HomeMy WebLinkAboutM5 HVAC GENERAL NOTES.pdfSHEET NUMBER
RE
V
I
S
I
O
N
S
:
DA
T
E
:
JO
B
N
O
:
DR
A
W
N
:
CH
E
C
K
E
D
:
AC
G
#
:
06
/
2
0
/
1
9
21
7
5
AA
,
K
K
,
S
O
AR
,
C
F
19
2
0
1
9
1
14
8
1
7
W
e
s
t
9
5
t
h
S
t
r
e
e
t
L
e
n
e
x
a
,
K
a
n
s
a
s
6
6
2
1
5
P
9
1
3
3
2
2
5
1
5
0
F
9
1
3
3
2
2
5
1
5
5
ww
w
.
A
c
e
r
t
u
s
G
r
o
u
p
.
c
o
m
FRANCHISEE
7300 W. 129TH STREET
OVERLAND PARK, KANSAS
66213
PHONE: (913) 327-5555
FAX: (913) 327-5850
16
3
W
M
A
I
N
S
T
.
S
U
I
T
E
T
B
D
RE
X
B
U
R
G
,
I
D
A
H
O
PI
Z
Z
A
H
U
T
#
2
1
7
5
06/20/19
NORMAL OPERATION AND MAINTENANCE INSTRUCTIONS.
PRIOR TO RECEIPT OF INSTRUCTIONS FROM THE DIVISION-15 DESIGN
12.
BUILDING SPACES.
PROFESSIONAL, THE OWNER OR ARCHITECTURAL DESIGN PROFESSIONAL WILL
REFER TO BUILDING AND STRUCTURAL DRAWINGS FOR DIMENSIONS OF
BE DONE AT THE CONTRACTOR'S RISK.
35.
36.
DRAWINGS.
38.
37.
39.
40.
OF THE EQUIPMENT AND SYSTEMS.
PRINTS OF CONTRACT DRAWINGS WILL NOT BE ACCEPTED AS FINAL RECORD
FROM A REFERENCE SUCH AS A WALL OR COLUMN CENTER LINE. MARKED UP
INSTALLED BY THIS CONTRACTOR. ALL UNDERGROUND WORK SHALL BE DIMENSIONED
INSTALLED LOCATIONS AND SIZES OF ALL PIPING, DUCTWORK AND EQUIPMENT
CONSTRUCTION PHASE OF THIS PROJECT, AND THE DRAWINGS SHALL SHOW EXACT
CONTRACT DRAWINGS SHOWING THE CHANGES MADE TO THE DRAWINGS DURING THE
RECORD DRAWINGS ON REPRODUCIBLE DRAFTING MEDIA TO THE SAME SCALE AS THE
THIS CONTRACTOR SHALL PREPARE, UPON COMPLETION OF THE PROJECT, FINAL
THIS CONTRACTOR SHALL GUARANTEE ALL WORK DONE BY HIM AGAINST DEFECTS IN
MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR AFTER DATE OF
ACCEPTANCE BY THE OWNER. THIS GUARANTEE SHALL BE PRESENTED TO THE
OWNER IN WRITING AND ANY AND ALL DEFECTS DEVELOPING WITHIN THIS STATED
PERIOD SHALL BE REMEDIED TO THE FULL SATISFACTION OF THE OWNER BY THIS
THE ONE-YEAR GUARANTEE FOR ITEMS OF EQUIPMENT THAT THE OWNER ELECTS TO
BEGIN USING FOR HIS BENEFIT BEFORE THE COMPLETION OF THE ENTIRE PROJECT
SHALL BEGIN AT THE DATE OF "BENEFICIAL USE" BY THE OWNER. THIS DATE OF
"BENEFICIAL USE" SHALL BE ESTABLISHED JOINTLY BY THE ENGINEER, ARCHITECT,
REPRESENTATIVES IN THE COMPLETE OPERATION, ADJUSTMENT, AND MAINTENANCE
HOURS. DURING THIS TIME, THIS CONTRACTOR SHALL FULLY INSTRUCT THE OWNER'S
TO OPERATE THE ENTIRE INSTALLATION FOR A PERIOD OF ONE DAY OF EIGHT (8)
THE ENGINEER, THIS CONTRACTOR SHALL PROVIDE NECESSARY SKILLED PERSONNEL
TESTS HAVE BEEN MADE, FINAL TESTING AND BALANCING WORK IS COMPLETE, AND
