the sensor is installed over time, the sensor compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty sensor. The sensor will then have to be cleaned or replaced. The PAD100-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs. NOTE: As required by NFPA, do not install the sensors until all construction is complete and the work area has been thoroughly cleaned. If the sensors have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service. The PAD100-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications. All bases will mount on a single gang, double gang, octagon, 4” square or mud ring electrical box. Device Description Stock No. PAD100-4DB 4” Standard Base 3992731 PAD100-6DB 6” Standard Base 3992732 PAD100-IB 6” base with an isolator module included. 3992730 PAD100-RB 6” base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 3992728 PAD100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729 PAD100-SPKB 6” base with speaker included 3992762 8830107 - REV B • 12/17PRINTED IN USA PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PAD100-4DB/6DB 4”/6” Addressable Detector Base Features Application The Potter PAD100-6DB and PAD100-4DB detector bases are used to install Potter’s addressable smoke and heat detectors. The PAD100- 6DB will mount on a single gang, double gang, octagon or 4” square electrical box. Description The PAD100-6DB and PAD100-4DB are low-profile, surface mount bases used with Potter’s addressable detectors. The base uses screw-clamp terminals that accept wire ranging from 22 to 14 AWG. When installed on recessed electrical boxes the PAD100-6DB is wide enough to completely cover the back box and the immediate surrounding area. The base is equipped with a locking tab to deter unauthorized removal of the attached detector. Technical Specifications Mounting Options Single gang, double gang, octagon, and 4” square box Terminals Screw-Clamp Type Wire Guage 22 to 12 AWG Dimensions Diameter: 6.3 in (166 mm) Height 0.72 in (18 mm) Shipping Weight 87g (3.07 oz) Material Durable Plastic • Terminals Marked with Polarity to assist with installation • Duplicate terminals for in and out SLC wiring • Terminals accept 22 to 12 AWG wire sizes • Installs on single gang, double gang, octagon or 4” square box • Locking tab prevents unauthorized detector removal • Product includes 5 year warranty 8830107 - REV B • 12/17PRINTED IN USA PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PAD100-4DB/6DB 4”/6” Addressable Detector Base S+ S- S+ S- Wiring Diagram Model Description Stock No. PAD100-6DB 6” Sensor Base 3992732 PAD100-4DB 4” Sensor Base 3992731 Ordering Information Locking Feature The PAD100-6DB and PAD100-4DB include a locking feature that prevents removal of the detector without using a tool. 1. To eliminate this feature, break off the locking tab (refer to Figure 1), and then install the detector. 2. To remove the detector from the base when the locking feature has been enabled, insert a small screw driver into the slot on the base to push the plastic tab while simultaneously turning the detector head counter-clockwise. Break off tab (gray area) in image to disable locking feature. To FACP Loop (SLC)First Detector Base Last Detector Base Insert small screwdriver into slot to remove detector from base. Fig. 1 Fig. 2 Fig. 3 PAD100-DUCTR Analog Addressable Duct Detector 8830098 - REV D • 3/18 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description The PAD100-DUCTR is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7”) is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws. Application The Potter Electric PAD100-DUCTR duct smoke detector provides early detection of smoke and products of combustion present in air moving through HVAC ducts in commercial, industrial and residential applications. The PAD100-DUCTR is compatible with the IPA and AFC/ARC series addressable fire alarm control panels. Technical Specifications Duct Detector Model Number PAD100-DUCTR Operating Voltage 24 VDC Current Draw 500 μA Detector Head Model PAD100-DD Detector Head Type Photoelectric Sensitivity Test Method Self diagnostic test Air Velocity 100 to 4000 ft./min Ambient Temperature 32°F to 120°F (0°C to 49°C) Humidity 10% to 85% Relative humidity (non-condensing) Housing Material Plastic backbox, clear plastic cover Finish Gray backbox with clear cover Dimensions 13 1/2”L x 4 1/2” W x 2 1/4” H Maximum Net Weight 2 lbs. Sampling Tubes 2.5 ft., 5 ft., or 10 ft. Relay contact rating 8A@30VDC, 10A@120VAC, 10A@250VAC Features • Detects