HomeMy WebLinkAboutPLANS - 19-00420 - 59 Professional Plz St - Strobel Dentist Office Solar ProjectSCOPE OF WORK
SYSTEM SIZE:STC: 33 x 350 = 11.580 kW
PTC: 33 x 337.7 = 11.144 kW DC
(33) BOVIET BVM6612-350
(1) SMA SB7.7-US
OWNER
NAME:DIRK STROBEL DENTIST OFFICE
PROJECT MANAGER
NAME:TREVER GERDES
PHONE: 2085698777
LECTRICIAN
NAMF:BRIAN MEYERS
LIC.NO: ELE-M-23939
AUTHORITIES HAVING JURISDICTION
BUILDING: CITY OF REXBURG
ZONING: CITY OF REXBURG
UTILITY:
DESIGN SPECIFICATIONS
OCCUPANCY: II
CONSTRUCTION:
ZONING:OFFICE
APPLICABLE CODES & STANDARDS
BUILDING: IBC 2015
ELECTRICAL: NEC 2017
FIRE:IFC 2015
PROJECT INFORMATION
NEW PV SYSTEM: 11.550 kWp
DIRK STROBEL DENTIST OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
2.1.1 SITE NOTES:
2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A
UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR
BUILDING ROOF VENTS.
2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED
ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN
ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S
INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE
BUILDING OR STRUCTURE.
2.2.1 EQUIPMENT LOCATIONS
2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED
OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES
310.15 (B)(2)(A) AND 310.15 (B)(3)(C).
2.2.3 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES
ACCORDING TO NEC 690.34.
2.2.4 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT
WITHIN SIGHT OF THE AC SERVICING DISCONNECT.
2.2.5 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL
ACCORDING TO NEC APPLICABLE CODES.
2.2.6 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR
USAGE WHEN APPROPRIATE.
2.3.1 STRUCTURAL NOTES:
2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO
CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A
DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A
MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY,
ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.
2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS.
IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL
REQUIREMENTS.
2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND
SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED
CONTRACTOR.
2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE
SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.
2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE
STAGGERED AMONGST THE ROOF FRAMING MEMBERS.
2.4.1 GROUNDING NOTES:
2.4.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND
GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH
USE.
2.4.3 PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL
ELECTRICAL EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN
ACCORDANCE WITH 250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE
UNGROUNDED.
2.4.4 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM
NEC TABLE 250.122.
2.4.5 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE
CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
2.4.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE
NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED
GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION
REQUIREMENTS.
2.4.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT
THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO
ANOTHER MODULE.
2.4.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED
GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
2.4.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50
THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A
GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47
AND AHJ.
2.4.10 DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING
THE REQUIREMENTS OF 690.41(B)(1) AND (2) TO REDUCE FIRE HAZARDS
2.5.1 INTERCONNECTION NOTES:
2.5.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12
(B)]
2.5.3 THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAY
NOT EXCEED 120% OF BUSBAR RATING [NEC 705.12(B)(2)(3)].
2.5.4 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT
CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE
BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE
BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITE
END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].
2.5.5 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL
RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF
BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE
EXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C).
2.5.6 FEEDER TAP INTERCONECTION (LOAD SIDE) ACCORDING TO NEC 705.12
(B)(2)(1)
2.5.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITH
SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.42
2.5.8 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT
FROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].
2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH
IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO
THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).
2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE
LOCKABLE, AND BE A VISIBLE-BREAK SWITCH.
2.6.4 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED.
THEREFORE BOTH MUST OPEN WHERE A DISCONNECT IS REQUIRED,
ACCORDING TO NEC 690.13.
2.6.5 ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE
INSTALLED IN CIRCUITS CONNECTED TO EQUIPMENT AT A LOCATION WITHIN
THE EQUIPMENT, OR WITHIN SIGHT AND WITHIN 10 FT OF THE EQUIPMENT. AN
EQUIPMENT DISCONNECTING MEANS SHALL BE PERMITTED TO BE REMOTE
FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTING MEANS CAN
BE REMOTELY OPERATED FROM WITHIN 10 FT OF THE EQUIPMENT,
ACCORDING TO NEC 690.15 (A).
