HomeMy WebLinkAboutTRUSS LOAD CALCULATIONS - 19-00401 - Pizza Hut - Tenant Remodel_$_i tructurall
F-1 por! pog riq
`-a`JU.J`a
E N G I N E E R I N G
6/23/2019
Brett Labrie
Lindgren-Labrie Architecture
247 N. Eagle Rd.
Eagle, Idaho 83616
RE: Rexburg In -Line
Rexburg, ID
RTU Addition
Brett,
Per our discussion regarding the above-mentioned project, the currently designed roof trusses and
framing have a 7501b add -load designed into each individual truss to allow for RTU placements within the
mechanical zones indicated on the S2 sheet. This information is noted in Keynote #7 on the S2 sheet.
Per this note, each roof truss can support up to 7501b at any point in addition to the typical roof dead and
snow loads. For example, a 15001b unit can be supported equally by two adjacent joists in the
mechanical zone and be structurally acceptable as each truss will support 7501b each.
If you have any questions, please don't hesitate to contact our office.
Sincerely,
David Sansotta, P.E.
E
14438 W
R
b OF ID
��1t?LAS 5a
06/26/2019
5509 N. Glenwood St. Boise, ID 83714 1 o: 208.501.2289 1 www.structuraledge.com