smoke in building HVAC ducts • Ships complete with housing and head • Compatible with addressable IPA and AFC/ARC series panels • SLC Class A, Class X & Class B • Installation without removing the head • Listed Air Velocity of 100 to 4,000 ft/minute • No screens or filters in housing • Durable plastic enclosure and clear cover • Integrated cover tamper switch • Utilizes simple snap in sampling tubes STN series • One form C relay • Compatible with supervised PAD100-DRTS remote test switch, MS-RA, MS-KA/R, MS-KA/P/R remote indicators • Product includes a 5 year warranty 8830098 - REV D • 3/18 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PAD100-DUCTR Analog Addressable Duct Detector Air duct smoke detectors shall be Potter Electric PAD100-DUCTR Series. The detectors shall be listed by Underwriters Laboratories per UL 268A. The detectors shall operate at air velocities from 100 feet per minute to 4000 feet per minute. The duct detector housings shall be of plastic construction and complete mechanical installation may be performed without removal of detector cover. Visual indication of alarm and power must be provided on detector front. Detector heads shall not require additional filters or screens which must be maintained. The housing shall contain a detector base and PAD100-DD duct smoke detector head. Terminal connections shall be of the screw type and be a minimum of # 12 screw. All wiring must comply with local codes and regulations. Detector shall use the STN series of sampling tubes. Engineering Specifications Wiring Diagrams Fig 1 Fig 2 Model Description Stock No. PAD100-DUCTR Analog Addressable Duct Detector 3992712 PAD100-DRTS Duct Remote Test Switch 3992711 MS-RA Remote Annunciator 1000256 MS-KA/R Remote Annunciator with Test/Reset Switch 1000254 MS-KA/P/R Remote Annunciator with Test Switch 1000253 Model Description Stock No. STN-2.5 2.5’ Sampling Tube 1000274 STN-5 5’ Sampling Tube 1000275 STN-10 10’ Sampling Tube 1000276 Ordering Information PAD100-DRTS Wiring MS-KA/P/R Wiring TO 24VDCPOWER FORM C RELAY10A, 250VAC TO NEXT MODULE FROM FACP OR PREVIOUS MODULE PAD100-DRTS SUPERVISION OPTION TO PAD100-DRTS Note: Keep jumper in“On” position when using the PAD100-DRTSfor full wiring supervision. 24VDC FROM FACP OR PREVIOUS MODULE FORM C RELAY10A, 250VAC TO NEXT MODULE FROM FACP ORPREVIOUS MODULE Note: Jumper must be in “O” position when using the MS-KA/P/R. 24VDC TO FACP OR NEXT MODULE TO MS-RA (RED WIRE)TO MS-RA (BLACK WIRE) SUPERVISION OPTIONSHOWN IN “OFF” POSITION GCS/GCC 24VDC S E R I E S Commander4 Series Selectable Candela Evacuation Signals •• AANNSSII//UULL 446644 aanndd AANNSSII//UULL 11997711 LLiisstteedd •• FFMM AApppprroovveedd •• CCSSFFMM::77113355--00556699::112222 ((GGCCCC)) 77112255--00556699::112233 ((GGCCSS)) •• MMEEAA::228855--9911--EE Product Listings Product Compliance •• NNFFPPAA 7722 •• AAmmeerriiccaannss wwiitthh DDiissaabbiilliittiieess AAcctt ((AADDAA)) •• IIBBCC//IIFFCC//IIRRCC •• CCiittyy && SSttaattee oorrddiinnaanncceess//LLaawwss//RReegguullaattiioonnss •• QQuuaalliittyy MMaannaaggeemmeenntt SSyysstteemm iiss cceerrttiiffiieedd ttoo:: IISSOO 99000011::22000088 Applications The GCS/GCC Series is a ceiling mount strobe or horn/strobe combination that offers dependable audible and visual alarms and the lowest current consumption. The GCS/GCCoffers tamperproof field selectable candela options of 15, 30, 75, 95, 115 and 150 candela. The GCC horn offers a continuous or synchable temporal three in 2400Hz and mechanical tone. All tones are easy for the professional to change in the field by using switches. The models are shipped from the factory in the temporal three alarm mode. The GC Series has a very minimal operating current and has a minimum flash rate of 1Hz regardless of input voltage. The Commander4 Series comes standard with the 4" mounting plate which incorporates the popular Super-Slide®feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The Commander4 also features the patented Checkmate®- Instant Voltage Verification feature which allows the installer to check the voltage drop draw without removing the signal. The GC Series appliances are ANSI/UL 464 and ANSI/UL 1971 listed for use with fire protective systems and are warranted for three years from the date of purchase. Standard Features • Nominal voltage 24VDC •Tamperproof field selectable candela options of 15, 30, 75, 95,115 & 150 •Super-Slide®Bracket - Ease of Supervision Testing • Checkmate®- Instant Voltage Verification • Unit Dimensions: 6” (15.24 