2.6.6 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A
RAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY
RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D)
2.6.7 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9,
AND 240.
2.6.8 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED,
THEREFORE BOTH REQUIRE OVER-CURRENT PROTECTION, ACCORDING TO
NEC 240.21. (SEE EXCEPTION IN NEC 690.9)
2.6.9 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION
ACCORDING TO NEC 690.11 AND UL1699B.
2.7.1 WIRING & CONDUIT NOTES:
2.7.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.
CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.
2.7.3 ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
2.7.4 EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE
LISTED AND IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV
MODULES WIRE LEADS SHALL BE LISTED FOR USE ON PV ARRAYS,
ACCORDING TO NEC 690.31 (A).
2.7.5 PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(6)].
2.7.6 MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.
2.7.7 ACCORDING TO NEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORS
COLORED OR MARKED AS FOLLOWS:
DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GREY AND
GREEN
DC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GREY
AND GREEN
2.7.8 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION
NEUTRAL- WHITE OR GREY
* IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE
TO BE MARKED ORANGE [NEC 110.15].
2017S
A-201
01EMAIN ENTRANCE DOOR PROPERTY LINE
SOLAR (PV) MODULE
EQUIPMENT GROUND
CONDUIT
FIRE CLEARANCE
(E) UTILITY METERM
S
PNL
VMEP
AC DISCONNECT
AC PANELBOARD
PV REVENUE METERMAIN ELECTRICAL PANEL
DC/AC INVERTER
DC DISCONNECT
COMBINER BOX
JUNCTION BOX
I
DCSW
CBR
JB U UTILITY POLE
TB
RSD
TAP BOX
RAPID SHUTDOWN
SUB (AC) PANEL
METER/MAIN
SUB
M/M
CBR
MODULE STRINGING
(DC) COMBINER BOX
A
B
MODULE STRINGING
MODULE STRINGING
ATTACHMENTS
RAILS
ROOF RAFTERS
N
EW
S
A-201
D1
26
SYMBOL LEGEND
C MODULE STRINGING
D MODULE STRINGING
SHEET KEYNOTE INDICATOR
DETAIL INDICATOR
ELEVATION INDICATOR
NORTH INDICATOR
DISCLAIMER: PLEASE NOTE THAT THE ABBREVIATIONS, ANNOTATIONS, AND SYMBOLS LISTED ARE INTENDED TO ILLUSTRATE THOSE THAT ARE COMMONLY USED; NOT ALL ARE NECESSARILY UTILIZED WITHIN THIS SET OF DRAWINGS.
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
T-001.00
COVER PAGE
(SHEET 1 OF 19)
01 AERIAL PHOTO
NOT TO SCALE
N
EW
S
02 PLAT MAP
NOT TO SCALE
PR
O
F
E
S
S
I
O
N
A
L
P
L
A
Z
A
N
EW
S
SHEET SCHEDULE
SHEET NUMBER SHEET TITLE
T-001 COVER PAGE
A-101 SITE PLAN
A-102 ELECTRICAL PLAN
E-601 SINGLE LINE DIAGRAM
A-103 SOLAR ATTACHMENT PLAN
E-602 PLACARD
S-501 ASSEMBLY DETAILS
R-001 - R-002 RESOURCE DOCUMENT
CONSTRUCTION NOTES
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
N
EW
S
01/8" = 1'-0"
SITE PLAN01 4'8'
A-101.00
SITE PLAN
(SHEET 2 OF 19)
P
R
O
F
E
S
S
I
O
N
A
L
P
L
A
Z
A
INVERTER
AC DISCONNECT
METERMAIN
28
'
-
6
"
39'-8"
13'-7"
9'
-
1
1
"
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.SEE SHEET T-001 FOR LEGEND OF SYMBOLS
MODULE:
BOVIET
BVM6612-350
350 WATTS
37.09"
77
.
