HomeMy WebLinkAboutE1 ELECTRICAL RISER DIAGRAM.pdfSHEET NUMBER
RE
V
I
S
I
O
N
S
:
DA
T
E
:
JO
B
N
O
:
DR
A
W
N
:
CH
E
C
K
E
D
:
AC
G
#
:
06
/
2
0
/
1
9
21
7
5
AA
,
K
K
,
S
O
AR
,
C
F
19
2
0
1
9
1
14
8
1
7
W
e
s
t
9
5
t
h
S
t
r
e
e
t
L
e
n
e
x
a
,
K
a
n
s
a
s
6
6
2
1
5
P
9
1
3
3
2
2
5
1
5
0
F
9
1
3
3
2
2
5
1
5
5
ww
w
.
A
c
e
r
t
u
s
G
r
o
u
p
.
c
o
m
FRANCHISEE
7300 W. 129TH STREET
OVERLAND PARK, KANSAS
66213
PHONE: (913) 327-5555
FAX: (913) 327-5850
16
3
W
M
A
I
N
S
T
.
S
U
I
T
E
T
B
D
RE
X
B
U
R
G
,
I
D
A
H
O
PI
Z
Z
A
H
U
T
#
2
1
7
5
06/20/19
5
E1
ELECTRICAL SERVICE RISER 6
1.ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC
CODE (NEC), THE AMERICANS WITH DISABILITIES ACT (ADA), AND ALL STATE AND LOCAL
REQUIREMENTS AND CODES.
2.REFER TO RELATED ARCHITECTURAL AND MECHANICAL DRAWINGS FOR RELATED INFORMATION
AND EQUIPMENT DESCRIPTIONS.
3.ALL LIGHTING FIXTURES AND MECHANICAL EQUIPMENT SHALL BE COMPLETELY CONNECTED BY
ELECTRICAL CONTRACTOR (BOTH POWER AND CONTROL WIRING).
4.ALL NEW LIGHTING FIXTURES SHALL BE FURNISHED WITH LAMPS.
5.ALL NEW TELEPHONE OUTLETS SHALL HAVE 3/4" CONDUIT WITH PULL WIRES ROUTED TO
TELEPHONE TERMINAL BOARD. CONDUIT SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR.
VERIFY TELEPHONE REQUIREMENTS WITH LOCAL TELEPHONE COMPANY.
6.VERIFY ALL OUTLET LOCATIONS ON THE JOB PRIOR TO ROUGH-IN.
7.PANELBOARDS SHALL BE U.L. LISTED FOR A MINIMUM 22,000 AIC FAULT CURRENT. CONTRACTOR
TO COORDINATE WITH SERVING UTILITY COMPANY AND LANDLORD TO PROVIDE PANELBOARDS
PROPERLY BRACED FOR AVAILABLE FAULT CURRENT.
8.PROVIDE TYPEWRITTEN SCHEDULE INDICATING EQUIPMENT DESCRIPTION AND/OR LOCATION FOR
EACH CIRCUIT IN PANEL DOOR.
9.SAFETY SWITCHES SHALL BE GENERAL DUTY WITH CLASS "J" FUSE CLIPS.
10.FUSES SHALL BE BUSSMAN LPJ OR EQUAL BY GOULD SHAWMUT OR LITTLE FUSE.
11.PROVIDE SWITCH DUTY BREAKERS FOR CIRCUITS BEING SWITCHED AT PANEL.
12.PROVIDE HACR TYPE BREAKERS FOR ALL HVAC EQUIPMENT.
13.ALL BREAKERS SHALL BE 1" BREAKERS. ELECTRICAL CONTRACTOR SHALL NOT PLACE (2) CIRCUIT
BREAKERS IN (1) CIRCUIT BREAKER SPACE (I.E. TANDEM BREAKER OR 1/2" BREAKER).
