Building Review on 07/19/2019:
Permit Number: 18-00569Permit Details
Building - Commercial
Permit Issued Date:
Final Inspections Required
Fire Sprinkler Final Inspection HVAC Final Inspection
Plumbing Final Inspection Fire Department Final Inspection
Public Works Final Inspection Fire Alarm Final Inspection
Planning and Zoning Final Inspection Commercial Electrical Final Inspection
Commercial Building Final
1050 N 2nd E
1050 N 2nd E - Porter RV Storage
Inspection Details
quinton.owens@rexburg.org
Inspected By: Quinton Owens
Building Review on 07/19/2019:
D ESCRIPTIO N CO M M EN TS STATUS
504 - Allowable height (Feet/Stories)
506 - Allowable area
S-1 occupancy (not identified on plans) and V-B
construction (not identified on plans):
* This building exceeds the allowable 9,000 sf
area without sprinklers (Enclosed storage
review).
* Fire walls added for complying building
separation (Enclosed storage review)
* New submitted open storage also exceeds
allowed area and is without firewall separation
(see notes on fire walls)
REVISIONS
Exterior walls meet the requirements of IBC
Section 705
* Closed storage buildings have required
exterior separation (approved)
* Open storage building's distance to property
line requires fire rating on both sides of exterior
wall adjacent to property line (open storage
units submitted after first review).
REVISIONS
Structural Docs identify snow, wind, seismic and
other loads per IBC Chp. 16
NOTE: The Seismic Design Category D in the
IBC does not have any sub-category, just D (be
sure to use IBC criteria and not the IRC).
* Received an email but no copy of a stamped
letter on the closed storage building.
REVISIONS
Fire walls meet the requirements of IBC Section
706
3 hr Fire wall separation is not shown on plans.
Same requirements apply based on building
area even with the one side open. The fire walls
shall have extend 18" beyond front of roof or
have 4 ft extensions on either side per section
706.5. (Roof overburn protection still applies
and back wall already has a rating requirement
due to fire separation to property line).
* ADDITIONAL OPTION is to physically separate
building into smaller areas with 10 ft min
REVISIONS
Page 1 of 2
(Continued)
Permit Number: 18-00569
D ESCRIPTIO N CO MMEN TS STATUS
between buildings, then exterior side wall only
requires 1 hour rating and no overburn
protection on roof or wall.
Use classification is identified as per IBC Section
302
Not Identified on plans. Rental storage units =
S-1 (ALWAYS IDENTIFY OCCUPANCY TYPE ON
PLANS)
* Open storage building added 7/16 (also S-1
occupancy)
APPROVED
Concealed spaces are fireblocked/draftstopped
per Section 718
Will be approved based on inspection per
requirements of IBC 718
* IF TRUSSES BECOME ENCLOSED,
DRAFTSTOPPING SHALL SUBDIVIDE ATTIC
SPACES INTO AREAS NO LESS THAN 3,000 SF.
APPROVED
All buildings shall be classified as one of the five
construction types defined in Section 602.
Not shown on plans. ALWAYS IDENTIFY
CONSTRUCTION TYPE ON PLANS.
(commbustible materials default to V-B)
APPROVED