cm) x 2.6” (6.604 cm) •Synchronize strobe and/or horn with Gentex AVSM Control Module •Prewire entire system, install mounting bracket, then install signals • Documented lower installation and operating costs • Input Terminals 12 to 18 AWG •Switch Selection for High or Low dBA •Switch Selection for 2400Hz or Mechanical Tone •Switch Selection for Continuous or Temporal 3 •Tamperproof re-entrant grill • Surface mount with the GCSB (Gentex Ceiling Surface Mount Box) • Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions) •Faceplate available in red or off-white Patents •• 77,,337755,,661177 MMaayy 2200,, 22000088 MMooddeell NNuummbbeerr PPaarrtt NNuummbbeerr NNoommiinnaall VVoollttaaggee CCaannddeellaa GCS24CR 904-1213-002 24VDC 15, 30, 75, 95, 115, 150 GCS24CW 904-1215-002 24VDC 15, 30, 75, 95, 115, 150 GCS24PCR 904-1214-002 24VDC 15, 30, 75, 95, 115, 150 GCS24PCW 904-1216-002 24VDC 15, 30, 75, 95, 115, 150 MMooddeell NNuummbbeerr PPaarrtt NNuummbbeerr NNoommiinnaall VVoollttaaggee CCaannddeellaa RReevveerrbbeerraanntt ddBBAA @@ 1100fftt.. ppeerr AANNSSII//UULL 446644 IInn AAnneecchhooiicc RRoooomm ddBBAA @@ 1100fftt.. GCC24CR 904-1209-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCC24PCR 904-1210-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCC24CW 904-1211-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCC24PCW 904-1212-002 24VDC 15, 30, 75, 95, 115, 150 81-86 90 GCS Series 24 Volt Ceiling Mount Selectable Strobe GCC Series 24 Volt Ceiling Mount Selectable Horn/Strobe HHoorrnn MMooddee MMiinniimmuumm ddBBAA @@ 1100fftt.. ppeerr AANNSSII//UULL 446644 ((HHIIGGHH)) MMiinniimmuumm ddBBAA @@ 1100fftt.. ppeerr AANNSSII//UULL 446644 ((LLOOWW)) RReegguullaatteedd 2244VVDDCC MMaaxx.. OOppeerraattiinngg @@ HHiigghh SSeettttiinngg ((mmAA)) Temp 3 2400Hz 83 75 23 Temp 3 Mechanical 81 73*22 Continuous 2400Hz 86 78 23 Continuous Mechanical 84 76 22 Candela 15cd 30cd 75cd 95cd 115cd 150cd 2244VVDDCC ((1166--3333 VVoollttss))2244VVDDCC 7722mmAA 110011mmAA 116677mmAA 220000mmAA 221144mmAA 228866mmAA UL Max1 120mA 120mA 200mA 220mA 290mA 321mA NOTES: •Operating temperature: 32°to 120°F (0° to 49°C). The GC Series is not listed for outdoor use. •The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. •For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual. •Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe products (see Technical Bulletin Number 014). *Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). 11 RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual. MMooddeell DDeessiiggnnaattiioonnss:: C = Ceiling Mount R = Red Faceplate W = White Faceplate All units are available in plain (no lettering). PPllaaiinn uunniittss aarree nnoonn--rreettuurrnnaabbllee.. GC24 Product Strobe Current Ratings (mA) GCC24 Product Horn Decibel and Current Ratings (mA) Mounting Super-Slide® 1. SLIDE ONTO BRACKET 2. INSERT LOCKING SCREW Checkmate®Instant Voltage Verification Switch positions 1 and 2 in the down position to select isolated horn and strobe power inputs. Switch 3 selects between temporal or non-temporal tone. Up is temporal. Switch 4 selects between mechanical or high frequency tone. Up is mechanical. Switch 5 selects between high or low dBA. Up is high dBA. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. NOTICE:CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES. 3. SNAP COVER OVER ASSEMBLY Switch Locations GCS/GCC 24VDC S E R I E S 551-0051-06 24 units per carton 29 pounds per carton Important Notice: These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. Architect & Engineering Specifications The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSI/UL 1971 for the GCS and ANSI/UL 464 for the GCC. The notification appliance shall also be listed with the California State Fire Marshal (CSFM) and the Bureau of Standards and Appeals (NYC). The notification appliance (combination audible/visible units and audible units only) shall produce a peak sound output of 90dBA or greater as measured at 24VDC in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The appliance shall have an operating current of 72mA or less at 24VDC for the 15 candela strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. NOTES: •All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. See Technical Bulletin 014 for additional information. •FFOORR SSYYNNCCHHRROONNIIZZAATTIIOONN WWIIRRIINNGG IINNFFOORRMMAATTIIOONN,, RREEFFEERREENNCCEE AAVVSSMM CCOONNTTRROOLL MMOODDUULLEE DDAATTAA SSHHEEEETT ((555511--00003311)) AANNDD//OORR AAVVSSMM