14.USE ONLY INSULATED COPPER CONDUCTORS IN CONDUIT. CONDUCTORS SHALL BE SIZED PER
DRAWINGS AND N.E.C. (MINIMUM # 12 COPPER) MINIMUM CONDUCTOR INSULATION SHALL BE TYPE
"THWN/THHN" FOR ALL CONDUCTORS. NO ROMEX ALLOWED. A GROUND WIRE SIZED PER N.E.C. ART.
250-66 (SERVICE GROUND) OR N.E.C. ART. 250-122 (EQUIPMENT GROUND) SHALL BE PULLED IN ALL
CONDUIT.
15.ALUMINUM CONDUCTORS ARE SPECIFICALLY PROHIBITED.
16.COMPLETE SYSTEM SHALL BE GROUNDED PER N.E.C. ARTICLE 250-66.
17.ISOLATED GROUND OUTLETS: CONNECT PANEL B ISOLATED GROUND BUS TO SYSTEM GROUND AT
PANEL A. RUN ISOLATED GROUND IN SAME CONDUIT WITH CIRCUIT CONDUCTORS.
18.ALL CONDUIT WILL BE INSTALLED CONCEALED IN WALLS OR ABOVE ACCESSIBLE CEILING TILES. DO
NOT EXPOSE CONDUIT.
19.PROVIDE ELECTRICAL DEVICES AND WIRING TO COMPLY WITH N.F.P.A. 96.7-3.1.3 FOR POWER
SHUT-OFF ON ALL ELECTRICAL EQUIPMENT UNDER OVEN HOOD. VERIFY INSTALLATION AND
OPERATION REQUIREMENTS WITH EXTINGUISHING SYSTEM SUPPLIER.
20.BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS FOR CLARITY ONLY, CONTRACTOR
MAY GROUP SINGLE POLE BRANCH CIRCUITS IN MULTIPLE CIRCUIT HOME RUNS. (2 CIRCUITS MAX @
120/240V. 3Ø & 1Ø). A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
POWER, RECEPTACLE, AND LIGHTING CONDUITS.
21.FINAL CONNECTIONS TO ALL DIRECT CONNECTED KITCHEN EQUIPMENT SHALL BE WITH U.L.
APPROVED LIQUIDTIGHT CONDUIT. PROVIDED WITH GROUND WIRE SIZED PER N.E.C. ART. 250-122.
22.PROVIDE STAINLESS STEEL COVERPLATES FOR ALL WIRING DEVICES. COVERPLATES SHALL BE
EQUAL TO PASS & SEYMOUR.
23.ALL RECEPTACLES AND SWITCHES TO BE GRAY.
24.ALL CONDUITS TO BE CONCEALED INCLUDING SECURITY SYSTEM CONDUITS. E.C. SHALL INSTALL
SECURITY SYSTEM CONDUITS AND LABEL CONDUIT FOR SECURITY USE.
25.ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONNECTIONS FOR FIRE ALARM CONTROL PANEL
AND DUCT SMOKE DETECTORS AND COMPLY WITH N.F.P.A. 90A 4-4.
26.RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS, FITTINGS, LOW VOLTAGE WIRING AND LINE
VOLTAGE WIRING SHALL BE SECURELY FASTENED IN PLACE TO THE ABOVE STRUCTURE.
ELECTRICAL DEVICES LAYING DIRECTLY ON THE CEILING GRID IS STRICTLY PROHIBITED. SUPPORT
WIRES THAT DO NOT PROVIDE SECURE SUPPORT SHALL NOT BE PERMITTED AS THE SOLE SUPPORT.
SUPPORT WIRES AND ASSOCIATED FITTINGS THAT PROVIDE SECURE SUPPORT AND THAT ARE
INSTALLED IN ADDITION TO THE CEILING GRID SUPPORT WIRES SHALL BE PERMITTED AS THE SOLE
SUPPORT. WHERE INDEPENDENT SUPPORT WIRES ARE USED, THEY SHALL BE SECURED AT BOTH
ENDS. CABLES AND RACEWAYS SHALL NOT BE SUPPORTED BY CEILING GRIDS.