DIVISION OF THE SPECIFICATIONS WILL NOT BE ACCEPTED UNTIL ALL ACCEPTANCE
AFTER COMPLETION OF ALL WORK AND TESTS AND AT SUCH TIME AS DESIGNATED BY
IT IS TO BE CLEARLY UNDERSTOOD THAT THE SYSTEMS INCLUDED UNDER THIS
MAINTAINED IN A NEAT CONDITION AND SHALL CLEARLY SHOW ANY CHANGES FROM
REVIEW BY THE ENGINEER, ARCHITECT, AND THE OWNER. DRAWINGS SHALL BE
THIS PROJECT. THESE DRAWINGS SHALL BE AVAILABLE AT THE JOB SITE FOR
MADE TO THE DRAWINGS AND SPECIFICATIONS DURING THE CONSTRUCTION PHASE OF
OF CONTRACT DRAWINGS, PRINTS, AND SPECIFICATIONS FOR RECORDING CHANGES
THIS CONTRACTOR SHALL DESIGNATE AND MAINTAIN A COMPLETE UP-TO-DATE SET
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
THE INSTALLATION IS OPERATING PROPERLY.
ORIGINAL CONTRACT DRAWINGS AND SPECIFICATIONS.13.
14.
15.
16.
17.
18.
19.
20.
21.
ON THE PROJECT.
MECHANICAL EQUIPMENT.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK FITTING INTO PLACE IN A
SATISFACTORY AND NEAT WORKMANLIKE MANNER IN EVERY PARTICULAR TO THE
APPROVAL OF THE ENGINEER. PAINT EXPOSED DUCTWORK PER ARCHITECT.
BETWEEN THE INSTALLATION OR THE PROGRESS OF THE WORK OF ANY CONTRACTOR
CONTRACTOR SHALL CONFER WITH ALL OTHER CONTRACTORS REGARDING THE
LOCATION AND SIZE OF PIPES, EQUIPMENT, FIXTURES, CONDUIT, DUCTS, OPENINGS,
SWITCHES, OUTLETS, ETC., IN ORDER THAT THERE MAY BE NO INTERFERENCE
THE OWNER MAY CHANGE THE LOCATION OF ANY EQUIPMENT FIVE FEET AND ANY
PIPING, DUCTWORK, CONDUIT, ETC., TEN FEET IN ANY DIRECTION WITHOUT EXTRA
CHARGE, PROVIDED SUCH CHANGES ARE MADE PRIOR TO INSTALLATION OF
ALL REFERENCES TO CONTRACTORS IN SPECIFICATIONS AND DRAWINGS SHALL REFER
TO THE RESPECTIVE TRADE CONTRACTOR PERFORMING THAT PORTION OF THE WORK.
SHOULD THERE BE ANY DISCREPANCIES OR A QUESTION OF INTENT, REFER THE
MATTER TO THE ENGINEER FOR A DECISION BEFORE ORDERING ANY EQUIPMENT OR
WHERE WORK CONNECTS TO THAT OF ANOTHER TRADE OR TO PIPING OR EQUIPMENT
IN PLACE, FIELD MEASUREMENTS SHALL BE MADE TO MAKE CONNECTING WORK COME
MINOR ITEMS AND ACCESSORIES OR DEVICES REASONABLY INFERRED AS NECESSARY
TO THE COMPLETE AND PROPER INSTALLATION AND OPERATION OF ANY SYSTEM
SHALL BE PROVIDED BY THE CONTRACTOR FOR SUCH SYSTEM, WHETHER OR NOT
THEY ARE SPECIFICALLY CALLED FOR BY THE SPECIFICATIONS OR DRAWINGS.
CAREFULLY CHECK AND COORDINATE THE LOCATION AND LEVEL OF ALL PIPES,
DUCTS, ETC. RUN PRELIMINARY LEVELS AND CHECK WITH ALL OTHER CONTRACTORS
SO THAT CONFLICTS IN ALL LOCATIONS MAY BE AVOIDED.
