HomeMy WebLinkAboutSITE PLAN - 19-00416 - 980 Westwood Dr - Solar PanelsISSUE
July 11, 2019
DRAWN BY
KM
Gaylen Jensen
980 Westwood Drive
Rexburg, Idaho
83440
(208) 313-1081
PROJECT
Solar Photovoltaic
SYSTEM SIZE
4.96kW
Empire Solar Group
3250 N 750 E
Layton, UT 84041
License# 026803
01
Site Info
INVERTER(S)
SolarEdge 3800H + 16 P-320 Optimizers
PANELS
16 Silfab SLA-M 310
AZIMUTH
180°
ROOF PITCH
32°
MAIN SERVICE PANEL
INVERTER
SOLAR PV
MODULES, TYP.
FIRE LANE SETBACKS:
-3’ RIDGES & EDGES
-18” HIPS & VALLEYS
AC KNIFE SWITCH
DISCONNECT
METER
MAIN INVERTER
KNIFE SWITCH
DISCONNECTMAIN
PANEL
ISSUE
July 11, 2019
DRAWN BY
KM
Gaylen Jensen
980 Westwood Drive
Rexburg, Idaho
83440
(208) 313-1081
PROJECT
Solar Photovoltaic
SYSTEM SIZE
4.96kW
Empire Solar Group
3250 N 750 E
Layton, UT 84041
License# 026803
02
1-Line
Diagram
INVERTER(S)
SolarEdge 3800H + 16 P-320 Optimizers
PANELS
16 Silfab SLA-M 310
INTEGRATED
DC DISCONNECT
(A)(B)(E)(M)
Utility Interactive
Inverter
SolarEdge
3800H-US
(H)
INTEGRATED RAPID
SHUTDOWN
DISCONNECT
NEMA 3R RATED
JUNCTION BOX
(K)
(4) #10 THWN-2
(1) #10 THWN-2 EGC
MIN. 3/4” EMT
P-320 DC
OPTIMIZERS
(K)
(4) #10 PV WIRE
(1) #6 BARE COPPER
FREE AIR MAIN SERVICE
DISCONNECT
200A/2P
M
GEC
2P 20A
(D)(F)(I)(J)(L)
MIN.200A RATED
MAIN SERVICE PANEL
(3) #10 COPPER THWN-2
(1) #10 COPPER THWN-2 GND
MIN. 3/4" EMT CONDUIT
*MIN* 20A RATED
NON-FUSED
AC DISCONNECT
(A)(D)
(3) #10 COPPER THWN-2
(1) #10 COPPER THWN-2 GND
MIN. 3/4" EMT CONDUIT
NOTE:
-The load calculations shall comply with NEC 220, 710, and 702.4 as applicable for Stand-Alone, Hybrid, Optional Standby Systems, and the down sizing of the Main Overcurrent Protective Device to allow for a larger Point of Connection in accordance with NEC 705.12 (B) (2) (3) (b)
- The Solar PV Systems calculations shall be provided and verified at the time of electrical inspections to verify compliance with NEC 110.14 (C), 310.15, 690.7, 690.8, 690.53,690.54, and 705.12.
-The PV Source/AC disconnect and wiring methods to the Meter Base/Socket or to the Service Entrance Conductors, and location of the overcurrent protection shall be in accordance with NEC 230.43, 230.70, 230.79 (D), 690.13 (C), and 705.3
-Overcurrent Protection for the Solar PV System shall comply with NEC 690.9 and 705.60
WARNING
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH TERMINALS
BOTH LINE AND LOAD SIDES MAY BE
ENERGIZED IN THE OPEN POSITION
PHOTOVOLTAIC
COMBINER PANEL
DO NOT ADD LOADS
(A) (C) (D)
PHOTOVOLTAIC BACKFED
BREAKER: 20A @ 240V
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
(E)
WARNING
PHOTOVOLTAIC POWER SOURCE
PER NEC 690.31 (G)(3)
PER NEC 690.54
PER NEC 690.17 (E)
WARNING
ELECTRICAL SHOCK HAZARD
THE DC CONNECTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE
UNGROUNDED AND MAY BE ENERGIZED
PER NEC 690.35 (F) WARNING
ELECTRICAL SHOCK HAZARD
IF A GROUND FAULT IS INDICATED
NORMALLY GROUNDED CONDUCTORS MAY
UNGROUNDED AND MAY BE ENERGIZED
PER NEC 690.5 (E)
PER NEC 690.13 (B) PER NEC 690.13 (B)
PHOTOVOLTAIC SYSTEM
DC DISCONNECT
PER NEC 690.13 (B)
WARNING
INVERTER OUTPUT CONNECTION:
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
(F)
(G) (H)
PER NEC 705.12 (2)(b)
WARNING
DUAL POWER SUPPLY
SOURCES: UTILITY GRID AND
PV SOLAR ELECTRIC SYSTEM
PER NEC 705.12 (2)(c)
(I)
(J)
(K)
NOTE: ALL SIGNAGE WILL BE PERMANENTLY ATTACHED
AND WEATHER RESISTANT PER NEC 110.2(B)
MAXIMUM DC VOLTAGE: 480V
MAX DC AMPS OF SYSTEM: 20A
MAX DC AMPS OF OPTIMIZERS:15A
(B)
PER NEC 690.53
PER NEC 690.56 (C)(3)
(L)
LABEL L WILL BE
REFLECTIVE AND LOCATED
ON THE MAIN PANEL
BOARD OR WITHIN 3’ OF IT
SOLAR PV SYSTEM IS EQUIPPED WITH RAPID
SHUTDOWN: TURN RAPID SHUTDOWN SWITCH TO
‘’OFF’’ POSITION TO SHUT DOWN PV SYSTEM AND
REDUCE SHOCK HAZARD IN ARRAY
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SYSTEM
PER NEC 690.56(C)(3)
(M)
A String of 16
Silfab SLA-M 310
ISSUE
July 11, 2019
DRAWN BY
KM
Gaylen Jensen
980 Westwood Drive
Rexburg, Idaho
83440
(208) 313-1081
PROJECT
Solar Photovoltaic
SYSTEM SIZE
4.96kW
Empire Solar Group
3250 N 750 E
Layton, UT 84041
License# 026803
03
Labels
INVERTER(S)
SolarEdge 3800H + 16 P-320 Optimizers
PANELS
16 Silfab SLA-M 310
WARNING LABELS: WHERE SHOWN, WHITE LETTERS ON RED BACKGROUND, NON-BOLD ARIAL OR SIMILAR FONT, MIN 3/8” LETTER HEIGHT IN ALL CAPS.