EL
E
C
T
R
I
C
A
L
R
I
S
E
R
DI
A
G
R
A
M
S
&
P
A
N
E
L
SC
H
E
D
U
L
E
S
NOTE:
ALL CONDUCTORS SHALL BE COPPER, WITH
THWN/THHN INSULATION.
'A''B'
OUTSIDEINSIDE
PROVIDE (4)#3, (1)#8 GROUND,
AND (1)#8 ISOLATED GROUND
IN 1-1/4" CONDUIT.
M
EXISTING UTILITY METER AND S.E.
DISCONNECT TO REMAIN.
PROVIDE (2) 2"C EACH WITH (4) #3/0, (1) #3
GROUND AND (1)#3 ISOLATED GROUND FROM
LANDLORD'S EXISTING METER TO PANELBOARD
'A' WITHIN TENANT SPACE. COORDINATE ALL
REQUIREMENTS AND CONNECTIONS WITH
LANDLORD AND SERVING UTILITY COMPANY
PRIOR TO ROUGH-IN.
2
4ELECTRICAL GENERAL NOTES
1SYMBOL LEGEND
NOTE:
ALL HOOD, OVEN AND FRYER CIRCUITS ARE TO BE ROUTED FROM PANELBOARD 'A', THROUGH THE HOOD
CONTROL PANEL, THEN TO FINAL TERMINATION POINT. REFER TO PANELBOARD SCHEDULE FOR HOOD CONTROL
PANEL CIRCUIT DESIGNATION.
ELECTRICAL PANELS
7ELECTRIC SERVICE LOAD SUMMARY
HCP,N
HCP,N
HCP,N
N
N
GF,HCP,N
GF,HCP,N
GF,HCP,N
GF,HCP,N
GF,N
GF,N
GF,N
GF,N
GF,N
N
GF,N
GF,N
CKT
#
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
CIRCUIT
DESCRIPTION
EF-1
SF-1
EF-2
SPARE
HOOD CONTROL PANEL POWER & HOOD LTS
OVEN #1 (C3-029)
OVEN #2 (C3-029)
OVEN #3 (C3-029)
FRYER (C2-001)
PROOFER (P3-003)
VISICOOLER (R2-007)
MAKETABLE (P2-001)
UNDERCOUNTER FREEZER (R3-011)
DISHWASHER (Z3-001)
ROOF TOP RCPTS
HOLDING CABINET (S15-001)
WINGSTREET REFRIGERATOR (R4-013)
BUS AMPS:
MAIN SIZE / TYPE:
VOLTS/PHASE:
MOUNTING:
225A
200A MCB
208Y/120V, 3PH, 4W
SURFACE
BREAKER
AMPS
15
25
15
20
15
20
20
20
20
20
20
20
20
20
20
30
15
P
1
1
1
1
1
2
2
2
1
2
1
1
1
1
1
1
1
WIRE
SIZE
12
12
12
12
12
12
12
12
12
12
12
12
12
12
10
12
LOAD
(VA)
672
1,392
528
0
500
1,040
1,040
1,040
1,040
1,040
1,040
900
1,920
1,920
780
1,536
696
1,800
540
2,316
360
PER PHASE SUB-TOTALS
TOTAL CONNECTED PANELBOARD (VA)
TOTAL CONNECTED PANELBOARD (AMPS)
TOTAL PANELBOARD DEMAND (VA)
TOTAL PANELBOARD DEMAND (AMPS)
LOCATION:
NEMA RATING:
AFC VALUE:
AIC RATING:
PANELBOARD A
CONNECTED PER PHASE (VA)
A
1,609
1,045
1,966
3,479
4,887
4,503
4,042
21,531
B
2,329
1,545
1,966
3,479
4,887
3,663
6,249
24,118
65,877
183
61,705
171
BACK OF HOUSE
NEMA 1
VERIFY
EXISTING
C
1,465
2,085
1,220
3,339
3,747
4,767
3,605
20,228
LOAD
(VA)
937
937
937
1,045
1,045
1,045
926
926
180
2,439
2,439
2,439
2,967
2,967
2,967
2,967