BLADE DAMPERS WHERE INDICATED. ALL ALUMINUM CONSTRUCTION.
AIR DISTRIBUTION SHALL BE TITUS, OR OTHER APPROVED EQUAL. PROVIDE OPPOSED
MATERIALS, OR BEFORE STARTING ANY RELATED WORK.
TRUE AND LINE UP WITH THE ITEM BEING CONNECTED.
41.
42.
INDOOR AIR QUALITY STANDARDS.
44.
45.
43.
THE SMOKE DETECTORS IN THE DUCTWORK. THE ELECTRIC CONTRACTOR SHALL
MOUNTED UPSTREAM FROM OUTSIDE CONNECTION. HVAC CONTRACTOR SHALL MOUNT
DETECTORS SHALL BE IONIZATION TYPE. DETECTOR IN RETURN AIR DUCT SHALL BE
DOWN FANS IN AIR CONDITIONING EQUIPMENT UNITS UPON DETECTION OF SMOKE.
MOUNT SMOKE DETECTORS IN SUPPLY AIR AND RETURN AIR DUCTWORK TO SHUT
GAS PIPE SHALL BE SCHEDULE 40 BLACK STEEL. UNDERGROUND GAS PIPE SHALL
IN CONCEALED SPACES, REGARDLESS OF PRESSURE SHALL BE WELDED. ALL PIPE
BE COATED AND WRAPPED. PROVIDE CATHODIC PROTECTION AS REQUIRED. GAS PIPE
SHOULD SPACE USAGE OR OCCUPANCY CHANGE IN THE FUTURE, IT IS THE OWNER'S
RESPONSIBILITY TO MAINTAIN COMPLIANCE WITH APPLICABLE VENTILATION AND/OR
THIS CONTRACTOR, AND THE OWNER. THIS CONTRACTOR SHALL PREPARE A LETTER
STATING THAT THE OWNER HAS REQUESTED "BENEFICIAL USE". THIS LETTER SHALL
THE OWNER, IN ORDER TO MAINTAIN THE INDOOR AIR QUALITY FOR THIS FACILITY IN
COMPLIANCE WITH BUILDING CODES, SHOULD PROVIDE A CONTINUING MAINTENANCE
PROGRAM FOR THE HEATING, VENTILATING AND AIR CONDITIONING (H.V.A.C.) SYSTEMS.
THE H.V.A.C. SYSTEMS FOR THIS FACILITY WERE DESIGNED TO MEET OR EXCEED THE
WIRE THE DETECTORS AS REQUIRED.
EXPOSED TO PRESSURE ABOVE 1 PSI SHALL BE WELDED.
BE SIGNED BY THE OWNER, THIS CONTRACTOR, AND THE ARCHITECT.
INDOOR AIR QUALITY REQUIREMENTS OF ASHRAE 62-1989.
23.
24.
25.
26.
27.
THE ENGINEER PRIOR TO SUBMITTING HIS BID.
FOR DELIVERY TO THE OWNER.
APPROVED BY THE ENGINEER.
EQUIPMENT.
28.
MATERIALS USED IN THIS WORK WHICH ARE SUBJECT TO APPROVAL BY
UNDERWRITERS (UL) SHALL BEAR THE UNDERWRITERS LABEL OF APPROVAL.
MANUFACTURER'S TRADE NAMES OR CATALOG NUMBERS USED IN THESE
SPECIFICATIONS AND INDICATED ON THE DRAWINGS ARE NOT TO BE CONSIDERED AS
PROPRIETARY. THEIR PURPOSE IS TO DENOTE TYPE, SIZE, QUALITY, AND DESIGN OF
WHERE EQUIPMENT IS SPECIFIED AS "OR EQUAL", IT SHALL MEAN EQUAL AS
THE CONTRACTOR IS FREE TO OFFER FOR CONSIDERATION SUBSTITUTE ITEMS OF
EQUIVALENT TYPE, SIZE, QUALITY, AND PERFORMANCE AFTER THE CONTRACT IS
SIGNED; HOWEVER, HE SHALL BE PREPARED TO FURNISH SPECIFIED MATERIALS AND
EQUIPMENT WHERE SUBSTITUTIONS ARE REJECTED ON HIS ORIGINAL SUBMITTAL.