MARKINGS SHALL BE REFLECTIVE, WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (UL-969).
PV PLACARD AND SIGNAGE
ISSUE
July 11, 2019
DRAWN BY
KM
Gaylen Jensen
980 Westwood Drive
Rexburg, Idaho
83440
(208) 313-1081
PROJECT
Solar Photovoltaic
SYSTEM SIZE
4.96kW
Empire Solar Group
3250 N 750 E
Layton, UT 84041
License# 026803
04
Inter-
connection
INVERTER(S)
SolarEdge 3800H + 16 P-320 Optimizers
PANELS
16 Silfab SLA-M 310
INTERCONNECTION PHOTOS
ISSUE
July 11, 2019
DRAWN BY
KM
Gaylen Jensen
980 Westwood Drive
Rexburg, Idaho
83440
(208) 313-1081
PROJECT
Solar Photovoltaic
SYSTEM SIZE
4.96kW
Empire Solar Group
3250 N 750 E
Layton, UT 84041
License# 026803
05
Notes
INVERTER(S)
SolarEdge 3800H + 16 P-320 Optimizers
PANELS
16 Silfab SLA-M 310
ROOF NOTES:
ENGINEERED ROOF TRUSSES - UPPER CHORD AT 24" O.C.
ROOFING MATERIAL: COMPOSITE SHINGLE
SINGLE LAYER
PHOTOVOLTAIC NOTES:
EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE 2017 NEC, 2015 IECC, 2015 IFC, 2015 IBC, 2015 IRC, AND ALL APPLICABLE
REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
PHOTOVOLTAIC SYSTEM IS FIXED, ROOF MOUNTED, AND RESIDENTIAL GRID TIED.
GROUND WIRE MUST BE CONTINUOUS AND INSTALLED TO ALLOW FOR MODULE REMOVAL WITHOUT DISRUPTING CONTINUITY. ALL MODULE
GROUND CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH NEC 690.43 - 690.46.
PHOTOVOLTAIC MODULES WILL BE BONDED TO RAIL WITH WILEY WEEB WASHERS. GROUNDING WILL BE BONDED TO RAIL
USING WILEY WEEB LUGS 6.7.
FOLLOW MANUFACTURERS SUGGESTED INSTALLATION PRACTICES AND WIRING SPECIFICATIONS.
WIRES SHALL BE RATED AND LABELED "SUNLIGHT RESISTANT" WHERE EXPOSED TO AMBIENT TEMPERATURE.
ALL PHOTOVOLTAIC WIRES WILL PERMANENTLY BE SUPPORTED OFF ROOF BY WILEY PV WIRE CLIPS.
ALL PHOTOVOLTAIC MODULES WILL NOT COVER OR BLOCK ANY ROOF VENTS, PLUMB VENTS, FURNACE, AND/OR WATER HEATER VENTS.
PHOTOVOLTAIC BACK-FEED WILL BE INSTALLED IN MAIN SERVICE ENTRANCE LOCATED ON SOUTH WALL OF RESIDENCE.
DC CONDUIT LABELS WILL BE PROVIDED EVERY 10' ALONG RACEWAY AND WITHIN 12" OF EVERY PENETRATION POINT PER NEC 390.31(E)(3).
BACK FED BREAKER WILL BE INSTALLED ON THE OPPOSITE END OF THE BUSBAR FROM THE MAIN FEEDERS PER NEC 705.12(D)(7).
ISSUE
July 11, 2019
DRAWN BY
KM
Gaylen Jensen
980 Westwood Drive
Rexburg, Idaho
83440
(208) 313-1081
PROJECT
Solar Photovoltaic
SYSTEM SIZE
4.96kW
Empire Solar Group
3250 N 750 E
Layton, UT 84041
License# 026803
06
Rail
INVERTER(S)
SolarEdge 3800H + 16 P-320 Optimizers
PANELS
16 Silfab SLA-M 310
Stanchion Detail:
5/16" X 3 1/2" GALVANIZED LAG BOLTS
Strain Relief
Connector LB
Rain Tight EMT
Connector
EMT
Oatey Flashing
ROOF PENETRATION DETAIL
2X4 TRUSS
24’’ O.C.
PENETRATION
POINT
MODULE
RAIL
NOT TO EXCEED
1/4 OF MODULE
LENGTH
ISSUE
July 11, 2019
DRAWN BY
KM
Gaylen Jensen
980 Westwood Drive
Rexburg, Idaho
83440
(208) 313-1081
PROJECT
Solar Photovoltaic
SYSTEM SIZE
4.96kW
Empire Solar Group
3250 N 750 E
Layton, UT 84041
License# 026803
07
Optimizer
Map
INVERTER(S)
SolarEdge 3800H + 16 P-320 Optimizers
PANELS
16 Silfab SLA-M 310
PROJECT # 4579