0
1
"
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01/4" = 1'
ELECTRICAL PLAN012'4'
A-102.00
ELECTRICAL PLAN
(SHEET 3 OF 19)
(N) (1) INVERTER
(N) (1) AC DISCONNECT
EXTERIOR EQUIPMENT
(E) (1) METER/MAIN
A MODULE STRINGING
FIRE CLEARANCE
B MODULE STRINGING
3'-0" FIRE ACCESS PATH 3'-0" FIRE ACCESS PATH
3'-0" FIRE ACCESS PATH
3'-0" FIRE ACCESS PATH
3'-0" FIRE ACCESS PATH
C MODULE STRINGING
A A A A
A A A A
A
A
С
С
С
С
С
С
С
В
В
В
В
С
С
С
С
В
ВВВ
В
A
В В
ARRAY 3 - 5.600 kW
[x16] (N) MODULES
TILT: 20 DEGREES
AZIMUTH: 90 DEGREES
N
EW
S
ARRAY 2 - 2.450 kW
[x7] (N) MODULES
TILT: 20 DEGREES
AZIMUTH: 180 DEGREES
ARRAY 1 - 3.500 kW
[x10] (N) MODULES
TILT: 20 DEGREES
AZIMUTH: 270 DEGREES
(N) (1) TIGO
ACCESS
POINT
RS-485
(N) (1) TIGO CCA
MODULE:
BOVIET
BVM6612-350
350 WATTS
37.09"
77
.
0
1
"
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
03/16" = 1'
ROOF FRAMING PLAN012'-8"5'-4"
A-103.00
ROOF FRAMING PLAN
(SHEET 4 OF 19)
ROOF MATERIAL IS ASPHALT SHINGLE
RAILLESS SOLAR MODULES ATTACHED
TO ROOF SURFACE (SEE SHEET S-501
FOR MOUNTING DETAILS)
N
EW
S
19
'
-
3
"
34
'
-
8
"
19'-3"
TRUSSES
03
TO UTILITY
GRID (UG)
L1 L2
N
(E) GROUNDING
ELECTRODE
GROUND
ROD
(E) MAIN SERVICE PANEL
120/240 V 1Ø, 3W
MAIN BUSS:200A
N
G
(E) UTILITY
METER
TO (E)
LOADS
NN L2 L1
EQUIPMENT ABOVE
LINE IS (N) NEW
EQUIPMENT BELOW
LINE IS (E) EXISTING
UNLESS OTHERWISE
NOTED.
G
04
(N) 60А
AC DISCONNECT
TIGO CLOUD
CONNECT
CONTROLLER
L2 N
G
G L1
01
(N) SMA
SB7.7-1SP-US-40-240V
BOVIET
BVM6612-350
SMA TS4-R-O
OPTIMIZERS
11 11 11
G
02
(N) JUNCTIION BOX
(E) 40А
(E) MAIN
A200
TAP
TIGO ACCESS POINT
RS
-
4
8
5
C
A
B
L
E
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01 SINGLE LINE DIAGRAM
NOT TO SCALE E-601.00
SINGLE LINE DIAGRAM
(SHEET 5 OF 19)
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS
IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL
01 3 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.71 (55.8°C)1 11.98A 14.98A 55A 39.05A 75°C 50A
02 1 10 AWG THWN-2, COPPER 1" DIA PVC-40 6 N/A 10 AWG THWN-2, COPPER 0.71 (55.8°C)0.8 11.98A 14.98A 45A 25.56A 75°C 35A
03 1 8 AWG THWN-2, COPPER 1" DIA PVC-80 2+N N/A 10 AWG THWN-2, COPPER 0.96 (33.8°C)1 32A 40A 55A 52.8A 75°C 50A
04 1 8 AWG THWN-2, COPPER 1" DIA PVC-80 2+N 40A 10 AWG THWN-2, COPPER 0.96 (33.8°C)1 32A 40A 55A 52.8A 75°C 50A
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE BOVIET BVM6612-350 PM1-33 33 PIECES 1 BOVIET BVM6612-350 350W 72 CELLS, POLYCRYSTALLINE SILICON
INVERTER SMA SB 7.7-1SP-US-40 (240V)I1 1 PIECE 1 SMA SB 7.7-1SP-US-40 (240V) 7680W INVERTER
MONITORING TIGO TIGO CCC C1 1 PIECE 1 TIGO CLOUD CONNECT CONTROLLER
MONITORING TIGO TAP T1 1 PIECE 1 TIGO ACCESS POINT (TAP)
MODULE OPTIMIZER SMA TS4-R-S PO1-33 33 PIECES 1 SMA TS4-R-O OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)
DISCONNECT SQUARE D D222NRB SW1 1 PIECE 1 SQUARE D D222NRB, 2-POLE, 60A, 240VAC OR EQUIVALENT