CCOONNTTRROOLL MMOODDUULLEE MMAANNUUAALL ((555500--00228844)) FFOORR SSYYNNCCHHRROONNIIZZAATTIIOONN MMOODDUULLEE WWIIRRIINNGG DDIIAAGGRRAAMMSS.. AAVVSSMM CCOONNTTRROOLL MMOODDUULLEE DDAATTAA SSHHEEEETT AANNDD MMAANNUUAALL CCAANN BBEE OOBBTTAAIINNEEDD AATT hhttttpp::////wwwwww..ggeenntteexx..ccoomm OORR CCAALLLL GGEENNTTEEXX CCOORRPPOORRAATTIIOONN AATT 11--880000--443366--88339911.. Conventional GC Series Wiring Diagrams GEC/GES/GEH Series Fixed Candela Evacuation Signals 24 VDC, Commander2 Horn, Strobe and Horn/Strobe 24 units per carton, 28 pounds per carton Assembled in the USA Applications The Commander2 Series is a low profile strobe, horn and horn/strobe combination that offers dependable audible and audible/visual alarms and the absolute lowest current available. The GE Series is available in fixed candela options of 15/75 and 177. The Commander2 Series horn offers a continuous or synchable temporal 3 in 2400Hz and mechanical and, chime as well as a whoop tone. All tones are easy for the professional to change in the field by using switches. The Commander2 Series is shipped with the standard 4" mounting plate which incorporates the popular Super-Slide® feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The Commander2 Series also features the patented Checkmate® Instant Voltage Verification feature which allows the installer to check the voltage drop draw and match it to the blueprint. The GE Series appliances are ANSI/UL 464, ANSI/UL 1971, ANSI/UL 1638, CAN/ULC S525 (24 VDC only) and/or CAN/ULC S526 (24 VDC only), listed for use with fire protective systems and are warranted for three years from date of purchase. Standard Features • Nominal voltage 24 VDC for horn, strobe and horn/strobe • Nominal voltage 12 VDC for horn • Fixed candela models of 15/75 and 177 • Unit Dimensions: 5” (12.7 cm) high x 4.5” (11.43 cm) wide x 2.5” (6.35 cm) deep • Super-Slide® Bracket, Ease of Supervision Testing • Checkmate® Instant Voltage Verification • Prewire entire system, install mounting bracket, then install signals • Documented lower installation and operating costs • Input terminals 12 to 18 AWG • Switch selection for high or low dBA • Switch for 2400 Hz, mechanical, chime and tones • Switch for continuous or temporal 3 (not available on whoop tone) • Synchronize strobe and/or horn with Gentex AVSM Control Module • Silence audible while visual appliance will remain flashing • Tamperproof re-entrant style grill and locking screw (optional use) • Surface mount with the GSB (Gentex Surface Mount Box) • Faceplate available in red or off-white • Wall mount Product Listings • ANSI/UL 464, ANSI/UL 1971 and/or ANSI/UL 1638 Listed • CAN/ULC S525 and/or CAN/ULC S526 Listed (24 VDC only) • CSFM: 7135-0569:122 (GEH-24 & GEC-24) 7125-0569:123 (GES-24) 7135-0569:130 (GEH-12) • MEA: 285-91-E-XV Patents • 7,375,617 May 20, 2008 Product Compliance • NFPA 72 • Americans with Disabilities Act (ADA) • IBC/IFC/IRC • City & State Ordinances/Laws/Regulations • Quality Management System is certified to: ISO 9001:2008 GEC / GES / GEH - Selectable Candela Evacuation Signals GE 24 Strobe Current Ratings (mA) Candela UL Max 15/75 cd 67 mA 177 cd 213 mA R = Red Faceplate, W = White Faceplate All units are available in plain (no lettering) Plain units are not returnable ALERT and AGENT bezels available for order * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). GE 12 VDC / 24 VDC Horn Decibel (dBA) and Current Ratings (mA) 12 VDC (8-17.5 Volts)24 VDC (16-33 Volts) Horn DecibelLevels (dBA)Horn Current Ratings (mA Horn DecibelLevels (dBA)Horn Current Ratings (mA) Horn Mode Minimum SPL at 10ft., per ANSI/UL 464 (HIGH) Minimum SPL at 10ft., per ANSI/UL 464 (LOW) UL MAX Regulated 12 VDC Operating Current (HIGH) Minimum SPL at 10ft., per ANSI/UL 464 (HIGH) Minimum SPL at 10ft., per ANSI/UL 464 (LOW) UL MAX Regulated 24 VDC Operating Current (HIGH) Temporal 3 2400 Hz 76 dBA 69 dBA*29 mA 78 dBA 71 dBA*28 mA Temporal 3 Mechanical 75 dBA 68 dBA*26 mA 76 dBA 70 dBA*25 mA Temporal 3 Chime 62 dBA*60 dBA*13 mA 70 dBA*66 dBA*15 mA Continuous 2400 Hz 79 dBA 74 dBA*29 mA 81 dBA 74 dBA*28 mA Continuous Mechanical 78 dBA 72 dBA*26 mA 80 dBA 72 dBA*25 mA Continuous Chime 63 dBA*61 dBA*13 mA 70 dBA*66 dBA*15 mA Whoop 78 dBA 71 dBA*55 MA 82 dBA 69 dBA*56 mA GEH 12 VDC or GEH 24 VDC Low Profile Evacuation Horn Model Part Number Voltage (VDC)Reverberant dBA at 10ft.Anechoic Room dBA at 10ft. GEH12-R 904-1239-002 12 70-82 dBA 100 dBA GEH12-W 904-1241-002 12 70-82 dBA 100 dBA GEH24-R 904-1205-002 24 70-82 