SHOULD ANY PART OF THE PLANS OR SPECIFICATIONS BE FOUND TO BE IN
CONFLICT WITH APPLICABLE CODES OR ORDINANCES, THIS CONTRACTOR SHALL NOTIFY
THIS CONTRACTOR SHALL MAKE APPLICATION TO THE LOCAL BUILDING CODE
ENFORCEMENT OFFICIALS TO OBTAIN ALL INSPECTION PERMITS REQUIRED, AND SHALL
PAY ALL NECESSARY FEES FOR SAME. HE SHALL, AT THE CONCLUSION OF THE
INSTALLATION, SECURE A CERTIFICATE OF INSPECTION, PROPERLY SIGNED BY THE
CONTROLLING BUILDING CODE ENFORCEMENT DEPARTMENT, WHICH SHALL STATE THAT
ALL RULES HAVE BEEN COMPLIED WITH AND THAT THE WORK IS SATISFACTORY. AT
PROJECT COMPLETION, THIS CONTRACTOR SHALL SUBMIT CERTIFICATE OF INSPECTION
THE DRAWINGS FOR THE WORK UNDER THIS DIVISION OF THE SPECIFICATIONS ARE
INTENDED AS DESIGN ONLY, AND THEY INDICATE THE REQUIRED GENERAL SCOPE OF
THE WORK. THEY ARE NOT SHOP DRAWINGS, AND SHOULD NOT BE USED AS SUCH.
ALL MATERIALS SHALL BE NEW AND OF THE QUALITY SPECIFIED. APPARATUS AND 22.
IDENTIFIED.
THE DRAWINGS ARE INTENDED AS DESIGN ONLY AND INDICATE THE
THE DIVISION-15 DESIGN PROFESSIONAL'S CONTRACT SERVICES DOES NOT
REFRIGERANT PIPES SHALL BE TYPE K HARD DRAWN COPPER. INSULATE
GENERAL SCOPE OF THE DIVISION-15 WORK CONTEMPLATED AND DO NOT
CONSTITUTE SHOP DRAWINGS AND SHOULD NOT BE USED AS SUCH. DIVISION-
15 DRAWINGS ARE GENERALLY DIAGRAMMATIC AND, EXCEPT WHERE
DIMENSIONS ARE SHOWN, ARE NOT INTENDED TO SHOW THE EXACT
LOCATION OF PIPES, DUCTWORK, OUTLETS, FIXTURES, OR EQUIPMENT.
DIVISION-15 CONTRACTOR(S) ACKNOWLEDGE AND UNDERSTAND THAT THE
CONTRACT DOCUMENTS FOR DIVISION-15 WORK MAY CONTAIN ERRORS,
OMISSIONS, INCONSISTENCIES, CONFLICTS, CODE VIOLATIONS AND IMPROPER
USE OF MATERIALS. SUCH DEFICIENCIES WILL BE CORRECTED WHEN
THE DIVISION-15 CONTRACTOR(S) SHALL AGREE TO CAREFULLY STUDY THE
CONTRACT DOCUMENTS AND REPORT AT ONCE IN WRITING TO THE DIVISION-
15 DESIGN PROFESSIONAL ANY DEFICIENCIES THE CONTRACTOR(S) MAY
DISCOVER. THE DIVISION-15 CONTRACTOR(S) FURTHER AGREES TO REQUIRE
EACH SUBCONTRACTOR TO LIKEWISE STUDY THE DOCUMENTS AND REPORT
AT ONCE ANY DEFICIENCIES DISCOVERED. THE DIVISION-15 CONTRACTOR(S)
SHALL RESOLVE ALL REPORTED DEFICIENCIES WITH THE DIVISION-15 DESIGN
PROFESSIONAL PRIOR TO AWARDING ANY SUBCONTRACTS OR STARTING ANY
WORK WITH THE CONTRACTOR'S OWN EMPLOYEES. IF DEFICIENCIES CANNOT
BE RESOLVED BY THE DIVISION-15 DESIGN PROFESSIONAL AND THE
CONTRACTOR(S) WITHOUT ADDITIONAL TIME OR ADDITIONAL EXPENSE, THE
DIVISION-15 DESIGN PROFESSIONAL AND THE CONTRACTOR SHALL SO