2,967
2,967
3,502
3,933
3,245
LEGEND:
TS - VIA TIME SWITCH
GF - GROUND FAULT INTERRUPTER
FA - FIRE ALARM / RED / LOCKING TAB
EM - EMERGENCY LTG. / LOCKING TAB
HCP - ROUTE VIA HOOD CONTROL PANEL
WIRE
SIZE
12
12
12
12
10
8
8
SR
GROUND BUS:
ISOL. GROUND BUS:
FEED THRU LUGS:
SECTIONS:
BREAKER
P
3
3
2
1
3
3
3
3
AMPS
20
20
20
20
30
35
35
100
CIRCUIT
DESCRIPTION
WALK-IN FREEZER CONDENSOR
(W1-002)
WALK-IN COOLER CONDENSOR
(W1-001)
WALK-IN FREEZER EVAPORATOR
WALK-IN COOLER EVAPORATOR
RTU-3
RTU-1
RTU-2
PANELBOARD 'B'
YES
NO
NO
1 OF 1
N - NEW BREAKER IN EX PNLBD
LCK - PAD LOCKABLE BREAKER
IN OPEN POSITION
IG - ISOLATED GROUND
SR - RE: SERVICE RISER
CKT
#
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
N
N
N
N
N
N
N
N
EM
GF,IG
GF,IG
LC
LCK
CKT
#
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
CIRCUIT
DESCRIPTION
COOLER/FREEZER LIGHTS
BACK AREA & EM LIGHTS
COOLER/FREEZER POWER
POS AT TELEPHONE BOARD
(2) KMS AT MAKETABLE
FRONT SIGNAGE
WATER HEATER (Z13-003)
SPARE
SPARE
LIGHTING CONTROLS
SPARE
SPARE
SPARE
SPARE
SPARE
BUS AMPS:
MAIN SIZE / TYPE:
VOLTS/PHASE:
MOUNTING:
125A
MLO
208Y/120V, 3PH, 4W
SURFACE
BREAKER
AMPS
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
P
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
WIRE
SIZE
12
12
12
12
12
12
12
12
LOAD
(VA)
400
953
500
180
1,440
1,200
216
0
0
360
0
0
0
0
0
PER PHASE SUB-TOTALS
TOTAL CONNECTED PANELBOARD (VA)
TOTAL CONNECTED PANELBOARD (AMPS)
TOTAL PANELBOARD DEMAND (VA)
TOTAL PANELBOARD DEMAND (AMPS)
LOCATION:
NEMA RATING:
AFC VALUE:
AIC RATING:
PANELBOARD B
CONNECTED PER PHASE (VA)
A
746
680
1,216
860
0
3,502
B
1,493
1,440
500
500
0
3,933
10,680
30
11,405
32
BACK OF HOUSE
NEMA 1
VERIFY
MATCHING EXISTING
C
685
1,560
1,000
0
0
3,245
LOAD
(VA)
346
540
185
500
0
360
1,000
500
1,000
500
500
0
0
0
0
LEGEND:
TS - VIA TIME SWITCH
GF - GROUND FAULT INTERRUPTER
FA - FIRE ALARM / RED / LOCKING TAB
EM - EMERGENCY LTG. / LOCKING TAB
LC - LIGHTING CONTACTOR
WIRE
SIZE
12
12
12
12
12
12
12
12
12
12
GROUND BUS:
ISOL. GROUND BUS:
FEED THRU LUGS:
SECTIONS:
BREAKER
P
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
AMPS
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
CIRCUIT
DESCRIPTION
FRONT AREA/RR/EF-3 & EM LIGHTS
SHOW WINDOW RCPT
CUSTOMER CASH OUT MONITOR