dBA 100 dBA GEH24-W 904-1207-002 24 70-82 dBA 100 dBA GES 24 VDC Low Profile Evacuation Strobe Model Part Number Voltage (VDC)Strobe Candela GES24-177WR 904-1183-002 24 177 GES24-177WW 904-1203-002 24 177 GES24-15/75WR 904-1167-002 24 15 (ANSI/UL 1971) / 75 (ANSI/UL 1638) GES24-15/75WW 904-1187-002 24 15 (ANSI/UL 1971) / 75 (ANSI/UL 1638) GEC 24 VDC Fixed Candela, Low Profile Evacuation Horn/Strobe Model Part Number Voltage (VDC)Strobe Candela Reverberant dBA at 10ft.Anechoic Room dBA at 10ft. GEC24-177WR 904-1143-002 24 177 70-82 100 GEC24-177WW 904-1163-002 24 177 70-82 100 GEC24-15/75WR 904-1127-002 24 15 (ANSI/UL 1971) / 75 (ANSI/UL1638)70-82 100 GEC24-15/75WW 904-1147-002 24 15 (ANSI/UL 1971) / 75 (ANSI/UL 1638)70-82 100 Notes • Operating temperature: 32° to 120°F (0° to 49°C) • The GE Series is not listed for outdoor use • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual. 12 VDC models are DC only. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode, its sound pressure is the same as the continuous mode. • This appliance is not recommended for use on coded or pulsing signaling circuits 4.5”11.4 cm 2.5”6.35 cm Gentex Super-Slide® Mounting Bracket Allows the installer to prewire the system, test for system supervision, remove the signal head until occupancy, switch out Gentex signals without changing mounting brackets and has locking edge connector for snap-in-place installation. Gentex Checkmate® Instant Voltage Verification It is often necessary to confirm the voltage drop along a line of devices. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. Notice: Care should be taken to not short the test probes. 5.0”12.7 cm Fire Protection Products Group | 10985 Chicago Drive | Zeeland, MI 49464 gentex.com | Phone: 616.392.7195 | Toll-free: 800.436.8391 | Fax: 616.392.4219 551-0049-03 Architect & Engineering Specifications The audible and/or visible signal shall be Gentex GES, GEC, GEH Series or approved equal and shall be listed by Underwriters Laboratories (ANSI/UL) for use with fire protective signaling systems (ANSI/UL 1971, ANSI/UL 1638 and/or ANSI/UL 464) and with CAN/ULC S526 (24 VDC) and CAN/ULC S525 (24 VDC) with intended use in fire alarm systems. The notification appliance (GEC and GEH) shall produce a peak sound output of 100 dBA or greater at 12 VDC or 24 VDC as measured in an anechoic chamber and shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2 Hz regardless of power input voltage. The strobe appliance shall have an operating current of 67 mA or less at 24 VDC for the 15/75 Cd for the strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The GEC and GES Series shall be mounted on the wall. The GEH Series shall be universal mount. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power at 24 VDC and 8-17.5 volts with at 12 VDC. The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. Important Notice: These materials have been prepared by Gentex Corporation (“Gentex”) for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person’s activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. GEC/GES/GEH Series Fixed Candela Evacuation Signals WGES / WGEC Series Outdoor Evacuation Signals 24 VDC Outdoor Commander Strobe and Horn/Strobe 1 unit per carton, 3 pounds per carton Assembled in the USA Applications The Outdoor Commander Series is a outdoor listed strobe and horn/strobe comination that offers dependable visible and/or audible alarms for all outdoor needs. The WGE Series offers a fixed 75 candela strobe. The WGEC horn/strobe offers a continuous or synchable temporal 3 in 2400Hz, mechanical and chime as well as a whoop tone. All tones are easy for the professional to change in the field by the use of switches. Included with the WGE Series is the GOE or GOELP outdoor enclosure. The enclosure is made of high quality Lexan® material, providing protection from weather related conditions and allowing the necessary full candela output. This highly constructed enclosure meets various installation requirements including deterring moisture from entering the enclosures. The Outdoor Commander Series is equipped with a standard 4” mounting plate which incorporates the Super-Slide® feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The WGE Series also features the Checkmate® instant voltage verification feature which allows the installer to check the voltage drop draw and match it to the blueprint. The WGE Series appliances are ANSI/UL 464, ANSI/UL 1638, CAN/ULC S525 and/or CAN/ULC S526 listed for use with fire