WIRING GEN-10-AWG-PV-WIRE-CU WR1 270 FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 135 FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2 60 FEET 1 10 AWG THWN-2, COPPER, RED (POSITIVE)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 60 FEET 1 10 AWG THWN-2, COPPER, BLACK (NEGATIVE)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-3 270 FEET 1 10 AWG THWN-2, COPPER (GROUND)
WIRING GEN-8-AWG-THWN-2-CU-RD WR3 10 FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR3 10 FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR3 10 FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIREWAY GEN-PVC-40-1.0" DIA WW2 20 FEET 1 PVC-40 CONDUIT, 1'' DIA
WIREWAY GEN-PVC-80-1.0" DIA WW3-4 20 FEET 1 PVC-80 CONDUIT, 1'' DIA
OCPD GENERIC MANUFACTURER GEN-CB-40A-240VAC CB1 1 PIECE 1 FUSE, 40A, 240VAC
TRANSITION BOX GENERIC MANUFACTURER GEN-AWB-TB-4-4X JB1 1 PIECE 1 TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKS
SYSTEM SUMMARY
MPPT #1 MPPT #2 MPPT #3
MODULES IN SERIES 11 11 11
ARRAY VMP 424.6V 424.6V 424.6V
ARRAY IMP 9.07A 9.07A 9.07A
ARRAY VOC 517V 517V 517V
ARRAY MAX VOC 597.9V 597.9V 597.9V
ARRAY ISC 9.58A 9.58A 9.58A
ARRAY STC POWER 11,550W
ARRAY PTC POWER 10,616W
MAX AC CURRENT 32A
MAX AC POWER 7,680W
DERATED (CEC) AC POWER 7,680W
DESIGN TEMPERATURES
ASHRAE EXTREME LOW -25.5°C (-13.9°F), SOURCE: DECATUR (39.98°; -88.87°)
ASHRAE 2% HIGH 33.8°C (92.8°F), SOURCE: DECATUR (39.98°; -88.87°)
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD
RATING RATED POWER MAX OUTPUT
CURRENT
MAX INPUT
CURRENT MAX INPUT VOLTAGE CEC WEIGHTED
EFFICIENCY
I1 1 SMA SB 7.7-1SP-US-40 (240V)240V FLOATING 40A 7680W 32A 3X18A 600V 97.0%
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM1-33 33 BOVIET BVM6612-350 350W 321.7W 9.58A 9.07A 47V 38.6V -0.146V/°C (-0.31%/°C)15A
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 SQUARE D DU222RB OR EQUIV.60A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
CB1 1 40A 240VAC
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
FRONT
PV ARRAY
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
N
E
W
S
E-602.00
PLACARDS
(SHEET 6 OF 19)
MAIN DISTRIBUTION
UTILITY DISCONNECT
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 6
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 32 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL 11
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 12
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVISE
LABEL 13
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
LABEL 8
AT UTILITY METER
[NEC 690.56(B)]
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL 10
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 7
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA
STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE
BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS
AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
PLAQUE
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH
OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE
PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE
INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
LABEL 3 INVERTER
AT EACH APPLICABLE DC DISCONNECTING
MEANS
[NEC 690.53]