COMPUTER
SPARE
CONVENIENCE RCPTS
POS #1/#3
POS #2
POS #4/#5
POS #6
BACK CASH OUT
SPARE
SPARE
SPARE
SPARE
YES
YES
NO
1 OF 1
ST - SHUNT TRIP
LCK - PAD LOCKABLE BREAKER
IN OPEN POSITION
IG - ISOLATED GROUND
OL - RE: ONE-LINE DIAGRAM
CKT
#
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
EM
IG
GF,IG
IG
GF,IG
GF,IG
GF,IG
GF,IG
COMMERCIAL LOAD SUMMARY
LOAD DESCRIPTION
LIGHTING
POWER & HVAC
BUILDING AREA:
INTERIOR LIGHTING
EXTERIOR LIGHTING
SIGNAGE
MINIMUM GENERAL LIGHTING PER NEC-220 x 125%
MINIMUM TRACK LIGHTING/SHOW WINDOW PER NEC-220 x 125%
EXISTING
RECEPTACLES
MISCELLANEOUS EQUIPMENT
REFRIGERATION EQUIPMENT
KITCHEN
HVAC - SUMMER
HVAC - WINTER
SUPP. ELECTRIC HEAT
MOTORS
LARGEST MOTOR
1,512 SQ. FT
SUB-TOTAL (VA)
SUB-TOTAL (AMPS)
VOLTAGE:
CONNECTED
LOAD (VA)
1,630
0
1,200
0
1,620
11,101
8,338
13,992
20,466
0
216
7,314
0
65,877
183
208Y/120V, 3PH, 4W
x
x
x
x
x
x
x
x
x
x
x
x
x
DEMAND
FACTOR
125%
125%
125%
100%
100%;50%
100%
100%
65%
100%
100%
100%
100%
25%
=
=
=
=
=
=
=
=
=
=
=
=
=
SUB-TOTAL (VA)
SUB-TOTAL (AMPS)
SERVICE SIZE (AMPS)
SPARE CAPACITY (AMPS)
DEMAND
LOAD (VA)
0
0
1,500
3,780
0
0
1,620
11,101
8,338
9,095
20,466
0
216
7,314
0
63,430
176
200
24
F.A.C.P. IS FOR MONITORING SMOKE
DUCT DETECTORS ONLY. E.C. SHALL
PROVIDE ALL CONNECTIONS TO
COMPLY WITH N.F.P.A 90A 4-4.
BACKBOARD NETWORK EQUIPMENT LAYOUT
RJ45 TYPICAL
6
11
10
9
8
4
5
3
2
1
7
12
14
15
AMP.INC. #558260-1 (12 PORT) CAT. 5, MINI PATCH
PANEL, MOUNT VERTICALLY AT 6" BELOW CEILING
(4 PAIR, 24 GA. CAT. 5 TYP.) TO
PATCH PANEL
CUSTOMER CASH OUT MONITOR (MOUNT AT 7'-8" A.F.F.)
OFFICE APPLIANCE AT MANAGER'S DESK (NOT PHONE)
OFFICE COMPUTER AT MANAGER'S DESK
WINGSTREET UPLINK (FRONT COUNTER)
P.O.S. WINGSTREET LINE (FINISH STATION SIDE)
BUMP PAD/MONITOR #2 AT MAKETABLE
BUMP PAD/MONITOR #1 AT MAKETABLE
BUMP PAD/MONITOR AT CUT TABLE
P.O.S. ORDER ENTRY STATION (BACK AREA)
P.O.S. ORDER ENTRY STATION
P.O.S. ORDER ENTRY STATION (FRONT COUNTER)
P.O.S. ORDER ENTRY STATION (DISPATCH)
P.O.S. ORDER ENTRY STATION (FRONT COUNTER)
P.O.S. ORDER ENTRY STATION
BACK WALL AT TELEPHONE BOARDBACK WALL AT TELEPHONE BOARD
NOTES:
1. RJ45 FEMALE WALL PLATES TYPICAL AT ALL
TERMINATION POINTS (CAT 5).
2. ALL WIRING FROM WALL PLATES TO
EQUIPMENT BY OWNER.