protective systems and are warranted for three years from date of purchase. Standard Features • Nominal voltage 24 VDC • Fixed 75 candela • GOE Unit Dimensions: 5.84” (14.83 cm) high x 4.81” (12.22 cm) wide x 4.22” (10.72 cm) deep • GOELP Unit Dimensions: 5.84” (14.83 cm) high x 4.81” (12.22 cm) wide x 3.25” (8.255 cm) deep • Super-Slide® - Ease of Supervision Testing • Checkmate® Instant Voltage Verification • Prewire entire system, install mounting bracket, then install signals • Input terminals accept 12 to 18 AWG • Horn/strobe switch selection for high or low dBA • Horn/strobe switch for 2400 Hz, mechanical, chime and whoop tones • Horn/strobe switch for continuous or temporal 3 (not available on whoop tone) • Synchronize strobe and/or horn by using Gentex AVSM Control Module • Silence audible while visual appliance will remain flashing • Tamperproof re-entrant grill and locking screw (optional use) • GOE/GOELP made of clear Lexan® - provides maximum visibility and reliability for effective visible signaling - allowing full 75cd output • Faceplate available in red or off-white • Wall mount Product Listings • ANSI/UL 464 and ANSI/UL 1638 Listed • CAN/ULC S525 and/or CAN/ULC S526 Listed • CSFM: 7135-0569:122 (WGEC) 7125-0569:127 (WGES) 7300-0569:124 (ENCLOSURE) • MEA: 285-91E-XVI Product Compliance • NFPA 72 • Americans with Disabilities Act (ADA) • IBC/IFC/IRC • Quality Management System is certified to: ISO 9001:2008 WGES / WGEC - Outdoor Evacuation Signals NOTE: Must order the GOE or GOELP (sold separately) when using the GEH24 in an outdoor application. WGE 24 VDC Series Strobe Current Ratings Candela 24 VDC UL Max 75 cd 112 mA 170 mA * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). R = Red Faceplate, W = White Faceplate LP = Low Profile (GOELP Enclosure) All units are available in plain (no lettering) Plain units are not returnable WGES / WGEC is shipped with the GOE or GOELP Outdoor Enclosure GEH Low Profile Evacuation Horn Model Part Number Voltage (VDC) Reverberant dBA at 10ft. Anechoic Room dBA at 10ft. GEH24-R 904-1205-002 24 70-82 dBA 100 dBA GEH24-W 904-1207-002 24 70-82 dBA 100 dBA WGES24 Evacuation Outdoor Strobe Model Part Number Voltage (VDC)Candela WGES24-75WR 904-1219-002 24 75 WGES24-75WW 904-1220-002 24 75 WGES24-75WRLP 904-1261-002 24 75 WGES24-75WWLP 904-1263-002 24 75 WGEC24 Evacuation Outdoor Horn/Strobe Model Part Number Voltage (VDC)Candela Reverberant dBA at 10ft.Anechoic Room dBA at 10ft. WGEC24-75WR 904-1217-002 24 75 70-82 dBA 100 dBA WGEC24-75WW 904-1218-002 24 75 70-82 dBA 100 dBA WGEC24-75WRLP 904-1257-002 24 75 70-82 dBA 100 dBA WGEC24-75WWLP 904-1259-002 24 75 70-82 dBA 100 dBA WGE 24 VDC Horn Decibel (dBA) and Current Ratings (mA) Horn Decibel Levels (dBA)Horn Current Ratings (mA) Horn Mode Minimum SPL at 10ft. per ANSI/UL 464 (HIGH) Minimum SPL at 10ft. per ANSI/UL 464 (LOW) UL MAX Regulated 24 VDC Operating Current (HIGH) Temp 3 2400Hz 78 dBA 71 dBA*28 mA Temp 3 Mechanical 76 dBA 70 dBA*25 mA Temp 3 Chime 70 dBA*66 dBA*15 mA Continuous 2400Hz 81 dBA 74 dBA*28 mA Continuous Mechanical 80 dBA 72 dBA*25 mA Continuous Chime 70 dBA*66 dBA*15 mA Whoop 82 dBA 69 dBA*56 mA 4.81”12.22 cm 4.22”10.72 cm 5.84”14.83 cm Gentex Super-Slide® Mounting Bracket Allows the installer to prewire the system, test for system supervision, remove the signal head until occupancy, switch out Gentex signals without changing mounting brackets and has locking edge connector for snap-in-place installation. Gentex Checkmate® Instant Voltage Verification It is often necessary to confirm the voltage drop along a line of devices. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. Notice: Care should be taken to not short the test probes. Notes • The WGE Series is listed for outdoor use. Indoor operating temperature: 32° to 120°F (0° to 49°C). Outdoor operating temperature: -31° to 150°F (-35° to 66°C) • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode, its sound pressure is the same as the continuous mode. • This appliance is not recommended for use on coded or pulsing signaling circuits Fire Protection Products Group | 10985 Chicago Drive | Zeeland, MI 49464 gentex.com | Phone: 616.392.7195 | Toll-free: 800.436.8391 | Fax: 616.392.4219 551-0047-04 Architect & Engineering Specifications The audible and/or visible signal shall be Gentex WGES, WGEC Outdoor Evacuation Signal Series or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSI/UL 1638 and/or ANSI/UL 464 and CAN/ULC S526 and/or CAN/ULCS525. The notification appliance (WGEC) shall