HomeMy WebLinkAboutREVIEW RESPORT - 17-00378 - 525 S Center St - BYUI - Smith RemodelReview
Report
Current Building Review Status: REVISIONS
Application Number: 17-00378Permit Details
Application Received Date: 07/10/2017
Commercial Remodel
Application Approved Date:
Application Approved Status: APPROVED
07/10/2017
525 South Center St
BYUI - Smith Remodel
Status of Plan Reviews Completed
07/12/2017Electrical Review COMPLETED
07/12/2017Plumbing Review N/A
07/12/2017HVAC Review COMPLETED
07/20/2017Fire Alarm Review COMPLETED
07/26/2017Building Review REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Building Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Accessible Means of Egress meets the
requirements of IBC Section 1007
REVISIONSWhere a space is required to have 2 exits, then two
accessible means of egress shall be provided (see
comments on aisles). Existing accessible means of
egress shall be maintained in alterations of existing
buildings (commentary on exception 1).
*Revisions Response : The tables and chairs within Classroom 250 have been rearranged and limited to less than 50, thus eliminating the need for a second means of egress.
Aisles meet the requirements of IBC Section 1017 REVISIONSRoom 250, classroom plan, does not meet aisle width
requirement for 2nd exit on east side of room.
*Revisions Response : The tables and chairs within Classroom 250 have been rearranged and limited to less
that 50, thus eliminating the need for a specific aisle width or a second means of egress from the room.
Assembly Exiting meets the requirements of IBC
Section 1028
REVISIONS* 20" is provided between chairs in room 240.
(approved)
* Aisle access width for seating at tables shall
be measured to a line 19" from the table edge.
36" between tables leaves only 17" clear width
(see IBC 1028.10.1)
*Revisions Response : The number of occupants was reduced from 60 to less than 50, thus eliminating the need for an aisle access width to meet IBC 1028.10.1. See attached documents.
Fire resistance rating of building elements meet
the req. of IBC Sect 703, 704
Maintain rating of existing fire protected
elements.
COMPLETED
Reviewed By: Quinton Owens
Review Date: 07/26/2017
Plan Review Details
quinton.owens@rexburg.org
Building Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Building Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Automatic sprinklers are provided or exempted as
per IBC Section 903.2
Existing building. Room changes affecting
sprinkler heads to be approved by Dale.
COMPLETED
Page 2 of 2
Approval of plans does not constitue approval of variance from code