INFORM THE OWNER AND/OR THE ARCHITECTURAL DESIGN PROFESSIONAL IN
WRITING. ANY WORK THAT IS PERFORMED RELATED TO THE DEFICIENCIES
THE ARCHITECTURAL DESIGN PROFESSIONALS, THE OWNER AND THE
INCLUDE CONSTRUCTION PHASE SERVICE. THE ARCHITECTURAL DESIGN
PROFESSIONAL AND/OR THE OWNER WILL PROVIDE THE CONSTRUCTION
PHASE SERVICES. THE DIVISION-15 CONTRACTOR SHALL BE AWARE THAT THE
ARCHITECTURAL DESIGN PROFESSIONAL AND/OR THE OWNER ARE SOLELY
RESPONSIBLE FOR THE INTERPRETATIONS OF THE CONTRACT DOCUMENTS
AND OBSERVATIONS OF THE WORK OF DIVISION-15 CONTRACTORS DURING
THE CONSTRUCTION PHASE OF THIS PROJECT. ANY DEVIATION FROM THE
CONTRACT DOCUMENTS BY DIVISION-15 CONTRACTORS MUST BE
AUTHORIZED AND APPROVED BY THE ARCHITECTURAL DESIGN
PROFESSIONAL AND/OR THE OWNER BEFORE THE DEVIATION CAN BE
INCORPORATED INTO THIS PROJECT. DIVISION-15 CONTRACTORS SHALL BE
HELD LIABLE FOR ALL DEVIATIONS FROM THE CONTRACT DOCUMENTS,
RECORDED OR UNRECORDED, THAT HAVE NOT BEEN AUTHORIZED AND
APPROVED BY THE ARCHITECTURAL DESIGN PROFESSIONAL AND/OR THE
REFRIGERANT PIPE WITH 3/4" ARMAFLEX CLOSED CELL INSULATION ON
46.
47.
OWNER.
48.
29.
30.
31.
32.
SPACES.
COST TO THE OWNER.
33.
34.
FOR NOT LESS THAN FIVE YEARS.
THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND, EXCEPT WHERE DIMENSIONS ARE
SHOWN, ARE NOT INTENDED TO SHOW THE EXACT LOCATION OF PIPES, DUCTWORK,
RECOMMENDATIONS SHALL BE KEPT IN THE JOB SUPERINTENDENT'S OFFICE
AND INSTALLED COMPLETE. A COPY OF THE MANUFACTURER'S INSTALLATION
MANUFACTURER OR REQUIRED FOR PROPER OPERATION SHALL BE FURNISHED
WITH THE BEST RECOMMENDATIONS OF THE MANUFACTURER OF THE EQUIPMENT.
DRAWINGS, ALL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE
UNLESS SPECIFICALLY INDICATED OTHERWISE IN THESE SPECIFICATIONS OR ON THE
HEREIN WHOSE PRODUCTS HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE
IN THE MANUFACTURE OF MECHANICAL EQUIPMENT OF TYPES AND SIZES SPECIFIED
MATERIALS AND EQUIPMENT SHALL BE PROVIDED BY FIRMS REGULARLY ENGAGED IN
REFER TO BUILDING AND STRUCTURAL DRAWINGS FOR ALL DIMENSIONS OF BUILDING
WORK OF OTHER TRADES SHALL BE MADE BY THIS CONTRACTOR AT NO ADDITIONAL
REQUIRED OR NECESSARY TO AVOID INTERFERENCE WITH STRUCTURE OR WITH THE
ANY OFFSETS IN DUCTWORK OR PIPING OR CHANGES IN LOCATION OF EQUIPMENT
AND SHALL BE AVAILABLE TO THE ENGINEER'S REPRESENTATIVE AT ALL TIMES.
BEFORE COMPLETING WORK AND BEFORE REQUESTING FINAL PAYMENT, THIS
OPERATING MAINTENANCE AND SERVICE MANUALS:
OUTLETS, FIXTURES, OR EQUIPMENT.