produce a peak sound output of 100dBA or greater at as measured in an anechoic chamber and shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/ visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 170mA or less for the 75Cd strobe circuit. The appliance shall also be capable of meeting the candela requirements of the ADA (75cd). The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power for 24 volt models. The appliance shall be capable of testing supervision without disconnecting wires. Also the appliance shall be capable of mounting to a surface back box. The unit shall also be able to verify voltage at the unit without removing unit. The appliance has extended temperature range of -31° to 150°F (-35° to 66° C). The appliance shall satisfy virtually all outdoor and severe environment applications. The GOE Enclosure is includes a gasket that must be inserted between the box and mounting bracket. There are drain holes in the back box to allow for drainage, the seal on the GOE Enclosure is not water tight. The GOELP Enclosure includes a weather seal for mounting to wall and intended for use with universal electrical box. To allow for drainage, bottom edge of enclosure is not water tight. Important Notice: These materials have been prepared by Gentex Corporation (“Gentex”) for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person’s activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. WGES / WGEC Series Outdoor Evacuation Signals Code-compliant standard or mercantile metal models (right and left, respectively) . • Sole Path Cellular and Dual Path Cellular &/or IP Models • Choice of plans (varies by model) - check-ins from 200 seconds, to 5-minutes to 1 hour, Verizon or AT&T • Patented Signal Boost™ signal amplification circuit and high-gain performance antenna for longer range and reliability nationwide • Money-saving 2G Tradeup incentive credit • Bonus: Full High-Speed Napco Panel remote uploading/ downloading • COMPLIANCES: NFPA72 Editions: 2013, 2010, 2007; UL 864, 9th Ed., UL1610, UL985, UL1023, NYFD (as back-up); CSFM Commercial Fire Alarm Communicators: Sole & Dual Path Cellular &/or IP Napco StarLink3 Universal Fire Alarm Communicators UL and NFPA 72 Fire Code-Compliant, the StarLink Series Wireless Commercial Fire Alarm Sole Path & Dual Path Communicators provide universal support for any brand 12V to 24V fire alarm control panel, reporting in Contact ID and 4/2. With broadest coverage footprint available in Verizon Network Certified ™ CDMA or GSM 3/4G models on the AT&T network, as well as mercantile models, all provide the most economical solution and for easy, versatile installation. Safeguard Accounts & Reliability. For applications currently relying upon quickly-disappearing traditional phone lines, StarLink wireless communicators can be used for primary or backup communications, and will not only safeguard the fire alarm reporting transmissions for the future, but provide the end-user monthly savings for each costly FACP-dedicated landline they replace. And, for upgrading older wireless fire alarm communicators on 2G and other phased-out cellular networks, all StarLink Fire radios, offer a $100 tradeup incentive to help defray the cost of the hardware replacement to the advanced state-of- the-art StarLink model of choice. Flexible Performance & Reporting Options. StarLink Fire provides full data reporting, in sole and dual path, as a primary or backup, to any central station of your choice, without requiring any special equipment on premises. Ultra-affordable plans are available to meet various codes and requirements, with supervisory check-ins from 200 seconds, to 5-minutes, to an hour. The units are very easily activated, plans and options are selected, and 24/7 account management is provided all through www. napcocomnet.com. And, StarLink Fire Communicators are easily connected to any panel or Fire Alarm Control Panel (FACP) standardly operating between 12V and 24V. Flexible in any application, StarLink Fire also comes in standard, or Mercantile Models in metal housings, with code- compliant supervision, with or without using conduit; and choice of power options, powered by the panel or using its own 120V Power Supply. • Universal full event sole path cellular & dual path cellular &/or IP commercial fire alarm reporting from any panel brand, virtually anywhere • For use as primary or backup communications on all 12V-24V control panels and FACPs that communicate using Contact ID and 4/2 (such as on legacy