OPERATING CURRENT: 9.07 A DC
OPERATING VOLTAGE:424.6 V DC
MAX SHORT CURRENT:9.58 A DC
MAX VOLTAGE:597.9 V DC
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
WEST SIDE OF THE BUILDING
SHEET KEYNOTES
1. ROOF MATERIAL: ASPHALT SHINGLE
2. ROOF STRUCTURE: TRUSS
3. ATTACHMENT TYPE: SNAPNRACK, A MOUNT
4. MODULE MANUFACTURER: BOVIET
5. MODULE MODEL: BVM6612-350
6. MODULE LENGTH: 77.01 IN.
7. MODULE WIDTH: 39.01 IN.
8. MODULE WEIGHT: 58.42 LBS.
9. SEE SHEET A-103 FOR DIMENSION(S)
10. MIN. FIRE OFFSET: 3'-0" FIRE ACCESS PATH
11. TRUSS SPACING: 24 IN. O.C.
12. TRUSS SIZE: 2X4 NOMINAL
13. LAG BOLT DIAMETER: 5/16 IN.
14. LAG BOLT EMBEDMENT: 2.5 IN.
15. TOTAL # OF ATTACHMENTS: 88
16. TOTAL AREA: 688.42 SQ. FT.
17. TOTAL WEIGHT: 1976.7 LBS.
18. WEIGHT PER ATTACHMENT: 22.46 LBS.
19. DISTRIBUTED LOAD: 2.87 PSF.
20. MAX. HORIZONTAL STANDOFF: 48 IN.
21. MAX. VERTICAL STANDOFF:
LANDSCAPE: 26 IN., PORTRAIT: 43 IN.
22. STANDOFF STAGGERING: NO
23. RAIL MANUFACTURER (OR EQUIV.): SNAPNRACK
24. RAIL MODEL (OR EQUIVALENT): SERIES 100 NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
S-501.00
ASSEMBLY DETAILS
(SHEET 17 OF 19)
SNAPNRACK B MOUNT
ROCK-IN
CHANNEL NUT
ROW LINK 3D VIEW ROW LINK SIDE VIEW
ROW LINK
ROW LINK SHALL OCCUR
WITHIN 1" TO 6" FROM
THE NEAREST ADJACENT
MODULE PANEL EDGE.
SNAPNRACK FLASHTRACK COMP
SNAPNRACK B MOUNT
ROW LINK
STANDARD MODULE (TYP.)
SNAPNRACK B MOUNT.
ROW LINK SHALL
ONLY OCCUR
BETWEEN TWO ROOF
ATTACHMENTS IN
THE SAME ROW.
A
DETAIL A
SNAPNRACK A MOUNT
SUPPORT SPACING (DISTANCE
BETWEEN ROOF ATTACHMENTS).
SEE APPROPRIATE ENGINEERING
TABLES FOR MAXIMUM SUPPORT
SPACING.
SNAPNRACK C LINK
SNAPNRACK B MOUNT
SNAPNRACK A MOUNT
LEVELER
MODULE
LEVELER BOLT
SPACER, TO BE REMOVED
WHEN C LINK FALLS ON MOUNT
MIN 5.0 INCHES
END OF FLASHING
TO RDIGE
MOUNT CLAMP BOLT**
SNAPNRACK
RIDGE EXTENSION
MODULE A
LEVLER
H TRACK H TRACK
FLASH TRACK
FLASHING
ROCK-IN/DROP-IN CHANNEL NUT (2)
DETAIL A
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
R-001.00
RESOURCE DOCUMENTS
(SHEET 18 OF 19)
NEW PV SYSTEM: 11.550 kWp
ENGINEER OF RECORD
DATE:06.27.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
DIRK STROBEL DENTIST
OFFICE
59 PROFESSIONAL PLAZA
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
R-002.00
RESOURCE DOCUMENTS
(SHEET 10 OF 19)