AUXILIARY PIPING, ELECTRIC CONNECTIONS, ETC., RECOMMENDED BY THE
CONTRACTOR SHALL COMPILE AND DELIVER FOUR INDEXED, HARD COVER,
II.
III.
I.
IV.
A. EACH ITEM OF EQUIPMENT
B. VALVES AND SPECIALTIES
AND SERVICE COMPANIES.
D. SPECIAL ITEMS
C. CONTROLS
NAME/MARK/NUMBER.
V.
NAMES, ADDRESSES, AND TELEPHONE NUMBERS OF THIS CONTRACTOR AND
ALL EQUIPMENT SUPPLIERS, SYSTEMS INSTALLATION SUBCONTRACTORS,
MECHANICAL INSTALLATION DRAWINGS (AS-BUILT) WITH ITEMS IDENTIFIED BY
MANUFACTURER'S DESCRIPTIVE LITERATURE, FINAL APPROVED SHOP DRAWINGS,
PERFORMANCE DATA, CURVES, RATINGS, DIAGRAMS, SPARE PARTS AND
REPLACEMENT PARTS LISTS, INSTALLATION AND OPERATING INSTRUCTIONS,
WHERE DIAGRAMS ARE TOO LARGE FOR THE BINDER, ARRANGE MANILA
STEP-BY-STEP PROCEDURES FOR STARTING AND STOPPING THE SYSTEMS,
MAINTENANCE AND SERVICE MANUALS FOR:
POCKETS WITH REINFORCED HOLES TO HOLD FOLDED DRAWINGS.
THREE-RING BINDERS CONTAINING:
HVAC - GENERAL NOTES:
1.
2.
3.
4.
5.
7.
6.
COMPLETE THE INSTALLATION.
SMACNA STANDARDS. KITCHEN HOOD AND EXHAUST DUCTWORK SHALL BE CARBON
STANDARDS, & ALL APPLICABLE LOCAL, STATE, & NATIONAL CODES.
8.
9.
10.
11.
CONDENSATE DRAIN PIPE SHALL BE SCH. 40 P.V.C. INSULATED WITH 1/2" ARMAFLEX,
UNOCCUPIED AMBIENT NOISE LEVEL FOR H.V.A.C. SYSTEM SHALL BE NO MORE THAN
25 dB AS MEASURED ON AN "A" WEIGHTED SCALE.
OR EQUAL, INSULATION. MIN. SIZE SHALL BE 3/4".
THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL STARTERS, DISCONNECTS, AND ALL
CONTROL DEVICES (NOT OTHERWISE PROVIDED) FOR ALL H.V.A.C. EQUIPMENT. ELECTRICAL
CONTRACTOR WILL FURNISH & INSTALL ALL POWER WIRING. THIS CONTRACTOR SHALL
FURNISH & INSTALL ALL CONTROL WIRING. ALL WIRING SHALL BE INSTALLED IN CONDUIT.
GENERAL CONTRACTOR WILL PROVIDE ALL REQUIRED OPENINGS IN FLOORS AND EXTERIOR
WALLS FOR INSTALLATION OF H.V.A.C. EQUIPMENT, PIPING AND/OR DUCTWORK.
TOOLS, ETC. REQUIRED FOR A COMPLETE SYSTEM OF HEATING, VENTILATING AND AIR
CONDITIONING AS DESIGNATED ON THE DRAWINGS, INCLUDING ALL NECESSARY PARTS,
ACCESSORIES, ETC. REQUIRED BY STATE OR LOCAL CODES OR TO SATISFACTORILY
DUCTWORK SHALL BE GALVANIZED STEEL AND CONSTRUCTED PER APPLICABLE
ALL WORK SHALL BE PURCHASED AND INSTALLED PER ALL APPLICABLE INDUSTRY
DRAWINGS SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR.
UNLESS NOTED OTHERWISE ON THE DRAWINGS, ALL WORK SHOWN ON THE H.V.A.C.
THIS CONTRACTOR SHALL FURNISH ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT,
M5
ACCORDANCE WITH NFPA 96, SBC AND JMC. DUCTWORK SIZES SHOWN ON
STEEL (0.054 INCH MIN. IN THICKNESS). FABRICATED AND INSTALLED IN
DRAWINGS ARE INTERIOR DIMENSIONS.