panels) • Reports to any Central Station nationwide, with your choice of cellular networks: Verizon Network Certified CDMA or GSM 3/4G on AT&T • Easy, flexible installation, activation & online account management • Cost-saving models and plans for any code requirement. Substantial savings over monthly dedicated landline charges. And, $100 saving incentive with any 2G Communicator upgrade (unlimited). COMMERCIAL FIRE StarLink Fire Specifications STANDARD MODELS: • Durable ABS plastic housing includes three keyhole slots for mounting (for commercial application, aligns with triple gang boxes.) • Dimensions: 5-3/8”x 7-7/8”x 1-7/8” (HxWxD) • Weight: 13.5 oz • 3 LED Indicators - Green, Signal Strength; Amber- Busy/ Activation; Red-Trouble • Patented Signal Boost™ signal amplification circuit and high- gain performance antenna • Operating Environment: 0 to 49º C (32-120ºF), up to 93% humidity (non-condensing) • 12V - 24V Universal FACP Support, auto-current sensing. Support all brands communicating in Contact ID and 4/2 • Powered by Panel, Low current draw, 71mA standby, 200mA transmit MERCANTILE MODELS (similar to above, with): • Locking Metal Enclosure with Hinged door & 2 key-slots for wall mounting (LED indicators, inside). • Dimensions: 9-5/8”x 11-3/4” x 3-3/8”D (HxWxD) • Weight: 8 lbs (max., power supply models) • Electrical Ratings for 120VAC, 60Hz • For Models with Power Supply: • Input Voltage:  120VAC Nominal • Input Current: 400mA maximum • Maximum Charging Current:  200mA • Electrical Ratings for +12V • For Models without Power Supply: • Input Voltage:  11-15VDC (power-limited output from listed control panel) • Input Current: 71mA with peak RF transmission current of 200mA. • Electrical Ratings for the IN 1 Burg/Fire Input: • Input Voltage: 9-15VDC • Maximum Input Current: Up to 2mA from FACP NAC circuit • Electrical Ratings for IN 2 and IN 3: • Maximum Loop Voltage: 15VDC • Maximum Loop Current:  1.2mA • Electrical Ratings for 3 PGM Outputs: • Open Collector Outputs:  Maximum voltage 3V when active; 15V maximum when not active • Maximum PGM Sink Current: 50mA mount. • Operating Environment 0 to 49º C (32-120ºF), up to 93% humidity (non-condensing) • 12V - 24V Universal FACP Support, auto-current sensing. Support all brands communicating in Contact ID and 4/2. Ordering Information COMMERCIAL FIRE SOLE PATH CELLULAR & DUAL PATH CELLULAR &/OR IP (“I” MODELS):* SLE-CDMA-FIRE Standard ABS (Red) Fire Sole Path Alarm Communicator, Cellular CDMA, Verizon-Network Certified SLE-CDMAI-FIRE as above, Dual Path Alarm Communicator, Cellular &/or IP (primary or backup, selectable) SLECDMA-CFB-PS Commercial Fire Mercantile model in red metal housing, CDMA, Verizon-Network Certified. Direct 120VAC Powered (w/ provisions for backup battery/charger). Or, Optional TRF20 plug-in transformer may be used, where codes permit SLECDMA-CFB Commercial Fire Mercantile model in red metal housing on CDMA, Verizon-Network Certified Powered directly from control panel Note: Substitute prefix “SLE3/4G-” on any models above for AT&T 3/4G Network ACCESSORIES: SLE-DLEXT Optional, as above, for downloading, extends distance to Napco panel up to 100’ TRF20 Optional Plug in AC Transformer, 16.5V / 20VA (use is subject to local code compliance) SLE-DLCBL Optional High-Speed Napco Panel Up/download cable 333 Bayview Ave., Amityville, NY 11701 USA 1-800-645-9445 • Fax: 1-631-789-9292 www.napcosecurity.com COMPLIANCES: NFPA 72 Editions: 2013, 2010, 2007; UL 864, 9th Ed., UL1610, UL985, UL1023; NYFD (as back-up); CSFM *StarLink Fire are also rated to support Intrusion/Burglary alarm reports where applicable. StarLink™ and Signal Boost are trademarks of NAPCO. Pats. Pending. Specifications subject to change. ©NAPCO, NAPCO Security Technologies Inc. (NASDAQ:NSSC) A676D 2016.5 * Verizon and Verizon Network Certified, UL, AT&T and other trademarks, are trademarks of their respective companies, and are unaffiliated with NAPCO. SLE-GSM-3/4G Standard Burglary Radio (Black), GSM 3/4G on AT&T Network powered by panel. SLE-CDMA as above, but CDMA communications, Verizon-Network Certified. SLECDMA-CB Commercial Burglary CDMA Radio, Verizon Certified, in white metal housing. Powered directly from control panel. SLE3/4G-CB as above, but GSM 3/4G on AT&T Network. SLE3/4G-CB-TF Commercial Burglary CDMA, Verizon Certified in white metal housing with power supply powered by plug-in 16.5V / 20VA transformer & provision for battery. Also Available: StarLink Intrusion Radios in standard and mercantile versions