3. ELECTRICAL CONTRACTOR TO MARK EACH
RJ45 WALL PLATE AND EACH DATA CABLE AT
PATCH PANEL TO INDICATE WHICH STATION
OR PIECE OF EQUIPMENT EACH WIRE RUNS.
4. P.O.S. INSTALLATION CONTRACTOR TO VERIFY
QUANTITY AND LOCATION OF ALL ORDER
ENTRY STATIONS.
5. ELECTRICAL CONTRACTOR IS RESPONSIBLE
FOR ALL POS WIRING AND ALL TELEPHONE
WIRING WITHIN THE SPACE. COORDINATE
WITH NPC CONSTRUCTION MANAGER.
6. ELECTRICAL CONTRACTOR TO PROVIDE A SET
OF (4) FOUR CONDUCTORS CAT 5 CABLES
FROM PIZZA HUT SPACE TO INCOMING
PHONE PROVIDER JUNCTION POINT.
7. ELECTRICAL CONTRACTOR TO RUN A
CONTINUITY CHECK ON EVERY DATA CABLE
AND PROVIDE DOCUMENTATION WITH NPC
CONSTRUCTION MANAGER.
9. ELECTRICAL CONTRACTOR TO PROVIDE (2)
TWO PATCH PANELS AS SPECIFIED.
8. ELECTRICAL CONTRACTOR TO PUNCH DOWN
(B TYPE) EVERYTHING TO DATA PATCH PANEL.
13OFFICE PRINTER AT MANAGER'S DESK
3POS WIRING DIAGRAM
24
P
O
R
T
S
W
I
T
C
H
24
P
O
R
T
S
W
I
T
C
H
ROUTER
APC 750
BATTERY BACKUP
DSL/
CABLE
MODEM
CA
T
5
/
T
E
L
E
P
H
O
N
E
LI
N
E
S
I
N
TELEPHONE LINES (CAT 5)
DATA LINES (CAT 5)
INTERNET IN
TE
L
E
P
H
O
N
E
L
I
N
E
S
PORTABLE BASE
CONTROLLER
12
P
O
R
T
P
A
T
C
H
P
A
N
E
L
12
P
O
R
T
P
A
T
C
H
P
A
N
E
L
INDICATES SWITCH SCHEME
SPEAKER IN CEILING
EMERGENCY LIGHT HEADS UNIT WITH BATTERY BACK-UP
P.O.S. CASH REG. CONDUIT W/ 4 PAIR CAT. 5 CABLE
WP
EM
J J
a,b,c
JUNCTION BOX
WEATHER PROOF
EXIT LIGHT CEILING/WALL
ISOLATED GRD.DUPLEX GROUNDED RECEPTACLE & MTG. HT.
SWITCHES 1P, 3P, PILOT LT. ECT.
SPECIAL OUTLET (SEE SCHEDULE)
SINGLE GROUNDED RECEPTACLE-NEMA 5-20R (UNO)
DUPLEX GROUNDED-NEMA 5-20R (UNO) RECEPTACLE & MTG. HT.
D
T
R
1
DIMMER SWITCH
FAN RHEOSTAT
THERMOSTAT
TELEPHONE
P
SYMBOL DESCRIPTION
LEGEND
DUPLEX GROUNDED OUTLET (GFCI)
DOUBLE DUPLEX GROUNDED OUTLET
GFCI
IG
15"
S
S
3
S
NOTE:
PER NEC, ALL 15 AND 20A, 120V RECEPTACLES IN COMMERCIAL KITCHENS REQUIRED TO BE GFCI
PROTECTED.
TV JUNCTION BOX WITH COAXIAL CABLE FACE PLATE
S
DISCONNECT SWITCH
60/3 = 60 AMP SWITCH, 3 POLE
60/3/40 = 60 AMP SWITCH, 3 POLE, 40 AMP FUSE
NOTE:
PER NEC, ALL SINGLE PHASE RECEPTACLES UP TO 50A IN COMMERCIAL KITCHENS REQUIRED TO
BE GFCI PROTECTED.
INDICATES UNSWITCHED NIGHT LIGHTNL