REFERENCE PROJECT SUMMARY ON SHEET T1 (TITLE SHEET) FOR ALL APPLICABLE CODES.
DUCT WRAP EQUAL TO FIBERGLAS TYPE FRK. HOOD EXHAUST DUCT SHALL BE EXTERNALLY
INTERNALLY INSULATED. INSULATE ALL RECTANGULAR OUTSIDE AIR, SUPPLY AIR, AND
DUCTWORK LOCATED INSIDE OF BUILDING, EXCEPT HOOD EXHAUST DUCT, SHALL BE
RETURN AIR DUCTWORK WITH 1.5" THICK, 2#/SQ, FT. DENSITY DUCT LINER EQUAL TO
FIBERGLAS. ALL TRAVERSE DUCT JOINTS SHALL BE SEALED WITH MASTIC OR MASTIC PLUS
TAPE. ROUND DUCT SHALL BE EXTERNALLY INSULATED WITH 2" THICK, 3#/SQ. FT. DENSITY
WRAPPED WITH FIREMASTER INSULATION (NOT OTHERWISE PROVIDED) AS REQUIRED, IN
THE SUCTION LINE AND 1/2" ARMAFLEX CLOSED CELL INSULATION ON
THE LIQUID LINE.
ORDER TO MEET ALL APPLICABLE CODES.
RESTROOM FACILITIES SHALL BE VENTILATED AS INDICATED ON THE DRAWINGS,
& PER CODE.
49.
COMPLIANCE WITH ALL APPLICABLE LOCAL, STATE, AND NATIONAL CODES IS
SPECIFICALLY REQUIRED.
50.
INSTALL H.V.A.C. EQUIPMENT AS NOTED ON THE DRAWINGS. PROVIDE ACCESS TO
OF SEISMIC BRACING SYSTEMS. ALL SEISMIC RESTRAINTS SHALL BE IN ACCORDANCE
PROFESSIONAL ENGINEER WITH MIN. FIVE YEARS EXPERIENCE IN THE DESIGN
FOR REVIEW. THE SHOP DRAWINGS SHALL BEAR THE SEAL OF A LICENSED
ALL SEISMIC BRACING DEVICES SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER
COMPLY WITH LOCAL SEISMIC BRACING REQUIREMENTS FOR ALL HVAC EQUIPMENT.
WITH ALL APPLICABLE BUILDING CODES.
EQUIPMENT PER CODE REQUIREMENTS.
PROVIDE THERMOSTAT - "HONEYWELL" VISION PRO-COMMERCIAL. FOR UNITS WITH ECONOMIZER -
WHITE RODGERS G3272C.
FRYER HOOD SUPPRESSION SYSTEM
MANUFACTURERS: ANSUL, KIDDE, OR APPROVED EQUAL.
FEATURES: WET CHEMICAL FIRE EXTINGUISHING SYSTEM INCLUDING
DETECTORS, CONTROL HEADS, PRESSURE CYLINDERS, PULL STATIONS, MAIN
GAS SHUT-OFF VALVE AND NOZZLES TO PROVIDE A COMPLETE AUTOMATIC
FIRE EXTINGUISHING SYSTEM IN CONFORMANCE WITH N.F.P.A. 96 AND U.L.
300. CONCEAL ALL PIPING EXCEPT THAT WHICH HAS BEEN SPECIFICALLY
APPROVED BY THE OWNER'S INSPECTOR.
SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR SUBMITTAL OF EXTINGUISHING SYSTEM FOR
APPROVAL BY LOCAL AUTHORITIES.
FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED TO PROTECT THE
EXHAUST DUCT AND FRYER HOOD FOR THE DOUBLE GAS FRYER. INSTALL
GAS SOLENOID SHUT-OFF VALVE IN GAS LINE SERVING THE APPLIANCE
BEING SERVED BY THE FRYER HOOD. VALVE SHALL SHUT-OFF GAS AND
ELECTRICAL TO THE APPLIANCE WHEN SUPPRESSION SYSTEM IS ACTIVATED.
51.
HV
A
C
G
E
N
E
R
A
L
NO
T
E
S